FIRE PUMP ESSENTIALS. Chamco Industries

Similar documents
SPP Pumps Inc. Atlanta

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility

TECHNICAL ADVISORY BULLETIN

Fire Pump Plan Review March 2010

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

FAIRBANKS NIJHUIS FIRE PUMPS.

Design & Construction Standards, Revised January

Pressure Limiting Driver (PLD)

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS.

Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

TOPIC: KNOWLEDGE: K1.01 [3.3/3.5] Which one of the following contains indications of cavitation in an operating centrifugal pump?

FIRE FIGHTING PACKAGES

BERMAD Fire Protection

VERTICAL TURBINE AND PROPELLER PUMPS

Axial and Mixed Flow Pumps for Large Volume Pumping

Trash Pumps Models: 56200, , 56201, , 56300, , 56301,

SJT / SJM / SJP Large Vertical Pumps

TECHNICAL INFORMATION Bulletin

TECHNICAL INFORMATION Bulletin

Para la protecció n de la vida y las propiedades, las Bombas de Incendio AC ofrece paquetizados que satisfacen cada necesidad.

300 Series PA Pump and Cooler Assemblies

OPERATION & MAINTENANCE MANUAL. for VERTICAL INLINE PUMPS

Goulds Water Technology

Model: 400E-2M. Bermad Electrically Controlled Deluge Valve with Easy Lock Manual Reset. Installation Operation Maintenance. Application Engineering

Pump Maintenance - Repair

Horizontal Split Case Fire Pumpset Diesel Engine Driven

Model 1210C Battery Powered Pump Shown. Description

The cylinder head bolts tightening stages have been updated as listed in Table 1.

TRAINING BULLETIN Fire Apparatus Pump Test

C. starting positive displacement pumps with the discharge valve closed.

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz

NFPA 20 Update 2013 Edition. Revision Cycle. NFPA 20 Update /1/2013. Goals and Objectives

The Jockey Pump, an Important Part of a Fire Pump System.

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

BERMAD Fire Protection

Approval Standard for Centrifugal Fire Pumps (Horizontal, End Suction Type)

N/NH Truck-mounted fire pump series

FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE

Pumps: Convert mechanical energy (often developed from electrical source) into hydraulic energy (position, pressure and kinetic energy).

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

Fire Protection Pumps

PUMPS TYPE OF PUMP PRESSURE/FLOW RATING CHARACTERISTICS. Centrifugal Low Pressure/High Flow Flow changes when

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

TROUBLESHOOTING GUIDE

BOWIE PUMPS OPERATION - MAINTENANCE

Centrifugal Fans and Pumps are sized to meet the maximum

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Volkswagen Jetta, Golf, GTI 1999, Liter VR6 2V Engine Mechanical, Engine Code(s): AFP 17 Engine-Lubrication (Page GR-17)

Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE

Owner s Manual. Models: 2S5P & 3S5P OPERATION AND MAINTENANCE OF SELF-PRIMING CENTRIFUGAL TRASH PUMPS PEDESTAL DRIVE

Fire Pump Applications

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

3", 4", 6" & 8" Model H Series Alarm Check Valve Installation and Maintenance Guide

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Power Cube Open Source Ecology Page 1. Power Cube. Version 4

BLADDER SURGE CONTROL SYSTEM

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Model F822 thru F834 Mulsifyre Directional Spray Nozzles, Open, High Velocity General Description

Vertical selfpriming Side-Channel Pumps Type WPV

IMPORTANT SAFETY NOTICE

Diesel Engine Driven Generators Page 1 of 6

Pumping Fuel & Fuel Oil

APPENDIX F VIBRATION TESTING PROCEDURE

The conditions below apply to the curves shown on the following pages.

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

world class fire pumps

2" & 3" Poly Wet Seal Pump Instruction Manual

World-Class Fire Suppression Pumping Solutions

Oil and Coolant Circulating Heating System. Model - OCSM

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

Air Eliminators and Combination Air Eliminators Strainers

Minor losses include head losses through/past hydrants, couplers, valves,

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

Clark County Fire Prevention

Bell & Gossett Parts List DHP-650-PL. Replacement Parts for Hoffman Series VBF & Hoffman Series HBF. Boiler Feed Units

Chapter 3.5: Fans and Blowers

TD01211 PIN: NX nd Edition. Water Motor Alarm MODEL: NX010 TECHNICAL DATA

Volkswagen New Beetle 2.0 Liter 4-cyl General, Engine (Engine Code AEG) 17 Engine-Lubrication system (Page GR-17)

Commercial Gas Furnace Upflow

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

2100 AD Mirror Elevator Ball Nut Replacement Procedure

4" SUBMERSIBLE PUMPS

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

Type D3 PROTECTOSPRAY Directional Spray Nozzles, Open, Medium Velocity General Description

MODEL INSTALLATION INSTRUCTIONS

FIXED DISPLACEMENT HYDRAULIC VANE PUMPS BQ SERIES

INSTALLATION, OPERATION & MAINTENANCE MANUAL

Pump Selection and Sizing (ENGINEERING DESIGN GUIDELINE)

Vertical Pumps for the Oil & Gas Industry

First Revision No. 147-NFPA [ Global Input ] Submitter Information Verification. Committee Statement

AABC Specifications for Testing and Balancing HVAC Systems

Horizontal Jet Pumps 1/3-1-1/2 HP

AIR LINE VALVES AND GAUGES

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford

Transcription:

FIRE PUMP ESSENTIALS Chamco Industries

THE FIRE PUMPS FOUR TYPES/STYLES OF FIRE PUMPS Horizontal, split case. (250 usgpm - 5000 usgpm) Vertical Turbine. ( 250 usgpm - 5000 usgpm ) End Suction. ( commercial ) Vertical Inline. ( commercial )

FIRE PUMP TYPES DIESEL DRIVEN HORIZONTAL ELECTRIC DRIVEN HORIZONTAL

FIRE PUMP TYPES JOCKEY PUMP VERTICAL TURBINE FIRE PUMP & ENGINE

ENGINES Engines are UL or FM approved for Fire Service, and built by: Caterpillar ( full range, mostly above 200hp ) Cummins ( limited range, 100-300hp ) Clarke Engine ( best range, 50-700 hp )

RIGHT ANGLE GEAR DRIVES Right Angle Gear Drives are FM approved for Fire Service, and built by: Randolph Manufacturing Amarillo Gear Johnson Gear

FIRE PUMP CONTROLLERS Pump Control panels, for Electric and Diesel drives are UL or FM or ULC approved for Fire Service, and built by: Cutler Hammer Firetrol Metron

FIRE PUMP CONTROLLERS Control panels for Diesel drives and Jockey Pumps:

NFPA 20 Does not specify when or if a fire pump must be installed Specifies: How, Components, Equipment, Power Source are acceptable to use Provides the minimum requirements needed for satisfactory operation of listed fire pumps NFPA 20 covers every type of listed fire pump Most common is centrifugal

Equivalency 1.5 1.5.2 NFPA 20 is not intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed in this standard. AHJ has the final call

NFPA 20 Terms Shall Mandatory requirement Should Indicates a recommendation that is advised but not required

What Makes a Pump a Fire Pump 4.2 Stationary pumps shall be selected based on the conditions under which they are to be installed and used Capacities are based on calculated system demand, and pressures are based on available pressure from the water supply

What Makes a Pump a Fire Pump 4.4.1 Unit Responsibility One supplier for pump, driver, controls Typically falls on the pump manufacturer SHOULD was used not Shall Recommendation, having unit responsibility helps ensure that all components are compatible 4.5 Certified Shop Test Needs to be furnished from the pump manufacturer to the purchaser, and must include head capacity and BHP Why? To verify that the fire pump was tested by the manufacturer prior to shipment and met the conditions.

What Makes a Pump a Fire Pump 4.6.5 Head The Head available from a water supply shall be figured on the basis of a flow for 150% rated capacity. (EG: 1000GPM pump shall be able to reach a capacity of 1500GPM)

What Makes a Pump a Fire Pump 4.7 Pumps, Drivers, and Controllers 4.7.3 A Pump shall not be equipped with more than one driver 4.7.4 Each pump shall have it s own dedicated driver 4.7.5 Each driver shall have it s own dedicated controller

What Makes a Pump a Fire Pump 4.7.7 Maximum Pressure for Centrifugal Pumps 4.7.7.1 The net pump shutoff pressure plus the maximum static suction pressure adjusted for elevation shall not exceed the pressure for which the system components are rated Ex: 1000Gpm @ 145psi, shut off pressure is 168psi, and suction pressure is 30psi. You need to have 250# fittings on the discharge side of the system. Don t over design the pump and use a throttle device to regulate pressure!!

NFPA 20 4.8 Centrifugal Pump Capacities Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

Automatic (circulation) Relief Valve 4.11.1.3 The valve shall provide flow of sufficient water to prevent the pump form overheating when operating at shutoff. Up to 2500GPM the nominal size shall be ¾ 3000GPM and higher shall be 1 Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

Devices in Suction Piping 4.14.9 Devices in Suction Piping. 4.14.9.1 No device or assembly, unless identified in 4.14.9.2 that will stop, restrict the starting, or restrict the discharge of a fire pump or pump driver shall be installed in the suction piping. The purpose is to prohibit anything in the suction that would cause excess turbulence, friciton loss, or cut off the flow to the pump while running at 150% capacity. Cutting off the supply would cause catastrophic failure to the pump. Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

Water Flow Test Devices Every fire pump needs a method for performing the acceptance test. 1) Test Header Flows readings are usually taken with a Pitot tube 3) Flowmeter A special pipe is run for the discharge back to the water supply with a flowmeter, control valve, and check valve in the line. 4.20.1.1 A fire pump installation shall be arranged to allow the test of the pump at its rated conditions as well as the suction supply at the maximum flow available from the fire pump. Two objectives: 1) To make sure the pump itself will function correctly 2) Make sure the water supply can deliver the correct amount Under no circumstance may a fire pump be placed into service without an acceptance test!!! Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

Automatic Air Release 6.3.3 Automatic Air Release. 6.3.3.1 Unless the requirements of 6.3.3.2 are met, pumps that are automatically controlled shall be provided with a listed float-operated air release valve having a normal 0.50 in. (12.7 mm) minimum diameter discharge to atmosphere. Air in the impeller can cause cavitation, dmage the impeller, and negatively impact pump perfomance! Ref.: Copyright 2006 National Fire Protection Association. All Rights Reserved.

Listed Fire Pump Controllers 10.1.2.1 All controllers and transfer switches shall be specifically listed for electric motor driven Fire Pump Service 12.1.3.1 All controllers shall be specifically listed for diesel engine-driven fire pump

Field Acceptance Testing 14.2.4.1 A copy of the manufacturers certified pump test characteristics curve shall be available for comparison of the results of the field acceptance test 14.2.5.2.1 The fire pump shall perform at minimum, rated, and peak loads without objectionable overheating of any component

NFPA 20 14.5.2.1 Whenever a critical path component in a piece of centrifugal pump equipment is replaced, changed, or modified, a field/on-site retest shall be performed Table 14.5.2.4

TESTING METHODS

Courtesy of Proctor & Gamble, Cincinnati, OH

Two hydrants are normally required to conduct a flow test of the water supply. This is the flow hydrant, the second hydrant will only have a pressure gauge and will be used to obtain a static (no flow) and residual pressure reading (while water is flowing).

FLOW IN GPM H E A D.... A PUMP CHURN Pressure ACTUAL CITY WATER FROM FLOW TEST B RATED 100 % FLOW. C 150 % RATED 100% FLOW

PUMP FLOW DETERMINATION WITH ( UL / FM ) FLOW METER

PUMP FLOW DETERMINATION WITH NOZZLE ( UL / FM ) PLAY PIPE and PITOT TUBE

<FM> Short Play Pipe 1 1/8 Nozzle 1 ¾ Nozzle Pitot Tube Underwriters Play Pipe 1 ¾ Nozzle

Maintenance

Owner / Operators trained in required maintenance, weekly operation, required testing, and record keeping? Did the pump distrbutor provide the required instruction manuals and a weekly check list for the required weekly testing, maintenance, and inspections of the pump, driver, and controller? NFPA 20 14.3 NFPA 25 4.1-4.3 If not, he is not doing his job!!! Weekly Check list should include those items required by NFPA 25 Chapter 8.

Review ALL Required Weekly/Annual Maintenance NOTE: Clean Grease Forced out of the Drain hole with PLUG REMOVED!! Check For Excess Grease

Annual Alignment Check AFTER alignment has been re-checked (ANNUALLY) the coupling should be lubricated and reassembled. Be sure to check the set screws for tightness

EMERGENCY MANUAL STARTING PROCEDURE (11.6.6) CUMMINS SET at 120 % of Rated RPM ** #1 COOLING WATER #2 FUEL # 3 NOTE! BE SURE THAT YOU KNOW WHERE THE OVERSPEED RESET IS ON EVERY TYPE OF ENGINE THAT YOU SELL!! CRANK

Develop a check list of your own for both electric and diesel Fire Pumps. -OR- Make a copy of NFPA 25, Chapter 8 for use as a guide for weekly checks.

HAVE THESE FOLKS BEEN PROPERLY TRAINED?

? This is the ONLY WM case relief valve on record, that always had a tight shut off with NO nuisance leakage - until the fire pump overheated and was destroyed!!

Vertical Turbine Fire Pump NFPA 20 (7. 1)

NOTE: Automatic air release NFPA 20 (7.3.5.2.3) SHALL BE Located between the fire pump and the discharge check valve. * Motor HP and current limits, multiplied by the service factor, must not be exceeded under any condition of pump load. CHECK! NFPA 20 (9.5.2)*

NOTE: Automatic air release SHALL BE Located in the highest point in the discharge line, between the fire pump and the discharge check valve. NFPA 20 (7.3.5.2.3) *

NFPA 20 (7.6.2.3) ACCESS FOR REMOVAL?**

NFPA 20 ( 7.4.3.7.2 ) I beams must be parallel to the engine!*

NFPA 20 ( 7.4.3.7.2 )

One degree of off-set is the preferred angle, per drive shaft manufacturers!! NFPA 20 (7.5.1.8.2)*

NFPA 20 (7.6.1.3)* Top Shaft Nut is used to raise shaft and impellers approximately 1/8 inch. (see instruction book)

NFPA 20 2007 Screen openings equal to 1 sq. in. for every GPM (pump capacity at 150%) (at LOWEST Water LEVEL) NFPA 20 (5.14.8)* Water Vel, 2 /sec Max Water Vel. 1 /sec Max * #12 Confirm proper submergence (Pump Length) * (7.2.2.2) NFPA 20 (A.7.2.2.2) (5.14.8)

Removable screens NFPA 20 (5.14.8.3) Intake size NFPA 20 (5.14.8.4)*

With a vertical turbine fire pump a plugged screen will affect the water level in the sump and a plugged basket strainer on the bottom of the pump will reduce the total pump performance as the flow increases. NFPA 20 2003 Zebra Mussel Infestation (5.14.8.12)

VTFP INTAKE PROBLEMS.. Removable screens NFPA 20 (5.14.8.3) Intake size??? NFPA 20 (5.14.8.4) 2 ft/sec and 1 Sq. Inch per GPM at 150% Flow?

Pond Maintenance -OR- Lack of!!!