Studying Transient Lightning Effects on 230 KV Double-Circuit Lines using Tower Modeling

Similar documents
zcable Model for Frequency Dependent Modelling of Cable Transmission Systems

IJCSN International Journal of Computer Science and Network, Volume 2, Issue 4, August 2013 ISSN (Online) :

Lightning Arresters P KVA P KVA. Description & Installation

Lightning current simulation in the laboratory - parameters, procedures and test equipment -

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

EVALUATING WAVE FILES TO DETERMINE THE SEVERITY OF THE ULTRASONIC EMISSIONS

Transient and Lightning Protection for the Water Industries

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Following are definitions for major parameters to consider when selecting a power line polarity protection diode for an automotive application.

13.10: How Series and Parallel Circuits Differ pg. 571

Reduction of Lightning Caused Interruptions on Electric Power Systems Reduction Des Compures Dues a la Faudre Dans Les Reseaux

TWO-DIMENSIONAL FINITE ELEMENT ANALYSIS OF FORCED CONVECTION FLOW AND HEAT TRANSFER IN A LAMINAR CHANNEL FLOW

An extended EMC study of an electrical powertrain for transportation systems

SES Training & Certification Programs Welcome to the SES Grounding, EMI and Lightning Academy

Discussion on Class I & II Terminology. IEEE PES Transformers Committee Fall Meeting 2011 Boston, MA

SLOT FRINGING EFFECT ON THE MAGNETIC CHARACTERISTICS OF ELECTRICAL MACHINES

POWER AND VOLTAGE RATING

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Telecommunication Line Protectors

Study of Lightning Damage Risk Assessment Method for Power Grid

Analysis of Pollution Impact on Potential Distribution of Suspension Type Discs Insulators in Overhead Lines

Separation of power and information technology cabling

Joslyn Clark Controls, Inc.

ADVANCED LOCAL PREDICTORS FOR SHORT TERM ELECTRIC LOAD

Line Reactors and AC Drives

Substation Grounding Study Specification

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

EFFECTS OF CORONA RING DESIGN ON ELECTRIC FIELD INTENSITY AND POTENTIAL DISTRIBUTION ALONG AN INSULATOR STRING

The following table shows approximate percentage wise the

How To Test For Safety On A Power Cable

EVALUATION OF CURRENTS AND CHARGE IN SURGE PROTECTIVE DEVICES IN LOW-VOLTAGE DISTRIBUTION NETWORKS DUE TO DIRECT LIGHTNING STRIKES

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

Chapter 9 Balanced Faults

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

Design of Bidirectional Coupling Circuit for Broadband Power-Line Communications

Mode Patterns of Parallel plates &Rectangular wave guides Mr.K.Chandrashekhar, Dr.Girish V Attimarad

Implementation of the Movable Photovoltaic Array to Increase Output Power of the Solar Cells

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

Power System review W I L L I A M V. T O R R E A P R I L 1 0,

A Custom-made MATLAB Based Software to Manage Leakage Current Waveforms

Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection

Effect of Remote Back-Up Protection System Failure on the Optimum Routine Test Time Interval of Power System Protection

SECTION 2 Transmission Line Theory

Coupling Effect in Substation Ground Measurements

MEASUREMENT OF TRANSFER IMPEDANCE AND SCREENING ATTENUATION EFFECTS ON CABLES USING TRI-AXIAL METHOD

FEASIBILITY OF ELECTRICAL SEPARATION OF PROXIMATE GROUNDING SYSTEMS AS A FUNCTION OF SOIL STRUCTURE

Fault location on power cables. Fault location on power cables

An experimental investigation of heat transfer of free convection on triangular fins in order to optimize the arrangement of fins

Optimizing the hydraulic designing of pressurized irrigation network on the lands of village Era by using the computerized model WaterGems

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

An Ethernet Cable Discharge Event (CDE) Test and Measurement System

Power surges can also be generated by equipment in your facility such as:

This is a preview - click here to buy the full publication TECHNICAL REPORT

Resistors. Some substances are insulators. A battery will not make detectible current flow through them.

Assessment of the Technical Issues relating to Significant Amounts of EHV Underground Cable in the All-island Electricity Transmission System

LIGHTNING DETECTION IMPROVEMENT FALLS BROUGHT TO ESKOM S TRANSMISSION LINE DESIGN AND FAULT ANALYSIS

High Voltage Transient Analysis

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Charged cable event. 1 Goal of the ongoing investigation. 2 Energy sources for the CDE. Content

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Power over Ethernet plus Isolation requirements. David Law 3Com

GPR Polarization Simulation with 3D HO FDTD

Automatic Train Control based on the Multi-Agent Control of Cooperative Systems

Project description. Power Electronics for Reliable and Energy efficient Renewable Energy Systems

HEAT TRANSFER IM LECTURE HOURS PER WEEK THERMODYNAMICS - IM _1

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

Fusible Disconnect Switch

Poznan University of Technology Faculty of Electrical Engineering

A Practical Guide to Dielectric Testing

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Submarine Cable Power Transmission using DC High-Voltage Three-Level Converters

INTERNATIONAL STANDARD

THE LIGHTNING PROTECTION INTERNATIONAL STANDARD

Low-resolution Image Processing based on FPGA

INVESTIGATION OF ELECTRIC FIELD INTENSITY AND DEGREE OF UNIFORMITY BETWEEN ELECTRODES UNDER HIGH VOLTAGE BY CHARGE SIMULATIO METHOD

Design of an U-slot Folded Shorted Patch Antenna for RF Energy Harvesting

Estimating Line-Flow Limits

Design and Simulation of Soft Switched Converter Fed DC Servo Drive

The Application and Benefits of Multi-phase Auto-reclosing

DDX 7000 & Digital Partial Discharge Detectors FEATURES APPLICATIONS

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Experiment NO.3 Series and parallel connection

Electromagnetic Wave Simulation Software Poynting

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

EMI in Electric Vehicles

Power Quality Standards for Electric Service

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

An Efficient AC/DC Converter with Power Factor Correction

IEC ESD Immunity and Transient Current Capability for the SP72X Series Protection Arrays

DRAFT. University of Pennsylvania Moore School of Electrical Engineering ESE319 Electronic Circuits - Modeling and Measurement Techniques

Nexus Technology Review -- Exhibit A

Common Emitter BJT Amplifier Design Current Mirror Design

Parametric variation analysis of CUK converter for constant voltage applications

Transcription:

International Journal of Science and Engineering Investigations vol. 2, issue 19, August 2013 ISSN: 2251-8843 Studying Transient Lightning Effects on 230 KV Double-Circuit Lines using Tower Modeling S. M. Hassan Hosseini 1, Ali Rostami 2, Samed Hasannia Ghassab 3 1,2,3 Islamic Azad University, South Tehran Branch, Tehran, Iran ( 1 smhh110@azad.ac.ir, 2 arostami68@gmail.com, 3 Hasannia.samed@gmail.com) Abstract- Excess lightning voltage in long transmission lines are of great importance. In this article, we attempt to study the 230 KV double-circuit transmission line. In the carried out study, in order to evaluate phase to earth sparks, and tower side sparking to conductors, three prevalent tower models in transient studies including simplified multistory, and simplified extended line model were evaluated. Results obtained from simulations using ATP/EMTP software will prove helpful in finding the best model in terms of performance against lightning. Keywords- Excess Voltage, Transient Behavior, Multistory Model, Simplified Multistory Model, Simplified Extended Line Model, ATP/EMTP Software some extent. One of the suitable new proposed models for towers is the, which is a parallel R-L model with wide usage in Japan for analysis of thunder strikes. II. SYSTEM MODEL The 230 KV double-circuit transmission line is used in some regions based on the special conditions of transmission paths. Figure (1) shows the structure and geometrical parameters of the studied tower. The tower foot resistance is 10 ohms, and wave range of the thunder strike is 50 KA. [6]. I. INTRODUCTION Lightning, as the most important external source of excess transient voltage generation in power networks. The added importance of transient voltages caused by lightning can be found in their destructive role in power networks. With the development of power transmission lines and the importance of power supply to different regions, power transmission line cuts due to lightning strike has attracted the attention of man engineering and designers of power transmission line. Lightning can cause destruction of conductors, and this problem mainly results in power line cuts leading to power outages. The problem of modeling transient behavior of a tower at the time of lightning strikes in very important, and was accomplished in 1930. For a well-designed transmission line, direct contact of phase conductors rarely occurs. Nonetheless, lightning strikes account for numerous yearly exits due to sparking phenomena from towers to conductors (back flashover) [2]. Field measurements and tests are effective tools in evaluating and obtaining insight of transient structure of a tower. Insulative design of power systems and studying the behavior of lightning and thunder strikes on power systems is necessary. Therefore, excess voltage from thunder strikes is an important factor in conserving post and power station instruments [3]. Hence, a combination model from transmission lines and tower are employed for analyzing the effect of thunder strikes on power systems, and some studies have been carried out in this regard, which based on the applied model for the tower, it is expected that results will differ to III. Figure 1. Tower model DIFFERENT TOWER MODELS In order to model the tower in form of a transmission line, the specific impedance and wave velocity must be determined. 19

Then, they can be modeled using the steady transmission lines model. Further, we will attempt to examine different models for tower modeling, which have been obtained using theoretical laboratory approximations. Figure (3) shows the simulated circuit in ATP/EMTP for the multistory tower. A. Multistory Model The tower and its are shown in figure (1). In this model, the transmission line tower is considered as a collection of series circuits along with parallel R-L circuits. The mentioned circuits signal attenuation of fluid wave along the length of the tower. Because only R-L parameters for 500 KV transmission line are accessible, therefore in order to use them for a 230 KV sample, geometrical dimensions must be converted. For this purpose, equations (1) to (4) have been employed. Here γ is coefficient of diffusion equal to 0.8, α is coefficient of damping equal to 1, V t is wave diffusion velocity equal to 300m/µs[8, 9]. ( ) ( ) (1) Figure 3. Multistory equivalent circuit ( ) (2) ( ) ( ) (3) ( ) (4) The tower s is shown in figure (2), and values matching this model are given in table 1. Impedance for each section of the tower is a constant value given in reference [7] for all towers. B. Simplified Multistory Model In this model, the parallel R-L circuits present in the are eliminated. One of the reasons for sparking in the is the presence of the parallel R-L circuits. Hence, simulation has been carried out using the simplified Multistory model, in other words without the parallel R-L circuits [8, 9]. The specific impedance and other parameters of the simplified model are the same as those of the multistory tower. Moreover, the equivalent circuit used in ATP/EMTP software is shown in figure (4). Figure 4. The simplified multistory equivalent circuit TABLE I. R1(Ω) R2(Ω) R3(Ω) R4(Ω) R (Ω) Figure 2. The of a tower EQUIVALENT PARAMETERS OF THE MULTISTORY MODEL 12/81 18/13 18/13 33/47 10 L1(mh) 0.00273 Zt1(Ω) 220 L2(mh) 0.00387 Zt2(Ω) 220 L3(mh) 0.00387 Zt3(Ω) 220 L4(mh) 0.00714 Zt4(Ω) 150 ---- ----- ----- ---- Because the Multistory model is designed for a 500 KV transmission line, and the fact that the height of the 500 KV tower is not the same as the 230 KV tower, therefore evaluating the specific impedance of the tower is necessary. Different relations have been presented regarding the method of calculating the specific impedance of a tower. The relation given in equation (5), while simple and easy, presents an acceptable and adaptable value with the measured specific impedance of the tower. The mentioned equation is obtained from figure (5) and presented as follows [10]: International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 20

( ) (5) Where is the total equivalent radius. R is obtained from equation (6). ( ) (6) Figure (8) to (10) show the range of excess voltages generated on the tower head (place of thunder strikesurge). As seen in the mentioned figures, the highest created excess voltage on the tower head is of the, and the lowest value relates to the simplified extended line, while the simplified stands in between. The model of the tower used in ATP/EMTP software is shown in figure (6). In all conducted simulations, eave velocity is equal to light speed and considered 300m/µs. Figure 8. Range of the generated voltage in the place of thunder strike surge in the Figure 5. Tower equivalent structure Zt1= Zt2= Zt3= Zt4= 126.7(Ω) Figure 6. Impedance equivalent to the simplified extended line IV. EXAMINING SIMULATION RESULTS In this section, results gathered from simulation using ATP/EMTP software are presented. A shockwave has a range of 50 KA, wave front of 1 microsecond, and wave tail of 70 microseconds. The thunder strike current on surge, for example, reaches its peak within the period of 0 to 10 microseconds (wave face), and then reduces to half of this amount within 20 to 100 microseconds (wave tail). The distribution of this current is shown in figure (9). 50% of thunder strikes have a peak current larger than 50 KA. In rare cases, the peak current can surpass 200 KA. In addition, measurement results show that approximately 90% of thunder strikes are negative [11]. Therefore, in this article, the negative peak of thunder strikes was simulated and tested. Figure (7) shows the thunder strike wave simulated in ATP/EMTP software. 0 [ka] -10-20 -30-40 -50-60 0 5 10 15 20 [us] 25 (f ile surge-f inall.pl4; x-v ar t) c:xx0401-gard Figure 7. Shockwave with negative peak Figure 9. Range of the generated voltage in the place of thunder strike surge in the simplified Figure 10. Range of the generated voltage in the place of thunder strike surge in the simplified extended line model Figure (11) to (13) show the range of excess voltage generation in tower arms relative to the ground. It can be seen that the range differences relative to the ground is low in the extended line model and simplified multistory, and the possibility of sparking on this phase is less. However, in the, there is a larger difference in tower arm voltages. International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 21

Figure 11. Voltage range created in tower arms relative to the ground in the Figure 15. Range of the voltage generated on both ends of insulators in the simplified Figure 12. Voltage range created in tower arms relative to the ground in the simplified Figure 16. Range of the voltage generated on both ends of insulators in the simplified extended line model Figures (17) and (18) show the wave forms generated in phases relative to the ground. Figure 13. Voltage range created in tower arms relative to the ground in the simplified extended line model Figure (14) and (16) show the shape of waves generated on both ends of the insulators. Figure 17. Range of excess voltage generated in phases of the multistory model Figure 14. Range of the voltage generated on both ends of insulators in the Figure 18. Range of excess voltage generated in phases of the simplified International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 22

Figure 19. Range of excess voltage generated in phases of the extended line model V. COCLUSION According to the results from simulations for different tower types, and by applying negative polarity waves on the tower, the following results were obtained: 1. For negative polarity, the current range due to thunder strike on the surge point for the extended line model has the lowest amount of excess voltage range, and the Multistory model acquires the highest excess voltage range, while the simplified Multistory model stand in between. 2. According to this negative polarity of voltage ranges from the tower arm to the ground, the gained the highest value, and the simplified extended line had the lowest value. The simplified Multistory model stands in between, and due to the fact that the difference between phase ranges in the extended line model and simplified multistory are not significant, this notions a possibility of equal probability in flashover in all three phases. 3. The voltage range due to thunder strike surge on insulators in the has the highest value, and the simplified extended line model the lowest, while the simplified stands in between. 4. Excess voltage range in phases of the has the highest value, and the simplified extended line model the lowest, while the simplified stands in between. The obtained results indicate that for the examined line, the simplified extended line model is suitable for this tower. [3] N. Nagaoka, A development of frequency dependent tower model,trans". Inst. Elect. Eng. Japan,vol. 111-B, no. 1, pp. 51 56, 1991. [4] T. Hara, O. Yamamoto, M. Hayashi, and T. Nagai, Transmission tower model for lightning surge analysis, Trans. Inst. Elect. Eng. Japan, vol. 114-B, no. 6, pp. 595 600, 1994. [5] Guide to Lightning Protection Design of Power Stations, Substations and Underground Transmission Lines, (in Japanese), CRIEPI Rep. no. T40, 1995. [6] YasuyukiAkagi, keijisato lowe noise conductor for harmonizing 1000 kv transmission lines with the Environment u.d.c.621.315.14.027.89:534.11:[551.556+537.525.3] [7] MasaruIshii,Tatsuo Kawamura, Multistory Transmission'tower Model For Lightning Surge Analysis, IEEE Transactions on Power Delivery,Vol. 6, No. 3, July 1991 [8] T. Ueda, M. Yoda, and I. Miyachi, Characteristics of lightning surges observed at 77 kv substations, Trans. Inst. Elect. Eng. Japan, vol. 116- B, no. 11, pp [9] T. Ueda, S. Neo, T. Funabashi, T. Hagiwara, and H. Watanabe, Flashover model for arcing horns and transmission line arresters, in Proc. Int. Conf. Power Syst. Transients, 1995, pp. 328 333. [10] Power Line Tower Lightning Surge Impedance Computation, a Comparison of Analytical and Finite Element Methods, International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela (Spain), 28th to 30th March, 2012 [11] K.L. Cummins, E.P.Krider, andm.d.malon, ''The U.S.NationalLightning Detection Network TM and Application of Cloud-to-Ground Lightning Data by Electric Power Utilities,''IEEE Transactions on Electromagnetic Compatibility, 40, 4, pp.465-480. S. M. Hassan Hosseini was born in Tehran, in 1969. He received his B.Sc. degree in electrical power engineering from Mashhad Ferdowsi University, Mashhad, Iran in 1993. He received his M.Sc. and Ph.D. degrees in electrical power engineering in 2000 and 2005 from Azad University South-Tehran Branch and Science & Research Branch, Tehran, Iran, respectively. He held the position of Assistant Professor in Azad University South-Tehran Branch from 2005. From 2008 to 2009 he was as deputy and from 2009 till 2011 he was as the manager of electrical engineering department of Azad University South-Tehran Branch. His research interest is transient modeling of transformer, Partial Discharge, High Voltage Engineering, Electrical Insulation, Substation and Hydropower. Ali Rostami received B. Sc. Degree from IAU Boroujerd branch, Lorestan, Iran in electrical engineering, in 2010. He is currently pursuing the M. Sc. degree from IAU South Tehran Branch REFERENCES [1] Esmaeili Naghibi, Sajjad, and Najafi Ravadanegh, Sajjad, Modeling a super distribution tower for analyzing excess voltage of flashovers, 21 st Electrical Engineering International Conference (98-F-PTL-291) 2006 PSC.) [2] Takamitsu Ito, Toshiaki Ueda, Hideto Watanabe,Toshihisa Funabashi, Lightning Flashovers on 77-kVSystems: Observed Voltage Bias Effects and Analysis IEEE Transactions on Power Delivery, Vol. 18, No 2, April 2003 S. Hasannia Ghassab was born in Joybar, Mazandaran, Iran in 1987.He received his B.Sc. degree in Electronic engineering from Amol Shomal University, in 2010. He is currently pursuing the M. Sc. degree in electrical power engineering from IAU south Tehran Branch. International Journal of Science and Engineering Investigations, Volume 2, Issue 19, August 2013 23