IEC Functional Safety Assessment. ASCO Numatics Scherpenzeel, The Netherlands

Size: px
Start display at page:

Download "IEC 61508 Functional Safety Assessment. ASCO Numatics Scherpenzeel, The Netherlands"

Transcription

1 IEC Functional Safety Assessment Project: Series 327 Solenoid Valves Customer: ASCO Numatics Scherpenzeel, The Netherlands Contract No.: Q09/04-59 Report No.: ASC R003 V1 R Assessment Version V1, Revision R3, May 29, 2012 Chris O'Brien The document was prepared using best effort. The authors make no warranty of any kind and shall not be liable in any event for incidental or consequential damages in connection with the application of the document. All rights reserved.

2 Management summary This report summarizes the results of the functional safety assessment according to IEC carried out on the: Series 327 Solenoid Valves The functional safety assessment performed by exida consisted of the following activities: - exida Certification assessed the development process used by ASCO Numatics by an onsite audit and review of the safety case (technical file) created for the initial certification. The safety case provides detailed results showing how the product and processes meet the requirements of IEC exida Certification reviewed and assessed a detailed Failure Modes, Effects, and Diagnostic Analysis (FMEDA) of the devices to document the hardware architecture and failure behavior. The functional safety assessment was performed to the requirements of IEC 61508, SIL 3. A full IEC safety case was prepared, using the exida SafetyCaseDB tool, and used as the primary audit tool. Hardware process requirements and all associated documentation were reviewed. The manufacturing quality system was reviewed. Environmental test reports were reviewed. Also the user documentation was reviewed. The results of the Functional Safety Assessment can be summarized by the following statements: The Series 327 Solenoid Valves were found to meet the requirements of SIL 3. The manufacturer will be entitled to use the Functional Safety Logo. The manufacturer may use the mark: Chris O'Brien Page 2 of 17

3 Table of Contents Management summary Purpose and Scope Project management exida Roles of the parties involved Standards / Literature used Reference documents Documentation provided by ASCO Numatics Documentation generated by exida Product Description IEC Functional Safety Assessment Methodology Assessment level Results of the IEC Functional Safety Assessment Functional Safety Management Safety Requirements Specification and Architecture Design Hardware Design Manufacturing Validation Verification Modifications User documentation Hardware Assessment Terms and Definitions Status of the document Liability Releases Future Enhancements Release Signatures Chris O'Brien Page 3 of 17

4 1 Purpose and Scope Generally three options exist when doing an assessment of sensors, interfaces and/or final elements. Option 1: Hardware assessment according to IEC Option 1 is a hardware assessment by exida according to the relevant functional safety standard(s) like IEC or EN The hardware assessment consists of a FMEDA to determine the fault behavior and the failure rates of the device, which are then used to calculate the Safe Failure Fraction (SFF) and the average Probability of Failure on Demand (PFD AVG ). This option shall provide the safety instrumentation engineer with the required failure data as per IEC / IEC and does not include an assessment of the development process. Option 2: Hardware assessment with proven-in-use consideration according to IEC / IEC Option 2 is an assessment by exida according to the relevant functional safety standard(s) like IEC or EN The hardware assessment consists of a FMEDA to determine the fault behavior and the failure rates of the device, which are then used to calculate the Safe Failure Fraction (SFF) and the average Probability of Failure on Demand (PFD AVG ). In addition, this option includes an assessment of the proven-in-use demonstration of the device and its software including the modification process. This option is useful in combination with end user failure records for doing a prior use justification. Option 3: Full assessment according to IEC Option 3 is a full assessment by exida according to the relevant application standard(s) like IEC or EN 298 and the necessary functional safety standard(s) like IEC or EN The full assessment extends option 1 by an assessment of all fault avoidance and fault control measures during hardware and software development. This assessment shall be done according to option 3. This document shall describe the results of the IEC functional safety assessment of the ASCO Numatics Series 327 Solenoid Valves. The assessment has been carried out based on the quality procedures and scope definitions of exida Certification S.A. Chris O'Brien Page 4 of 17

5 2 Project management 2.1 exida exida is one of the world s leading knowledge companies specializing in automation system safety and availability with over 300 years of cumulative experience in functional safety. Founded by several of the world s top reliability and safety experts from assessment organizations and manufacturers, exida is a partnership with offices around the world. exida offers training, coaching, project oriented consulting services, internet based safety engineering tools, detail product assurance and certification analysis and a collection of on-line safety and reliability resources. exida maintains a comprehensive failure rate and failure mode database on process equipment. 2.2 Roles of the parties involved ASCO Numatics exida Consulting exida Certification Manufacturer of the Series 327 Solenoid Valves Provided services to support ASCO Numatics and performed the original functional safety assessment of the Series 327 Solenoid Valves. Performed the IEC Functional Safety Assessment according to option 3 (see section 1) as an independent organization. The assessment was performed by Chris O Brien, assessor, who was not involved in the execution of the audited activities. ASCO Numatics contracted exida in October 2009 with the IEC Functional Safety Assessment of the above mentioned devices. 2.3 Standards / Literature used The services delivered by exida were performed based on the following standards / literature. [N1] IEC (Parts 1-7): 2000 Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems Chris O'Brien Page 5 of 17

6 2.4 Reference documents Documentation provided by ASCO Numatics [D1] Initial Marketing Data Marketing Data Sheet Template Sheet, Rev A; 1/01 [D2] Marketing Data Sheet Marketing Data Sheet for 327 and NF Low Temperature [D3] Technical Specification Sheet (TSS), Rev A; 11/3/2009 Product Technical Specification Sheet, 327 Artic Conditions [D4] MP-I-121, 10/24/2003 Procedure for handling of ASCO Valve, Inc. Stop Orders [D5] EDP-013, Rev AF; 6/2/2009 Request for Engineering Investigation or Change [D6] EDP-145, Rev G; 8/12/08 Valve Engineering Design Review Process [D7] [D8] EDP-148, Rev A; 5/16/2002 Qualification Test Plan procedure NPD2-001, Rev B; 11/10/09 New Product Development for Platform Products [D9] GBP-07, Rev B; 11/8/2009 ECN User Guide [D10] ELP-161, Rev E; 11/8/82 [D11] VSP-14, 9/1/05 [D12] QTP template, Version 19; 10/5/05 [D13] QTR Conducting valve engineering laboratory life tests Procedure for handling valve returns Qualification Test Plan Matrix - template Qualification Test Report - Cover Sheets [D14] QTP: QTP BF Qualification Test Plan, 327 Arctic Conditions; 5/18/2009 [D15] Catalog 34, online; 1/31/2010 [D16] Safety Manual, Rev 0; 5/09 [D17] P202, Rev C; 8/8/2007 [D18] QTP No.: 262B03 QTP BF Solenoid Valves, Air Operated Valves, Combustion Products, Accessories Catalog Safety Manual for Solenoid Pilot Valves Behandeling Customer Troubles (Handling Customer Complaints) Qualification Test Plan Matrix, 327B3(WS)IS modifications Chris O'Brien Page 6 of 17

7 2.4.2 Documentation generated by exida [R1] [R2] [R3] ASC R001 V1 R4 Series 327 Solenoid Valves FMEDA Report, 05/17/2012 ASC R002 SafetyCase Review, V1 R2, 05/29/2012 ASC R003 V1 R3 IEC Assessment.doc, 5/29/2012 FMEDA report ASCO Series 327 Solenoid Valves ASCO IEC Compliance Assessment, SafetyCaseDB Review IEC Functional Safety Assessment, ASCO Numatics Series 327 Solenoid Valves (this report) Chris O'Brien Page 7 of 17

8 3 Product Description The Series 327 Solenoid Valves are 3/2 solenoid valves that are direct operated with a balanced poppet. The Models 327B are basic flow models with ¼ inch pipe connections. The Models 327A are high flow models with ¼ and ½ inch pipe connections. The Models 327B are available in a redundant configuration. The Series 327 Solenoid Valves are offered in four coil power levels. The Series 327 Solenoid Valves are available with manual operators that are used to reset the solenoid to the energized position after a trip. The manual operators do not serve a safety function. Table 1 lists the model numbers and coil versions of the Series 327 Solenoid Valves covered by this FMEDA. Table 1 Coil Options Basic Model Number Coil Power 327B0/8327G Basic Power (10.0 to 14 W) 327B1 Medium Power ( W) 327B2 Reduced Power ( W) 327B3 Low Power (1.8 W) 327A6 Basic Power (10.0 to 14 W) Figure 1 shows a direct operated, basic flow, balanced poppet Series 327 Solenoid Valves. Figure 1: Series 327 Solenoid Valve Chris O'Brien Page 8 of 17

9 Table 2 gives an overview of the different versions that were considered in the FMEDA of the Series 327 Solenoid Valves. Table 2 Version Overview Model 327B0/8327G 327B1 327B2 327B3 327B3(WS)IS 327A6 Redundant 327B0 Redundant 327B1 Redundant 327B2 Redundant 327B3 MO 1 (Manual Operator) NVR 2 (Manual Operator) Configuration De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed / Normally Open De-Energize to trip / Energize to trip, Normally Closed De-Energize to trip / Energize to trip, Normally Closed De-Energize to trip / Energize to trip, Normally Closed De-Energize to trip / Energize to trip, Normally Closed De-Energize to trip De-Energize to trip Energize to trip applications failure rates do not take into account the loss of power to the solenoid. The Series 327 Solenoid Valves are classified as a Type A 3 devices according to IEC 61508, having a hardware fault tolerance of 0. 1 The MO manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. 2 The NVR manual operator option is used to reset the solenoid manually. It is not part of the safety function of the solenoid valve but does contribute to the failure rates of the solenoid valve. 3 Type A component: Non-Complex component with well-defined failure modes, for details see of IEC Chris O'Brien Page 9 of 17

10 4 IEC Functional Safety Assessment The IEC Functional Safety Assessment was performed based on the information received from the ASCO Numatics and is documented in [R2]. 4.1 Methodology The full functional safety assessment includes an assessment of all fault avoidance and fault control measures during hardware and software development (if applicable) and demonstrates full compliance with IEC to the end-user. The assessment considers all requirements of IEC Any requirements that have been deemed not applicable have been marked as such in the full SafetyCase report, e.g. software development requirements for a product with no software. As part of the IEC functional safety assessment the following aspects have been reviewed: Development process, including: o Functional Safety Management, including training and competence recording, FSM planning, and configuration management o Specification process, techniques and documentation o Design process, techniques and documentation, including tools used o Validation activities, including development test procedures, test plans and reports, production test procedures and documentation o Verification activities and documentation o Modification process and documentation o Installation, operation, and maintenance requirements, including user documentation Product design o Hardware architecture and failure behavior, documented in an FMEDA Manufacturing process o Manufacturing quality system The review of the development procedures is described in sections 5.1 through 5.8. The review of the product design is described in section Assessment level The Series 327 Solenoid Valves have been assessed per IEC to the following levels: SIL 3 capable The development procedures will be assessed as suitable for use in applications with a maximum Safety Integrity Level of 3 (SIL3) according to IEC Chris O'Brien Page 10 of 17

11 5 Results of the IEC Functional Safety Assessment exida assessed the development process used by ASCO Numatics for this development against the objectives of IEC parts 1 and 2. A detailed SafetyCase was completed, see [R2]. This functional safety assessment has shown that the process sufficiently meets the requirements of IEC 61508, SIL 3. The assessment investigated the compliance with IEC of the processes, procedures and techniques as implemented for the ASCO Numatics development. The investigation was executed using subsets of the IEC requirements tailored to the SIL 3 work scope of the development team. The result of the assessment can be summarized by the following observations: The audited ASCO Numatics development process complies with the relevant managerial requirements of IEC SIL Functional Safety Management FSM Planning ASCO Numatics has a 7-phase staged-gate process in place for product development with specific deliverables, reviews and approvals at each gate. This is documented in NPD2-001 [D8]. The same process is used for modifications. This process and procedures referenced herein fulfill the requirements of IEC with respect to functional safety management. Version Control All documents as called out for in NPD2-001 are under version control. Design drawings and documents are also under version control. Training, Competency recording Personnel training records are kept per standard quality procedures. Engineering personnel involved in the project have received IEC training. ASCO Numatics hired exida to be the independent assessor per IEC and to provide specific IEC knowledge. 5.2 Safety Requirements Specification and Architecture Design The first step for any new development is the creation of a Marketing Data Sheet (MDS) [D2] by the Marketing Department. Once this has been reviewed and the project accepted, engineering will develop the project Technical Specification Sheet (TSS) [D3]. This captures in detail all the requirements for the devices, such as critical functions, performance targets etc. exida reviewed the content of the specification for completeness per the requirements of IEC As the valves are simple electro-mechanical devices, there is no need for a separate architecture design phase. The MDS and TSS will indicate if the design is new or based on an existing design. Requirements as specified in the Technical Specification Sheet (TSS) are tracked through all development phases. Items from IEC , Table B.1 include project management, documentation, separation of safety requirements from non-safety requirements, structured specification, and inspection of the specification. As the function of the valve is simple and clearly defined there is no need for semiformal methods such as functional block diagrams. The application is considered when specifying the requirements; the devices may be required to meet specific applications standards. This meets SIL 3. Chris O'Brien Page 11 of 17

12 5.3 Hardware Design The hardware design process consists of two distinct phases: concept verification, and design and development. During concept verification all possible solutions are reviewed and the most promising is detailed. During this phase also the Qualification Test Plan and Agency Approval Plan is developed (equal to validation plan per IEC 61508). In the design and development phase, the design is further detailed and Qualification testing is performed on beta units. Per EDP-145 [D6], a preliminary design review, an intermediate and final design review is conducted. ASCO Numatics has standards for documentation with specified output documents. ASCO Numatics uses ProE and AutoCad as development tools. Version numbers should be listed and re-qualification should be done when the tool vendor makes revisions. Re-qualification test results should be documented and reviewed. ASCO Numatics confirmed that tool re-qualification is performed. Items from IEC , Table B.2 include observance of guidelines and standards, project management, documentation (design outputs are documented per NPD2-001 and other quality guidelines), structured design, modularization, use of well-tried components, and computer-aided design tools. This meets SIL Manufacturing The Series 327 Solenoid Valves are manufactured in an ISO certified facility. All units are functionally tested. Field returns are tracked and reviewed monthly to identify quality issues and performance issues. Customer feedback is solicited and reviewed to identify performance issues and opportunities for product improvements. This meets SIL Validation Validation Testing is done via a documented plan, the Qualification Test Plan, written per the Technical Specification Sheet and includes compliance testing per application standards, through the Agency Approval Plan which is part of the QTP. The QTP is traceable to the TSS. As the Series 327 Solenoid Valves are purely electro-mechanical devices with a simple safety function, there is no separate integration testing necessary. However, the solenoids do undergo several separate tests before valve body and solenoid are integrated; this is part of the Qualification Test Plan. The Series 327 Solenoid Valves perform only 1 safety function, which is extensively tested under various conditions during validation testing. Procedures are in place for corrective actions to be taken when tests fail. Every run of the Qualification Test Plan is documented in a Qualification Test Report and reviewed. Items from IEC , Table B.3 include functional testing, project management, documentation, and black-box testing (for the considered devices this is similar to functional testing). Field experience and statistical testing via regression testing are not applicable. This meets SIL 3. Items from IEC , Table B.5 included functional testing and functional testing under environmental conditions, project management, documentation, failure analysis (analysis on products that failed), and expanded functional testing and black-box testing. Interference surge immunity testing is not applicable and fault insertion testing is not feasible for these devices. Instead a detailed FMEDA was performed. This meets SIL 3. Chris O'Brien Page 12 of 17

13 5.6 Verification The development and verification activities are defined in the New Product Development Process for Platform Products, NPD For each phase the objectives are stated, as well as required input and output documents and review activities. Checklists are used for e.g. the review of the Marketing Data Sheet. Design reviews are governed by EDP-145, Valve Engineering Design Review Process. Per NPD2-001, the following verification steps are defined: product idea review, concept definition review, feasibility review, design and development review, pilot run review, and introduction review. All verification activities are documented. This meets SIL Modifications Modifications are done per the Engineering Change Notice procedure [D9]. A web-based system is in place to track ECNs. The ECN system allows to user to identify if a certified device is affected. Affected documents and/or drawings are also listed. If design changes are identified as a result of an ECN, they are usually treated as a derived product and therefore the same general procedure is used for both new development and modifications. All design change requests are reviewed to determine if there is any negative impact on product safety. This review is done by both the assigned engineer and the appropriate engineering manager. This meets SIL User documentation ASCO Numatics creates the following user documentation: product catalog [D15] and safety manual [D16]. Items from IEC , Table B.4 include operation and maintenance instructions, user friendliness, maintenance friendliness, project management, documentation, limited operation possibilities (valve performs well-defined action) and operation only by skilled operators (operators familiar with type of valve, although this is partly the responsibility of the end-user). This meets SIL Hardware Assessment To evaluate the hardware design of the Series 327 Solenoid Valves a Failure Modes, Effects, and Diagnostic Analysis was performed by exida. This is documented in [R1]. A Failure Modes and Effects Analysis (FMEA) is a systematic way to identify and evaluate the effects of different component failure modes, to determine what could eliminate or reduce the chance of failure, and to document the system in consideration. An FMEDA (Failure Mode Effect and Diagnostic Analysis) is an FMEA extension. It combines standard FMEA techniques with extension to identify online diagnostics techniques and the failure modes relevant to safety instrumented system design. From the FMEDA failure rates are derived for each important failure category. Table 3 lists these failure rates as reported in the FMEDA reports. The failure rates are valid for the useful life of the devices. Based on ASCO Numatics endurance test data and general field failure data a useful life period of approximately 10 years is expected for the Series 327 Solenoid Valves. This is listed in the FMEDA reports. Chris O'Brien Page 13 of 17

14 Table 3 Failure Rates According to IEC (in FITs) Model Failure Category sd su 4 327B0/8327G 327B1&2 327B3 327B3(WS)IS 327B0 Redundant 327B1&2 Redundant 327B3 Redundant 327A6 MO NRV dd du SFF 5 De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % Energize To Trip % De-Energize to Trip W/PVST % Energize To Trip W/PVST % De-Energize to Trip % De-Energize to Trip W/PVST % De-Energize to Trip % De-Energize to Trip W/PVST % 4 It is important to realize that the Residual failures are included in the safe undetected failure category according to IEC Note that these failures on their own will not affect system reliability or safety, and should not be included in spurious trip calculations 5 The SFF must be calculated for the complete final element. These values are only valid when the solenoid valve constitutes the entire final element. Chris O'Brien Page 14 of 17

15 When using the MO or NRV options the failure rates for these options must be added to the failure rates of the Solenoid Models they are used with. For SIL 2 applications, the PFD AVG value needs to be 10-3 and < This means that for a SIL 2 application without partial valve stroke testing, the PFD AVG for a 1-year Proof Test Interval of the Series 327 Solenoid Valves is approximately equal to 10% of the range for the 327A6. When performing partial valve stroke testing at regular intervals, the Series 327 Solenoid Valve minimally contributes to the overall PFD AVG of the Safety Instrumented Function. These results must be considered in combination with PFD AVG values of other devices of a Safety Instrumented Function (SIF) in order to determine suitability for a specific Safety Integrity Level (SIL). It is the responsibility of the Safety Instrumented Function designer to do calculations for the entire SIF. For redundant use, common cause failure between the solenoid valves has to be considered. The Safety Manual should include estimation of the common cause factor β; β is estimated to be 5% for all options. exida recommends the accurate Markov based exsilentia software tool for this purpose. The analysis shows that design of the Series 327 Solenoid Valves can meet the hardware requirements of IEC 61508, SIL 2 when used as a single final element (HFT = 0) and IEC 61508, SIL 3 for redundant use (HFT > 0). Chris O'Brien Page 15 of 17

16 6 Terms and Definitions Fault tolerance FIT FMEDA HFT Low demand mode PFD AVG SFF SIF SIL SIS Type A (sub)system Type B (sub)system Ability of a functional unit to continue to perform a required function in the presence of faults or errors (IEC , 3.6.3) Failure In Time (1x10-9 failures per hour) Failure Mode Effect and Diagnostic Analysis Hardware Fault Tolerance Mode, where the frequency of demands for operation made on a safetyrelated system is no greater than twice the proof test frequency. Average Probability of Failure on Demand Safe Failure Fraction summarizes the fraction of failures, which lead to a safe state and the fraction of failures which will be detected by diagnostic measures and lead to a defined safety action. Safety Instrumented Function Safety Integrity Level Safety Instrumented System Implementation of one or more Safety Instrumented Functions. A SIS is composed of any combination of sensor(s), logic solver(s), and final element(s). Non-Complex (sub)system (using discrete elements); for details see of IEC Complex (sub)system (using micro controllers or programmable logic); for details see of IEC Chris O'Brien Page 16 of 17

17 7 Status of the document 7.1 Liability exida prepares reports based on methods advocated in International standards. Failure rates are obtained from a collection of industrial databases. exida accepts no liability whatsoever for the use of these numbers or for the correctness of the standards on which the general calculation methods are based. 7.2 Releases Version: V1 Revision: R3 Version History: V1, R3: Added 327B3(WS)IS to report, C. O Brien, May 29, 2012 V1, R2: Added 8327G to report, S. Close, Sep 15, 2010 V1, R1: Released; January 31, 2010 V0, R1: Draft; January 31, 2010 Authors: Chris O'Brien Review: V0, R1 Rachel Amkreutz; January 31, 2010 Release status: Released 7.3 Future Enhancements At request of client. 7.4 Release Signatures Rachel Amkreutz Chris O Brien, Partner Chris O'Brien Page 17 of 17

IEC 61508 Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter.

IEC 61508 Functional Safety Assessment. Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter. 61508 SIL 3 CAPABLE IEC 61508 Functional Safety Assessment Project: K-TEK Corporation AT100, AT100S, AT200 Magnetostrictive Level Transmitter Customer: K-TEK Corporation Prairieville, LA USA Contract No.:

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Inductive NAMUR sensors Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 03/11-10 Report No.: P+F 03/11-10 R015 Version V1, Revision R1.1, July

More information

IEC 61508 Functional Safety Assessment. United Electric Controls Watertown, MA USA

IEC 61508 Functional Safety Assessment. United Electric Controls Watertown, MA USA IEC 61508 Functional Safety Assessment Project: One Series Safety Transmitter Customer: United Electric Controls Watertown, MA USA Contract No.: Q12/10-073 Report No.: UEC 1210073 R002 Version V1, Revision

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Plant-STOP 9475 Company: R. STAHL Schaltgeräte GmbH Waldenburg Germany Contract No.: STAHL 13/04-027 Report No.: STAHL 13/04-027 R024 Version V1,

More information

Final Element Architecture Comparison

Final Element Architecture Comparison Final Element Architecture Comparison 2oo2 with diagnostics: Lower False Trip Rate and High Safety Project: Safety Cycling Systems Architecture Review Customer: Safety Cycling Systems, L.L.C. 1018 Laurel

More information

Effective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers

Effective Compliance. Selecting Solenoid Valves for Safety Systems. A White Paper From ASCO Valve, Inc. by David Park and George Wahlers Effective Compliance with IEC 61508 When Selecting Solenoid Valves for Safety Systems by David Park and George Wahlers A White Paper From ASCO Valve, Inc. Introduction Regulatory modifications in 2010

More information

Hardware safety integrity Guideline

Hardware safety integrity Guideline Hardware safety integrity Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed

More information

Version: 1.0 Latest Edition: 2006-08-24. Guideline

Version: 1.0 Latest Edition: 2006-08-24. Guideline Management of Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se Quoting of this report is allowed but please

More information

Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments

Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments Understanding Safety Integrity Levels (SIL) and its Effects for Field Instruments Introduction The Industrial process industry is experiencing a dynamic growth in Functional Process Safety applications.

More information

Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004)

Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004) Selecting Sensors for Safety Instrumented Systems per IEC 61511 (ISA 84.00.01 2004) Dale Perry Worldwide Pressure Marketing Manager Emerson Process Management Rosemount Division Chanhassen, MN 55317 USA

More information

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator

Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator Instruction Manual Supplement ED, ES, ET, EZ, HP, HPA Valves with 657/667 Actuator Safety manual for Fisherr ED,ES,ET,EZ, HP, or HPA Valves with 657 / 667 Actuator Purpose This safety manual provides information

More information

MXa SIL Guidance and Certification

MXa SIL Guidance and Certification MXa SIL Guidance and Certification SIL 3 capable for critical applications Experience In Motion Functional Safety in Plants Safety and instrumentation engineers demand that a functional safety system s

More information

Certification Report of the STT25S Temperature Transmitter

Certification Report of the STT25S Temperature Transmitter Certification Report of the STT25S Temperature Transmitter Revision No.: 1.2 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2009-Jul-10 SAS-135/2006T STT25S Temperature Transmitter

More information

SAFETY MANUAL SIL RELAY MODULE

SAFETY MANUAL SIL RELAY MODULE PROCESS AUTOMATION SAFETY MANUAL SIL RELAY MODULE KFD0-RSH-1.4S.PS2 ISO9001 3 With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions The exida 61508 Certification Program V1 R8 October 19, 2007 exida Geneva, Switzerland Sellersville, PA 18960, USA, +1-215-453-1720 Munich, Germany, +49 89 4900 0547 1 Exida

More information

Basic Fundamentals Of Safety Instrumented Systems

Basic Fundamentals Of Safety Instrumented Systems September 2005 DVC6000 SIS Training Course 1 Basic Fundamentals Of Safety Instrumented Systems Overview Definitions of basic terms Basics of safety and layers of protection Basics of Safety Instrumented

More information

IEC 61508 Overview Report

IEC 61508 Overview Report IEC 61508 Overview Report A Summary of the IEC 61508 Standard for Functional Safety of Electrical/Electronic/Programmable Electronic Safety-Related Systems exida Sellersville, PA 18960, USA +1-215-453-1720

More information

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. March 2009. Valves

Guidelines. Safety Integrity Level - SIL - Valves and valve actuators. March 2009. Valves Valves Guidelines Safety Integrity Level - SIL - Valves and valve actuators March 2009 VDMA German Engineering Federation Valves Manufacturers Association Chairman: Prof.-Dr.-Ing. Heinfried Hoffmann Managing

More information

ISO 26262:2011 Functional Safety Assessment Report. Texas Instruments Richardson, TX USA. Project: TDA2X ADAS SoC. Customer:

ISO 26262:2011 Functional Safety Assessment Report. Texas Instruments Richardson, TX USA. Project: TDA2X ADAS SoC. Customer: ISO 26262:2011 Functional Safety Report Project: TDA2X ADAS SoC Customer: Texas Instruments Richardson, TX USA Contract No.: Q13/09-037 Report No.: TI 13-09-037 R002 Version V1, Revision R1, January 23,

More information

SAFETY MANUAL SIL Switch Amplifier

SAFETY MANUAL SIL Switch Amplifier PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable: The General

More information

SAFETY MANUAL SIL SWITCH AMPLIFIER

SAFETY MANUAL SIL SWITCH AMPLIFIER PROCESS AUTOMATION SAFETY MANUAL SIL SWITCH AMPLIFIER KF**-SR2-(Ex)*(.LB), KFD2-SR2-(Ex)2.2S ISO9001 2 With regard to the supply of products, the current issue of the following document is applicable:

More information

Frequently Asked Questions

Frequently Asked Questions Frequently Asked Questions The exida Certification Program Functional Safety (SIL) Cyber-Security V2 R3 June 14, 2012 exida Sellersville, PA 18960, USA, +1-215-453-1720 Munich, Germany, +49 89 4900 0547

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the hardware safety integrity of the Valvetop ESD Valve Controller manufactured by TopWorx Inc. 3300 Fern Valley Road Louisville Kentucky 40213 USA

More information

Vetting Smart Instruments for the Nuclear Industry

Vetting Smart Instruments for the Nuclear Industry TS Lockhart, Director of Engineering Moore Industries-International, Inc. Vetting Smart Instruments for the Nuclear Industry Moore Industries-International, Inc. is a world leader in the design and manufacture

More information

A methodology For the achievement of Target SIL

A methodology For the achievement of Target SIL A methodology For the achievement of Target SIL Contents 1.0 Methodology... 3 1.1 SIL Achievement - A Definition... 4 1.2 Responsibilities... 6 1.3 Identification of Hazards and SIL Determination... 8

More information

Reducing Steps to Achieve Safety Certification

Reducing Steps to Achieve Safety Certification Reducing Steps to Achieve Safety Certification WP-01174-1.0 White Paper This white paper describes the successful steps in achieving certification for an FPGA implementation of an application certified

More information

Functional Safety Management of the development process of safety related programmable electronic systems at Jaquet Technology Group

Functional Safety Management of the development process of safety related programmable electronic systems at Jaquet Technology Group Functional Safety Management of the development process of safety related programmable electronic systems at Jaquet Technology Group Document type: Certification Report Client: Jaquet Technology Group

More information

SAFETY LIFE-CYCLE HOW TO IMPLEMENT A

SAFETY LIFE-CYCLE HOW TO IMPLEMENT A AS SEEN IN THE SUMMER 2007 ISSUE OF... HOW TO IMPLEMENT A SAFETY LIFE-CYCLE A SAFER PLANT, DECREASED ENGINEERING, OPERATION AND MAINTENANCE COSTS, AND INCREASED PROCESS UP-TIME ARE ALL ACHIEVABLE WITH

More information

SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR

SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR SAFETY LIFECYCLE WORKBOOK FOR THE PROCESS INDUSTRY SECTOR The information and any recommendations that may be provided herein are not intended

More information

DeltaV SIS for Burner Management Systems

DeltaV SIS for Burner Management Systems January 2011 Page 1 DeltaV SIS for Burner Management Systems RESULTS Inhibit startup when unsafe conditions exist Protect against unsafe operating conditions, including improper fuel quantities Provide

More information

SIL manual. Structure. Structure

SIL manual. Structure. Structure With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central

More information

,g) rrrs {fd fi. f il'ltdä. Failure Modes, Effects and Diagnostic Analysis. ABB Automation Products GmbH Alzenau Germany

,g) rrrs {fd fi. f il'ltdä. Failure Modes, Effects and Diagnostic Analysis. ABB Automation Products GmbH Alzenau Germany ' I rrrs {fd fi 1;;,g) -.- f il'ltdä Failure Modes, Effects and Diagnostic Analysis Project: Temperature transmitters TSP***, TT*200-*H and TT*3*0-*H with 4..20 ma output Customer: ABB Automation Products

More information

SAFETY MANUAL SIL SMART Transmitter Power Supply

SAFETY MANUAL SIL SMART Transmitter Power Supply PROCESS AUTOMATION SAFETY MANUAL SIL SMART Transmitter Power Supply KFD2-STC4-(Ex)*, KFD2-STV4-(Ex)*, KFD2-CR4-(Ex)* ISO9001 2 3 With regard to the supply of products, the current issue of the following

More information

Safety Requirements Specification Guideline

Safety Requirements Specification Guideline Safety Requirements Specification Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary Safety Requirement

More information

Is your current safety system compliant to today's safety standard?

Is your current safety system compliant to today's safety standard? Is your current safety system compliant to today's safety standard? Abstract It is estimated that about 66% of the Programmable Electronic Systems (PES) running in the process industry were installed before

More information

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity

Value Paper Author: Edgar C. Ramirez. Diverse redundancy used in SIS technology to achieve higher safety integrity Value Paper Author: Edgar C. Ramirez Diverse redundancy used in SIS technology to achieve higher safety integrity Diverse redundancy used in SIS technology to achieve higher safety integrity Abstract SIS

More information

Mitigating safety risk and maintaining operational reliability

Mitigating safety risk and maintaining operational reliability Mitigating safety risk and maintaining operational reliability Date 03/29/2010 Assessment and cost-effective reduction of process risks are critical to protecting the safety of employees and the public,

More information

Logic solver application software and operator interface

Logic solver application software and operator interface Logic solver application software and operator interface By RJ Perry, Control Systems Consultant Correctly implemented and structured functional logic, together with operator interface displays, can improve

More information

Viewpoint on ISA TR84.0.02 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President

Viewpoint on ISA TR84.0.02 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President Viewpoint on ISA TR84.0.0 Simplified Methods and Fault Tree Analysis Angela E. Summers, Ph.D., P.E., President Presented at Interkama, Dusseldorf, Germany, October 1999, Published in ISA Transactions,

More information

TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com. Being able to demonstrate competency is now an IEC 61508 requirement:

TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com. Being able to demonstrate competency is now an IEC 61508 requirement: CC & technical support services TÜV FS Engineer Certification Course www.silsupport.com www.tuv.com Being able to demonstrate competency is now an IEC 61508 requirement: CAPITALISE ON EXPERT KNOWLEDGE

More information

Safety Manual BT50(T) Safety relay / Expansion relay

Safety Manual BT50(T) Safety relay / Expansion relay Safety Manual BT50(T) Safety relay / Expansion relay ABB Jokab Safety Varlabergsvägen 11, SE-434 39, Sweden www.abb.com/jokabsafety Read and understand this document Please read and understand this document

More information

Achieving Functional Safety with Global Resources and Market Reach

Achieving Functional Safety with Global Resources and Market Reach Achieving Functional Safety with Global Resources and Market Reach 0A 0B Burner management systems Combustion controls Electric vehicle components (on-board, off board) Electrosensitive equipment Elevator

More information

CASS TEMPLATES FOR SOFTWARE REQUIREMENTS IN RELATION TO IEC 61508 PART 3 SAFETY FUNCTION ASSESSMENT Version 1.0 (5128)

CASS TEMPLATES FOR SOFTWARE REQUIREMENTS IN RELATION TO IEC 61508 PART 3 SAFETY FUNCTION ASSESSMENT Version 1.0 (5128) CASS TEMPLATES FOR SOFTWARE REQUIREMENTS IN RELATION TO PART 3 SAFETY FUNCTION ASSESSMENT Version 1.0 (5128) Report No. T6A01 Prepared for: The CASS Scheme Ltd By: The 61508 Association All comment or

More information

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability

Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability Fisher FIELDVUE Instrumentation Improving Safety Instrumented System Reliability 2 Improving Safety Instrumented System Reliability Improving Safety Instrumented System Reliability 3 Safety Instrumented

More information

How to Upgrade SPICE-Compliant Processes for Functional Safety

How to Upgrade SPICE-Compliant Processes for Functional Safety How to Upgrade SPICE-Compliant Processes for Functional Safety Dr. Erwin Petry KUGLER MAAG CIE GmbH Leibnizstraße 11 70806 Kornwestheim Germany Mobile: +49 173 67 87 337 Tel: +49 7154-1796-222 Fax: +49

More information

Machineontwerp volgens IEC 62061

Machineontwerp volgens IEC 62061 Machineontwerp volgens IEC 62061 Insert Photo Here Safety solution Architect Safety Local Business Leader Benelux. Stephen Podevyn Safety Solution Seminar Agenda deel 1 1. Richtlijnen en normen 2. Safety

More information

TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification

TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification TÜV Rheinland Functional Safety Program Functional Safety Engineer Certification The TÜV Rheinland Functional Safety Program is a unique opportunity to provide certified evidence of competency in functional

More information

Mobrey Magnetic Level Switches

Mobrey Magnetic Level Switches Horizontal Float Switch Mobrey Magnetic Level Switches www.emersonprocess.com Horizontal Float Switch Contents Introduction Scope and Purpose of the Safety Manual...page 3 Skill Level Requirement...page

More information

Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems

Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems Overview of IEC 61508 - Design of electrical / electronic / programmable electronic safety-related systems Simon Brown The author is with the Health & Safety Executive, Magdalen House, Bootle, Merseyside,

More information

functional Safety UL Functional Safety Mark

functional Safety UL Functional Safety Mark functional Safety UL Functional Safety Mark Program UL Functional Safety Mark Program With the advent and evolution of functional safety standards in North America and Europe, UL is now offering a UL Functional

More information

Application Functional Safety IEC 61511

Application Functional Safety IEC 61511 Application Functional Safety IEC 61511 Introduction Functional safety must be an integral part of the project execution if we shall succeed to make safe application program We can t test and audit safety

More information

Functional Safety Management: As Easy As (SIL) 1, 2, 3

Functional Safety Management: As Easy As (SIL) 1, 2, 3 Functional Safety Management: As Easy As (SIL) 1, 2, 3 Abstract This paper outlines the need for planning in functional safety management. Recent events such as the Montara blowout and the Deepwater Horizon

More information

Safety controls, alarms, and interlocks as IPLs

Safety controls, alarms, and interlocks as IPLs Safety controls, alarms, and interlocks as IPLs Angela E. Summers, Ph.D., P.E. SIS-TECH Solutions 12621 Featherwood Dr. Suite 120, Houston, TX 77034 Keywords: safety controls, alarms, interlocks, SIS,

More information

PABIAC Safety-related Control Systems Workshop

PABIAC Safety-related Control Systems Workshop Health and and Safety Executive PABIAC Safety-related Control Systems Workshop KEY STANDARDS FOR ELECTRICAL & FUNCTIONAL SAFETY OF PAPERMAKING MACHINES: APPLICATION & USE Steve Frost HM Principal Electrical

More information

ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL

ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL 61508-3 ª IEC: 1997 1 Version 12.0 05/12/97 COMMISSION CEI ELECTROTECHNIQUE IEC INTERNATIONALE 61508-3 INTERNATIONAL ELECTROTECHNICAL COMMISSION Functional safety of electrical/electronic/ programmable

More information

Version: 1.0 Last Edited: 2005-10-27. Guideline

Version: 1.0 Last Edited: 2005-10-27. Guideline Process hazard and risk Comments on this report are gratefully received by Johan Hedberg at SP Swedish National Testing and Research Institute mailto:johan.hedberg@sp.se -1- Summary This report will try

More information

Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511

Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511 Valves and Solenoid Valves testet and certified byrheinhold & Mahla according to IEC 61508/61511 Manfred Dietz Manfred.dietz@rum.de +49-69-305 2663 SAMSON Dr. Thomas Karte Tkarte@samson.de +49-69-4009

More information

Application Technique. Safety Function: Magnetic Door Switch Monitoring

Application Technique. Safety Function: Magnetic Door Switch Monitoring Application Technique Safety Function: Magnetic Door Switch Monitoring Products: MC1 Magnetically-coded Door Switch, Guardmaster Dual-input Safety Relay Safety Rating: CAT. 3, PLd to EN ISO 13849-1: 2008

More information

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry.

Safety Integrated. SIMATIC Safety Matrix. The Management Tool for all Phases of the Safety Lifecycle. Brochure September 2010. Answers for industry. SIMATIC Safety Matrix The Management Tool for all Phases of the Safety Lifecycle Brochure September 2010 Safety Integrated Answers for industry. Functional safety and Safety Lifecycle Management Hazard

More information

Overview of Medical Device Design Controls in the US. By Nandini Murthy, MS, RAC

Overview of Medical Device Design Controls in the US. By Nandini Murthy, MS, RAC Overview of Medical Device Controls in the US By Nandini Murthy, MS, RAC 18 controls are a regulatory requirement for medical devices. In the US, compliance with the design controls section of 21 Code

More information

WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS)

WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS) WELLHEAD FLOWLINE PRESSURE PROTECTION USING HIGH INTEGRITY PROTECTIVE SYSTEMS (HIPS) Angela E. Summers, Ph.D., P.E., President, SIS-Tech Solutions, LP Bryan A. Zachary, Director, Product & Application

More information

Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System

Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System Take a modern approach to increase safety integrity while improving process availability. DeltaV SIS Process Safety System Whether standalone or integrated, choose a smart, modern safety system designed

More information

Impact of Safety Standards to Processes and Methodologies. Dr. Herbert Eichfeld

Impact of Safety Standards to Processes and Methodologies. Dr. Herbert Eichfeld Impact of Safety Standards to Processes and Methodologies Dr. Herbert Eichfeld Impact to Processes, Methodologies, Products Processes + New/changed role descriptions (e.g. safety manager) + Assignments

More information

What is CFSE? What is a CFSE Endorsement?

What is CFSE? What is a CFSE Endorsement? ENDORSEMENT PROGRAM The CFSE endorsement program helps current holders of CFSE and CFSP certification build /demonstrate expertise and knowledge in specific focus areas of functional safety. What is CFSE?

More information

SOFTWARE VERIFICATION RESEARCH CENTRE SCHOOL OF INFORMATION TECHNOLOGY THE UNIVERSITY OF QUEENSLAND. Queensland 4072 Australia TECHNICAL REPORT

SOFTWARE VERIFICATION RESEARCH CENTRE SCHOOL OF INFORMATION TECHNOLOGY THE UNIVERSITY OF QUEENSLAND. Queensland 4072 Australia TECHNICAL REPORT SOFTWARE VERIFICATION RESEARCH CENTRE SCHOOL OF INFORMATION TECHNOLOGY THE UNIVERSITY OF QUEENSLAND Queensland 4072 Australia TECHNICAL REPORT No. 99-30 A Survey of International Safety Standards Axel

More information

ISO 26262 Introduction

ISO 26262 Introduction ISO 26262 Introduction Prof. Christian Madritsch 2012 Table of Contents Structure of ISO 26262 Management of Functional Safety Product Development System Level Product Development Hardware Level Product

More information

R214 SPECIFIC REQUIREMENTS: INFORMATION TECHNOLOGY TESTING LABORATORY ACCREDITATION PROGRAM

R214 SPECIFIC REQUIREMENTS: INFORMATION TECHNOLOGY TESTING LABORATORY ACCREDITATION PROGRAM The American Association for Laboratory Accreditation Document Revised: R214: Specific Requirements: Information Technology Testing Laboratory Accreditation July 13, 2010 Program Page 1 of 26 R214 SPECIFIC

More information

SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen. 61508 Compliance of Actuators and Life Cycle Considerations. SAMSON AG Dr.

SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen. 61508 Compliance of Actuators and Life Cycle Considerations. SAMSON AG Dr. SIL in de praktijk (Functional Safety) 23.04.2015 - Antwerpen SAMSON AG Dr. Thomas Karte 61508 Compliance of Actuators and Life Cycle Considerations 2015-04-23 SAMSON AG Dr. Karte - 61508 Compliance of

More information

SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP

SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP SOFTWARE-IMPLEMENTED SAFETY LOGIC Angela E. Summers, Ph.D., P.E., President, SIS-TECH Solutions, LP Software-Implemented Safety Logic, Loss Prevention Symposium, American Institute of Chemical Engineers,

More information

Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager

Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager SIL Made Simple Michael A. Mitchell, Cameron Flow Control, DYNATORQUE Product Manager KEY WORDS: Safety Integrity Level (SIL) Safety Instrumented Systems (SIS) ISA 84.01, IEC 61511 Partial Stroke Test

More information

INTEGRATED MANAGEMENT SYSTEM MANUAL IMS. Based on ISO 9001:2008 and ISO 14001:2004 Standards

INTEGRATED MANAGEMENT SYSTEM MANUAL IMS. Based on ISO 9001:2008 and ISO 14001:2004 Standards INTEGRATED MANAGEMENT SYSTEM MANUAL IMS Based on ISO 9001:2008 and ISO 14001:2004 Standards Approved by Robert Melani Issue Date 30 December 2009 Issued To Management Representative Controlled Y N Copy

More information

Software Test Plan (STP) Template

Software Test Plan (STP) Template (STP) Template Items that are intended to stay in as part of your document are in bold; explanatory comments are in italic text. Plain text is used where you might insert wording about your project. This

More information

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4" to 1" NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power

% ^ ) 0.55 W Low Power Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies 1/4 to 1 NPT. 2/2 3/2 4/2 5/2 5/3 SERIES Low Power .55 W Solenoid Valves Aluminum, Brass, or Stainless Steel Bodies /" to " NPT / 3/ / 5/ 5/3 Features Molded one-piece solenoid with highly efficient solenoid cartridge and.55 W low wattage coil Standard

More information

AP1000 European 18. Human Factors Engineering Design Control Document

AP1000 European 18. Human Factors Engineering Design Control Document 18.2 Human Factors Engineering Program Management The purpose of this section is to describe the goals of the AP1000 human factors engineering program, the technical program to accomplish these goals,

More information

Controlling Risks Safety Lifecycle

Controlling Risks Safety Lifecycle Controlling Risks Safety Lifecycle Objective Introduce the concept of a safety lifecycle and the applicability and context in safety systems. Lifecycle Management A risk based management plan for a system

More information

Automation, Software and Information Technology. Test report of the type approval safety-related automation devices

Automation, Software and Information Technology. Test report of the type approval safety-related automation devices Automation, Software and Information Technology Test report of the type approval safety-related automation devices GuardPLC 1200 GuardPLC 1600 GuardPLC 1800 GuardPLC 2000 GuardPLC Distributed I/O Report-No.:

More information

HEF4011B. 1. General description. 2. Features and benefits. 3. Ordering information. 4. Functional diagram. Quad 2-input NAND gate

HEF4011B. 1. General description. 2. Features and benefits. 3. Ordering information. 4. Functional diagram. Quad 2-input NAND gate Rev. 6 10 December 2015 Product data sheet 1. General description 2. Features and benefits 3. Ordering information The is a quad 2-input NAND gate. The outputs are fully buffered for the highest noise

More information

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives

Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives User Manual Safe Torque Off Option (Series B) for PowerFlex 40P and PowerFlex 70 Enhanced Control AC Drives Catalog Number 20A-DG01 Topic Page General Description 2 What Is the DriveGuard Safe Torque Off

More information

ISO 9001:2000 Gap Analysis Checklist

ISO 9001:2000 Gap Analysis Checklist ISO 9001:2000 Gap Analysis Checklist Type: Assessor: ISO 9001 REQUIREMENTS STATUS ACTION/COMMENTS 4 Quality Management System 4.1 General Requirements Processes needed for the quality management system

More information

Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems.

Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems. Using a Failure Modes, Effects and Diagnostic Analysis (FMEDA) to Measure Diagnostic Coverage in Programmable Electronic Systems. Dr. William M. Goble exida.com, 42 Short Rd., Perkasie, PA 18944 Eindhoven

More information

Camar Aircraft Products Co. QUALITY MANUAL Revision D

Camar Aircraft Products Co. QUALITY MANUAL Revision D QUALITY MANUAL Revision D Gujll'y Manual Introduction The purpose of this manual is to describe the Quality Assurance Program implemented by Camar Aircraft Products Co. (hereafter referred to as C.A.P.C.)

More information

ISO 9001 (2000) QUALITY MANAGEMENT SYSTEM ASSESSMENT REPORT SUPPLIER/ SUBCONTRACTOR

ISO 9001 (2000) QUALITY MANAGEMENT SYSTEM ASSESSMENT REPORT SUPPLIER/ SUBCONTRACTOR Page 1 of 20 ISO 9001 (2000) QUALITY MANAGEMENT SYSTEM ASSESSMENT REPORT SUPPLIER/ SUBCONTRACTOR SUPPLIER/ SUBCONTRACTOR NAME: ADDRESS: CITY AND STATE: ZIP CODE: SUPPLIER/MANUFACTURER NO PHONE: DIVISION:

More information

Considerations When Validating Your Analyst Software Per GAMP 5

Considerations When Validating Your Analyst Software Per GAMP 5 WHITE PAPER Analyst Software Validation Service Considerations When Validating Your Analyst Software Per GAMP 5 Blair C. James, Stacy D. Nelson Introduction The purpose of this white paper is to assist

More information

HEF4021B. 1. General description. 2. Features and benefits. 3. Ordering information. 8-bit static shift register

HEF4021B. 1. General description. 2. Features and benefits. 3. Ordering information. 8-bit static shift register Rev. 10 21 March 2016 Product data sheet 1. General description 2. Features and benefits 3. Ordering information The is an (parallel-to-serial converter) with a synchronous serial data input (DS), a clock

More information

ISO 9001:2008 Audit Checklist

ISO 9001:2008 Audit Checklist g GE Power & Water ISO 9001:2008 Audit Checklist Organization Auditor Date Page 1 Std. 4.1 General s a. Are processes identified b. Sequence & interaction of processes determined? c. Criteria for operation

More information

CE Marking and Technical Standardisation

CE Marking and Technical Standardisation GAMBICA Technical Guide CE Marking and Technical Standardisation Guidelines for application to Electrical Power Drive Systems Edition 4 : 2015 CE Marking and Technical Standardisation Guidelines for application

More information

PROJECT MANAGEMENT PLAN TEMPLATE < PROJECT NAME >

PROJECT MANAGEMENT PLAN TEMPLATE < PROJECT NAME > PROJECT MANAGEMENT PLAN TEMPLATE < PROJECT NAME > Date of Issue: < date > Document Revision #: < version # > Project Manager: < name > Project Management Plan < Insert Project Name > Revision History Name

More information

TÜ V Rheinland Industrie Service

TÜ V Rheinland Industrie Service TÜ V Rheinland Industrie Service Business Area: Automation / Functional Safety Contact Minsung Lee +82-2-860-9969 mailto : minsung.lee@kor.tuv.com Sales Account Manager for Functional Safety Fax +82-2-860-9862

More information

PFSE Premier Functional Safety Engineering Safety Instrumented Systems Course Outline

PFSE Premier Functional Safety Engineering Safety Instrumented Systems Course Outline in cooperation with TÜV Industrie Service GmbH Automation, Software and Information Technology - ASI PCS is TÜV Industrie Service GmbH, ASI accepted course provider for the TÜV Functional Safety Program

More information

Testing Automated Manufacturing Processes

Testing Automated Manufacturing Processes Testing Automated Manufacturing Processes (PLC based architecture) 1 ❶ Introduction. ❷ Regulations. ❸ CSV Automated Manufacturing Systems. ❹ PLCs Validation Methodology / Approach. ❺ Testing. ❻ Controls

More information

University of Paderborn Software Engineering Group II-25. Dr. Holger Giese. University of Paderborn Software Engineering Group. External facilities

University of Paderborn Software Engineering Group II-25. Dr. Holger Giese. University of Paderborn Software Engineering Group. External facilities II.2 Life Cycle and Safety Safety Life Cycle: The necessary activities involving safety-related systems, occurring during a period of time that starts at the concept phase of a project and finishes when

More information

OPERATIONAL STANDARD

OPERATIONAL STANDARD 1 of 11 1. Introduction The International Safe Transit Association (ISTA), a non-profit association whose objective is to prevent product damage and excess packaging usage within the distribution environment.

More information

ASSESSMENT OF THE ISO 26262 STANDARD, ROAD VEHICLES FUNCTIONAL SAFETY

ASSESSMENT OF THE ISO 26262 STANDARD, ROAD VEHICLES FUNCTIONAL SAFETY ASSESSMENT OF THE ISO 26262 STANDARD, ROAD VEHICLES FUNCTIONAL SAFETY Dr. Qi Van Eikema Hommes SAE 2012 Government/Industry Meeting January 25, 2012 1 Outline ISO 26262 Overview Scope of the Assessment

More information

GuardLogix Controller Systems

GuardLogix Controller Systems Safety Reference Manual GuardLogix Controller Systems Catalog Numbers 1756-L61S, 1756-L62S, 1756-L63S, 1756-L71S, 1756-L72S, 1756-L73S, 1756-L73SXT, 1756-LSP, 1756-L7SP, 1756-L7SPXT, 1768-L43S, 1768-L45S

More information

Hydraulic/pneumatic drive Cylinder (machine actuator) Optoelectronics Light curtain (sensor) Electronics Control system Danger! Hydraulics/pneumatics Valves (actuators) Safety control SRP/CS subsystem

More information

How to design safe machine control systems a guideline to EN ISO 13849-1

How to design safe machine control systems a guideline to EN ISO 13849-1 How to design safe machine control systems a guideline to EN ISO 13849-1 SP Technical Research Institute of Sweden Johan Hedberg Andreas Söderberg Jan Tegehall SP Electronics SP REPORT 2011:81 How to design

More information

ISO 9001:2000 AUDIT CHECKLIST

ISO 9001:2000 AUDIT CHECKLIST ISO 9001:2000 AUDIT CHECKLIST No. Question Proc. Ref. Comments 4 Quality Management System 4.1 General Requirements 1 Has the organization established, documented, implemented and maintained a quality

More information

Requirements-driven Verification Methodology for Standards Compliance

Requirements-driven Verification Methodology for Standards Compliance Requirements-driven Verification Methodology for Standards Compliance Serrie-justine Chapman (TVS) serrie@testandverification.com Mike Bartley (TVS) mike@testandverification.com Darren Galpin (Infineon)

More information

ABB industrial drives. Application guide ACS800-01/U1/04/04LC/04M/U4/11/U11/14/31/U31/104/104LC Safe torque off function (+Q967)

ABB industrial drives. Application guide ACS800-01/U1/04/04LC/04M/U4/11/U11/14/31/U31/104/104LC Safe torque off function (+Q967) ABB industrial drives Application guide ACS800-01/U1/04/04LC/04M/U4/11/U11/14/31/U31/104/104LC Safe torque off function (+Q967) List of related manuals Single drive and drive modules hardware manuals ACS800-01/U1

More information