Fire Alarm Systems FPC-500 Conventional Fire Panel FPC-500 Conventional Fire Panel www.boschsecrity.com High-vale modern optics sitable for pblic access areas Plain text LCD Available for 2, 4 or 8 detector zones for p to 64, 128 or 256 detectors Optional se of EOL modle (EN 54-13 reqirement) Strong 3 A power spply The FPC 500 x Conventional Fire Panel is the ideal soltion for small and medim-sized objects. Thanks to the proven conventional line technology a cost-saving fire alarm system can be set p. Three types are available: FPC 500 2: 2 zones for p to 64 detectors FPC 500 4: 4 zones for p to 128 detectors FPC 500 8: 8 zones for p to 256 detectors With the integrated LCD display, the panel can be programmed and operated. The optional extensions sch as relay modles, open collector modles and key switches allow frther tailoring to ser needs. System Overview Z1 Z8 IN1, IN2 ALARM RLY, FAULT RLY AUX Up to 8 zones Up to 2 inpts (FPC 500 2 and FPC 500 4 one inpt) Two NAC otpts (500 ma each) Alarm and falt relay AUX power spply (500 ma) Emergency power spply, p to 2 x 7.2 Ah 1 LEDs 2 LCD display with zone nmbers
2 FPC-500 Conventional Fire Panel 3 Zone keys and zone stats LEDs 4 Operating panel Fnctions The fire panels of FPC-500 series have the following featres available: Alarm verification Dal-detector dependency Dal-zone dependency Intermediate alarm storage Programmable delays Switching between day and night mode (AV) Event and test history Alarm conter Operating levels The fire panels have three different operating levels. No access code is reqired for level 1. Access to level 2 and 3 reqires for-digit codes (level 2 also accessible with optional key switch). The access codes for level 2 and 3 can be changed. Different test fnctions are available. On level 1 LED, bzzer and LCD tests can be rn. On level 2 and 3 additional tests for zones, otpts and NACs can be rn. Programming Yo can program the panel easily via the keypad and LCD display. The zones can be configred independently allowing for a perfect tailoring to individal cstomer needs. The defalt programming helps getting acqainted qickly with the system and mst be modified slightly to fit many applications. Certifications and Approvals The provided options according to EN 54 2:1997/ A1:2006 inclde: Alarm conter Test condition Otpt to fire alarm devices Delays to otpts Dependencies on more than one alarm signal Type A dependency Type B dependency Region Certification Erope CE FPC-500 Germany VdS VdS-G211100 FPC-500 Erope CPD 0786-CPD-21105 FPC-500 Croatia ELTEH 145-SF/12 FPC 500 Installation/Configration Notes The fire panel mst be monted indoors in a dry, maintained place, note environmental conditions (see Technical Data). Mont the fire panel to the wall with the LCD at eye level. For optimm battery life, the fire panel shold only be operated at permissible operating temperatres (0 C to +40 C). Contry-specific standards and gidelines mst be observed when planning. Note the reqirements of yor local athorities and instittions (police, fire service). For an operation of the fire detection system according to EN 54 13, it is reqired to terminate every zone with an EOL modle. Maintenance Have maintenance and inspection work carried ot reglarly by trained, qalified personnel. Bosch Sicherheitssysteme GmbH recommends a fnctional and visal inspection at least once a year. Specifications according to EN 54-4 chapter 7.1 a) It is a power spply eqipment, sed in the fire alarm system FPC 500. It spplies the fire alarm system and the connected peripherals, and charges the two connectable batteries. b) Technical specifications 1) Recommended load 61 W 2) Inpt voltage 230 VAC +10%/-15%, 50-60 Hz Operating voltage 3) Commnication parameter none 26 VDC 29 VDC 4) Fse ratings 3.15A / 250 V 5) Batteries 2 x 7.0 7.2 Ah (max.) Lead-Acid Battery 6) Crrent consmption, max 7) Battery, max. internal I min I max, a I max, b 9) Line parameter Battery PCB power spply 800 mohm 70 ma 0.7 A Cable comes standard factory-made wiring 230 V power spply 1.5 mm 2 standard cable (max.) c) The power spply eqipment is a pre-assembled additional installation information is reqired. 1) For environmental conditions see technical specifications beneath. 2) The power spply eqipment is a pre-assembled additional monting instrctions are reqired. 3) Refer to installation gide FPC 500 for connecting instrctions.
3 FPC-500 Conventional Fire Panel d) The power spply eqipment is a pre-assembled additional commissioning instrctions are reqired. e) The power spply eqipment is a pre-assembled additional operating instrctions are reqired. f) Have maintenance and inspection work carried ot reglarly by trained, qalified personnel. Bosch Sicherheitssysteme GmbH recommends a fnctional and visal inspection at least once a year. Change the batteries reglarly. Contry-specific standards and gidelines mst be considered. Parts Inclded Qty. Components 1 Fire panel FPC-500-2/FPC-500-4/FPC-500-8 1 Labeling strips for zones 1 Labeling strips for LEDs 1 Qick Installation Gide 1 Qick Operation Gide 1 CD with Installation and User Gide, battery calclator and software flashing tool 1 EOL resistors for zones and inpts 1 Battery cable set 1 Cable ties for strain relief on power spply feeder 2 Rbber pads to fix batteries Technical Specifications Detector zones 2 4 8 Max. nmber of detectors in accordance with EN 54 2 Max. nmber of detectors per zone in accordance with EN 54 2 Max. extension modles 64 128 256 32 0 1 2 Prog. inpts 1 2 AUX otpt 1 NAC otpt 2 Electrical Inpt voltage Max. crrent consmption AC Power consmption Operating voltage I min I max, a I max, b Zones AUX NAC 230 VAC +10%/-15%, 50-60 Hz 275 ma 312 ma 375 ma 80 W 21.4 VDC to 29 VDC 70 ma 0.7 A voltage 20 VDC ±1VDC crrent max. 100 ma ±5 ma voltage 21 VDC to 29 VDC crrent 500 ma ±10% fse 0.75 A @ 60 V voltage 21 VDC to 29 VDC crrent 500 ma ±10% each fse 0.75 A @ 60 V Relay otpts contact rating 1 A @ 30 VDC OC otpts No indctive load. contact rating 20 ma @ 24 VDC recommended cable type Unshielded cable, 0.8 mm cable diameter to 1.5 mm² cable cross section Relays 2 Batteries 2 x 7.2 Ah (max.) Alarm conter Event history Test history 999 alarms 1000 events 1000 test events max. internal crrent consmption 800 mω
4 FPC-500 Conventional Fire Panel fse 5 A @ 60 V Discharge voltage threshold Commnication parameters NAC Normal Alarm Inpts A- 10 15 V B+ 0 0,5 V A- 0 1 V B+ 21 29 V 21.4 V End of line resistor 3.9 kω ±1% Zone (with resistors) 910 Ω ±5% No dal-detector dependency: 680 Ω ±5% End of line resistor 3.9 kω ±1% Zone (with EOL-Modle) 910 Ω ±5% No dal-detector dependency: 680 Ω ±5% Mechanics Dimensions ( H x W x D) 351 x 351 x 90 mm EMC emmission EN 61000-6-3 EMC immnity EN 50130-4 Vibrations EN 60068-2-6 Permissible operating temperatre Permissible storage temperatre Permitted relative hmidity Ordering Information FPC-500-2 Conventional Fire Panel Order nmber FPC-500-2 FPC-500-4 Conventional Fire Panel Order nmber FPC-500-4 FPC-500-8 Conventional Fire Panel Order nmber FPC-500-8 Accessories Relay Extension Modle Order nmber FPC-500-RLYEXT OC Extension Modle Order nmber FPC-500-OCEXT Access Key Order nmber FPC-500-KEY 0 C to +40 C -10 C to +55 C 95% non-condensing FLM-320-EOL2W Conventional EOL Modle 2-Wire for EN 54 13 compliant termination of conventional lines Order nmber FLM-320-EOL2W FLM-320-EOL4W-S Conventional EOL Modle 4-Wire for EN 54 13 compliant termination of conventional lines Order nmber FLM-320-EOL4W-S Weight 2200 g, withot batteries Hosing material Front ABS+PC Back ABS-FR Hosing color Front RAL 9003 (signal white) Back PANTONE 10 C (cool grey) Environmental conditions Protection class as per IEC 60529 Protection class as per EN 60950 IP 30 II
5 FPC-500 Conventional Fire Panel Represented by: Bosch Secrity Systems 2012 Data sbject to change withot notice 1252291339 en, V3, 21. May 2012