VFDs: Do s and Don ts What can t be controlled?

Similar documents
Specifying a Variable Frequency Drive s

Rotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

EET272 Worksheet Week 9

Understanding Variable Speed Drives

FREQUENCY CONTROLLED AC MOTOR DRIVE

HITACHI INVERTER SJ/L100/300 SERIES PID CONTROL USERS GUIDE

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

SECTION VARIABLE FREQUENCY DRIVES

Fundamentals of Inverter Fed Motors

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Discover the power of e-learning! The Quick Guide to AC Variable Frequency

MC Series Drives. Flexible, simple, rugged, robust! Phone: Fax: Web: info@actechdrives.

Variable Frequency Drives and Energy Savings

Line Reactors and AC Drives

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Digi-Motor Installation Guide

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

Operational Overview and Controls Guide

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Multimeter measurements on variable frequency drives using the new Fluke 289 DMM

8 Speed control of Induction Machines

Additional Benefits of VFDs In addition to energy savings and better process control, VFDs can provide other benefits:

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Simulation and Analysis of PWM Inverter Fed Induction Motor Drive

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

WIND TURBINE TECHNOLOGY

EFC Frequency converters

VARIABLE FREQUENCY DRIVES Revised 4/30/ Mechanical Systems

Number 1 in efficiency

Data Bulletin Variable Frequency Drives and Short-Circuit Current Ratings

Principles of Adjustable Frequency Drives

Power System Harmonics

GPD 506/P5 Start-up Procedure and Checklist

ENGINEERING BULLETIN No. EB 039 Product: Cooling Towers, Closed Circuit Coolers & Evaporative Condensers Date: June 2003

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

DC Motor control Reversing

VLT 6000 HVAC. Contents

BIG SAVINGS FOR A LOT MORE APPLICATIONS

*.ppt 11/2/ :48 PM 1

Speed Control Relays SX2

EXPERTS IN WATER COOLING SINCE aquastream ULTIMATE SUPER SILENT PUMP TECHNOLOGY. The ultimate pump system.

SPP Pumps Inc. Atlanta

1115 4G SERIES GOVERNOR ma ANALOGUE DIGITAL SPEED SETTING

Electric Motor Brake Horsepower Calculations

A1000 Cheat Sheet (Open Loop Vector)

Centrifugal Fans and Pumps are sized to meet the maximum

AC Motor Speed. n s = synchronous speed (in RPM), f = frequency (in Hz), and p = the number of poles

What Is Regeneration?

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

Motor Fundamentals. DC Motor

WYE-DELTA AND SOLID STATE STARTER APPLICATION GUIDE

Power Quality. Uninterruptible Power Supply

Small Scale Renewable Energy Control Systems

NX Series Inverters. HVAC Pocket Programming Guide

Frequency Converter Fv

Distributed Power, Renewables, Stored Energy and the Grid Blinkless Synchronous Inverter System

Product Data Bulletin

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

AMZ-FX Guitar effects. (2007) Mosfet Body Diodes. Accessed 22/12/09.

Z1000 HVAC Drive. 3 HP to 500 HP Fan and Pump Applications. Specifications

Phase-Control Alternatives for Single-Phase AC Motors Offer Smart, Low-Cost, Solutions Abstract INTRODUCTION

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING

We will discuss common industrial applications with guides for the proper use of electric motors on these.

User s Manual Before using the inverter, you need to read and save the safety instructions.

PeakVue Analysis for Antifriction Bearing Fault Detection

Module Title: Electrotechnology for Mech L7

Operating instructions

Speed Control Methods of Various Types of Speed Control Motors. Kazuya SHIRAHATA

ETZGAR CONVEYOR COMPANY Controls Section v12.05

Torque control MSF Softstarter

FRENIC5000MS5 for Machine Tool Spindle Drives

Pulse Width Modulated (PWM)

An Easy to Build and Operate Induction Generator

Unidrive M Energy Savings

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

Rotary Phase Converters

Centro-Matic Automatic Lubrication Systems System Controls

Experiment 8 : Pulse Width Modulation

PUSH BUTTON START INSTALLATION MANUAL

AC Induction Motor Slip What It Is And How To Minimize It

32VFD Variable Frequency Drives for Centrifugal Chillers

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

Installation & Operation Manual for Energenics Air-Flow Optimizer

Siemens Standard Drives. Application Handbook

Designed for multi-injector endurance testing, the

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Inductance. Motors. Generators

MOTOR CONTROL IS OUR NATURE

Technical Specification. Generating Set with Waukesha engine burning natural gas

Introduction. Motor Types

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Diesel Engine Driven Generators Page 1 of 6

TECHNICAL INFORMATION Bulletin

Parameter Settings for PowerFlex Drives Using Sine Wave Filters, dv/dt Filters, and Adjustable Voltage

Transcription:

VFDs: Do s and Don ts What can t be controlled? Kriss Schneider President Schneider Water Services St. Paul, OR Richland, WA www.schneiderwater.com PNWS-AWWA Conference Spokane Washington

Why We Are Here? To have a discussion, not for me to just ramble on! If you have questions don t hesitate to ask!! I don t know everything but I know how to find the answers, I will get you an answer

Variable Frequency Drive (VFD) The Basics A device used to vary the speed of a driven load i.e. pumps, blowers, compressors, conveyors to exactly match the process requirements and achieve energy savings

O.L. Protection Benefits of a VFD Phase Protection (reversal and loss) Voltage Imbalance Protection Loss of Water Pipe Fill Mode Auto restart after power outages Brown outs and decision making on what to do Broken Shaft shut down Can operate to maintain pressure, flow, water levels (reservoir, well) or a combination there of

Some Other Benefits Smooth start/stop transition, eliminate water hammer and reduce pipe line repairs and thrust bearing abuse Energy savings pay for the horsepower you are using. Don t waste your money There are programs out to help pay for energy savings it s worth a look

2K B1 B2 Power Supply L1 L2 L3 T1 T2 T3 IM 2K 1 2 3 4 5 6 7 8 11 Forward Run Reverse Run Multi-function Inputs Digital Common 15 (+15V, 20mA) 13 Main Ref.(0±10V) 14 Main Ref.(4-20mA) 16 Aux. Ref.(0±10V) 17 Analog Common 33 (-15V, 20mA) 0±10V 21 Common 22 0±10V 23 9 10 18 19 20 25 26 27 Multi-function Analog Output Multi-function Analog Output Multi-function Contact Output 250Vac/30Vdc, 1A Fault Contact 250Vac/30Vdc, 1A Multi-function Open Collector Outputs 48v, 50mA

VFD Basic Configuration Input AC Input Voltage Converter Non-Regulated Rectifier DC Voltage Inverter Voltage Controlled Output Variable Frequency Variable Voltage Constant V/f

VFD Principle Operation Input AC power, Converts to DC, Outputs Simulated AC Power Accomplished using Pulse Width Modulation (PWM) AC DC AC

The Control Board The Brains The control board accepts real world commands and controls the inverter to accomplish those commands Speed up Speed up VFD Sections Control Board Speed up

A Little Trivia Can VFDs turn motors slower than magnetic starters or reduced voltage starters? Can VFDs turn motors faster than magnetic starters or reduced voltage starters? Can existing standard (non-inverter duty) motors run off a VFD?

Single Phase Input Several Models of VFDs can operate with single phase input voltage and supply three phase voltage to the motor VFDs make great phase converters and you also get better motor protection than the alternatives The VFD just needs to be sized appropriately for the amp load difference. Typically doubling the VFD size works i.e. if you had a 5 hp three phase motor you would need a 10 hp VFD

Question? Can we operate a VFD with 115 Vac single phase input voltage and operate a 230 Vac three phase motor?

Input Reactors Use a three phase reactor when the power source transformer (KVA) is very large compared with the VFD capacity Good insurance to help smooth power fluctuations and minor surging Important to use with open delta three phase power It helps mitigate or reduce harmonic distortion by adding impedance to slow the rise and fall of the current

Output Reactors Located between the motor terminals on the VFD and the motor. Use when the cable length is excessive (depends on the manufacturer) I prefer to use them with any submersible pump installation

Programming The basics

VFDs - Submersibles 1 st consideration Proper sizing Submersibles have different amp ratings than typical squirrel cage motors Size to the amps of the motor, never choose a VFD that is maxed by the motor amps Example if the VFD is capable of 96 amps and the motor is rated at 94 amps, choose the next size bigger VFD Means better longevity

VFDs - Submersibles Typically long cable lengths, use output reactors Since VFDs use PWM high voltage spikes come back on the VFD and can cause damage again better longevity Optional for 230 Vac, Necessary for 460 Vac Always recommended

VFDs - Submersibles Overloads set to class 10 S.F. typically 1.15 Never allow to run below 30 hz. Typical motor thrust bearings need this minimum speed to operate properly When starting/stopping the time from 0 hz to 30 hz has to be no more than 1 second if longer a shorter motor life can be expected If the installation allows for it, coasting to stop rather than a ramp stop is preferred

VFDs - Submersibles Carrier Frequency The rate the VFD generates pulses Typically set from 4K to 5K hz (pulses per second) VFDs can typically adjust between 2K and 12K The higher the setting the quieter the operation but the motor takes a beating. More inefficient, more heat, shortened motor life The lower the setting the noisier the operation but it s harder on the VFD. It s a balancing act but the motor usually wins

VFDs Line Shaft Turbines Sizing Due to typically shorter cable length & more rugged motor design the sizing is typically smaller than with Submersibles No 30 hz minimum speed requirement like subs More of a hz range can be utilized, but since they are typically 1800 rpm rather than 3600 rpm the beneficial pumping rate range is not typically greater Typical well pump installation the range starts around the 40 to 45 hz range

VFDs Line Shaft Turbines Considerations for Critical Harmonics/Vibrations Typically in the start/stop ramp cycle Rotation of the shaft, pump impellors, water moving in the column, and thrust loading can cause damaging vibrations in the pumping system If these areas of vibration are present they can be programmed out in the drive The hope is these areas are not at a desired operating point this doesn t happen often

VFDs Line Shaft Turbines Programming can include activation of prelube solenoid with a delay to start timer (water lube) Oiler solenoid can be activated during pump running (oil lube) Motor heaters can be turned on when the pump isn t running With today s VFDs and pump software the options are almost limitless

VFDs Centrifugal Pumps Sizing not unlike LS pumps. More durable motors and typically shorter cable lengths Typically less issues with programming, very simplistic in operation with less tuning issues Used as single pump and as inline pressure boosters When used as booster, the use of VFDs simplify the lead/lag operation and gives a much more controllable pressure modulation

VFDs Centrifugal Pumps When using as a single supply pump they typically don t have a very large regulation window Pump Curves are typically flat, a lot of hz change for little performance change

VFDs Centrifugal Pumps Flat Curves Limited Regulation Steeper Curves Better Regulation

Challenge Encountered Pump panel with 3 VFD drives Each controlling a different dewatering well Long cables lengths In the middle of a city shopping mall One pump very erratic and uncontrollable Wiring checked ok, system been operating for years trouble free Spent many hours trying to track the problem

Challenge Encountered Finally put a scope on the transducer wires with power off to the pump panel Found an AC wave present Checked the grounding system from the utility Found the same wave present Figured the shielded wire had been compromised to the transducer Replaced the wire, made it better but not right Established a new ground for the control circuits on the VFDs and problem became manageable

Challenge Encountered Remember when installing VFDs try to keep the power conducting cables and low voltage cable separated as much as possible Do not run them in the same conduit Run shielded cable for all sensor leads No looping the ground when have multiple VFDs

Another Challenge Deep LS pump set and ramp down problems Large pump (1500 gpm), 10 column, 700 set, 500 static level, 400 hp motor When shutting down you wanted to be off the planet and not in the room Kept faulting on the DC Bus Which would make it turn off and on Had to have a ramp down cycle due to the plumbing arrangement

Another Challenge What we found is the ramp cycle was too fast and it was causing an induced voltage on the DC Bus and causing the fault Programmed it out and better now

QUESTIONS - DISCUSSION? Kriss Schneider kriss@schneiderwater.com Schneider Water Services 503-633-2666 www.schneiderwater.com