PROPOSED SPECIFICATION FOR ALUCOBOND PLUS Aluminium Composite Panel Cladding System Flat Stick Panel System - 4mm thick

Similar documents
PROPOSED SPECIFICATION FOR ALUCOBOND PLUS Aluminium Composite Panel Cladding System Fixed Watertight Cassette Panel System - 4mm thick

SECTION STANDING SEAM METAL ROOF

SECTION METAL WALL PANELS

SECTION STANDING SEAM METAL ROOFING

Preformed Metal Roofing and Siding

SECTION ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

City of San Diego, CWP Guidelines

Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW

SECTION PREFORMED METAL STANDING SEAM ROOFING

SECTION PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK

PART 1 GENERAL 1.1 SECTION INCLUDES

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023

SECTION METAL COMPOSITE MATERIAL WALL PANELS

Holiday Inn Express & Suites Covington (Newton County) 1. Standing-seam metal roofing, custom fabricated.

Fire Resistant Aluminum Composite Material Building Panels (FR) Section 07410

Composite Panel Firewall Systems

SECTION GUARDA SECURITY WINDOW SCREENS

GUIDELINE SPECIFICATIONS

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

I-Line - Snap-On Feature

SECTION STANDING SEAM METAL ROOFING

SECTION ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

Sapa: SECTION ARCHITECTURAL ALUMINUM HANDRAILS AND RAILINGS

SPECIFICATION Section Insulated Precast Concrete Wall Panels

Schlüter -KERDI-BOARD Substrate, structural panel, bonded waterproofing

Profiles in stock Standard catalogue. Discover the possibilities with aluminium profiles from Sapa

JANUARY, 2016 TR-7100 Windows (Fixed) 1 EC ALUMINUM WINDOWS Guide Specs

Pipe Clamps and Accessories

Light Architecture. Colors Sweden. Light

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades

SPECIFICATION Aluminum Module Frames. Allowed anodization before fabrication for clear frames.

FIRE RATED GLAZING System Guide

DIVISION 8, METAL SOUND CONTROL DOOR ASSEMBLIES PART 1 GENERAL 1.1 RELATED DOCUMENTS

A. Work on this project shall consist of, but is not limited to, the following:

Colonnade Security Pipe

INSTRUCTIONS FOR COORDINATION SECTION SOLID SURFACE FABRICATIONS

Steel Panel Frame. Exterior Steel Sheeting. Optional Rigid Insulation. Optional Steel Insulation Liner

The BASA Guide to the ISO Classification of Sealants for Building Construction

Master Panel 1000 W Wall

PMA MEDOC SHELLS USER S GUIDE

BETONYP building boards. The modern way of living.

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

Installation Window Building In Details

Assessing Curtain Walls

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

Master Panel 1000 R5 Roof

12.1 Schlüter -KERDI-BOARD

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec Master Spec Page 1

DENVER MODEL 30 X 30 SPECIFICATIONS

Fire Resistant Systems

Product Data Sheet ROCKPANEL Rockclad

1. The General conditions of the Contract and Supplementary General Conditions apply to this Division, except as qualified herein and/or excluded.

Sun Windows General Information Sun New Construction Window Installation Instructions

Façade panels for interior cladding on a wooden supporting structure

Installation guide for the SafeLine type anchorage device. Tested in compliance with EN 795: No.: SE-...

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

PTFE Slide Bearings 04/10 149

Temperature C Cure time to reach hours LSS > 1MPa minutes

PLASTIC VOLUME CONTROL DAMPERS OVERVIEW TYPE: GGB

ModuSec. Secure and efficient IT room solutions. Turnkey Modular Construction Fast clean build to any size or shape

James M. Pleasants Company

TARIFF CODE and updates standard

ENGINEERING SPECIFICATION PULTRUDED DYNARAIL FIBERGLASS LADDER & LADDER CAGES

Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood

Table of Contents PART 1 WINDOW SELECTION GUIDE. Window and Door Selection Guide

Test Report No. C829QPEN

Dubai Municipality Standard DMS 1: Part 5: 2004

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Architectural. Roofing. Basis of Design

Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description

INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP

Industrial Adhesives and Tapes Division 3M Center Building 225-3S-06 St. Paul, MN

Isover HVAC Application Handbook Installing fire protection insulation to metal ductwork

Industry. Rail Leading Innovation in a Dynamic Industry. Sika Services AG

SERIES NG 1800 STRUCTURAL STEELWORK

7. Installation. installation CAST-IN WINDOW SYSTEM 7.1. INSTALLATION OF WINDOW MAIN FRAME

INNOVATIVE. ADAPTABLE. ENERGY EFFICIENT.

FLASHMAN WINDOW AND DOOR FLASHING SYSTEM. Product. Scope. Appraisal No. 573 [2013]

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24,

PRODUCTBLADEN GT ROCKPANEL STRUCTURE

Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.

GigaCrete Specification PlasterMax

CHAPTER 7: Building Systems ROOFING SYSTEMS

SECTION EXPANSION CONTROL

Hoesch Matrix System individuell. ThyssenKrupp Steel Europe Thinking the future of steel

Construction. Sikadur-Combiflex. Sealing system for cracks and problem joints with large movements DESCRIPTION

STANDING SEAM SHEET METAL ROOFING

GUIDELINES FOR INSTALLATION OF AIR CONDITIONING UNITS PHILLIP STREET, SYDNEY

COLORADO MODEL. 35 x 65 SPECIFICATIONS

V-joint fascia soffit systems

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

FIREPROOF Panels Trimoterm

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality

Cable ladder installation at S.C.M. Chemicals Limited s titanium dioxide Plant in Western Australia

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope

Two most common lock nut groups: 1-Prevailing Torque Type Lock Nuts:

Transcription:

1. SCOPE OF WORK The scope of work includes the design, supply fabrication and installation of Alucobond PLUS aluminium composite panel cladding, complete with all necessary sub-structures, anchors, hardware and fittings to provide a total installation, fully in conformity with the requirements and intent of the drawings and specification herein. The cladding system shall be installed complete with matching copings, flashings etc. by an approved cladding specialist subcontractor in accordance with the manufacturer's recommendations. 2. DESIGN CONCEPT The proposed Alucobond PLUS cladding shall be based on a flat stick panel system and divided into individual panels as indicated on architectural drawings. A typical panel shall be bonded to suitable support members with an adhesive system that is supported by the adhesive manufacturers installation methods/specification and warranty. The installation method must be performance certified to meet the intended application and applied loads. Application of bonding systems shall be in strict conformity with the manufacturers specifications and recommendations. A construction joint of 8mm minimum shall be provided between cladding elements to cater for easy panel installation. All fixing and joint details shall be designed to provide for the expected thermal and structural movements. To conceal fixings and form a watertight seal, seal construction joint with a suitable silicone or polyurethane sealant. Sealant applied to be of a type in accordance with sealant manufacturer's recommendations. The edge of each panel (4 sides) shall be returned to provide a painted aluminium surface to receive the sealant. Raw cut edges with exposed core material to receive sealant shall not be permitted and are unacceptable. The system and method must be supported by the sealant manufacturers warranty. Horizontal cladding areas ideally should have a slope of 1:15 (4 approx) and to prevent staining should slope away from visible vertical facade areas. 3. DESIGN CRITERIA All Alucobond PLUS composite panel cladding shall be so designed to meet or exceed specified performances required for the prevailing local weather conditions. 3.1. Design Wind Loading : N/m2 positive and negative No cladding element shall sustain permanent deformation or failure Page 1 of 5

under loading equivalent 1.5 times the design wind pressure specified. 3.2. Deflection: Deflection of any aluminium frame shall not exceed 1/150 of the clear span. 3.3. Expansion and Contraction The cladding shall be so fabricated and erected as to provide for all expansion and contraction of the components. Any temperature change due to climatic conditions shall not cause harmful buckling, opening of joints, undue stress on fastening and anchors, noise of any kind or other defects. 3.4. Flatness With a gloss of 30% according to GARDNER Scale, the cladding surface taken individually shall not have any irregularities such as oil canning, waves, buckles and other imperfections when viewed at any position but not less than at an angle of 15 degrees to the true plane of the panel, with natural lighting of incident of not less than the same angle. 4. MATERIAL AND FINISHES 4.1. Cladding Material All cladding shall be 4.0mm thick Alucobond PLUS aluminium composite panel comprising a core containing not less than 70% non combustible mineral filling sandwiched between two skins of aluminium alloy PERALUMAN-100 (AlMg1-NS41) (a) Aluminium skin: 0.5mm thick (b) Mechanical Properties: : Tensile strength 130 N/mm2 0.2% proof stress 90 N/mm2 Elongation 5.65 So 10% Modulus of Elasticity 70,000 N/mm2 (c) Vibration: Average airborne sound transmission loss and Noise Damping R W 26 db (DIN 4109) (d) Rigidity (E x I) : 0.240 knm2/m (e) Panel weight : 7.6kg/m2 Page 2 of 5

(f) Finish The external cladding panel surface shall be factory prefinished by the manufacturer with a Fluoropolymer coating of either PVDF or FEVE or combination of both applied through a "REVERSE ROLLER COATING" process. Total dry-film thickness of the coating shall be 25 microns minimum consisting of a chromate conversion coating, an inhibitive primer and a top coat. The coated surface shall comply strictly with: EN13523 Coil Coated Metals Test Methods as required by ECCA (European Coil Coating Association) to achieve The Quality Label Category 1. AAMA 2605-11 The finished surface shall be factory protected with a self-adhesive peel-off foil, tested to withstand at least 3 months exposure to local weather conditions without losing the original peel-off characteristic or causing stains or other damages. Application of the Fluoropolymer coating system by means of spray coating before or after forming and shaping of the cladding elements shall not be permitted. The reverse side of the cladding panel surface facing the wall shall be in mill finish. (g) Colour/Gloss : As per ALUCOBOND standard colour chart with approx. 30% gloss according to GARDNER scale 4.2 The Alucobond PLUS ACM shall be CodeMark Certified for use as external cladding on buildings of type C construction according to BCA and tested in accordance with Australian and International Standards listed below. Test Description Result AS 1530.3 Simultaneous determination of Ignitability Index 0 Ignitibility, Flame Propagation, Flame Propagation 0 Heat Release and Smoke Release Heat Release 0 Smoke Release 0-1 ISO 9705 EN1305.1 DIN 4102.1 UBC 26-9 Full scale Room Test For Surface Products Classification Of Reaction To Fire Performance Fire Behaviour of Building Material & Elements NFPA 285 Intermediate Scale Multi Storey Flammability Test Group 1 Material according to BCA Specification C1.10.4 (b) (i) SMOGRA 1.385 m 2 /s 2 B s1,d0 B1 Passed 4.3. Aluminium extrusions Non visible extrusion shall be of aluminium alloy AA 6063-T5 in mill finish. Page 3 of 5

4.4 Double Sided Tapes Shall be 3M VHB 4991 or Tesa ACX Plus 7078 applied in accordance with the tape manufacturers recommendations, including all pretreatment, primers, surface preparation, processes and procedures to ensure bonding surfaces achieve maximum bond. 4.5. Fixings (a) Fasteners, including concealed screws, nuts, bolts and other items required for connecting aluminium to aluminium or aluminium to steel shall be in accordance with AS 3566.2 and of a type to suit its application and exposure conditions. Class 1 and 2: Internal applications. Class 3: External applications, moderate industrial and marine applications. Class 4: Severe marine applications (b) (c) Blind rivets used for fastening Alucobond PLUS panel to aluminium sub-frame shall be of aluminium alloy with stainless steel mandrel. All fixing anchors, brackets and similar attachments used in the erections, shall be of aluminium, non-magnetic stainless steel, zinc coated steel, or hot dip zinc galvanised steel. 4.6. Dissimilar Materials Where two surfaces of dissimilar material come into contact, such surfaces shall be insulated with a layer of PVC or Polyethylene tape. 5. FABRICATION 5.1. All cladding panels shall be factory fabricated and assembled in compliance with the manufacturer's Data Sheets and to the best standard of workmanship under experienced factory supervision and control. 5.2. All panels shall have their edges returned to ensure a full strength bond is achieved by the joint sealant. 5.3. If reinforcement of the panel will be required, an extruded aluminium profile of suitable cross-section and strength shall be bonded to the reverse side of the Alucobond PLUS panel using "3M VHB4991" or "Tesa 7078 ACX Plus" double sided tape. Application of bonding systems shall be in strict conformity with the manufacturer's specification and recommendations. 5.4. Each panel shall be marked on the reverse side for easy identification of size and location. Page 4 of 5

5.5. Finished panels shall be stored and transported to site in vertical position, face-toface resp. back-to-back, with adequate protection to prevent scratches and dents. 5.6 The factory applied protective peel-off foil shall only be removed after the panels have been installed on site. 6. INSTALLATION 6.1 Panels shall be stored on site in vertical position, face-to face resp. back-to back-, with adequate protection to prevent scratches and dents. 6.2 Any component parts which are observed to be defective in any way, including warped, bowed, dented, abraded and broken members must not be installed. Member or parts which have been damaged during installation or thereafter before the time of final acceptance shall be removed and replaced. 6.3 No cutting, trimming, welding or brazing of any component parts during erection, in any manner which would damage the finish, decrease the strength or result in a visual imperfection or failure in performance shall be executed during erection. Component parts which require alteration shall be returned to shop for fabrication, if necessary replaced with new parts. 6.4 Anchorage of the cladding structure to the building structure shall be by approved methods in strict accordance to the specification and approved shop and/or erection drawing. Supporting brackets shall be so designed as to provide three-dimensional adjustments and accurate location of cladding components. 6.5 All component parts shall be installed level, true to line with uniform joints and reveals. Maximum deviation for vertical member: 3mm max. in a 5.200m run and 5mm max. in an 11.00m run. Maximum deviation for horizontal members: 3mm max. in an 8.500m run. Maximum offset from true alignment between the abutting members shall not exceed 1.0mm. The tolerance of the width of the joints between two panels shall be maximum ± 2mm. 6.6 Cladding panels shall be left protected by the factory applied peel-off foil as long as possible. Under no circumstances shall the peel-off foil on individual panels be partially removed and left exposed to weathering. 6.7 Before handing over of the completed cladding, all peel-off foil shall be removed. Panels which were exposed to weathering without peel-off foil shall be cleaned in accordance with manufacturer's recommendation. Page 5 of 5