MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP)



Similar documents
MicroTech II McQuay Maverick II Rooftop Unit Controller BACnet Communication Module (MS/TP)

Daikin Magnitude TM Chiller Unit Controller BACnet Communication Module (MS/TP, IP, Ethernet)

MicroTech II Chiller Unit Controller BACnet Communication Module (MS/TP)

ServiceTools for MicroTech II Version 2.0 Applied Terminal Systems User Manual

MicroTech Remote Monitoring and Control Panel

mysensors mysensors Wireless Sensors and Ethernet Gateway Quick Start Guide Information to Users Inside the Box mysensors Ethernet Gateway Quick Start

Crow Limited Warranty. Print Version 017

ScreenLogic Wireless Connection Kit. Installation Guide. pool/spa control system

StorTrends 3400 Hardware Guide for Onsite Support

SoftRAID 5 QUICK START GUIDE. for OWC ThunderBay

Portable BACnet /IP to MS/TP Router

BACnet Automation Interface Module (Network Version)

SCREENLOGIC INTERFACE WIRELESS CONNECTION KIT

Ethernet Radio Configuration Guide

LabelWriter. Print Server. User Guide

Kvaser Mini PCI Express User s Guide

Mercury Helios 2 ASSEMBLY MANUAL & USER GUIDE

2013 VTech Printed in China US

MCR1900 Media Converter 19-Slot Chassis

ATTENTION RISQUE D ÉLECTROCUTION! NE PAS OUVRIR!

BroadBand PowerShield. User Manual

Application Note - Connecting an Electricity Meter to SolarEdge Devices (Europe and APAC)

What is Bitdefender BOX?

Universal Serial Bus (USB) to DH-485 Interface Converter

Evolution Digital HD Set-Top Box Important Safety Instructions

CAUTION RISK OF ELECTRIC SHOCK NO NOT OPEN

UniStream CPU-for-Panel

Business Audio System: Music & Messaging MP3 Player. by Grace Digital Audio. User Guide. Model No. GDI-USBM10

Medical Vacuum Systems-PXMI

FUSION R400 RAID USB 3.0

HP SATA/SAS hard drive and Solid State Drive installation

User Manual. PePWave Surf / Surf AP Indoor Series: Surf 200, E200, AP 200, AP 400. PePWave Mesh Connector Indoor Series: MC 200, E200, 400

Congratulations on your HomePortal purchase. To install your HomePortal and configure your home network, follow these steps.

How To Use An Nc Express5800 Card (Nec) With A Remote Management Card (Ec) On A Pc Or Mac Computer (Nemca) With An Ipa/Sda/Sdu) On An Ipad Or

BK MIKRO9. Tool monitoring system. Getting Started with Profibus Release 1.00 /

HP ProLiant DL380 G6 Carrier-Grade Server Read Before Install

Aura SSD. for the 2013 Apple Mac Pro INSTALLATION GUIDE

User Manual IC-485AI

QUICK START GUIDE CX-MC200LE-VZ

BODi rs BD004 Series Bandwidth-on-Demand Internet with Reliability and Survivability. Quick Start Guide NOTES

IEEE b WLAN PC Card

WLAN600 Wireless IP Phone Administrator s Guide

Legal Disclaimers. For C-UL Listed applications, the unit shall be installed in accordance with Part 1 of the Canadian Electrical Code.

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

Energy Smart Electric Water Heater Controller

Installation Instructions. Wireless Adapter/Repeater. Introduction Rev C

Installation Guide Wireless 4-Port USB Sharing Station. GUWIP204 Part No. M1172-a

Management Software. Web Browser User s Guide AT-S106. For the AT-GS950/48 Gigabit Ethernet Smart Switch. Version Rev.

USB 2.0 Peripheral Switch USER MANUAL US221A / US421A

MicroTech Remote Monitoring and Control Panel

Installation & Operation Manual HANDS-FREE BLUETOOTH MEDIA INTEGRATION KIT. Perfect for ANDROID TM

Installation Guide. Wyse D Class 4-GB RAM Upgrade Option Kit. Products: D90D7, D90DW. Issue: PN: L Rev. A

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

4 Port PCI Express Low Profile High Speed USB Card

Usage, Installation, Warranty and Service Information

How To Use An Ip Phone With A Sim Sim Sims 2 (Iphone) Or Ip Phone (Ip Phone) With A Microsoft Ip Phone 2 (Ipphone) With An Ipro (Ipro) Or Sims 1 (Ip

SHEET. BASautomation. BAS Router BACnet Multi-Network Router. BAS Router

Liebert Universal Monitor

HP Advanced Wireless Docking Station. User Guide

PRO 5000 CPE 1D Quick Installation Guide

Wireless Router Setup Manual

Perle Protocol Transparent Media Converter Modules

HP LaserJet MFP Analog Fax Accessory 300 Fax Guide

47611-GB4. Quick-Start Guide 10/100/1000 Mbps 4-Port Gigabit Router IMPORTANT INSTRUCTIONS SAFETY INFORMATION PRE-INSTALLATION CHECKLIST

4 Port PCI Express Gigabit Ethernet PoE PSE Network Card

ES-3305P V2 / ES-3308P V2. Quick Installation Guide / v1.0

LifeSize Networker Installation Guide

ADSL Modem Installation Guide. Model # 36R515 Part # Rev. D Revision Date 12/2000. ADSL Modem Installation Guide

E-Mon Communication Gateway Utility Instructions for BACnet/mstp

HLWLAN b/g/n Transceiver Kit

On/Off Relay Switch and 3-Way Switch Kit

Power Over Ethernet Adapters POE101

Intel RAID Maintenance Free Backup Unit 4 Quick Installation User's Guide

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

TL-PS310U Single USB 2.0 Port MFP and Storage Server

Operating instructions. AS-i Profibus gateway AC1411 / AC /00 04/2014

UPS Network Interface. Quick InstallationGuide

FN2001-A1 Network module (SAFEDLINK) Mounting Installation

FB-500A User s Manual

Installation Guide. Wyse C Class 2-GB RAM Upgrade Option Kit. Issue: PN: L Rev. A

USER MANUAL. PingBrother EPIW104 managed passive poe switch & IP watchdog

StructureScan HD Module. Installation Guide ENGLISH

5-port 10/100Base-TX Industrial Switch (314500) User s Guide

Quick Installation Guide 24-port PoE switch with 2 copper Gigabit ports and 2 Gigabit SFP ports (af Version 15.4W)

WIRELESS ACCESS POINT

dedicated KVM switch and rackmount screen technology User Manual IP-S101 Combo KVM Extender Designed and manufactured by Austin Hughes

8-port 10/100Base-TX +2-port 100Base-FX Switch. User s Guide

Targus Wireless RF Mouse USER S GUIDE. Making Your Mobile Life Easier.

Installation Instructions for FT-10 Network PowerCommand ATS Communication Module (NCM) Kits and

Introduction. Page 2 / 9

Installation Guide. Wyse VX0L and VX0LE Thin Clients 1-GB RAM Upgrade Option Kit. Issue: PN: L Rev. A

Advantium 2 Plus Alarm

USB VoIP Phone Adapter. User s Manual

IEEE 802.3af 4-Port Power over Ethernet Injector Hub POE-400. User s Manual

ATTENTION RISQUE D ÉLECTROCUTION! NE PAS OUVRIR!

Disclaimers. Important Notice

Installation Guide. APA-1460 SlimSCSI. PCMCIA-to-SCSI Host Adapter

Meridian 1 Meridian 1 Attendant PC LAN Interface Installation Guide

Disclaimers. Important Notice

Transcription:

Installation and Maintenance Manual IM 917-1 Group: Controls Part Number: IM 917 Date: October 2009 Supercedes: IM 917 MicroTech III Rooftop and Self Contained Unit Controller BACnet Communication Module (MS/TP) Applied Rooftop Models: RPE, RDE, RCE, RPS, RDT, RFS, RCS, RDS and RAH Self-Contained Models: SWP and SWT Maverick II Model MPS NOTICE Use this manual to physically install the McQuay MicroTech III Communication Module into the unit controller and connect the Applied Air Handling unit controller to your network. Use the appropriate McQuay Engineering Data (ED), known as the Protocol Information document, to integrate the unit into your network. The Protocol Information document contains addressing details, BACnet protocol information, and a list of the data points available to the network. See the Reference Documents section of this manual for Protocol Information document numbers. MicroTech III control integration literature is available from your local McQuay International sales representative and www.mcquay.com. 2009 McQuay International

Contents Figures Figures... 2 Revision History... 3 Reference Documents... 3 Limited Warranty... 3 General Information... 4 Hazard Identification Messages... 4 Description... 5 Application... 5 Component Data... 6 Light Emitting Diodes (LEDs)... 6 BACnet Network Connector... 7 Board-To-Board Connector... 7 Installation... 9 Contents of the BACnet Communication Module Kit... 9 Installing a new BACnet Communication Module... 9 Replacing an Existing BACnet Communication Module... 10 Integration... 11 Configuring the BACnet Communication Module... 11 BACnet MS/TP Addressing... 11 Service Information... 15 Test Procedures... 15 Parts List... 15 Installation Kit... 15 Figure 1. BACnet MS/TP Communication Module Attached to the Unit Controller... 5 Figure 2. BACnet Communication Module Components... 6 Figure 3. BACnet MS/TP Communication Module and Knockout... 7 Figure 4. Diagram of Board-to-Board Connector... 8 Figure 5. BACnet MSTP Communication Module with Board-to-Board Connector Inserted... 8 Figure 6. Unit Controller MSTP Setup Screen Change ApplyMSTPChgs... 12 Figure 7. Unit Controller MSTP Setup Screen Change Baud Rate... 12 2 IM 917-1

Revision History IM 917 October 2008 Initial release IM 917-1 October 2009 Added Maverick II (MPS) model. Updated keypad display navigation menu per global standards. Reference Documents Number Company Title Source ANSI/ASHRAE American Society of BACnet A Data Communication Protocol for Building www.ashrae.org 135-2001 Heating, Refrigerating and Air-Conditioning Engineers Automation and Control Networks OM 920 McQuay International MicroTech III Applied Air Handling Unit Controller Operation www.mcquay.com and Maintenance Manual ED 15112 McQuay International MicroTech III Rooftop and Self Contained Unit Controller www.mcquay.com Protocol Information, BACnet and LONWORKS Networks ED 15113 McQuay International MicroTech III Rooftop and Self Contained Unit Controller Protocol Information, BACnet Protocol Implementation Conformance Statement (PICS) www.mcquay.com Limited Warranty Consult your local McQuay Representative for warranty details. Refer to Form 933-43285Y. To find your local McQuay Representative, go to www.mcquay.com. Notice Copyright 2009 McQuay International, Minneapolis MN. All rights reserved throughout the world. McQuay International reserves the right to change any information contained herein without prior notice. The user is responsible for determining whether this software is appropriate for his or her application. The following are tradenames or registered trademarks of their respective companies: BACnet from the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.; Windows from Microsoft Corporation; McQuay, Maverick II, and MicroTech III from McQuay International. IM 917-1 3

General Information This manual contains the information you need to install the BACnet Communication Module on a MicroTech III Rooftop or Self-Contained Unit Controller (i.e. Applied Rooftop, Self-Contained, or Maverick II Unit), incorporate it into the BACnet network, and maintain it. Hazard Identification Messages! DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided.! WARNING Warnings indicate potentially hazardous situations, which can result in property damage, severe personal injury, or death if not avoided.! CAUTION Cautions indicate potentially hazardous situations, which can result in personal injury or equipment damage if not avoided.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Connections and service to the Unit Controller must be performed only by personnel knowledgeable in the operation of the equipment being controlled.! CAUTION Static sensitive components. Can cause equipment damage. Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work. Never unplug cables, circuit board terminal blocks, or power plugs while power is applied to the panel. NOTICE This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with this instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his or her own expense. McQuay International disclaims any liability resulting from any interference or for the correction thereof. 4 IM 917-1

Description The MicroTech III BACnet Communication Module incorporates a MicroTech III Rooftop or Self- Contained Unit Controller (i.e. Applied Rooftop, Self-Contained, or Maverick II Unit) into a BACnet local area network (LAN). It supports the BACnet MS/TP (EIA 485) data link layer (physical layer.) The BACnet Communication Module is a printed circuit board with a plastic enclosure that connects to the left side of the Unit Controller. The BACnet Communication Module provides access to the Unit Controller variables and parameters via BACnet (see Figure 1.) Figure 1. BACnet MS/TP Communication Module Attached to the Unit Controller Application The BACnet Communication Module connects the Unit Controller to a building automation system (BAS) on a BACnet local area network. It is the interface for the exchange of BACnet objects between the network and the unit controller. Refer to the McQuay MicroTech III Air Handling Unit Controller Operation Manual (OM 920) for keypad details. IM 917-1 5

Component Data Figure 2 shows the location of the major components of the BACnet Communication Module. Figure 2. BACnet Communication Module Components Network C + - Ref BUS LED BSP LED Light Emitting Diodes (LEDs) The BACnet Communication Module has a BSP LED and a BUS LED to indicate communication activity and status of the BACnet Communication Module. These indicators are visible when the communication module is connected to the Unit Controller and the unit is powered on (see Figure 2). BSP LED The BSP LED indicates the communication state between the BACnet Communication Module and the Unit Controller. The table below describes the status of the BSP LED. BSP LED Color Meaning Flashing between Red & Green Board Support Package (BSP) upgrade in progress Green Communication is established with the unit controller Communication is established between the communication module and the unit controller. Yellow The communication module is capable of communicating to the unit controller. However, communication is not established. Red flashing with 2Hz Red flashing with 2Hz = Software error. 1 Red Hardware error. 1 1 In the event that this should occur, cycle power to the unit controller to attempt to clear the problem. Contact the McQuay Controls Customer Support Group at 866-4MCQUAY (866-462- 7829) for additional assistance if necessary. 6 IM 917-1

BUS LEDs The BUS LED indicates the communication status between the BACnet Communication Module and the BACnet MS/TP network. The table below describes the status of the BUS LED. BUS LED Color Green Red Orange / Yellow Meaning The unit controller is capable of communicating to the network. The unit controller is not capable of communicating to the network. Communication module is initializing. BACnet Network Connector An RS485 connector connects the BACnet Communication Module to the MS/TP Network and has three pins: +, -, and ref (see Figure 2). Board-To-Board Connector The board-to-board connector connects the Unit Controller to the BACnet Communication Module (see Figures 3 and 4). Figure 3. BACnet MS/TP Communication Module and Knockout IM 917-1 7

Figure 4. Diagram of Board-to-Board Connector Figure 5. BACnet MSTP Communication Module with Board-to-Board Connector Inserted 8 IM 917-1

Installation The following section describes how to field install a new BACnet Communication Module or replace an existing BACnet Communication Module on the MicroTech III Rooftop, Self-Contained or Maverick II Unit Controller so that it can be incorporated into the BACnet network. The Communication Module can be factory or field installed. See Parts List for details.! CAUTION Electrostatic discharge hazard. Can cause equipment damage. This equipment contains sensitive electronic components that may be damaged by electrostatic discharge from your hands. Before you handle a communications module, you need to touch a grounded object, such as the metal enclosure, in order to discharge the electrostatic potential in your body. Contents of the BACnet Communication Module Kit The following is the list of items included in the field-installed kit: The BACnet Communication Module Board-to-board connector (separate) Network connector (attached) Installing a new BACnet Communication Module Follow these steps to install a BACnet Communication Module on the Unit Controller to incorporate it into an existing BACnet network.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the Unit Controller. 1. Remove power from the Unit Controller. 2. Remove the knockout on the far left end of the unit controller or BACnet Communication Module (see Figure 3.) Note: To prevent damage to the unit controller, insert a small screwdriver or other tool to the tab on the bottom of the unit controller and pull the screwdriver away from the controller. 3. Remove the knockout on the far right side of the BACnet Communication Module. 4. Insert the board-to-board connector into the BACnet Communication Module (see Figures 3 and 4). Note that it only fits one way and that the baffles must line up with corresponding slots in BACnet Communication Module and the unit controller (see Figures 4 and 5). 5. Insert the other end of the board-to-board connector to the far left side of the unit controller or other communication module, if attached (see Figure 1on page 5). 6. Connect the BACnet Communication Module to the network by inserting a network cable into the communication module s network connector (see Figure 2 on page 6). IM 917-1 9

Note: A crossover cable is required if connecting directly to the unit. A straight-through cable may be used if connecting through a network hub. 7. Power up the unit controller. 8. The unit controller automatically resets itself approximately 20 seconds after it is powered up. This reset is necessary so that the BACnet Communication Module is synchronized with the unit controller. Note: There is a limit of three devices that can be attached to the left side of the unit controller. Replacing an Existing BACnet Communication Module Follow these steps to remove an existing BACnet Communication Module from the unit controller and replace it with a new BACnet Communication Module.! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment must be properly grounded. Only personnel knowledgeable in the operation of the equipment being controlled must perform connections and service to the Unit Controller. 1. Remove power from the Unit Controller. 2. Locate the BACnet Communication Module to the left of the Unit Controller (see Figure 1). 3. Pull the network cable connector from the BACnet Communication Module. 4. Grasp the BACnet Communication Module and carefully pull it from the Unit Controller. 5. Install the new BACnet Communication Module. 6. Insert the network cable connector into the BACnet Communication Module (see Figure 2 for location of network connector). 7. Power up the Unit Controller. 9. The unit controller automatically resets itself approximately 20 seconds after it is powered up. This reset is necessary so that the BACnet Communication Module is synchronized with the unit controller. 10 IM 917-1

Integration Once the BACnet Communication Module has been properly installed on the unit controller, it is then possible to integrate the unit controller into a building automation system (BAS) via the BACnet MS/TP network. The configuration process is described in the following section. Configuring the BACnet Communication Module The BACnet Communication Module can be configured using the keypad/display on the Unit Controller. The unit is ready to operate with the default parameter values in the unit controller after you change the default parameters for your particular network. Refer to the appropriate MicroTech III Applied Air Handling Unit Controller Operation Manual (OM 920) for default values and keypad operating instructions. Refer to McQuay Protocol Document ED 15112 for descriptions of the available BACnet objects BACnet MS/TP Addressing The BACnet MS/TP Media Access Control (MAC) address is a one-octet address that must be set during the BACnet Communication Module configuration. The MAC address must be unique to the MS/TP network and have a valid range of 0-127. Additionally, there are certain parameters that must be set properly to verify communication between the Unit Controller and the MS/TP network. Table 1 provides details about these addressing parameters. See your system integrator for additional information regarding proper BACnet MS/TP addressing. Note: Refer to Operation Manual OM 920 for details regarding the MicroTech III Applied Air Handling Unit Controller keypad/display. To Configure the Module using the Keypad/Display: 1. Navigate to the Enter Password screen if you have not already entered a password. If you have entered a password, skip to step 3. 2. Enter Password: 6363. 3. Continue to navigate to BMS Communications\MSTP Setup. Note: The MS/TP Setup menu only appears if a BACnet Communication Module installed correctly (see Installation section of this document for details.) If the BACnet Communication Module is installed correctly and this menu still does not appear, cycle power to the unit controller and repeat the procedure from Step 3 above. 4. Modify the parameters as necessary (see Table 1 for a complete list.) 5. Continue to navigate to BMS Communications\MSTP Setup and change ApplyMSTPChgs from No to Yes (see Figure 6). 6. On the MSTP Setup menu, verify the settings of all parameters. This procedure may take a minute while the BACnet Communication Module powers up. Changing the MS/TP Data Transmission Rate The options for baud rate (in bps) include: 9600, 19200, 38400, and 76800. The factory default baud rate is 38400 bps. IM 917-1 11

! WARNING Electric shock hazard. Can cause personal injury or equipment damage. This equipment has exposed electrical connections inside BACnet Communication Module. Only personnel that are knowledgeable in the operation of this equipment must perform connections and service to the BACnet Communication Module. Changing the MS/TP Data Transmission Rate: 1. Navigate to the Enter Password screen if you have not already entered a password. If you have entered a password, skip to step 3. 2. Enter Password: 6363. 3. Navigate to the BMS Communications\MSTP Setup and change the baud rate to desired value (see Figure 7). 4. Continue to navigate to BMS Communications\MSTP Setup and change ApplyMSTPChgs from No to Yes (see Figure 6). Figure 6. Unit Controller MSTP Setup Screen Change ApplyMSTPChgs Figure 7. Unit Controller MSTP Setup Screen Change Baud Rate Configurable Parameters Table 1 defines the network parameters of the BACnet Communication Module that must be set using the keypad/display in order to establish communication between the Unit Controller Unit and the BAS. Change parameters as required for your network. Note: To save alteration of these parameters, select ApplyMSTPChgs under Advanced Menus/MSTP Setup (see Step 4 from previous section). For additional information on using the keypad/display, refer to OM 920. 12 IM 917-1

Table 1. Network Configuration Menu Parameter Value (Range)/Definition Initial Value/Note ApplyMSTPChg No-Yes/Apply MSTP Changes. No Setting this to yes will cycle power to the controller to allow the network setup changes to take place. Device Instance 0-4194303/Device Instance of the BACnet Communication Module. 368136/This must be unique throughout the entire BACnet network. MS/TP Address 1 Name 0-127/ This is the MS/TP address of the BACnet Communication Module. Up to a 17-character Device Object Name. Change this value as needed to match installation parameters. 18/ Each device on the BACnet network must have a unique MS/TP address. POL904_FF2BEE/This name must be unique throughout the entire BACnet network. The last 6 characters of the default are the last 6 digits of the MAC Address, which is printed on a label located on the left end of the module. Apply MSTP Change must be activated for changes to the Device Object Name to take effect. Baud Rate 1 9600-19200-38400-76800/ Data 38400 transfer speed. Max Master 0-127/ This variable specifies the 127 highest possible address for master. nodes and shall be less than or equal to 127. Max Info Frames 0-255/ This variable specifies the 10 maximum number of information frames the BACnet Communication Module may send before it must pass the token. RcvHrtBt 0-6553.5/Receive Heartbeat 0 Seconds/Setting this value to 0 disables the receive heartbeat feature. Unit Support Off-On/Controls the type of units that are passed through BACnet (English or Metric). On/To set the unit for Metric, set Unit Support to Off. If Unit Support is On, they type of units will be set to the same units as the keypad. Term Resistor 1 No-Yes No NC Dev 1 0-4194303/Alarm Recipient Device 1 0 (no device)/this is the device instance of the BACnet workstation or device that will receive the alarm notification. Use this in place of the Recipient List in the Notification Class. IM 917-1 13

Parameter Value (Range)/Definition Initial Value/Note NC Dev2 0-4194303/Alarm Recipient Device 2 0 (no device)/this is the device instance of the BACnet workstation or device that will receive the alarm notification. Use this in place of the Recipient List in the Notification Class. NC Dev3 0-4194303/Alarm Recipient Device 3 BACnetBSP Basic Support Package Version 1.0.11 1 Parameter only available via the keypad/display; designates the location of the unit on the network. 0 (no device)/this is the device instance of the BACnet workstation or device that will receive the alarm notification. Use this in place of the Recipient List in the Notification Class. Note: If unit controller application software requires uploading in the field, the network configuration parameters revert to their default values. Please contact the McQuay Applied Air Handling Customer Support Group at 763-553-5151 for assistance with upgrading unit controller application software. 14 IM 917-1

Service Information Test Procedures Parts List If you can control the unit from its keypad, but you are not able to communicate with unit via the network, follows these steps: Check the network wiring Check the network parameters and verify that they are correct and that there are no duplicate devices on the network Check communications If the BACnet Communication Module still does not respond, contact the McQuay Controls Customer Support Group at 866-4MCQUAY (866-462-7829). Installation Kit Description MicroTech III BACnet Communication Module-MS/TP kit (kit includes communication module with attached network connector board-to-board connector, and Installation Manual) Part Number 090016710 IM 917-1 15

This document contains the most current product information as of this printing. For the most current product information, please go to www.mcquay.com. All McQuay equipment is sold pursuant to McQuay s Standard Terms and Conditions of Sale and Limited Warranty. www.mcquay.com (800) 432-1342