Building damage patterns in Kathmandu Valley due to 25th April Earthquake. Kiran Acharya

Similar documents
ASSESSMENT AND RETROFITTING OF EXISTING RC BUILDINGS IN VIETNAM IN TERMS OF EARTHQUAKE RESISTANCES

Chapter. Earthquake Damage: Types, Process, Categories

Chapter 3 DESIGN AND CONSTRUCTION FEATURES IMPORTANT TO SEISMIC PERFORMANCE

Prepared For San Francisco Community College District 33 Gough Street San Francisco, California Prepared By

Unit 4 Lesson 6 Measuring Earthquake Waves. Copyright Houghton Mifflin Harcourt Publishing Company

SEISMIC DESIGN. Various building codes consider the following categories for the analysis and design for earthquake loading:

3. Observed Damage in Railway Viaducts

bi directional loading). Prototype ten story

Current Status of Seismic Retrofitting Technology

PERFORMANCE BASED SEISMIC EVALUATION AND RETROFITTING OF UNSYMMETRICAL MEDIUM RISE BUILDINGS- A CASE STUDY

Seismic Risk Prioritization of RC Public Buildings

6 RETROFITTING POST & PIER HOUSES

Preliminary damage survey report on 2015 Nepal Gorkha Earthquake

Foundations 65 5 FOUNDATIONS. by Richard Chylinski, FAIA and Timothy P. McCormick, P.E. Seismic Retrofit Training

DISASTER RESISTANCE EARTHQUAKES AND STRUCTURES

ETABS. Integrated Building Design Software. Concrete Shear Wall Design Manual. Computers and Structures, Inc. Berkeley, California, USA

ASSESSMENT AND PROPOSED STRUCTURAL REPAIR STRATEGIES FOR BRIDGE PIERS IN TAIWAN DAMAGED BY THE JI-JI EARTHQUAKE ABSTRACT

REVISION OF GUIDELINE FOR POST- EARTHQUAKE DAMAGE EVALUATION OF RC BUILDINGS IN JAPAN

Expected Performance Rating System

STRUCTURAL ASSESSMENT REPORT BOLINAS MARINE STATION - BOLINAS, CALIFORNIA

4 EFFECTS OF SURFACE FAULT RUPTURE ON INFRASTRUCTURE

REPAIR AND RETROFIT OF BRIDGES DAMAGED BY THE 2010 CHILE MAULE EARTHQUAKE

4B The stiffness of the floor and roof diaphragms. 3. The relative flexural and shear stiffness of the shear walls and of connections.

Building Condition Assessment: North Howard Street Baltimore, Maryland

Technical Notes 3B - Brick Masonry Section Properties May 1993

What is Seismic Retrofitting?

SECTION 7 Engineered Buildings Field Investigation

(1) Minami Nagamachi and Naka Nagamachi viaducts between Shiraishi Zao and Sendai Stations on the Tohoku Shinkansen line

A Report on Post-Earthquake Rapid Visual Damage Assessment of Buildings Of Tribhuvan International Airport

Seismic retrofitting on structures in urban areas

Sisal Composite Ltd. Apparel 4 Ltd. JM Knit Ltd. Natun Para, Hemayetpur, Savar, Dhaka-1340 ( N, E)

Seismic Retrofitting for School Buildings in Japan Nonstructual Seismic Retrofitting

Seismic Risk Evaluation of a Building Stock and Retrofit Prioritization

Miss S. S. Nibhorkar 1 1 M. E (Structure) Scholar,

Project Report. Structural Investigations Hotel del Sol Yuma, Arizona

EAST LYME HIGH SCHOOL

Lighthouse Engineering, L.L.C.

SEISMIC UPGRADE OF OAK STREET BRIDGE WITH GFRP

Five reasons buildings fail in an earthquake and how to avoid them

SEISMIC DESIGN OF HIGHWAY BRIDGES

Presentations. Session 1. Slide 1. Earthquake Risk Reduction. 1- Concepts & Terminology

Building Condition Assessment: West Lexington Street Baltimore, Maryland

Post Earthquake Quick Damage Inspection of Buildings in Nepal

SLAB DESIGN. Introduction ACI318 Code provides two design procedures for slab systems:

Hunter College school of Social Work Thesis Proposal

Chincha and Cañete, Peru, Based

Magnitude 7.2 GUERRERO, MEXICO

FOUNDATION DESIGN. Instructional Materials Complementing FEMA 451, Design Examples

Structural Failures Cost Lives and Time

SEISMIC CAPACITY OF EXISTING RC SCHOOL BUILDINGS IN OTA CITY, TOKYO, JAPAN

CH. 2 LOADS ON BUILDINGS

Seismic performance evaluation of an existing school building in Turkey

Chapter. Restoration of Damaged Structures

16. Beam-and-Slab Design

Design of reinforced concrete columns. Type of columns. Failure of reinforced concrete columns. Short column. Long column

DESIGN OF SLABS. Department of Structures and Materials Engineering Faculty of Civil and Environmental Engineering University Tun Hussein Onn Malaysia

Lighthouse Engineering, L.L.C.

ARCHITECTURE. Asst. Prof. Meltem VATAN KAPTAN

POST AND FRAME STRUCTURES (Pole Barns)

Seismic Retrofit of Bridges - A Short Course

SEISMIC ANALYSIS AND RETROFITTING OF R.C.C STRUCTURE

In this study analytical investigation of effect of retrofit application using carbon fiber (CFRP) on seismic behavior of a monumental building at

Earthquakes and Data Centers

National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067

Performance-based Evaluation of the Seismic Response of Bridges with Foundations Designed to Uplift

CONTRIBUTION TO THE IAEA SOIL-STRUCTURE INTERACTION KARISMA BENCHMARK

How To Design A Post Tensioned Deck For A Building

Important Points: Timing: Timing Evaluation Methodology Example Immediate First announcement of building damage

REPAIR, RESTORATION AND STRENGTHENING OF BUILDINGS

Detailing of Reinforcment in Concrete Structures

The earthquake source

Residential Deck Safety, Construction, and Repair

Development of Guidance Information for the Repair and Rebuilding of Houses Following the Canterbury Earthquake Series

Vulnerability Assessment of Kathmandu Valley and Surrounding Areas based on Comprehensive Damage Investigation of the 2015 Gurkha, Nepal Earthquake

EARTHQUAKE DESIGN OF BUILDINGS

1997 Uniform Administrative Code Amendment for Earthen Material and Straw Bale Structures Tucson/Pima County, Arizona

Personal Information. Professional Education

Chapter 6 ROOF-CEILING SYSTEMS

Seismic Isolation Retrofitting of Japanese Wooden Buildings

ASHULIA APPARELS LTD. Client Summary Report

Property Inspection. 83A Ascot Avenue North New Brighton Christchurch STRUCTURAL REPORT

Cover page. Introduction to the Earthquake Resistance Capacity Assessment and Reinforcement of Taipei Water Department Office Building.

2016 IDEERS Rules for Graduate Teams. The List of Rule Revisions

Seismic Analysis and Design of Steel Liquid Storage Tanks

Basement & Foundation Damage

Chapter 3 Pre-Installation, Foundations and Piers

Earthquake Resistant Design and Risk Reduction. 2nd Edition

14 September Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste St. Paul, MN 55102

Methods for Seismic Retrofitting of Structures

KCC Event Brief: 2014 La Habra Earthquake

Earthquakes Natural and Induced. Rick Aster Professor of Geophysics and Department Head Geosciences Department Colorado State University

Numerical modelling of shear connection between concrete slab and sheeting deck

9.3 Two-way Slabs (Part I)

Transcription:

Building damage patterns in Kathmandu Valley due to 25th April Earthquake Kiran Acharya (acharyakiranraj@gmail.com, kacharya@baseengr.com) This report presents the nature of the earthquake that struck Nepal on 25th April, 2015 and the damages observed in the buildings in Kathmandu valley.

Table of Contents A. Nepal Earthquake... 2 1) Introduction... 2 2) Ground motion Record... 2 B. Damaged buildings in Kathmandu Valley... 4 C. Observations and Conclusions... 40 Kiran Acharya kacharya@baseengr.com Page 1

A. Nepal Earthquake 1) Introduction A strong earthquake of magnitude 7.8 Richter scale struck the central part of Nepal on 25 th April, 2015 at shallow depth of 15 km. The epicenter was located at Barkpak village of Gorkha district, 77 km NW of Kathmandu. Early modeling of this earthquake implies dimensions of ~120x80 km, directed from the hypocenter eastwards, and towards Kathmandu. As a result, substantial seismic energy was generated by faulting very close to the city 1. Figure 1: Map showing the location of the epicenter propagation of the rupture towards Kathmandu (Source: USGS) 2) Ground motion Record As recorded at the station in Kantipath, Kathmandu, the ground motion plot is shown below. The ground motion is divided in to three components, two horizontal components and one vertical component. The recorded PGA at the station was 0.16g, while the derived PGA in Kathmandu valley was 0.73g. The derived maximum PGA is 1.32g in Sindhupalchowk district, which suffered the maximum structural damages and casualties due to the shaking. As per UBC 97, the design PGA is 0.44g in Kathmandu valley. Figure showing the recorded PGA at the Kantipath station. (Source: USGS) Kiran Acharya kacharya@baseengr.com Page 2

Figure: Long period acceleration ground motions recorded at Kantipath, Kathmandu station. (Source: USGS) From the ground motion plot, as seen above, the ground vibration is slow in nature in Kathmandu valley Because of this slow nature of the earthquake high rise buildings and flexible mid-rise buildings are expected to suffer maximum damage due to such shaking, while low to stiff mid-rise buildings are expected to suffer least damage. Kiran Acharya kacharya@baseengr.com Page 3

B. Damaged buildings in Kathmandu Valley Figure- Ground fissures in Bhaktapur district. There is no damage in the nearby houses seen in the photo (Photo by Kiran Acharya) Kiran Acharya kacharya@baseengr.com Page 4

The land along the marked width has been settled by around 1.5 m. No major cracks in the surrounding houses except tilting and shifting of the affected house. (Photo by Kiran Acharya) Surface ruptures in the settled part of the land (Photo by Kiran Acharya) Kiran Acharya kacharya@baseengr.com Page 5

Maximum damages on the walls and floors of the green house seen in the previous figure. (Photo by Kiran Acharya) Kiran Acharya kacharya@baseengr.com Page 6

Tilting of the house by around 1 m near the surface cracks (Photo by Kiran Acharya) Kiran Acharya kacharya@baseengr.com Page 7

Tilting of the red house. No structural damage in the white house (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 8

Settlement of the front garden of the white house seen in the previous figure by around 1.5 m (Photo by Kiran) Houses near the surface rupture. These are two different houses (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 9

Stump of the 9 storey tall Dharahara tower. It felled down towards the marked direction (Photo by Kiran) Kathmandu Durbar Square (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 10

An artist depicting the ruined Palace in his canvas (Photo by Kiran) (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 11

Durbar High School (Photo by Kiran) Damage in the roofs of a school in Bhaktapur. There are not even minor cracks at other locations (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 12

Pink colored is the retrofitted part of the school while the other had not been retrofitted. (Photo by Kiran) This Y Shaped 4 story school building has no cracks on the walls except on the floor of one room on ground floor, shown aside. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 13

Damaged house near to the Y shaped school building. (Photo by Kiran) Surprisingly no damage in the marked house, near to the above cracked house. The building on the left corner of the photograph is the retrofitted school building which has no damage at all. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 14

Damaged old houses in the village of Bhaktapur district (Photo by Kiran) Roof of the retrofitted school building is damaged by the adjacent house (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 15

Relatively new buildings suffered no damage at all. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 16

Surprisingly no external cracks are visible in such building in Bhaktapur district. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 17

Column shear failure on the ground floor of the house Balaju, Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 18

Damaged column of the house in Balaju, Kathmandu area (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 19

Damages in the interior walls and columns of the house in Balaju, Kathmandu. Longitudinal rebar are buckled after concrete crushing at the soffit of the beam and at column base (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 20

Shear failure of the columns on ground story at the soffit of the beam due to short column effect induced by the infill wall in Balaju, Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 21

Complete collapse of first two story of a five story house Balaju, Kathmandu, due to soft story effect. There were no infill walls at the periphery of the ground floor. (Photo by Kiran) Close up view of the damaged columns of the previous building. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 22

Shear failure of the column at base of other building in Balaju, Kathmandu. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 23

Critical flexural crack at the column base in the building in Balaju, Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 24

More damage in the buildings on right side than on the left side of the road in Balaju, Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 25

Horizontal cracks in Swyambhu stupa, Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 26

Collapsed buildings due to soft story effect, Sitapaila, Kathmandu (Photo by Kiran) Damaged columns at the marked location of the previous photos (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 27

Collapsed building in Sitapaila, Kathmandu. All the rebar were spliced at the same location in the column as marked in the diagram. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 28

Damages in the infill walls and at the corners of the high-rise apartment buildings Kathmandu (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 29

Soft story collapse of another building in Sitapaila, Kathmandu. No stirrups were provided at the beam column joint location. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 30

Collapsed houses in Sitapaila, Kathmandu (Photo by Kiran) Collapse of a two story frame structure in Sitapaila, Kathmandu. Column bases on the upper story are also damaged. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 31

Damaged column bases on upper story of the previous building (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 32

Soft story collapse of a 5 story house in Dhapasi, Kathmandu Kiran Acharya kacharya@baseengr.com Page 33

Infill wall damage of a 17 storey tall apartment building in Kathmandu (Right face of the building) (Photo by Kiran) Left face of the building. Damage to the middle part of the structure may be attributed to the higher mode participation. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 34

Front face of the building (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 35

Damage in Spandrel on left face of the (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 36

Overturning of a 7 storey tall building in Kapan area, Kathmandu (Photo by Surya Raj Acharya) Longitudinal reinforcements were spliced at same location in the column and building overturned by lap splice failure at tension location (Photo by Surya Raj Acharya) Kiran Acharya kacharya@baseengr.com Page 37

Another view of the 7 story tall building (Photo by Surya Raj Acharya) Repaired diagonal shear cracks in a school building in Imadol area, Lalitpur (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 38

Horizontal crack at the beam interface in a wall that was constructed after constructing the frame in Lalitpur. No other cracks are seen in this 4 story RC frame building except similar vertical cracks at column interface. (Photo by Kiran) No damage at all in such buildings in Bhaktapur. (Photo by Kiran) Kiran Acharya kacharya@baseengr.com Page 39

C. Observations and Conclusions Following observations are made in Kathmandu valley after the earthquake 1. Long period ground acceleration resulted in the damage of relatively flexible structure where as stiff structures suffered less damage in Kathmandu valley. 2. Buildings where infill walls were constructed after constructing the frames suffered more cracks at beam and column interface, while, the buildings where infill walls and frames were constructed together suffered no such damages. 3. Most of the buildings with complete infill walls on ground floors and buildings without infill walls on ground floor but with larger column dimensions 12 x12, suffer minor to no damage. 4. Most of the columns are failed by crushing of the concrete at the soffit of the beam or at column base leading to the subsequent buckling of the longitudinal bars. 5. In some buildings it is observed that the building could not resist the overturning moment due to lap splice failure on the tension side. It was observed that all the longitudinal rebar were spliced at same location in such buildings. 6. Complete collapse of the ground floor and in some cases up to 2nd floor of mid-rise buildings (4 to 6 story tall) due to soft story mechanism. This kind of buildings did not have infill walls on the periphery grid on ground floor for commercial purpose and the column sizes were 9 x9. 7. No major damage in the components of the building near to surface fissures. However they suffer excessive tilting and settlement 8. Collapse of the cultural heritages dated back up to 5 th century. 9. Complete collapse of the over aged masonry buildings. 10. Partial collapse of the wooden roofs of relatively new load bearing masonry buildings. Other part of the building remain intact with no critical damage 11. High rise buildings and mid-rise flexible buildings are at more risk than the low to mid-rise stiff buildings in Kathmandu valley. 12. Damage pattern of the High-rise building like Park View Horizon apartment may be attributed to the excitement of higher modes of vibration. 13. Strong beam-weak columns are observed in the collapsed RC frame buildings in Kathmandu. 14. A low rise house in Sindhupalchowk and Gorkha would experience more than double seismic force than the same house in Kathmandu would have experienced. This is primarily due to almost double value of Peak Ground Acceleration (PGA) in Sindhupalchowk and Gorkha (1.32g) than the PGA in Kathmandu (0.73g) and also due to the stiff nature of soil in Gorkha and Sindhupalchowk. Kiran Acharya kacharya@baseengr.com Page 40