The University of Texas at Austin September 30, 2011

Similar documents
Industry Standards Activity Overview

SPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING

FOCONEC. Network Connectivity & Cabling Management. Overview: Features: Brighter Future

Pretium Connector Housings

SECTION COMMUNICATIONS OPTICAL FIBER OSP CABLING

Pretium EDGE HD Solutions

7.4 3M No Polish Connector

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

Reliable, Consistent, Quality

Optical Fiber Cabling Components Standard TELECOMMUNICATIONS INDUSTRY ASSOCIATION

SECTION TESTING OF FIBER OPTIC CABLES

Plug & Play Universal Systems

Patch Cords for Data Center Applications

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

White Paper: 10GbE Fiber A Practical Understanding and Functional Approach

Overcoming OM3 Performance Challenges

Maintaining Proper Polarity for Modular Pre-terminated Fiber Systems. Rudolph A. Montgelas Fiber Optic Senior Product Manager Ortronics/Legrand

Fiber Optics in Harsh Environment Applications

BICSInews. plus. Show Issue. september/october 2012 volume 33, number 5. + Migration to High-Speed Ethernet

FTE Cabling Best Practices Author: Todd Bill, RCDD/NTS

FOA Technical Bulletin. Guide To Fiber Optic Installation

Polymer Coated Fiber Cable (PCF)

Secure/Keyed LC System Solutions Overview

Fibre optic testing best practices

Overcoming Space Challenges and Reducing Costs with Small-Diameter Cable Technology. White Paper

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

SECTION DATA COMMUNICATIONS. A. Complete vertical and horizontal Communication/Data Network System as indicated.

UniCam High-Performance Connectors, Multimode and Single-Mode

Discontinued. Volition. Fiber Optic Cable. 3Innovation

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Keyed LC Connector Solution

BICSI :Building Industry Consulting Service International

Fiber Plant Design Considerations for Active DAS Mike Brownson VP DAS Technical Solutions Hutton Communications

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

Fiber Optic Cordage. Interconnect A Furukawa Company. Product Description. Why OFS Interconnect Cordage?

Structured Cabling Statement of Work

Cable Assemblies. Features and Benefits

Structured and Point to Point Network Cabling for Industrial Automation

Fiber Optic Specifications

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

ETD Fiber Optic Products

SECURE Fiber Optic Products

SECTION TELECOMMUNICATIONS ACCEPTANCE TESTING

Cable Assembly Solutions at the Speed of Light

Cabling & Test Considerations for 10 Gigabit Ethernet LAN

THE AMP NETCONNECT MT-RJ OPTICAL FIBER SYSTEM

Cable Installation Project

Field-Installable Fusion Splice-on Connector

Guidelines. LANscape Solutions Recommended Fiber Optic Test Guidelines. Table of Contents. 1. Introduction. 2. Why Test? 1. Introduction...

Planning, Designing and Installing a Pre-Terminated Copper and Optical Cabling System for the Data Center

As today s evolving data centers

Types of Optic Cable andApplications

Table of Contents. Fiber Trunking 2. Copper Trunking 5. H-Series Enclosures 6. H-Series Mods/Adapter Panels 7. RSD Enclosures 8

Open System Architecture

Arista and Leviton Technology in the Data Center

Cable Assemblies. Pretium EDGE Reverse Polarity Uniboots Photo LAN ST Compatible Ultra PC 12-Fiber Cable Assembly Photo LAN2784

Fiber-to-the-Home/FTTH

B E C A U S E Y O U R B U S I N E S S R U N S T H R O U G H U S A BERK-TEK WHITE PAPER. Cabling for. Secure Government Networks.

Cable Assemblies. Corning Cable Systems

A. Provide roughing-in, including the empty boxes, conduit, pull strings, etc. under Division 26 for the following related Sections:

The migration path from 10G to 40G and beyond for InstaPATCH 360, InstaPATCH Plus and ReadyPATCH installations

University of Nevada, Reno Campus Design & Construction Standards

The color scheme for the fibers in the cable complies with the Telcordia (formerly Bellcore) specification.

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION STRUCTURE CABLING TESTING

UT Southwestern Medical Center Information Resources Cable Installation Standard

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

Optical Fiber Data Center Field Testing. ANSI/BICSI Data Center Design and Implementation Best Practices

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

Fiber Optic Cable Assemblies. Pigtails, Jumpers (simplex and duplex), Fanouts, Pre-connectorized Multi-Fiber Cable

SECTION FIBER OPTIC CABLE AND ACCESSORIES

Data Centre & Enterprise Solutions. RapidNet

Cable Assemblies. A LANscape. Solutions Product

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION

DATA CENTER. Solutions Guide FIBER OPTICS DATA CENTER CABLES CATEGORY CABLES POWER CORDS

Best Practices for Ensuring Fiber Optic System Performance. David Zambrano

SECTION TELECOMMUNICATION ROOMS

Specifying an IT Cabling System

Testing and troubleshooting enterprise fiber-optic cabling. Presenter: Neftali Usabal Fluke Networks - LATAM

ETA International FIBER OPTICS INSTALLER CERTIFICATION SUPPLEMENTAL STUDY PACKAGE (For U.S. Military Personnel) EXAM FEE - $150.00

Data Center Cabling Design Trends

Data Center Fiber Cabling Topologies and Lengths. Paul Kolesar IEEE HSSG, September 2006

Corning Cable Systems Optical Cabling Solutions for Brocade

1U Multi-Function Fibre Enclosure

TIA Fiber Optics LAN Section (FOLS) LAN Standards, News & Trends Report

Installing and Testing

TIER-1/TIER-2 FIBER CERTIFICATION KITS

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Belden. Optical Fiber Catalog. One Enterprise. One Infrastructure. One Partner. Belden IBDN FiberExpress Systems

FIBER OPTIC CABLE PLANT DOCUMENTATION

HARTING Ethernet Cabling 8-poles Overview

TIA Releases Guidelines for Maintaining Polarity Using Array Connectors

Enterprise Networks. Core Products FOR. Local Area Networks. Data Centers AND

Indoor/Outdoor Tight-Buffered Cable Lowers Installation Costs, Reduces Time, and Increases Reliability

Master Format Division 27 - Communications

Structured Connectivity Solutions Field Testing Guidelines for Fiber-Optic Cabling Systems

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE AND COMPONENTS. January 15, 2016

Plug - Type (Male/Female) Attenuators CAA series Singlemode

A Guide to Patch Cord Management

Transcription:

SECTION 27 13 23 COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING PART 1 - GENERAL 1.1 SUMMARY A. This section shall govern the products and installation of optical fiber (single-mode and multimode). 1.2 RELATED DOCUMENTS A. The latest versions of the following codes, standards, and guidelines shall be followed. Bring to ITS immediate attention where construction documents or conditions differ from requirements in codes, standards, guidelines and specifications. B. The following codes, as required by law: 1. National Electric Code (NEC) 2. ANSI/IEEE C2 National Electrical Safety Code C. The following standards: 1. TIA-569-B Commercial Building Standard for Telecommunications Pathways and Spaces 2. ANSI/TIA-568-C.0, Generic Telecommunications Cabling for Customer Premises 3. ANSI/TIA-568-C.3, Optical Fiber Cabling Components Standard. 4. ANSI/TIA/EIA-604-10A, FOCIS 10, Fiber Optic Connector Intermatability Standard Type LC 5. TIA-492AAAD, Detail Specification for 850-μm Laser-Optimized, 50-um Core Diameter/125-μm Cladding Diameter Class la Graded-Index Multimode Optical Fibers Suitable for Manufacturing OM4 Cabled Optical Fiber 6. ANSI/TIA-758-A, Customer-Owned Outside Plant Telecommunications Infrastructure Standard 7. ANSI/TIA/EIA-455-1-B-2003, Cable Flexing for Fiber Optic Interconnecting Devices 8. ANSI/TIA/EIA-455-2-C-1998, Impact Test Measurements for Fiber Optic Devices 9. ANSI/TIA/EIA-455-4-C-2002, Fiber Optic Component Temperature Life Test 10. ANSI/TIA/EIA-455-5-C-2002, Humidity Test Procedure for Fiber Optic Components 11. TIA-455-6-B-2003, Cable Retention Test Procedure for Fiber Optic Cable Interconnecting Devices 12. ANSI/TIA/EIA-455-8-2000, Measurement of Splice or Connector Loss and Reflectance Using an OTDR 13. TIA-455-13-A-2002, Visual and Mechanical Inspection of Fiber Optic Components, Devices, and Assemblies 14. TIA-455-21-A-2002, Mating Durability for Fiber Optic Interconnecting Devices Communications Optical Fiber Backbone Cabling 27 13 23-1

15. ANSI/TIA/EIA-455-34-A-2002, Interconnection Device Insertion Loss Test 16. TIA-455-36-A-2002, Twist Test for Fiber Optic Connecting Devices 17. ANSI/TIA-455-78-B-2002, Optical Fibers Part 1-40: Measurement Methods and Test Procedures Attenuation 18. TIA-455-107-A-2004, Determination of Component Reflectance or Link/System Return Loss Using a Loss Test Set 19. ANSI/TIA/EIA-455-171-A-2001, Attenuation by Substitution Measurement for Short-Length Multimode Graded-Index and Single-Mode Optical Fiber Cable Assemblies 20. ANSI/TIA/EIA-455-185-1999, Strength of Coupling Mechanism for Fiber Optic Interconnecting Devices 21. TIA-492CAAB-2005, Detail Specification for Class IVa Dispersion-Unshifted Single-mode Optical Fibers With Low Water Peak 22. TIA 472C000-B/ICEA S-83-596-2001, Fiber Optic Premises Distribution Cable 23. TIA 472D000-B/ICEA S-87-640-1999, Fiber Optic Outside Plant Communications Cable 24. TIA 472E000/ICEA S-104-696-2003, Standard For Indoor-Outdoor Optical Cable 25. TIA 472F000/ICEA S-110-717-2003, Optical Drop Cables ANSI/TIA/EIA-455-188-2001, Low-Temperature Testing of Fiber Optic Components D. The following guidelines: 1. BICSI, Telecommunications Distribution Methods Manual (TDMM) 2. BICSI, Information Transport Systems Installation Methods Manual (ITSIMM) E. The following project specifications: 1. 27 05 53 Identification for Communications Systems 1.3 SUBMITTALS A. The following submittals are due at the Pre-Construction Phase, in accordance with submittal requirements in Section 27 00 00 Communications: 1. Product Information a) Provide manufacturer s product information cutsheet or specifications sheet with the specific product number identified or filled out. 2. Shop Drawings a) Provide scaled drawings (not less than 1/8 = 1-0 ) indicating routing of cable and type of pathway, including all pull points (to include pullboxes, communications LB, etc.). These locations are to be fully coordinated with all other trades. B. The following submittals are due Post-Construction, in accordance with the submittal requirements in Section 27 00 00 Communications: 1. Record Drawings Communications Optical Fiber Backbone Cabling 27 13 23-2

a) Provide scaled drawings (not less than 1/8 = 1-0 ) indicating actual installed routing of fiber and type/locations of all pathways and pull points. Design or shop drawings modified in the field will not be accepted. 2. Manufacturer and Maintenance Manuals for all installed equipment 1.4 QUALITY ASSURANCE A. All backbone optical fiber cable installation shall be performed in a neat and workmanlike manner. B. Equipment and materials shall be of the quality and manufacture indicated. The equipment specified is based on the acceptable manufacturers listed. Where approved equal is stated, equipment shall be equivalent in every way to that of the equipment specified and subject to the approval of The University of Texas at Austin Design and Planning Department on submittals provided. C. Trained technicians who have successfully attended an optical fiber training program, which have obtained a certificate as proof their installation knowledge shall install the backbone optical fiber cabling. Proof of optical fiber training shall be carried by the technician while performing any work. If proof is not provided on site, the technician may be excused from the site at no cost to the University. These certificates may have been issued by any of the following organizations or an equivalent organization: 1. Manufacturer of the fiber optic cable and/or the fiber optic connectors. 2. Training organizations (e.g., BICSI, A Telecommunications Association). 1.5 DEFINITIONS A. FDU Fiber distribution unit. A rack-mounted fiber housing unit. PART 2 PRODUCTS 2.1 CABLE A. The Advanced System Warranty as required by Section 27 00 00 shall govern cable manufacturer selection. B. Indoor/outdoor cable shall include a water-blocking material. C. Meet the environmental requirements for the area into which it is placed. For example, cabling placed in plenum space shall be listed as OFNP. D. Optical fibers shall be industry-standard color coded in accordance with ANSI/TIA-598-C E. Singlemode Fiber 1. Singlemode cable shall: a) Meet OS2 fiber requirements (TIA-492CAAB-2005, Detail Specification for Class IVa Dispersion-Unshifted Single-mode Optical Fibers With Low Water Peak) b) Indoor cable shall have a sheath color of yellow c) Armored cables shall be used. Communications Optical Fiber Backbone Cabling 27 13 23-3

d) Acceptable manufacturers (who shall also provide the Advanced System Warranty): 1) Corning 2) Hitachi 3) Mohawk 4) Superior Essex 5) Systimax F. Multi-mode Fiber 1. Multimode cable shall: a) Meet OM4 fiber requirements (TIA-492AAAD, Detail Specification for 850-μm Laser-Optimized, 50-um Core Diameter/125-μm Cladding Diameter Class la Graded-Index Multimode Optical Fibers Suitable for Manufacturing OM4 Cabled Optical Fiber) b) Indoor cable shall have a sheath color of aqua. c) Fibers shall be pre-terminated with MTP connectors (12-fibers per MTP connector) on each end of the fiber cable. d) Method B shall be used for installation and maintaining optical fiber polarity (see ANSI/TIA-568-C.0). e) Meet the environmental requirements for the area into which it is placed. For example, cabling placed in plenum space shall be listed as OFNP. f) Armored cables shall be used. g) Acceptable manufacturers (who shall also provide the Advanced System Warranty): 1) Corning 2) Hitachi 3) Mohawk 4) Superior Essex 5) Systimax PART 3 - EXECUTION 3.1 GENERAL A. Provide all labor, materials, tools and equipment required for the complete and proper installation of backbone optical fiber cabling. B. In order to conform to the overall project event schedule, the contractor shall survey and coordinate the backbone optical fiber cabling installation with other applicable trades. C. All backbone optical fiber cabling shall be installed point-to-point (e.g., equipment room to telecommunications room) without splice points other than a fusion splice of the single-mode pigtails Communications Optical Fiber Backbone Cabling 27 13 23-4

D. Each cable type shall be terminated in its own 4U high fiber distribution unit (FDU). A maximum of 144 fibers per 4U FDU shall be permissible. For example, up to 144 50/125µm (OM4) fibers shall terminate in its own FDU per telecommunications room. E. Single-mode (OS2) cabling shall be used. 1. Fusion splice pigtails (LC/APC) shall be used for terminating the cable and inserted in LC/APC single-mode adapters. 2. Polarity shall be maintained using consecutive-fiber positioning (see ANSI/TIA-568-C.0) F. Multi-mode (OM4) cabling shall be used. 1. Multi-mode (OM4) cable shall be ordered pre-terminated with 12-fiber MTP connectors on each end. The MTP connectors shall plug into transitions (cassettes) having LC/UPC connectors on the front of the FDU. 2. Polarity shall be maintained using Method B for array connectors (see ANSI/TIA-568-C.0). G. Follow all manufacturers instructions. H. Coordinate with all other trades prior to installation. END OF SECTION Communications Optical Fiber Backbone Cabling 27 13 23-5