ACR Air-Core Reactors Dry Type

Similar documents
FACTS. Solutions to optimise network performance GRID

Transformers. Special transformers Reactors products

MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS

Power Capacitor Units for improved power quality

Introduction. Harmonics and IEEE 519 Page 1 of 19

Table of Contents. TransformerIQ FAQs 1

The design and performance of Static Var Compensators for particle accelerators

Power transformers. Special transformers Railway

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

SF 6 Gas Insulated Switchgear Type SDF for 170 kv

Guidance for upgrading to GB (IEC : 2005, MOD)

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5

Line Reactors and AC Drives

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

High Voltage Power Supplies for Analytical Instrumentation

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Short Circuit Current Calculations

How To Build A Low Voltage Capacitor Lvcp

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Secondary Unit Substations

3. Cooling System Closed-loop Pure Water-cooling. Rated Voltage: 6 ~ 66kV. Rated Current: 4000A (phase current).

Power Transmission and Distribution. Shunt reactors for medium and highvoltage. From development to use

Application Note. So You Need to Measure Some Inductors?

Transformer Design & Design Parameters

Direction of current flow through conductor. Fig. 1 Magnetic field generated by current flow

MV POWER CAPACITORS AND BANKS. All film dielectric MV Power Capacitors QUALITY MADE IN ITALY

CAPACITOR BANK TESTING SWP

RC NETWORKS SALES GUIDE

CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)

Unified requirements for systems with voltages above 1 kv up to 15 kv

6 ELECTRICAL PARAMETERS

Product Data Bulletin

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

Grounding Demystified

HVDC 2000 a new generation of high-voltage DC converter stations

SECTION DRY-TYPE TRANSFORMERS

Current Limiting Protector For Systems rated kV and continuous currents through 5000A.

STRATO LED Drivers 70W, Single output

Specification guide no. 9 Active harmonic conditioner from 20 to 480 A

Lightning Arresters P KVA P KVA. Description & Installation

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle

IRON-CORE REACTORS FOR DETUNING POWER CAPACITORS IN MEDIUM AND LOW VOLTAGE NETWORKS

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Reactive Power Compensation. ABB High Voltage Products June 19, 2013 Slide 1

Capacitor Voltage Transformer. Answers for energy.

FILM CAPACITORS FOR ELECTRONIC LIGHTING

PI144K - Winding 311 APPROVED DOCUMENT. Technical Data Sheet. Generator Solutions AS

High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

Voltage Regulator SPAU 341 C. Product Guide

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

DIRECT CURRENT GENERATORS

Bourns Resistive Products

PM734F - Technical Data Sheet Winding 28

Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty Safety notes Policy Warranty.

MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL MTE Corporation

INTRODUCTION TO HARMONIC ASSESSMENT IN POWER SYSTEMS

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Lead & Magnet Wire Connection Methods Using the Tin Fusing Method Joyal A Division of AWE, Inc.

PI044E - Winding 311 APPROVED DOCUMENT. Technical Data Sheet

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

National Craft Assessment and Certification Program S P E C I F I C A T I O N S

Power Capacitors and Harmonic Filters Buyer s Guide

Typical Data Requirements Data Required for Power System Evaluation

Modeling of Transmission Lines

Principles of Adjustable Frequency Drives

GENERIC REQUIREMENTS FOR UNINTERRUPTIBLE POWER SYSTEMS (UPS) TABLE OF CONTENTS

Earth Fault Detection Basics in Theory

Circulating Current Relay. Type IRXm

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS

Cable Solutions for Servo and Variable Frequency Drives (VFD)

Engineering innovation

The electrical energy produced at the gen

How To Understand The Electrical Power Supply Of A Power Supply System

Hyperlinks are Inactive

2012 San Francisco Colloquium

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

Chapter 11. Inductors ISU EE. C.Y. Lee

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

Iron Powder Cores for Switchmode Power Supply Inductors. by: Jim Cox

INTERNATIONAL STANDARD

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

ELECTRICAL ENGINEERING Vol. III - Induction Motor and Self-Excited Induction Generator - Tze-Fun Chan

Instrument Transformers Application Guide

Earthing Guidance Notes

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

A Practical Guide to Dielectric Testing

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Diesel Engine Driven Generators Page 1 of 6

Low Voltage Products

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements

Transcription:

Air-Core Reactors Dry Type Power compensation Air-Core Reactors () provide a linear response of impedance versus current which is essential for numerous applications. The dry type design is maintenance free and environmentally friendly. Alstom Grid has more than 50 years experience in designing and manufacturing Air-Core Reactors for various market segments around the world, including power generation, T&D networks, industrial facilities, OEMs and electrical test laboratories. For both industrial environments and networks, Alstom Grid offers a broad range of cost-effective solutions: Current-limiting reactors limit the fault currents to levels compatible with existing protection/control equipment and as a result provide for a very cost-effective solution. Neutral-earthing reactors are connected between the neutral of a power system and earth to limit the line-to-earth current to a desired value under system earth fault conditions. Smoothing reactors reduce the harmonic currents and transient overcurrents (ripple) in DC systems. Harmonic filter reactors are usually connected with capacitors and resistors in filter circuits to reduce harmonic content in the network which cause higher losses, high neutral currents and interference with computer and telecommunications equipment and which are responsible for high harmonic distortion levels. Shunt reactors compensate for the capacitive currents of long transmission lines or cables, allowing more active energy to pass through the system. Damping reactors limit the inrush and outrush currents of capacitor banks. Discharge reactors are used in the bypass/ discharge circuit in series compensation systems to limit the capacitor discharge current. Arc-furnace series reactors provide the necessary power factor correction and limit the unstable arc-furnace current and voltage. Power flow control reactors control the current into two or more parallel circuits. Motor starting reactors are connected in series with a motor to limit the inrush current during the motor starting operation. Special applications: test lab reactors are special s used in test laboratories, mainly for current-limiting purposes. Other devices include duplex current-limiting reactors, split-phase shunt or zero tolerance reactors, etc. Customer Benefits High mechanical strength to withstand elevated shortcircuit forces Low noise level for noise sensitive applications Conservative temperature rise for extended service life Customized space saving solutions for installations in compact areas Surface treatment for protection against UV radiation and pollution Minimum maintenance requirements and environmentally friendly GRID 1

Inducing Energy with Success 1. Applications 1.1. Current-limiting This reactor is series connected to the transmission line or to the feeder for limiting the current under system fault conditions to levels compatible with the protection equipment of the circuit. It is a very costeffective solution, as it eliminates the need for upgrading the entire switching and protection system when the short-circuit power of the system is increased. This reactor is designed to offer specified impedance and to withstand the rated and fault (short-time) currents during a specified period of time. 1.1 Current-limiting reactors 1.2. Neutral-earthing This single-phase reactor is used to ground the neutral point of three-phase networks to limit the current in the event of a fault between phase and ground. If the circuit is perfectly balanced, the resulting current flow through the reactor will be zero and there will be no losses. G ~ 1.4. Harmonic filtering The harmonic currents are distortions introduced to the network as a result of the operation of power electronics devices, large inductive machines, etc. 1.4 HV harmonic filter 1.2 Neutral-grounding reactor 1.3. Smoothing Smoothing reactors are used to reduce the harmonic currents and transient overcurrents in the DC system. They are used in HVDC links and industrial applications such as rectifiers, traction systems, etc. These harmonic currents create several network problems, such as: Greater losses Malfunctioning control systems High neutral currents Interference with computers Interference with telecommunications equipment. M 1.1 Current-limiting reactor seismic design 1.3 Smoothing reactor 1.4 Filters reactors 2

1.5.1 SVC Moreover, most utilities impose high fees when a certain HDL (Harmonic Distortion Level) threshold is reached. Harmonic filter reactors, in association with capacitor units and, occasionally, resistors, create a filter circuit tuned to a certain frequency (resonance frequency) so as to reduce, block or provide a low impedance path for the harmonic currents in the audio frequency range. They are connected either in a parallel or in a series configuration. Harmonic filters are typically installed in substations, in SVCs (Static VAr Compensators) and in HVDC links. The reactors are designed to meet specific design criteria such as Quality-factor, tolerance of the inductance between phases and of the reactor itself. Special low Q-factor requirements can be met using an integrated damping circuit. 1.5. Shunt These reactors are used in a parallel configuration to compensate for the capacitive currents of long transmission lines or cables. As a result, they allow the flow of more active energy through the system. In a low-load situation, shunt reactors may be used to reduce the voltage rise due to capacitance of the transmission line and, in so doing, reduce corona losses. In many installations, the reactors are connected to the tertiary winding of the high voltage transformer. 1.5.1. SVC (Static VAr Compensation) SVC applications are used to provide dynamic voltage stabilization, improve synchronous stability and operate as steady-state voltage support. The SVC can also be required for dynamic load balancing in industrial installations using large electrical motors and other equipment with variable loads. Typical applications include steel works (steel mills, 1.5.1 tcr reactor cranes, arc-furnaces), paper mills, mining companies, etc. SVC systems provide dynamic power compensation for utilities and industry networks. The main benefits include dynamic voltage support, improvement of system stability, power oscillation damping, reactive power balancing, flicker control and reduction of losses. SVC normally consists of a combination of thyristor-controlled reactors (TCR), thyristor-switched capacitors and reactors (TSC and TSR), mechanically-switched capacitor banks (MSC) and harmonic filters (HF). 1.6. Damping reactor This reactor is series connected with one or more capacitor banks to limit the inrush currents that occur during their switching operation. It is designed to offer a specified impedance and to withstand the rated current and the fault current in the event of a short-circuit associated with a high frequency discharge current of the capacitor bank. 1.5 shunt reactor connected to tertiary of HV Transformer 1.5.1 thyristor controlled reactors 1.6 Damping reactors 3

1.7. Discharge reactor This application includes reactors for series compensation systems which use capacitor banks series connected to the transmission lines. They: improve voltage regulation improve system transient stability increase transmission line capacity reduce electrical losses and save costs. 1.8. Arc-furnace series reactors The arc-furnace series reactor is connected in series with the electrodes of an arc-furnace used to smelt metals (iron, steel, aluminum, etc.). Its winding has a high mechanical strength to withstand the forces caused by the fast switching operations of the electrical arc and the high harmonic currents which are inherent to the electrical arc. 1.9. Power flow control These reactors are connected in series in a power system (usually a transmission line) to optimize the power flow through modification of the transfer impedance. They change the line impedance characteristic in such a way that the load flow can be controlled, ensuring maximum power transfer over adjacent transmission lines. 2.0. Motor starting The reactor is series-connected with a motor to limit the inrush current during the motor starting operation. After start-up, the reactor is typically by-passed to limit losses in continuous operation. The reactor can be dimensioned to be short-circuit-proof or not. 2.1. Special applications 2.1.1 Test laboratory reactors Test laboratories often require versatile reactors with taps to adjust the inductance value as well as flexible links to connect the reactor in parallel or in series according to test requirements. Usually, the rated current value is low, and the BIL or the short-time current is high. 1.8 Arc-furnace 1.8 Arc-furnace reactor It provides the necessary power factor correction and limits the very unstable arc-furnace current and voltage (flicker), specially during the melting process. 2.1.1 Special reactor for laboratories 4

2.1.2 Duplex current-limiting reactors Duplex currentlimiting reactors Duplex Reactor produce a low reactance under normal conditions Gen. and high reactance under fault conditions, with the advantage 2.1.2 Duplex reactor of a low voltage drop under normal conditions. This type of reactor can be used in systems which always remain isolated. The duplex reactor is designed in such a way that, under normal conditions, the magnetic fields of the two half-coils are opposite, resulting in a low reactance between power supply and load. In case of a fault in one feeding circuit, the fault current flows only through one half-coil, and consequently the opposite flux of the other half-coil is limited by the increased reactance of the half-coil in series with the feeder under fault conditions. 2.1.3 Split-phase shunt reactors Depending on the required ratings, shunt reactors can be manufactured with split-phase design to provide sufficient sensitivity in detecting turnto-turn faults. In this case, unbalance currents between two windings of the reactor can be informed for settings of the protection relays. 2.1.3 Split-phase reactor N1 IN1 I L T N2 I N2 1P1 1P2 1P2 2P2 2.1.4 Zero tolerance reactors It is possible to use a split-phase arrangement (two vertically installed part coils) if the inductance tolerance requirement is 0 (zero). The inductance is set at nominal value by adjusting the spacing of the part coils. 1S1 1S2 A T Alstom Grid has an experienced team of reactive power compensation specialists able to provide customized solutions to meet special customer needs. 2. Manufacture Alstom Grid s reactor windings consist of numerous aluminum or copper conductors connected in parallel. These conductors can be insulated single wires, insulated cables or aluminum profiles separated by fiberglass spacers. The cost-effective solution to be selected, in terms of dimensions and conductor type to be used in each design, depends on the required ratings for the equipment. For encapsulated design, the conductors are mechanically immobilized and encapsulated by epoxy impregnated fiberglass filaments forming cylinders. Depending on the reactor ratings, one or more of these cylinders are connected in parallel between aluminum or copper spiders. The individual cylinders are separated by fiberglass spacers forming cooling ducts. 5

3. Accessories 3.1. Corona rings When it is necessary to eliminate visible corona, Alstom Grid reactors are provided with suitable corona rings made from aluminum tubes. 3.3. Insulators Alstom Grid can provide all the necessary support insulators for the reactors. 3.4. Pedestals The pedestals provided with Alstom Grid reactors maintain the magnetic and electrical clearances required by the reactor design to minimize induced losses. 3.5. Enclosures On request, Alstom Grid can design and supply reactors with enclosures. 3.6. Tapping Reactors can be supplied with taps for variable inductance. Air-Core Reactor construction 1 2 3 Current limiting 4 3.2. Bird barriers On request, Alstom Grid can provide the reactors with bird barriers. The bird barriers consist of a temperature and UV resistant fiberglass reinforced plastic grid with square-shaped openings. The bird barrier does not adversely affect the cooling of the reactor. 5 Fig.01. Air-Core Reactor construction 1/ Lifting lug 2/ Spacers (cooling ducts) 3/ Crossarms (spider) 4/ Terminal 5/ Insulator 6/ Extension brackets (pedestals) 6 6

Cost-effective Solutions 4. Installation 4.1. Location Alstom Grid reactors are suitable for either indoor or outdoor installation. 4.3. Magnetic clearances Alstom Grid s basic guidelines for magnetic clearances are shown in figure 3. Reactors are often installed in existing substations or installed to replace existing reactors. Alstom Grid can design reactors to fit inside space limitations or to be mounted directly onto the existing foundations. Alstom Grid can also design reactors for use inside enclosures. In this case, the reactors are designed to avoid excessive heating. 4.2. Mounting arrangement Reactors can be mounted individually as single-phase units, side-by-side, or as threephase stacks, one coil on top of the other. Special mounting arrangements can be offered in case of space limitations. Figure 2 illustrates options available. Fig 02. Mounting arrangement B C 1.5xDs B 1.7xDs A TOP BOTTOM Ds 1.7xDs 1.0xDs 0.5xDs 0.5xDs 1.0xDs 5. T erminal orientation and hole patterns A: Reactor outer surface Keep metallic parts not forming closed loops outside B Keep metallic parts forming closed loops or large metallic parts outside C Ds: Reactor outer diameter Fig 03. Magnetic clearances Alstom Grid reactors are supplied with NEMA or IEC flat pad aluminum or copper terminals. Other standards can be supplied on request. Figures 4 & 5 show typical terminal orientations and hole patterns. Other terminal orientations and hole patterns can be provided on request. For copper connectors, bimetallic tin-plated interfaces can be provided. Fig 04. 6. Painting After the curing process, the reactor is carefully prepared before painting with a high grade quality enamel, which provides longterm protection against UV radiation. The typical colors are Munsell N6.5 grey, ANSI 70, RAL 7037 and RAL 5024, but other colors can be accommodated on request. In heavily polluted environments, Alstom Grid uses a special painting process (RTV), and reactors can be provided with a top cover to limit the adverse effects of pollution. Fig 05. 7

7. Formulas Some useful formulas: X L Inductive reactance (Ω) f Frequency (Hz) L Rated inductance (H) Q L Rated power (VAr) I N rated current (A) Q Quality-factor (Q-factor) R ac Effective resistance (Ω) at system or tuning frequency X L = 2 x π x x L Q L = I N 2 x x L Q = X L R ac Losses = Q L Q 8. Quality control At Alstom Grid, a continuous quality improvement system is in place based on the constant quest for optimized product design, procurement of materials and components, production and customer service. Products assembled by an experienced and welltrained workforce guarantee maximum customer satisfaction. Alstom Grid Worldwide Contact Centre www.grid.alstom.com/contactcentre Tel: +44 (0) 1785 250 070 www.grid.alstom.com Thanks to this fundamental principle, associated with a formal quality management system, all manufacturing units of Alstom Grid are ISO-9001, ISO 14001 and OHSAS 18001 certified. 9. Testing The reactor test program is carried out using measurement systems specifically developed for the purpose. Tests comply with international standards such as IEC, ANSI or equivalent. Numerous type tests have been successfully performed on Alstom Grid reactors at recognized laboratories such as KEMA (Holland), CESI (Italy), IREQ (Canada), CEPEL (Brazil) and LAPEM (Mexico). Type test reports are available on request. 10. Inquiry data Rated inductance (mh) or impedance (Ω) Rated current (A) Harmonic currents (A) System voltage (kv) BIL (kvp) Rated frequency (Hz) Thermal short-time current (karms)/ duration (s) Mechanical short-time current (kap) GRID Mounting arrangement Rated power (MVAr): for shunt reactors Additional information: seismic conditions, wind load, pollution level, salt spray, space limitations, operating altitude, compliance standard, ambient temperature, humidity, ice load, duty cycle, tap requirements, noise requirements, etc. 11. R&D activities Alstom Grid is at the forefront of innovation. The company boasts an international team of research and development experts with many years experience in the leadingedge technologies emanating from the predecessor companies. Its aim is to develop innovative, advanced technologies that best meet the market s needs at affordable cost and respecting the environment. The Alstom Grid R&D community works with a dedicated team focusing on reacting power compensation and harmonic filtering. One of its key ambitions is continued leadership in manufacturing solutions. GRID-Products-L3-_0602_V3_V2010_08_EN - Alstom Grid, the Alstom Grid logo and any alternative version thereof are trademarks and service marks of Alstom Grid. The other names mentioned, registered or not, are the property of their respective companies. The technical and other data contained in this document are provided for information only. Neither Alstom Grid, its officers nor employees accept responsibility for or should be taken as making any representation or warranty (whether express or implied) as to the accuracy or completeness of such data or the achievements of any projected performance criteria where these are indicated. No liability is accepted for any reliance placed upon the information contained in this brochure. Alstom Grid reserves the right to revise or change these data at any time without further notice. Printed on paper made with pure ECF (Elemental Chlorine Free) ecological cellulose produced from trees grown in production forests under responsible management, and selected recycled three-layer fibres.