Executive summary. by Heu Vang and Marco Chiari

Similar documents
LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Application Note AN- 1095

Line Reactors and AC Drives

Specifying a Variable Frequency Drive s

Cable Solutions for Servo and Variable Frequency Drives (VFD)

GenTech Practice Questions

Fundamentals of Inverter Fed Motors

UNDERSTANDING AND CONTROLLING COMMON-MODE EMISSIONS IN HIGH-POWER ELECTRONICS

Principles of Adjustable Frequency Drives

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

WIND TURBINE TECHNOLOGY

FREQUENCY CONTROLLED AC MOTOR DRIVE

Power Supplies. 1.0 Power Supply Basics. Module

WHITE PAPER. DC Motors Explained. DC Motors Explained: White Paper, Title Page

Application Note, Rev.1.0, September 2008 TLE8366. Application Information. Automotive Power

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

EMI and t Layout Fundamentals for Switched-Mode Circuits

Power Analysis of PWM Motor Drives

Variable Frequency Drive Troubleshooting with U1610A/U1620A

Case Studies in On-Line Measurement of PD in Motors Fed by Voltage Source PWM Drives

What Is Regeneration?

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Installation Considerations for IGBT AC Drives

EMI in Electric Vehicles

AN ISOLATED GATE DRIVE FOR POWER MOSFETs AND IGBTs

Measurement of Adjustable Speed Drives with Fluke Meters

A Practical Guide to Free Energy Devices

DC/DC power modules basics

The full wave rectifier consists of two diodes and a resister as shown in Figure

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

13 common causes of motor failure

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters

*ADVANCED ELECTRIC GENERATOR & CONTROL FOR HIGH SPEED MICRO/MINI TURBINE BASED POWER SYSTEMS

Offshore Platform Powered With New Electrical Motor Drive System

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

Multimeter measurements on variable frequency drives using the new Fluke 289 DMM

Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions Abstract INTRODUCTION

Chapter 4. LLC Resonant Converter

Technical Article MS-2443

Design and Applications of HCPL-3020 and HCPL-0302 Gate Drive Optocouplers

VICOR WHITE PAPER. The Sine Amplitude Converter Topology Provides Superior Efficiency and Power Density in Intermediate Bus Architecture Applications

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Type SA-1 Generator Differential Relay

Solving VFD-sourced Bearing Current Problems in AC Motors.

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

AND8008/D. Solid State Control Solutions for Three Phase 1 HP Motor APPLICATION NOTE

PowerFlex Dynamic Braking Resistor Calculator

Common Mode Choke Filtering Improves CMRR in Ethernet Transformer Applications. Application Note. June 2011

Troubleshooting accelerometer installations

Advanced Power Supply Topics

LM 358 Op Amp. If you have small signals and need a more useful reading we could amplify it using the op amp, this is commonly used in sensors.

Laboratory 4: Feedback and Compensation

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

A Practical Guide to Dielectric Testing

Bridgeless PFC Implementation Using One Cycle Control Technique

Module 11: Conducted Emissions

How To Understand The Electrical Power Supply Of A Power Supply System

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

IGBT Protection in AC or BLDC Motor Drives by Toshio Takahashi

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

ULRASONIC GENERATOR POWER CIRCUITRY. Will it fit on PC board

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Diode Applications. by Kenneth A. Kuhn Sept. 1, This note illustrates some common applications of diodes.

Lab 8: DC generators: shunt, series, and compounded.

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

Designers Series XII. Switching Power Magazine. Copyright 2005

Pulse Width Modulated (PWM)

Improving Efficiency in AC drives: Comparison of Topologies and Device Technologies

TOPOLOGIES FOR SWITCHED MODE POWER SUPPLIES

Three-phase monitoring relay CM-PFE

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

TDA4605 CONTROL CIRCUIT FOR SWITCH MODE POWER SUPPLIES USING MOS TRANSISTORS

How To Improve A Variable Frequency Drive

Switch Mode Power Supply Topologies

PARTIAL DISCHARGE INCEPTION TESTING ON LOW VOLTAGE MOTORS

Relationship between large subject matter areas

Following are definitions for major parameters to consider when selecting a power line polarity protection diode for an automotive application.

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

GLOLAB Two Wire Stepper Motor Positioner

PRECISION CAPACITOR CHARGING SWITCHING POWER SUPPLIES

Introduction. Harmonics and IEEE 519 Page 1 of 19

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

Guide to the electrical parameter classifications of IEC and IEC safety standards

Eliminate Ripple Current Error from Motor Current Measurement

6.101 Final Project Proposal Class G Audio Amplifier. Mark Spatz

Diode Circuits. Operating in the Reverse Breakdown region. (Zener Diode)

Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka

38 Series - Relay interface modules A

AMZ-FX Guitar effects. (2007) Mosfet Body Diodes. Accessed 22/12/09.

POWER LINE FILTERS FOR SWITCHING POWER SUPPLIES

Application Information Improving Efficiency in Smart Grid Applications With Fully Integrated Current Sensing ICs

The VOLTECH HANDBOOK of PWM MOTOR DRIVES. Andrew Tedd

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Product Data Bulletin

Transcription:

998-2095-10-17-13AR0 by Heu Vang and Marco Chiari Executive summary When electric motors are connected with Variable Speed Drives, some precautions must be taken. Motor cable length can create short time overvoltage at the motor terminal. This phenomenon results in premature ageing of the motor winding insulation, and, if not properly designed, will lead to motor failures. End users and consultants often underestimate this problem and neglect to apply best practices or to specify adequate countermeasures. This white paper provides guidance on how to avoid this potentially problematic situation.

Introduction In industrial environments, flexible control, energy efficiency, and low cost maintenance are all well documented benefits of variable speed drives (VSDs). However, when long cable lengths are utilized to connect VSDs to motors, motor winding insulation can deteriorate more quickly, and eventually the motor itself may fail. To understand the risks involved around this issue and the solution options available to address the situation, the technical characteristics of the drive and the motor first need to be understood. Within the VSD, the AC supply voltage is converted into DC by the use of a rectifier. DC power contains voltage ripples which are smoothed using filter capacitors. This section of the VSD is often referred to as the DC link. This DC voltage is then converted back into AC (see Figure 1). This conversion is typically achieved through the use of power electronic devices such as IGBT power transistors using a technique called Pulse Width Modulation (PWM). The output voltage is turned on and off at a high frequency, with the duration of on-time, or width of the pulse, controlled to approximate a sinusoidal waveform. Advancements in power component technology have enabled both increases in switching frequency and reductions in losses. IGBTs are commonly used in scenarios characterized by switching frequencies of up to16 khz and motor output frequencies of up to 1kHz. Input rectifier Output inverter Figure 1 A basic schematic of a variable frequency drive linked to a motor Mains L1 L2 L3 + U V W Motor In typical situations, the higher the switching frequency, the lower the output ripple motor current. In order to compensate for the losses, the IGBTs are switching fast (up to 1 µs). This high speed of switching coupled with a long length cable between the drive and the motor, creates a temporary overvoltage at the motor terminal connection. In fact, the overvoltage can exceed twice the DC bus voltage of the drive (see Figure 2). This can result in damage to the motor winding. The overvoltage condition occurs at the motor terminal. Below are examples of how overvoltage and overcurrent conditions can have an impact in the system: Effect on variable speed drive The main risk of an overcurrent condition in the speed drive is Short Circuit Fault (SCF). The peak current, due to the switching, can be read by the current sensors of the drive and lead to an unexpected fault. Another consequence of the capacitive peak current is a rise in IGBT temperature in relation with the switching frequency. These higher than normal temperatures reduce the lifetime of the speed drive. Schneider Electric White Paper Revision 0 Page 2

Overcurrent Figure 2 The impact of long motor cable length can manifest itself as both overcurrent and overvoltage situations Drive Motor Overvoltage Effect on the electric cabinet The disturbances that result from the long cable and motor interactions create high frequency circulation current into the ground and can disturb appliances that are connected on the same network. A frequent consequence is the triggering of differential protection relays which are located upstream of the drive. The high frequency currents that run through the cable motor also generate radiated emission which can disturb electronic devices around the motor cable. Effect on motor The overvoltage condition at the motor terminal can appear between two motor windings and can create partial discharge and premature ageing of winding insulation. This can then lead to complete motor failure. Note that the admissible overvoltage is dependent upon the class of the motor insulation (see Figure 4). End users and consultants often underestimate these types of phenomena and do not specify adequate countermeasures. Even if short term cost savings can be achieved by avoiding the extra cost of supplemental devices and options, in the long run this improper design approach can lead to motor breakdown or unexpected interruption of the applications. In critical applications like a water supply plant or a power station, this level of risk is not acceptable. Long motor cable length side effects In standard applications, when the motor cable exceeds 10 meters (32 feet) in length, overvoltage occurs. The longer the motor cable is, the higher the overvoltage that occurs (see Figure 3) 1. This negative effect is amplified when using a shielded cable. However, the overvoltage is limited to twice the DC bus voltage. The voltage rise time at the output of the drive, often referred to as dv/dt, generates higher transient peak current at higher switching frequencies. This is the result of parasitic capacitance (occurs when two conductors, such as the motor and the motor cable, at different potentials are in close physical proximity to one another. They are affected by each 1 GAMBICA Association for Instrumentation, Control and Automation, GAMBICA Technical Report N 1, Second Edition Variable Speed Drives and Motors, Motor Insulation Voltage Stresses under PWM Inverter Operation. Schneider Electric White Paper Revision 0 Page 3

others' electric field and store opposite electric charges like a capacitor). These transient currents increase the drive, cable, and motor losses. Peak voltage: 664 Volts Peak voltage: 824 Volts Peak voltage: 1300 Volts Figure 3 Longer cable lengths between drive and motor produce higher peak voltage at the motor terminal The most common IEC and NEMA standards, technical specifications, and guidelines for admissible voltages and current for various motor types are highlighted in Figure 4 2. The admissible overvoltage is dependent upon the class of the motor insulation. The relevant IEC and NEMA standards include the following: Figure 4 Limit lines for voltages of multiple motor types IEC 60034-17 Limit line for general purpose motors when fed by frequency converters, 500V motors. IEC 60034-25 Limit for converter rated motors: curve A is for 500V motors and curve B is for 690V motors. NEMA MG1 Definite purpose inverter-fed motors.. 2 GAMBICA Association for Instrumentation, Control and Automation, GAMBICA Technical Report N 1, Second Edition Variable Speed Drives and Motors, Motor Insulation Voltage Stresses under PWM Inverter Operation. Schneider Electric White Paper Revision 0 Page 4

For critical applications, a motor IEC60034-25 class B or NEMA 600V shall be specified. To reduce risk of motor fault when used with speed drive motor, IEC60034-25 B or NEMA 400 should be prescribed. Another side effect of using a VSD is the degradation of motor bearings. This is caused by common mode voltage generated by the inverter of the VSD (noise induced into a cable by the switching) and it generates high frequency current into the bearings of the motor. Depending upon the type of motor, and whether or not the bearing is isolated, three different common mode current loops could occur in the motor: 1. A loop between stators, windings, and the motor shaft. In this case the induction current flows around the bearing twice. 2. A loop between parasitic capacitor windings and motor shaft connected to ground by the load. This case can occur when the frame is not adequately grounded. The pulse capacitive current flows to the drive end bearing. 3. A loop between the parasitic capacitor of the stator, rotor windings, frame, and bearing. In this case, the frame is correctly connected to ground and the bearing current is a percentage of the common mode voltage. The bearing current occurs because of capacitive electrostatic discharge. Preventive measures In order to limit the impact of overvoltage and current peaks, several solutions should be evaluated. The viability of each solution is dependent upon the environment of the application. Software Protection Some VSDs are pre-configured with software which makes the solution more dependable. These modern variable speed drives always integrate a motor control that prevents a condition called double transition. This occurs when, simultaneously, one motor phase switches from minus to plus DC while another phase switches from positive to negative. Figure 5 Impact of software on the prevention of a double transition condition No software-assisted correction Software sets time limit between two PWM voltage pulses A PWM pulse which is too short with respect to the time constant of the cable can lead to the superimposition of 2 oscillations thus generating an overvoltage greater than 2 times the voltage bus DC condition. The latest generation of VSD technology avoids the superimposition of voltage reflection situation by setting a minimum time between two PWM voltage pulses (see Figure 5). Although setting this time limit slightly degrades the speed drive performance (-3% of torque), under normal conditions overall system performance is not impacted. Schneider Electric White Paper Revision 0 Page 5

Output reactor Output reactors oppose rapid changes in current and are generally installed in motor driven equipment to limit starting current. They may be used to protect variable-frequency drives and motors. In essence, a motor choke associated with the parasitic capacitance of the motor cable reduces the dv/dt and peak voltage. The effect will depend on the cable type and length. However, care is needed as reactors can theoretically extend the duration of overshoot (when an electronic signal exceeds its target) if an improper output reactor is selected. Output dv/dt filter Output dv/dt filters are the most cost effective solution to guarantee motor protection and reduction of overcurrent impact on speed drives. This filter reduces the dv/dt so the overvoltage effect and the capacitive leakage current between phases and phases to ground are minimized. Such filters offer flexibility because they can be used with most motors and any cable (independent of the type and length) without creating a problem. This method is recommended if the specifications of a particular motor are unknown. Sinus filter A special design of low pass filter (an electronic filter that passes low-frequency signals and reduces the amplitude of signals with frequencies higher than the cutoff frequency), called a sinus filter, allows high frequency currents to be shunted away. The result is that the voltage waveform at the motor terminal becomes pure sinusoidal. The differential sinus filter allows the complete suppression of the overvoltage effect, and reduces electro-magnetic compatibility (EMC) disturbance. Figure 6 Diagram of how a sinus filter works +VBUS Inverter -VBUS a b c Lf Lmc Cf Cmc CABLE 3*Cmcable Motor Cm L O A D Differential mode filter Common mode filter If the Sinus filter is associated with a common mode filter, this allows for the suppression of bearing currents (see Figure 6) and the reduction of the conducted EMC disturbances to the mains. The combination of those two filters presents the most robust solution for avoiding VSD-to-motor connection issues. This solution is also very cost effective if a long motor cable is used as long as a shielded cable is not required. Application Examples Some application areas are more directly impacted by the long cable length phenomenon than others. For example, in hoisting applications, motors spend a large part of their operating life in braking mode. The braking energy is transferred through freewheeling diodes back on to the intermediate DC link, thereby generating a 15-20% increase in the DC link voltage (and also, therefore, an increase in the the peak motor voltage). The effect is similar to increasing the voltage supply by up to 20%. In such cases, a 400V application should be treated as if it was being supplied with 480V. In applications where Schneider Electric White Paper Revision 0 Page 6

motors are run in parallel, the appropriate cable length should be calculated based on the sum of all the cables. For example, if three motors in parallel are connected to a single VSD, each with a 20 meter (66 foot) cable, the total length that should be calculated in not 20 meters, but should be 60 meters (197 feet). Precautions must be taken to protect the VSD from any unexpected tripping. Table 1 Recommended preventive measures will depend on motor characteristics and cable length Motor cable length (unshielded cable) Motor conforming to IEC60034-25 Motor NOTconforming to IEC60034-25 1 m (66 ft) < Lm < 50 m (164 ft) Filter not required dv/dt filter 50 m (66 ft) < Lm < 100 m (328 ft) Filter not required Sinus filter 100 m (328 ft) < Lm < 300 m (984 ft) Filter not required Sinus filter 300 m (328 ft) < Lm < 500 m (984 ft) dv/dt filter Sinus filter 500 m (328 ft) < Lm < 1000 m (984 ft) Sinus filter Sinus filter Note: When calculating cable lengths for the purpose of guarding against these overvoltage situations, a shielded cable should count as twice the length of an unshielded cable. For example, if a shielded cable is 100 meters in actual length, it should be considered to be equal to a 200 meter length standard cable in the calculation. Schneider Electric White Paper Revision 0 Page 7

2013 Schneider Electric. All rights reserved. An Improved Approach for Connecting VSD and Electric Motors Conclusion When variable speed drives (VSD) are used with motors, a combination of fast switching transistors and long motor cables can cause peak voltages up to twice the DC link voltage. In extreme cases, this high peak voltage can cause premature ageing of motor winding insulation which leads to overall motor failure. To ensure that motor life time is not compromised, a number of simple steps can be taken: Specification of a motor designed for speed drive applications (IEC60034-25 B or NEMA 400 should be prescribed). Specification of VSDs that integrate voltage reflection superimposition software suppression If possible reduce to a minimum the distance between motor and VSD If possible use unshielded cables Reduce the VSD switching frequency (a reduction to 2.5KHz is recommended) Following these simple recommendations, a 300 meter (984 feet) long cable (or shorter) can be utilized without having to purchase any additional options. For cables above 300 meters (984 feet) in length, the use of a dv/dt output filter or sinus filter is recommended depending upon the circumstance. If motor insulation levels are unknown (e.g., retrofit application), or if non-standard motors are deployed, depending on the motor cable length, a dv/dt filter or a sinus filter is recommended. About the authors Heu Vang is a Senior Power Conversion Engineer at Schneider Electric's Center. He holds a PhD in Electrical Engineering from INSA de Lyon, Villeurbanne, France. He is the head of Power Conversion system design team in Schneider Electric Drives centers in France and Japan. Marco Chiari is a senior VSD expert in Schneider Electric's Industry division. He holds a Bachelor s degree in Software Engineering from Politecnico di Milano. He has several years of experience in industrial applications with focus on variable speed drive automation. He has contributed to EU industrial automation fieldbus network projects. He is chairman of Gimelec, France, an industrial association of electrical manufacturers focused on intelligent energy management. Schneider Electric White Paper Revision 0 Page 8