INDUSTRY UPDATE: SAFETY INSTRUMENTED FIRE & GAS SYSTEMS (SI- FGS)



Similar documents
Basic Fundamentals Of Safety Instrumented Systems

Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments

Viewpoint on ISA TR Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President

Final Element Architecture Comparison

WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS)

Safety Requirements Specification Guideline

TABLE OF CONTENT

Selecting Sensors for Safety Instrumented Systems per IEC (ISA )

Failure Modes, Effects and Diagnostic Analysis

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

DeltaV SIS for Burner Management Systems

A methodology For the achievement of Target SIL

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability

Hardware safety integrity Guideline

Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager

Reduce Risk with a State-of-the-Art Safety Instrumented System. Executive Overview Risk Reduction Is the Highest Priority...

Safety controls, alarms, and interlocks as IPLs

SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP

IEC Functional Safety Assessment. ASCO Numatics Scherpenzeel, The Netherlands

Logic solver application software and operator interface

SAFETY LIFE-CYCLE HOW TO IMPLEMENT A

SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR

Version: 1.0 Latest Edition: Guideline

Safety Integrity Level (SIL) Assessment as key element within the plant design

SAFETY MANUAL SIL Switch Amplifier

Safety Manual BT50(T) Safety relay / Expansion relay

Mitigating safety risk and maintaining operational reliability

SAFETY MANUAL SIL SMART Transmitter Power Supply

IEC Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter.

Understanding Emergency Power Off (EPO)

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

Alarm and Detection/Suppression

Ammonia Detection System Codes and Design Specifications

Is Cost Effective Compliance with the IEC61511 Safety Lifecycle Sustainable?

B r u ne n r e Ma M n a a n g a e g m e e m n e t A S t S rai a gh g t h for o wa w r a d A p p r p oa o c a h c h Us U i s ng n g De D l e tav a

The Mission Critical Fire Protection Experts

SAFETY MANUAL SIL RELAY MODULE

HSE information sheet. Fire and explosion hazards in offshore gas turbines. Offshore Information Sheet No. 10/2008

USING INSTRUMENTED SYSTEMS FOR OVERPRESSURE PROTECTION. Dr. Angela E. Summers, PE. SIS-TECH Solutions, LLC Houston, TX

Experion Integrated Fire & Gas Safety and Security Monitoring at your fingertips! Ajay Varghese

MXa SIL Guidance and Certification

Application Requirement

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity

PLAN REVIEW GUIDE FOR FIRE ALARM

Overview of IEC Design of electrical / electronic / programmable electronic safety-related systems

Fire and Gas Solutions. Improving Safety and Business Performance

Is your current safety system compliant to today's safety standard?

Effective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers

Overview of Standards for CO Detection Products

Integrated Fire and Gas Solution - Improves Plant Safety and Business Performance

SAFETY MANUAL SIL SWITCH AMPLIFIER

Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System

TAMARAC FIRE RESCUE INSTRUCTIONS FOR FIRE ALARM PRE-SUBMITTAL CHECKLIST

Functional safety. Essential to overall safety

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September Answers for industry.

Performance Based Gas Detection System Design for Hydrocarbon Storage Tank Systems

,g) rrrs {fd fi. f il'ltdä. Failure Modes, Effects and Diagnostic Analysis. ABB Automation Products GmbH Alzenau Germany

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

Vetting Smart Instruments for the Nuclear Industry

rpsa FIRE PROTECTION ENGINEERS

INSIDE THIS ISSUE KUWAIT SECTION. December NEWSLETTER 2009 FROM SECTION PRESIDENT S DESK TECHNICAL WINDOW MEMBERS AREA PRODUCT REVIEW

SECTION FIRE ALARM AND DETECTION SYSTEMS

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator

SIL manual. Structure. Structure

Buckeye Detection Systems Fixed Detection Systems Application Survey

Version: 1.0 Last Edited: Guideline


Module 4, Lesson 12 Fire Alarm Systems

ISA CERTIFIED AUTOMATION PROFESSIONAL (CAP ) CLASSIFICATION SYSTEM

Q U A D S C A N I I GENERAL User Interface Enclosure Display QUADSCAN II Temperature Range RECEIVER DISPLAY Sensor Weight Optional Relay Enclosure

FACILITY SAFETY SIGNAGE GUIDE: 10 SIGNS TO SPOT DURING A PLANT WALKTHROUGH

Instructions. Eagle Quantum Premier Fire and Gas Detection/Releasing System Rev: 12/

Why SIL3? Josse Brys TUV Engineer

Certification Report of the STT25S Temperature Transmitter

Module 5. Fire and Emergency Alarm System Part I- Basics

Fire Alarm and Detection Systems And Central Station Monitoring Plan Submittal Guidelines

Integrating Control and Safety with Secure System Segregation

Frequently Asked Questions

UNDERSTANDING SAFETY INTEGRITY LEVEL

DET-TRONICS SPECIFICATION DATA. Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

Ammonia Detection System Codes and Design Specifications. Brian EuDaly, P.E. Calibration Technologies, Inc.

NATIONAL FIRE ALARM AND SIGNALING CODE

How to Select a Flame Detector

Frequently Asked Questions

NEMA SB Guide for Proper Use of System Smoke Detectors

Alarms Trips: The Ups and Downs

What Now? More Standards for Safety and Regulatory Compliance

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

ESTIMATION AND EVALUATION OF COMMON CAUSE FAILURES IN SIS

Whitepaper Modular Integration of Process Equipment Packages for Oil and Gas Facilities

WIRELESS REMOTE MONITORING OF CATHODIC PROTECTION SYSTEMS. John Hawkyard MICorr Deputy General Manager Rawabi Corrosion Technology Co Ltd Al-Khobar

SECTION ZONED (DC LOOP) FIREALARM SYSTEM

Methods of Determining Safety Integrity Level (SIL) Requirements - Pros and Cons

SECTION DETECTION AND ALARM

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

AGRI-ALERT 128 TOUCH AGRI-ALERT 800EZE ALARM SYSTEMS

PROGRAMMABLE LOGIC CONTROL

Automation, Software and Information Technology. Test report of the type approval safety-related automation devices

Transcription:

INDUSTRY UPDATE: SAFETY INSTRUMENTED FIRE & GAS SYSTEMS (SI- FGS) Mike Scott VP, Process Safety Applied Engineering Solutions Greenville, SC 29607 Bud Adler Director, Business Development Applied Engineering Solutions, Inc. Lake Mary, FL 32746 KEYWORDS Fire & Gas Detection Systems, FGS, Fire Panel, NFPA 72, EN 54, Safety Instrumented System, SIS, Safety Integrity Level, SIL, Safety Instrumented Fire & Gas System, SI-FGS, ANSI/ISA 84, IEC 61508, IEC 61511, Safety PLC ABSTRACT This paper will explore the current trends in the market place and industry in general with respect to Fire & Gas Detection Systems and their relationship to Safety Instrumented Systems. The concept of a Safety Instrumented Fire & Gas Detection System (SI-FGS) will be introduced and explained in detail. This will include a review of the following topics: Industry Update ISA S84 Fire & Gas sub-committee Logic Solver Update - FM & UL 864 approved SI-FGS Product Update FMEDA availability for Fire & Gas sensors and final control devices In support of this paper, the authors conducted an informal survey of Fire & Gas System OEM s, Engineering Firms and End Users, in an attempt to ascertain what are the driving factors towards the emergence and acceptance of Safety Instrumented Fire & Gas Detection Systems in the marketplace. INTRODUCTION The concept of a Safety Instrumented Fire & Gas Systems (SI-FGS) has emerged in the process industry. Its arrival is has generated both controversy and confusion. The term SI- 1 of 13

FGS represents the attempted application of performance based safety concepts to the design of Fire & Gas Detection Systems. ANSI / ISA S84.01 states that Fire & Gas Systems where operation action is required to initiate the system is not covered by the standard. Thus, those systems that automatically initiate an action could be addressed by the performance based Safety Instrumented System standards. However, the inherent differences between a Safety Instrumented System and a Fire & Gas System pose some challenges for an end user attempting to merge design techniques. This paper will discuss some of these differences and trends in industry. DIFFERENCES BEWTEEN SIS AND FGS To better understand the concept of a Safety Instrumented Fire & Gas System, let us first explore the relationship and inherent differences between the functionality and design of these two very important systems. A Safety Instrumented Fire & Gas System (SI-FGS) is a system comprised of initiating device sensors, logic solvers, final control elements, fire safety functions and / or notification appliances for the purpose of mitigating an event when predetermined conditions are violated. COMMUNITY EMERGENCY RESPONSE PLANT EMERGENCY RESPONSE MITIGATION Mechanical Mitigation Systems Safety Instrumented Control Systems Safety Instrumented Mitigation Systems PREVENTION Mechanical Protection System Process Alarms Operator Supervision Safety Instrumented Control Systems Safety Instrumented Prevention Systems Basic Process Control Systems Monitoring Systems (process alarms) Operator Supervision Process Design Figure 1 Typical risk reduction methods found in process plants 2 of 13

PREVENTION VERSUS MITIGATION A Safety Instrumented System by definition is designed to bring the process to a safe state when demand is placed upon it. For instance consider a scenario, possible rupture of a vessel with subsequent release of a flammable / toxic material that could result in on-site injuries and / or fatalities due to the ensuing fire. A Safety Instrumented System could be designed that would close the feed valve if a high-high pressure condition was detected, thus eliminating the source of overpressure. If this action is taken, the process is returned to a safe state and the potential hazardous event has been completely prevented. A Fire & Gas Detection System may include some preventative functions as described above. However, it is typically comprised of mitigating functions. A mitigating function is described as an action that does not prevent the hazardous event from occurring but instead initiates actions that reduce the potential consequences of the event after it has occurred. For instance in the example described above, one could implement a Fire & Gas System to detect the fire and / or release of the flammable material at the ruptured vessel and initiate a suppression action (water mist, foam system, etc.) This system would be designed to contain the fire to a single unit operation, lessen the potential for injuries to personnel through area alarming, and protect capital investment of the facility by quickly containing / extinguishing the fire. The Fire & Gas Detection system acted after the primary event (vessel rupture) had occurred in an attempt to lessen the consequence of this condition. Even if the Fire & Gas System does not initiate a suppression related action, the act of sounding alarms / beacons is a common mitigating action. By removing personnel from the hazardous zone one is mitigating potential injury to those workers. Refer to Figure 2 below for a typical P&ID depiction of the relationship between the above described Safety Instrumented System and Fire & Gas Detection System. 3 of 13

BV 200 I2 I2 Water Mist XV UA 203 HV 100 I1 Feed FCV PT 101 PSV 102 To Safe Location I2 Reactor I2 BSH 201 Flame Detector Figure 2 SIS & FGS Functions ASH 202 Combustible Gas Detector 4 of 13

ACTUATION STATE Another inherent difference between Safety Instrumented Systems and Fire and Gas Detection Systems is the basic design principal regarding de-energize to trip and energize to trip functionality. Most Safety Instrumented Systems are designed to de-energize (i.e. remove power, instrument air, etc.) upon detection of a potentially dangerous condition. Most Fire and Gas Detection Systems, on the other hand, are typically designed to energize (turn on power, instrument air, etc.) upon detection of a potentially dangerous condition. One needs to recognize that most of the failure data used in Probability of Failure on Demand (PFD) equations presented in various Safety Instrumented System literature sources represent deenergize to trip systems. In this mode of operation, it is generally assumed that a dangerous detected failure is converted to a nuisance trip through initiation of a diagnostic generated shutdown. Another critical concept associated with energize-to-trip systems is the mandate for some sort of source of back-up power to be provided to bring the system to a safe state upon loss of power. BACK-UP POWER REQUIREMENTS Another inherent difference between Safety Instrumented Fire & Gas Detection Systems and typical commercial Fire and Gas Detection Systems is power consumption. A commercial Fire & Gas System, specifically designed to meet NFPA 72, includes design provisions to minimize quiescent power consumption during the time frame the system is operating on back-up power. A Safety PLC based system on the other hand has been designed to operate using a de-energize-to-trip concept and, as such, specific steps to minimize power consumption have not been implemented in these type systems. Thus, a commercial Fire & Gas Detection System is going to draw micro / milli-amps whereby a Safety Instrumented Fire & Gas Detection System is going to draw many amps. Therefore, one needs to recognize that commercially available battery systems to support the power consumption requirements of a Safety PLC, while still meeting all of the diagnostic and supervision related requirements of NFPA 72 with FM and / or UL Approvals already in place, may not readily exist at this time. At the time of this writing the authors are aware of a newly FM-Approved battery system that is capable of supporting a Safety PLC based Safety Instrumented Fire & Gas Detection System. PRESCRIPTIVE VERSUS PERFORMANCE BASED SAFETY STANDARDS For example, NFPA 72 (or EN-54) contains a large number of prescriptive requirements with respect to the design and installation of Fire & Gas Detection systems. This includes requirements on initiating device circuit supervision, notification appliance circuit supervision, fire safety function circuit supervision, suppression system designs, etc. The concept of a Safety Instrumented Fire & Gas System requires implementing both the 5 of 13

prescriptive requirements of a standard like NFPA 72 or EN-54 as well as the requirements of a performance based standard such as ANSI/ISA S84.00.01-2004 in an attempt to design a system that has the best of both worlds. Implementation of both prescriptive and performance based requirements is easier said than done as the performance based requirements as described below still pose some interesting issues for industry to address. FUNCTIONAL TESTING REQUIREMENTS NFPA 72 or EN-54 does not specifically mandate functional testing of Fire & Gas Detection Systems based upon the architecture of the system and desired availability. Safety Instrumented Systems, on the other hand, have underscored the importance of functional testing and it s relationship to overall Probability of Failure on Demand calculations. This fundamental difference must be addressed for those intending to apply performance-based requirements to a Fire & Gas Detection / Mitigation System. 0.7 0.6 Probability of Failure on Demand (Probability) 0.5 0.4 0.3 0.2 0.1 0 1 4 7 10 13 16 19 22 25 28 31 34 37 40 Functional Test Interval (Time) Figure 3 Graph of PFD and Functional Testing Relationship As can be seen in Figure 3, for a given SIS architecture, the probability of failure increases with time. By conducting a functional test of the system you are attempting to identify any potential covert failures in the system. This results in a resetting of the PFD clock back down to a minimal PFD. FIRE VERSUS GAS REQUIREMENTS NFPA 72 specifies requirements associated with fire detection and / or mitigation. Gas detection is typically considered an additional action that is labeled as interference free. Depending on the Authority Having Jurisdiction (i.e. Local Fire Marshall) one may not be allowed to mix Fire, Gas & shutdown functions within a single system unless the system has been specifically approved for this application. This issue should be carefully researched to 6 of 13

ensure the all goals of the project can be readily and easily achieved. For the Authority Having Jurisdiction inform a user during Acceptance Testing that, combining Fire & Gas logic within the Safety PLC, is unacceptable would have a major impact on the project. The author s are aware of at least one NFPA 72 approved Safety Instrumented Fire & Gas Detection System that supports both Fire & Gas functionality. RELIABILITY ENGINEERING ISSUES The underlying principal behind Safety Instrumented System designs is based on reliability fundamentals regarding the failure modes of systems / devices and their impact on the ability of the system as a whole to perform it s intended function. Probability of Failure on Demand for a simple 1oo1 (One out of one) system is defined as: PFD avg = (λ DU x TI) / 2 Where, PFD avg Probability of Failure on Demand Average λ DU Failure Rate Dangerous Undetected TI Test Interval When evaluating this simplified equation, it must be recognized that the inherent differences between a de-energize-to-trip and energize-to-trip system regarding the definition of λ DU for each system. Consider the system described in Figure 2 above. BSH 201 Logic Solver UA 203 The following assumptions apply: Figure 4 Fire & Gas Schematic BSH-201 closes a contact when fire is detected Logic Solver is a Programmable Electronic System UA-203 is a alarm horn / strobe that is normally de-energized 7 of 13

Table 1 De-Energize-To-Trip Versus Energize-To-Trip Failure Modes # Failure Mode De-Energize-To-Trip Energize-To-Trip 1 A cut wire will result in a safe A cut wire will result in a dangerous Open Circuit Cut Wire detected trip when power is undetected failure unless specific associated with BSH-201 removed from the circuit (i.e. diagnostics have been included in the or UA-203 valve closes) design to detect this condition. 2 Logic Solver Output stuck OFF A stuck OFF output results in a safe detected trip when power is removed from the circuit (i.e. valve closes) A stuck OFF output represents a dangerous undetected failure unless specific diagnostics have been included in the design to detect this condition. 3 Logic Solver Output stuck ON A stuck ON output results in a dangerous undetected failure where power cannot be removed from the circuit (i.e. valve cannot be closed) A stuck ON output results in a safe detected failure where power circuit is energized (i.e. alarm horn / strobe sounded when no fire present). Note that if this was a Halon System that fired, this failure might be classified as a dangerous detected failure. Failure rate data and failure modes for a energize-to-trip design must be carefully evaluated to ensure PFD avg calculations yield accurate results. FIELD DEVICE WIRING DIFFERENCES Traditional Fire & Gas Systems utilize wiring schemes that allow many field devices to be daisy chained together on a single circuit. For instance, this type of circuit typically uses some sort of end of line device to monitor the contact state of multiple sensors or it can even use an addressable network / bus scheme. Safety Instrumented Systems, on the other hand, tend to have a single field device wired to a single I/O channel on the Safety PLC. This can result in increased costs for those attempting to migrate from a proprietary Fire & Gas System to a Safety PLC based Safety-Instrumented Fire & Gas Detection System. One should carefully review the wiring schemes required by the Safety Instrumented Fire & Gas Detection System to ensure the project s scope and funding includes the cost to engineer and install new conduit / cable to all field devices. The author s are aware of one NFPA 72 approved Safety Instrumented Fire & Gas Detection System that supports multiple field devices connected to a single I/O channel. Thus, all hope is not lost and, through careful research and due diligence, a user can, in fact, cost effectively migrate to a Safety Instrumented Fire & Gas System. PROPRIETY VERSUS OPEN SYSTEMS 8 of 13

A major driving factor towards the emergence of a Safety-Instrumented Fire & Gas Detection System seems to be the desire for a facility to utilize a common logic solver hardware platform for both Fire & Gas systems. This choice offers the following benefits: Ability to use a common Human Machine Interface Reduction in spare parts Common maintenance training / practices Common engineering platform for reduction in training / support hardware Desire to eliminate of older legacy proprietary systems and consolidate to a common platform Potential cost reduction of life of system by using one platform in lieu of two to accomplish the same task The same issues and economics that have virtually eliminated the proprietary Distributed Control System (DCS) are now forcing consolidation within the Fire & Gas and Safety Instrumented System marketplaces. In today s competitive global economy companies need every cost advantage they can get to remain competitive. INDUSTRY UPDATE ISA S84 FIRE & GAS DETECTION SUB-COMMITTEE FORMATION ISA has formed a new sub-committee to develop a technical report entitled Fire and Gas Systems (F&GS) Relationship to ANSI/ISA84.01-2004 (IEC 61511). The purpose of this technical report / guideline is to provide guidance for users and OEM vendors of industrial fire and gas systems to determine which, if any, safety instrumented functions of a F&GS should be implemented according to the requirements of ANSI/ISA 84.01-1996 and IEC 61511. The technical report / guideline will show examples of prescriptive functions that may be required by national fire codes, such as NFPA 72. This guideline, by reference to ANSI/ISA 84.01-1996 and IEC 61511, will demonstrate how to determine which functions are safety functions, and to determine the required SIL (Safety Integrity Level) for those safety functions. Also by reference to ANSI/ISA 84.01-1996, IEC 61508, and IEC 61511, the technical report / guideline will give some guidance as to how the safety functions can be implemented from a performance perspective to achieve the desired risk reduction. This subcommittee has generated a lot of interest from a variety of end users, OEM s and consultants. LOGIC SOLVER UPDATE At the time of writing this article, the authors are aware of three (3) different Safety PLC offerings that have been submitted to UL or FM for an application-based approval for Fire & Gas Detection. Also, two (2) different Fire System OEM s have developed Fire & Gas 9 of 13

Systems that have been TUV approved to meet a given Safety Integrity Level per IEC 61508. In addition, we are aware of a large number of recent projects where end users have been specifying the use of Safety PLC s for Fire & Gas Detection Systems. These requests for quotation all included performance criteria associated with meeting a specific Safety Integrity Level with respect to the logic solver. Thus, whether the demand has been created by end users or through a marketing campaign developed by manufacturer s of Safety PLC s, the fact remains that Safety PLC s are routinely being applied to Fire & Gas Detection designs with the requirement for meeting a specific Safety Integrity Level being imposed. SENSOR UPDATE A wide variety of fire and gas related sensors have had Failure Modes and Effects Diagnostics Analysis (FMEDA) performed. Refer to table below for a partial listing of some of these devices. As can be seen from the Table 2, several different OEM s have recognized the need to provide data for use in a performance-based safety instrumented system design. Table 2 FGS Sensors w/ FMEDA Data Available # Manufacturer Model # Description Optical-Thermal Loop Detector Heat / Smoke - IR Detector 1 Detectomat GmbH PL 3300 OT PIRECL Pointwatch Eclipse Hydrocarbon Gas - Infrared 2 Det-Tronics 3 Det-Tronics X3301 Multispectrum IR Flame Detector IR Flame Detector 4 Draeger PLMS ltd. Polytron Pulsar Gas - Open Path (IR absorption) 5 Dräger Safety AG & Co. KGaA IR Gas Transmitter Polytron 2IR - Type 334 Gas - Infrared 6 7 Dräger Safety AG & Co. KGaA Zellweger Analytics Limited Polytron 7000 Searchpoint Optima Plus IR point Gas - Electrochemical Gas - Infrared It is significant that sensor OEM s are beginning to provide data that could support the overall SI-FGS concept. CONCLUSION The concept of a performance-based Safety-Instrumented Fire & Gas Detection System (SI- FGS) is complex to say the least. Many issues need to be carefully considered when attempting to merge the prescriptive world of Fire & Gas Systems with the performance- 10 of 13

based world of Safety Instrumented Systems. However, end users and OEM s both appear to be driving industry towards convergence of design criteria. Let s review the facts: Numerous Fire & Gas Sensors have been submitted for FMEDA completion to support PFD calculations Several Safety PLC systems have been submitted for FM and / or UL Approval as Safety Instrumented Fire & Gas Detection Systems Several Fire Systems have been submitted to TUV for certification to IEC61508 A FM Approved battery system capable of supporting a Safety PLC based FGS is now commercially available ISA has formed a sub-committee to develop a technical report on the relationship of Fire & Gas Systems and Safety Instrumented Systems Thus, it appears that Safety-Instrumented Fire & Gas Detection Systems are gaining significant momentum and that can only benefit industry as a whole. DISCLAIMER Although it is believed that the information in this paper is factual, no warranty or representation, expressed or implied, is made with respect to any or all of the content thereof, and no legal responsibility is assumed therefore. The examples shown are simply for illustration, and, as such, do not necessarily represent any company s guidelines. The reader should use data, methodology, formulas, and guidelines that are appropriate for their own particular situation. REFERENCES 1. ANSI/ISA S84.01-1996, Application of Safety Instrumented Systems for the Process Industries, The Instrumentation, Systems, and Automation Society, Research Triangle Park, NC, 1996. 2. IEC 61508, Functional Safety of Electrical/Electronic/Programmable Safety-related Systems, Part 1-7,Geneva: International Electrotechnical Commission, 1998. 3. IEC 61511, Functional Safety: Safety Instrumented Systems for the Process Industry Sector, Parts 1-3, Geneva: International Electrotechnical Commission, 2003. 4. Goble, W.M., Control Systems Safety Evaluation & Reliability, 2 nd Edition, ISA, 1998 5. Marszal, E & Scharpf, E, Safety Integrity Level Selection Systematic Methods Including Layer of Projection Analysis, 2002, ISA, Research Triangle Park, NC 11 of 13

6. NFPA 72 National Fire Alarm Code, Quincy, MA, National Fire Protection Association, August, 2002 7. EN 54 Fire Detection And Fire Alarm Systems, European Standards (Norme Europenne), 2001 8. Kimberly A. Dejmek and Richard Skone, Standard's use spreading, but confusion still surrounds FGS, Fire and Gas, June 2003 12 of 13

ABBREVIATIONS AND DEFINITIONS 1oo1 1oo1D 1oo2 1oo2D 2oo3 IEC MTTFS PFDavg PLC RRF SI-FGS SIF SIL SIS 1-out-of-1 1-out-of-1 D (D for extensive self-diagnostics) 1-out-of-2 1-out-of-2 D (D for extensive self-diagnostics) 2-out-of-3 International Electrotechnical Commission Mean Time To Fail Spurious Average Probability of Failure on Demand Programmable Logic Controller Risk Reduction Factor Safety Instrumented Fire & Gas Detection System Safety Instrumented Function Safety Integrity Level Safety Instrumented System 13 of 13