This Guidance Notes is prepared by the Occupational Safety and Health Branch Labour Department



Similar documents
HVAC Systems and Indoor Air Quality. Douglas K. Spratt, M.Sc., P.Eng.

Indoor Air Quality Issues for Hotels

GENERAL VENTILATION HSG202

Information paper 20. Prepared by: David Clark. book:

FOREWORD OF THE SERIES

Mechanical and Natural Ventilation

INDOOR AIR QUALITY INTRODUCTION WHAT ARE THE SYMPTOMS OF SICK BUILDING SYNDROME? WHEN DID POOR INDOOR AIR QUALITY BECOME A PROBLEM?

A Simple Guide to Health Risk Assessment Office Environment Series OE 5/2003

PEOSH. Indoor Air Quality Training for Asthma-Friendly Schools Part I PEOSH Indoor Air Quality Standard Overview. Eric Weren, MSIH

This guidebook is prepared by the Occupational Safety and Health Branch Labour Department

Indoor Air Quality- What You Need to Know

Why Measure Carbon Dioxide Inside Buildings? By Rich Prill, Washington State University Extension Energy Program

Radford University. Indoor Air Quality Management Plan

THE APPLICATION OF OZONE FOR AIR TREATMENT: CASE STUDY OF A BINGO HALL HVAC SYSTEM

Mould Mould A Basic Guide

Biological Contamination in the HVAC System

INVESTIGATION OF INDOOR AIR QUALITY PROBLEMS IN UNIVERSITY OFFICES WITH A QUESTIONNAIRE

IEQ-15 Air Distribution System

INDOOR AIR QUALITY ASSESSMENT

Essam E. Khalil

"An Office Building Occupant's Guide to Indoor Air Quality"

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

ASTHMA REGIONAL COUNCIL

ASTACEA4 Inspect complex/central air conditioning systems

BCA Green Mark for Restaurants

3M Personal Safety Division 3M Center, Building W-75 St. Paul, MN, USA

Charles McCammon, Ph.D., CIH

about your house How to Get the Ventilation That You Need in Your House Figure 1 Infiltration and exfiltration of air in a house

OFFICE COPYING MACHINES

Public Employees Occupational Safety and Health Program

RECOMMENDATIONS FOR ENCLOSED ICE ARENA MANAGEMENT

Federation of European Heating, Ventilation and Air-conditioning Associations

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

DEA 350: HUMAN FACTORS: THE AMBIENT ENVIRONMENT (Spring 2008) HOMEWORK I PRINT THIS OUT AND HAND IT IN BY THE DUE DATE. [5 points per answer]

Indoor air quality monitoring made easy

Educational Performance, Environmental Management, and Cleaning Effectiveness in School Environments

Planning Guidance for Food and Drink Establishments

NORSOK STANDARD H-001 Rev. 4, Nov Heating, ventilation and air-conditioning

Risk Assessment for the Prevention of Heat Stroke at Work

There are several types of air cleaning devices available, each designed to remove certain types of pollutants.

INDOOR AIR QUALITY POST-OCCUPANCY ASSESSMENT. Massachusetts Department of Revenue 100 TradeCenter, Suite 760 Woburn, MA

i n d o o r a i r q u a l i t y I AQ EN 13779:2007 European standard Camfil Farr clean air solutions

A Breath of Poor Air: Inspecting Indoor Air Quality in the Classroom Ashley Schopieray

Working safely with metalworking fluids

Manual A - Minimising air pollution during building use

Which filter class for supply air is required in a typical HVAC system?

INDOOR AIR QUALITY ASSESSMENT INCIDENT RESPONSE. Sgt. William H. Carney Memorial Academy 247 Elm Street New Bedford, Massachusetts

Taking care of your indoor environment

Indoor Air Quality. 2. Test and identify sources that contribute to poor indoor air quality.

Causes and Prevention of Symptom Complaints in Office Buildings: Distilling the Experience of Indoor Environment Quality Investigators

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

SPECIAL APPLICATIONS

Welcome to the Office and Business Module.

Breathing The Air In Your Home Is Like Living In A Closed Jar. It s Enough To Make You Sick.

Part 2: Drying Out Your Home

HEATING, VENTILATION & AIR CONDITIONING

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

EXPLOSIVE ATMOSPHERES - CLASSIFICATION OF HAZARDOUS AREAS (ZONING) AND SELECTION OF EQUIPMENT

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Operating Instructions Split System Air Conditioner

Displacement ventilation

Building and Grounds Maintenance Checklist

Indoor Environmental Quality Management Plan

CONTROLLING AN OUTBREAK - MOLD RESTORATION

Carbon monoxide. General information

EFA PSBP. Natural Ventilation Strategy. Introduction. 1.1 Relevant legislation The Building Regulations 2010

Wildfire Smoke and Your Health

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Breathing-Air Quality Testing Regulations

WORKING IN CONFINED SPACES GUIDELINES

HVAC Processes. Lecture 7

OSHA Policies Regarding Mold. Fred Malaby, CIH, CSP Industrial Hygienist NEAIHA/NECOEM Meeting, September 28, 2007

HVAC Checklist - Long Form

CHAPTER 4 VENTILATION

10.10 Indoor Air Quality

Indoor Air Quality FILL YOUR HOME WITH AIR THAT IS AS CLEAN AS IT IS COMFORTABLE. READ ONLY

THE LEADER IN PERFORMANCE INDOOR AIR QUALITY MEASUREMENTS

Control of legionella bacteria in water systems

GUIDELINES FOR GOOD INDOOR AIR QUALITY IN OFFICE PREMISES

Both health-care facility classification and area classification, as per CSA, determine the design requirements.

Performance Assessment of EAGLE 5000 in Tobacco Smoke Environment. REPORT

Hospital Application Guide. Cost-effective climate control for hospitals

Safety in Offices and other General Areas

PANDA SPRAY BOOTH FILTER INFORMATION

Safe Method: Gas Safety in Catering Establishments

USER MANUAL HRV CONSTRUCTO 2.0ES* HRV CONSTRUCTO 1.5ES* * THESE PRODUCTS EARNED THE ENERGY STAR BY MEETING STRICT ENERGY EFFICIENCY

C H A P T E R

Drives and motors. A guide to using variable-speed drives and motors in retail environments

In addition, flammable solvents and thinners are often mixed with the above substances.

Solar Homes Catch the Sun. Are you planning a new house? Discover how you can apply solar architecture principles to:

HEALTHY BUILDINGS BUT LESS ENERGY CONSUMPTION How can Air Conditioning Technology help?

Product Code: VLB ml cartridges. Substance Name EC No. CAS No. % by Wt Hazard Symbols n Butylacetate

OSHA and Welding Exhaust

Sandblasting & Silica Exposure Control Plan

WHEN COPD* SYMPTOMS GET WORSE

SUMMARY OF ASHRAE S POSITION ON CARBON DIOXIDE (CO 2 ) LEVELS IN SPACES. Stephen Petty, P.E., C.I.H.

EXTREME HEAT/HUMIDEX ADVISORY FACT SHEET

Direct Fresh Air Free Cooling of Data Centres

CEN/TC 156. pren Date: CEN/TC 156. Secretariat: BSI ICS: Descriptors:

Transcription:

This Guidance Notes is prepared by the Occupational Safety and Health Branch Labour Department This edition July 2005 This Guidance Notes is issued free of charge and can be obtained from offices of the Occupational Safety and Health Branch of the Labour Department. It can also be downloaded from website of the Labour Department at http://www.labour.gov.hk/eng/public/content2_9.htm. For enquiries about addresses and telephone numbers of the offices, please call 2559 2297. This Guidance Notes may be freely reproduced for advertising, endorsement or commercial purposes. Please acknowledge the source as Guidance Notes on Ventilation and Maintenance of Ventilation Systems, published by the Labour Department.

Guidance Notes on Ventilation and Maintenance of Ventilation Systems

Foreword Efficient ventilation and proper maintenance of ventilation systems help provide a comfortable working environment for workers and avoid various invisible health hazards in buildings and workplaces. This Guidance Notes provides a general reference on ventilation and maintenance of ventilation systems. It helps to comply with the requirements laid down in the Section for ventilation under the Occupational Safety and Health Regulation. Functions of Ventilation 1. Ventilation is a process by which air is removed from and supplied to premises simultaneously. Its functions are: (a) to supply fresh air to meet the respiratory needs of the occupants; (b) to remove airborne contaminants such as dusts, mists, gases, vapours, tobacco smoke, body odours and bacteria which may pose health hazards or nuisance to the occupants; and (c) to maintain the temperature and humidity within an acceptable range that is appropriate to the activities on the premises. Guidance Notes on Ventilation and Maintenance of Ventilation Systems Fresh Air Composition 2. 'Fresh air' normally means air from outside the building. It should be, as far as possible, free from any contamination. The composition of pure dry air is: Oxygen 20.94% by volume Carbon dioxide 0.03% by volume Nitrogen & inert gases 79.03% by volume Dirty air O 2 CO 2 N 2 H 2 O Clean air 1

Guidance Notes on Ventilation and Maintenance of Ventilation Systems Ventilation Requirement 3. Ventilation requirements for different workplaces are varied because of different indoor activities and building designs. The basic methods for control of airborne contaminants are: elimination or control of sources fresh air supply of contaminants proper air distribution air filtration (purification) removal of contaminated air No Smoking 4. Sources of contaminants can be found inside and outside the workplace. Examples of indoor sources are new furniture and fittings which may emit volatile organic compounds, human bodies which give off odours and carbon dioxide, cigarette smoking, renovation work, etc. A no-smoking policy should be implemented in workplaces. Where smoking is allowed, it should be limited to a designated and isolated area which is equipped with an independent exhaust arrangement. Outdoor contaminants, such as dusts and vehicle exhaust, can get into workplaces through fresh air intake points. Thus, the intake points should be away from sources of contaminants, and fresh air should be filtered or cleaned before being supplied to the workplace. Workplace A Workplace B 2

5. For general workplaces where there is no smoking, the fresh air should be supplied at a rate of 0.3 to 0.5 cubic metres per minute per person. Where smoking is allowed, the supply rate should be more than 0.9 cubic metres per minute per person. In workplaces where hazardous air contaminants are produced, fresh air should be supplied and polluted air be removed at rates which can control the contaminant levels to those not causing adverse health effects. Local exhaust is usually recommended. Factors needed to be taken into account in designing the ventilation requirement include: the nature of the operations or activities the toxicity and rate of generation of hazardous substances the degree of expected occupancy the design of the premises. Readers may find some recommendations of fresh air supply rate for various activities in the appendix. 6. In a workplace without a specific source of contamination, the adequacy of ventilation can be measured indirectly with a carbon dioxide index method. As the concentration of carbon dioxide increases with human activities, background levels of other contaminants also increase. Carbon dioxide level frequently exceeding 1000 ppm (although carbon dioxide at such a level is not a health concern) could be a useful indicator for review of the ventilation supply distribution and the activities going on, especially when there is a complaint. Guidance Notes on Ventilation and Maintenance of Ventilation Systems 200 400 600 800 1000 1500 2000 ppm CO2 7. Where contaminant sources can be localised, the contaminants should be removed from the location before it spreads into the occupied zone. This can be achieved through control of local air movement by creation of pressure differentials, by exhaust fans or by careful location of inlet diffusers and air return inlets. 3

Guidance Notes on Ventilation and Maintenance of Ventilation Systems 8. A combination of sufficient outdoor air supply, good air distribution, air filtering and contaminated air removal can provide a cost effective means to the control of airborne contaminants. Thermal Environment 9. Thermal comfort perceived by a person depends on environmental and personal factors. Environmental factors which can be controlled by a ventilation system include air temperature, relative humidity and air speed. 10. In air-conditioned work environments, most workers carrying out light activities may feel comfortable when air temperature is maintained between 20 o C to 24 o C in the winter and 23 o C to 26 o C in the summer. 100 80 60 40 20 0 Winter 20 o C - 24 o C Summer 23 o C - 26 o C 11. People who perform light activities in moderate temperatures can accept a wide range of relative humidity. The indoor relative humidity should be kept between 40 % to 70 % to avoid workers feeling dry eyes and throat at low humidity and prevent flourishing growth of micro-organisms at high humidity. R.H. 40% - 70% 4

12. Either draught or stagnant air is unsatisfactory. The air speed at workstations should lie between 0.1 to 0.25 metres per second. People in warmer environments can withstand higher air speed. 0.1-0.25m/s Guidance Notes on Ventilation and Maintenance of Ventilation Systems Health Effects 13. A poorly designed ventilation system or inadequate ventilation may induce irritability, impair concentration and performance, and cause fatigue and headache. 14. Poor maintenance of a ventilation system will increase power consumption and running costs, and lower its performance, leading to accumulation of air contaminants and deviation from the optimum indoor environmental conditions. 5

Guidance Notes on Ventilation and Maintenance of Ventilation Systems 15. Furthermore, a poorly designed or maintained ventilation system will enhance dispersion of air contaminants, particularly micro-organisms dislodged from the dirty filters or grills of the system. These organisms may cause health hazards to the occupants of the premises. These include: (a) Legionnaires' disease Legionnaires' disease is a type of bacterial infection caused by Legionella pneumophila. It may be contracted by inhaling droplets which contain viable legionella bacteria from the fresh water cooling towers of airconditioning systems. Most reported cases have occurred in the 40 to 70 age group. The symptoms include high fever, chills, headache, muscle pain, and cough. This disease may not always be severe and in community outbreaks, mild cases may be recognised. (b) Humidifier fever This may be caused by inhaling water droplets from contaminated humidifiers, but the definite pathogen is unknown. It is said to be related to growth of bacteria, fungi or algae in the air filters. These organisms or their associated endotoxins may trigger complaints in sensitive individuals. The symptoms, including fever, general malaise, lethargy and aches, may occur 4 to 8 hours after starting work. After a break away from work, e.g. holiday, these symptoms will generally disappear. 6

16. Poor ventilation is a significant contributor to a phenomenon, known as 'Sick Building Syndrome'. The occupants of the building may complain of sore throat, headache, sore dry eyes, dry blocked nose, lethargy, general malaise and vague upper respiratory discomfort. There are no definite causes for the syndrome. Many factors have been suggested for the sick building syndrome. Stress may result from psycho-social factors such as poor relationship with colleagues and extremes of workload. Repetitive tasks and boredom are also stressful. Inhalation of solvent vapour from correcting fluid or corresponding thinner and side-stream smoke in a poorly ventilated building may cause vague discomfort. Furthermore, the physical environmental factors including lighting, humidity, noise and office layout may also be the contributing factors to stress and health complaints. Complaints are more likely from locations where population densities are higher, and symptoms are more likely to appear in the afternoon than in the morning. In general, people feel better when they are away from work. Guidance Notes on Ventilation and Maintenance of Ventilation Systems 7

Guidance Notes on Ventilation and Maintenance of Ventilation Systems Methods of Ventilation 17. Basically, methods to achieve the ventilation requirements may come under two categories: (a) Natural ventilation, and (b) Mechanical ventilation (i) induced dilution ventilation, i.e. stale air is extracted from the premises by exhaust fans whereas outside air infiltrates into the premises through available openings (ii) forced dilution ventilation, i.e. where air is forced into the premises by air blowers commonly via ducting systems. Natural Ventilation 18. Natural ventilation is the movement of air into and out of the premises through windows, doors or any openings without any mechanical aid. The rate of air exchange in this type of ventilation is inevitably unsteady as it is governed by geographical, meteorological and many other factors which are very often beyond the occupants' control. Natural ventilation is suitable only for control of modest heat load and very low emission of less toxic contaminants. Out In 19. Adequacy of air inlets and outlets is of great importance to natural ventilation. As a reference, premises relying entirely on natural ventilation should have openings of at least 5 to 10% of the floor area to obtain adequate ventilation in the summer. 8

Mechanical Ventilation 20. Induced dilution ventilation In this type of ventilation, contaminated air is extracted from the premises by propeller fans. The air pressure inside the premises is lower than outside. Air therefore infiltrates into the premises through openings. Proper arrangements of air inlets and outlets are of vital importance to such systems. In principle, cross ventilation should be effected as far as practicable. Sufficient replacement air is essential in maintaining the efficiency of the exhaust fan and avoiding the indoor air pressure being too negative. Exhaust Air Replacement Air Guidance Notes on Ventilation and Maintenance of Ventilation Systems 21. Forced dilution ventilation In this type of ventilation, air (preferably filtered and conditioned) is blown into the premises for ventilation. It is important to site the air inlets away from sources of contaminants. The system usually consists of a fan, a cooling/heating unit and a ducting system by which air is distributed to the required positions. Duct Air outlet Fan 9

Guidance Notes on Ventilation and Maintenance of Ventilation Systems 22. Dilution ventilation together with natural ventilation is suitable for the control of heat load and moderate emission of gases and vapours of low toxicity. It is, however, not advisable to apply this type of ventilation to hazardous operations as the volume of air necessary for dilution may be too high to be practicable. Maintenance of Mechanical Ventilation Systems 23. In using mechanical systems for ventilation, it is important to minimise any health hazard to the occupants. To achieve this, the following points should be observed: Proper inspection, cleaning, testing and maintenance schedules should be drawn up and followed. Replace air filters regularly. Inspect all components of the ventilation system for cleanliness and microbial growth regularly, and clean them as required. Test the performance of the system against the design specifications and make necessary adjustment or repair. If water cooling towers are used, they should be so maintained, e.g. use of biocides as appropriate, as to prevent the growth of micro-organisms. 24. Consult a competent ventilation maintenance agency for the proper maintenance of your ventilation system. Further Information If you have any queries about this booklet, please contact the Occupational Health Service of the Labour Department. Address : 15/F Harbour Building, 38 Pier Road, Central, Hong Kong Telephone : 2852 4041 Facsimile : 2581 2049 Email : enquiry@labour.gov.hk Website : http://www.labour.gov.hk Information on the services offered by the Occupational Safety and Health Council can be obtained through hotline 2739 9000. If you have any complaints about unsafe workplaces and practices, please call the Labour Department s occupational safety and health complaint hotline at 2542 2172. 10

Appendix Fresh air supply rate for general work activities in air-conditioned workplaces. (A) For places where the number of persons present is normally constant. Types of work activity Open plan offices, schools (non-smoking) Private offices (with moderate smoking), laboratories Conference rooms or offices (with heavy smoking) Canteens, restaurants Minimum fresh air supply rate (m 3 /min/person) 0.43 0.6 1.0 0.3 (based on the seating capacity and the number of employees) Remark The normal daily working hours or hours of stay are long e.g. 8 hours On average, people may not stay in the area for a long period Guidance Notes on Ventilation and Maintenance of Ventilation Systems (B) For places where the number of persons may vary from time to time. Types of work activity Shops, supermarkets department stores Kitchen (Restaurants) Minimum fresh air supply rate (m 3 /m 2 floor area / min.) 0.18 1.2 Remark Generally no smoking Additional exhaust for working areas are required Note: Local exhaust should be provided if harmful substances are generated. 11