Electrical safety requirements in DC distribution systems



Similar documents
Insulation resistance

Electrical safety. in control and auxiliary circuits. Safety objectives

12 SOLAR PHOTOVOLTAIC POWER SUPPLY SYSTEMS by John Ware. PV modules are current-limiting

PROTECTION AGAINST ELECTRIC SHOCK by John Ware

Criteria for Selecting a Residual-Current Device

AN Surging Ideas TVS Diode Application Note PROTECTION PRODUCTS. TRANSIENT IMMUNITY STANDARDS: IEC x

Residual Current Circuit Breaker

AN-3 SEVEN KEY CONSIDERATIONS BEFORE YOU START YOUR SLIC OR FXS PHONE LINE INTERFACE DESIGN

Unified requirements for systems with voltages above 1 kv up to 15 kv

AC Coupling of Inverters for Grid Tied PV Systems

ISOMETER IRDH275. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Vorläufiges Datenblatt

Application of Four-Pole Circuit Breakers within Data Centers

Application Note: Modbus/RS485 Wiring for Conext Core XC Series Inverters

LUXEON LEDs. Circuit Design and Layout Practices to Minimize Electrical Stress. Introduction. Scope LED PORTFOLIO

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Contactless Power Transfer : Inductive charging of EV

Video Camera Installation Guide

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

EMI in Electric Vehicles

ISL Insulation monitoring devices Continuous monitoring of IT systems from photovoltaic to industrial applications.

6.0 Electrical Installations

User s Manual Before using the inverter, you need to read and save the safety instructions.

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

ETAP 11 The Future of Power Systems Engineering & Operation - Today

Section B: Electricity

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

SELECTION OF FINAL CIRCUIT PROTECTION

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.

White Paper: Electrical Ground Rules

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

ESP 120 M1, ESP 208 M1, ESP 240 M1, ESP 415 M1, ESP 277 M1, ESP 480 M1 and M1R variants. Installation instructions ESP M1/M1R mains protectors

Roy Allen, Technical Training, 17FEB2015 ABB Solar Days Residential Products, Design & Application Rapid Shutdown. ABB Feb 27, 2014 Slide 1

Grounding Demystified

Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies

ABB Inc. April 19, 2011 Slide 1

Listed are common requirements that apply to existing solar installations when altered, added to or reconfigured.

egate INVOLAR Grid-Connected Photovoltaic Power Interface Model Number PIU4KA-230-UK User Operating Manual (Version_eGate(UK)G83_PIU4KA_1.

How To Understand The Electrical Power Supply Of A Power Supply System

Are you aware. Outline

Inverter / Charger Installation General Operations and AC and DC Connections

Application Information Improving Efficiency in Smart Grid Applications With Fully Integrated Current Sensing ICs

CHECKING AND TESTING ELECTRICAL INSTALLING WORK

Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance

Test Before Touch Easier Said Than Done. Ken Crawford, DuPont Kent Haggerty, Dupont

EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC)

1 Introduction. 2 Hazards From Electricity

By Mark Coles. This article looks at the temporary use of portable generators in floating, earthed and reference-earthing scenarios.

Electrical Grounding. Appendix C

Electrical Safety Tester Verification

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Re-defining the utility-scale inverter

Installation instructions for mains wire-in protectors ESP D1, D1R, D1/LCD and D1R/LCD variants

Fundamentals of Power

AN-2 TEN KEY CONSIDERATIONS BEFORE YOU START YOUR DAA OR FXO PHONE LINE INTERFACE DESIGN

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

HAZARDS, INCLUDING SHOCK, ARC FLASH AND FIRE

Electrical Fundamentals Module 3: Parallel Circuits

Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power

The reliability of the grid

Stroom voor elke toepassing

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

CONTINUOUS MONITORING AND AVOIDANCE OF RESIDUAL CURRENTS IN DATA CENTRES WITH RCM White paper Revision 2

Interfacing electrification and system reliability. Earthing of AC and DC railways 4,10,13

User Manual DONGGUAN SHENGYANG INDUSTRIAL CO., LTD. SY WMVC Smart Grid Tie Microinverter. Dongguan Shengyang Industrial Co., Ltd.

How to design SMPS to Pass Common Mode Lightning Surge Test

Line Reactors and AC Drives

Handheld portable appliance testers

INSTALLATION MANUAL. SAILOR 5080 AC Power Supply

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

The following table shows approximate percentage wise the

Satcon Solstice 100 kw System Solution

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

A Practical Guide to Free Energy Devices

The power of nature, the control of technology From ABB's experience, OVR PV: surge protection in photovoltaic plants

R.C.C.B. s two-pole LEXIC

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Experiment NO.3 Series and parallel connection

How the National Grid System Operates. Chris Gorman Lead Account Executive Syracuse

Manual Ranging MultiMeter

User Guide. Model Insulation Tester / Megohmmeter

A Practical Guide to Dielectric Testing

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER

White Paper. Fiber Optics in Solar Energy Applications. By Alek Indra. Introduction. Solar Power Generation

Solar Kit. Complete solution to optimize your photovoltaic system

ELECTRICAL DOCUMENTATION ACCORDING TO STANDARDS

Guide to the Selection & Use of Residual Current Devices

RELAYS Solar Energy Systems

Guidance for upgrading to GB (IEC : 2005, MOD)

Connecting a microgeneration system to a domestic or similar electrical installation

Transcription:

Electrical safety requirements in DC distribution systems PAUL J.L.AN TICHELEN, DOMINIQUE WEYEN ITO Boeretang 200, 2400 Mol BELGIUM Abstract: This paper focuses on the safety requirements for the DC bus distribution systems up to 1500 DC. High DC bus voltages are attractive for keeping the current and copper weight low. However, if the DC bus voltage exceeds 75 DC, additional safety measures are required. Regulations require double protection measures. The first protection is mostly provided by proper electrical insulation. A second active protection system is also installed, this detects insulation failures and switches off the power supply. Often the residual current detector (RCD) is used which detects leakage current in earthed systems but is difficult to build for DC systems. Another active technique is to install a floating or unearthed system with an insulation resistance monitoring device (IMD). In this paper the advantages and disadvantages of both systems are compared. A simple IMD technique is presented together with fault simulations and EMC immunity test results. This paper also contains a brief review of additional safety requirements for DC distribution systems. Keywords: safety, instrumentation, DC system. 1 Introduction This paper focuses on the safety requirements for the DC bus distribution systems. They are used in many new electrical systems like photovoltaic (P) installations[13], fuel cells, batteries, uninterruptible power supply (UPS) systems and electric vehicles(e)[8]. High DC bus voltages are highly effective at keeping the current low and producing light weight electronics. However, if the DC bus voltage exceeds 75 DC [6] additional safety measures are required[4, 6] in order to avoid the electrocution of users and maintenance personnel. Regulations require double protection measures[11] against electrocution. The first protection is mostly provided by proper electrical insulation. The second protection measure is mostly provided by an active protection system that detects failures and automatic disconnects the supply voltage. A double electrical insulation is also allowed under certain conditions[4, 11] but unpractical and provides no fault information. In this paper two active protection systems [14] will be compared for DC bus distribution systems. AC(50/60 Hz) systems are used for long periods. In these AC systems, the most common active protection system is the residual current detector (RCD) that detects leakage current in earthed systems. Another active protection system is an insulation resistance monitoring device (IMD) that measures insulation resistance between conductor and earth in a floating system. For installations in buildings both techniques are well defined in safety standards [9-12]. The building electrical safety standards are derived from [11] and are in Europe translated into national standards. According to these standards, several earthing systems can be installed for DC and AC distribution systems e.g. IT, TT or, TN wiring systems. For the residential distribution grid a TT system (fig. 2) is mostly used with an earthed neutral (N) conductor at the distribution transformer or power source. In this system, an active safety component with RCD can be installed. For application in a residential distribution grid the RCD protection is useful because it is able to locate and isolate the fault and the technology is easy. It is also possible to install an IT system (fig. 1) with lines L1, L2, L3 or N floating (not connected to earth). In these systems an active safety procedure with IMD can be installed. These IT systems are seldom used in AC distribution systems and more in DC distribution systems. Sometimes IT systems for AC distribution are used in hospitals or critical production environments [7]. The main scope of this paper is to present and compare IMD and RCD active protection systems for DC voltage distribution systems that exceed 75

DC and below 1500 DC. Therefore a practical case of a P system will be used. A simple IMD technique[15] for DC systems is also presented together with fault simulations and EMC immunity test results. Besides insulation faults the DC voltage distribution system needs to be protected against short circuit, over voltages and in some cases to lightning strikes, more information can be found in standards and literature [8,11]. Fig.1 Electrical grid with IT earthing Fig.2 Electrical grid with TT earthing A similar system can be installed in DC bus systems, e.g. a photovoltaic (P) grid coupled system with DC bus and inverter with transformer (fig. 3). The transformer provides galvanic insulation from the distribution grid. This insulation transformer is mostly integrated in the inverter. In this case an insulation fault on the DC bus will not propagate to the AC distribution grid. By consequence the DC bus needs to be protected and this can be done with a RCD. Therefore the star point of the P array needs to be earthed. A DC RCD can be installed and will detect any single insulation failure caused after the RCD. In this system a failure is only detected after the RCD and thus not in one side, e.g. the DC source or P panel itself which is a serious disadvantage for P applications. The RCD technology for DC systems is also quite complicated because a DC current measurement transformer has to be used. RCDs could be installed in multiple locations in the DC bus and they would be capable of locating faults but this features is not very useful for P applications. An insulation failure caused by human contact will result in human electrocution due to the current flow and a first contact failure is therefore unsafe. A symmetric insulation fault is one with an identical insulation failure on the positive and negative voltage terminal. This kind of fault is not detected with an RCD because both currents are identical(+ and -). Fig.3 P system with RCD protection and inverter with transformer P ARRAY 1 P ARRAY 2 INERTER INSULATION TRANSFORMER AC GRID 2 A P DC bus system with RCD In a typical AC residential distribution system the star point of the power source or distribution transformer and the protective enclosure is earthed (fig. 2). This protection system is called a TT electrical protection system(fig.2). A single insulation fault between a power line and the protective enclosure will cause a leakage current. This leakage current can be detected by a residual current detector (RCD) which will switch off the power in case of an insulation fault. Leakage current limits of 300 ma and 30 ma are typical. For application in a residential AC distribution grid the RCD protection is useful because it is able to locate and isolate the fault to one user or house. fuse RCD 3 A P DC bus system with IMD The operation of insulation safety devices is already well-known [2, 3]. They are regularly used in AC industrial electrical distribution systems and are called IT protection systems (fig. 1). The power sources or distribution transformer is unearthed or DC AC

floating and the protective enclosure is earthed. The insulation monitoring device (IMD) measures the insulation resistance between the power lines and protective enclosure and switches off power in case of failure. Insulation resistance limits are typically between 30 and 100 kohm. A similar system can be installed in a DC voltage distribution system, e.g. a photovoltaic (P) grid coupled system (fig. 4). These systems must be galvanic insulated from the distribution grid with an insulation transformer. In this case the distribution grid can be protected with an IMD. The insulation transformer will prevent the propagation of failures from the DC bus or P panels to the AC distribution grid. The complete P array and DC bus must be unearthed or connected to earth with a high impedance of at least 50 kohm. The IMD will detect an insulation failure anywhere in the system, thus before and after the location where the IMD is installed. This is a very practical feature and makes an IMD more practical then RCD for P systems. In a DC system the IMD can be constructed easily (see 4). Because the system is floating or unearthed, human contact insulation failure with one of the terminals will not cause high levels of current flow and electrocution will not be experienced. Fig.4: P system with IMD protection resistance values of R1, R2 and R1//R2 are calculated[15] on the basis of the voltage measurements (ins-meas1, ins-meas2 and meas) by the microcontroller. This microcontroller also allows the integration of other monitoring functions [8], undervoltage, monitoring, etc... Fig.5: Schematic drawing of DCSafe insulation monitoring function (patent pending). A P test was set up and used for the simulation of insulation faults. These panels have an output voltage of +/- 113 olt. Insulation faults were created on the +, the and both terminals of the solar panel and at intermediate voltage (0 ) of the solar panel. The test results are shown in table 1. P ARRAY 1 P ARRAY 2 fuse IMD INERTER DC AC INSULATION TRANSFORMER AC GRID From these experiments (table 1) we can conclude that the monitoring also works when an insulation fault occurs on an intermediate voltage of the solar panel and with a symmetrical fault on the + and terminal of the solar panel. The calculated value of the parallel resistance (R1//R2) gives, in this case, the alarm level for an insulation fault. 4 The DCSafe IMD system Fig. 5 shows a schematic drawing of the DCSafe insulation monitoring function[15]. This system is very compact and can be easily integrated with other devices(e.g. inverter). The microcontroller controls switch Q1 to the on or off state. Depending on the state, two voltages (m1 and m2) are measured. An additional voltage measurement is done for measuring the DC voltage produced by the source. Different insulation faults (Ri) are simulated. The unknown insulation 5 Advanced and basic IMD systems There are many IMD devices available on the market [8]. The basic IMD system measures an insulation fault in the complete system independent of its location, this is particular interesting in small grid applications (e.g. P). More advanced IMD systems can also locate and isolate separate sub circuit faults [8]. They combine the IMD with an current measurement technique to locate the fault. Such complicated systems are mainly used in large industrial or medical electrical distribution systems.

6 Symmetric insulation fault detection with RCD and IMD A symmetric insulation fault is one with an identical insulation failure on the positive and negative voltage terminal (e.g. fault 4 in table 1). In DC systems the like hood of this type of failure happening is not uncommon. A symmetric fault can also occur if there is a fault in the DC power source itself, at an intermediate voltage level in a stacked DC source (e.g. fault 5 in table 1). A symmetric fault is also introduced when the DC bus is loaded with a motor inverter and when an insulation failure occurs after the inverter (e.g. in an electric vehicle [8]). The IMD is able to detect all this faults(table I). An RCD can not detect a symmetric insulation fault because the induced leakage in the positive and negative conductor is identical. 7 Automatic disconnection of supply actions If a first insulation fault occurs in an IT system and the fault current is limited in such a way that the dangerous touch voltage is less than the conventional voltage limit their must be no disconnection of this first fault. An alarm of the first fault can be given via LED and alarm contacts. It is important that this fault will be eliminated as soon as possible. If a second fault occurs before the elimination of the first fault, the system must be disconnected. 8 Comparison of IMD versus RCD The discussed properties of the RCD and IMD techniques are compared and summarized in table 2. Table 2: Comparison of RCD versus IMD DC bus safety system IMD IMD RCD ref. Property Basic Advanced 1 failure detection in power source yes yes no 2 failure detection in stacked DC sources yes yes no 3 sensitive multilevel yes yes no 4 fault location in complex distribution systems no yes yes 5 symmetric fault (e.g. after motor inverter) yes yes no 6 cost low high medium 7 1st human contact cause electrocution(unsafe) no no yes 9 EMC immunity tests on DCsafe IMD Sources of voltage surges are numerous, but the most common and most well-known source is a lightning strike. Lightning transients may result from a direct strike or indirect from induced voltages and currents. IEC 61000-4-5 addresses the most severe transient conditions on both power and data lines. Electrical fast transients occur as a result of arcing contacts in switches and relays. IEC 61000-4-4 specifies the EFT threat in both power and data lines. The DCsafe insulation monitoring device was tested to the immunity of surges and transients. Therefore Electrical Fast Transients of 2 k and Surges of 1 k (Line to line) and 2 k (Line to Earth) were generated by the Transient 1000 generator. The insulation monitoring device continues to operate as intended (performance criterium B). Table 1: Test results of different simulated insulation faults (Ri) Ri KΩ fault ref. Location Source m1 m2 R1 R2 R1 // R2 30 1 + terminal 111.6 0.996 0.75 32 4359 32 30 2 - terminal 113.5 0.222 0.17 2671 29 29 30 3 + terminal 110.4 0.313 0.28 38 12 8.9 10 - terminal 30 4 + terminal 113.9 0.823 0.699 20 55 14 30 - terminal 30 5 Intermediate (0) 113.9 0.618 0.472 61 59 30

10 Conclusions Finally it can be concluded that the IMD offers more features(table 1) then RCD for energy systems with DC bus voltages exceeding 75 DC. The basic IMD is the ideal choice for small power grid applications with one central protection device. The DCSafe basic IMD is particularly interesting because it is compact and can integrate other monitoring functions in the microcontroller or can be embedded in the application(e.g. inverter). For larger DC bus systems where fault location is important advanced IMD techniques can be used. References: [1] IEC 60479-1 (1994-09): Effects of currents on human beings and livestock. [2] IEC 61557-1 (1997-02): Electrical safety in low voltage distribution systems up to 1000 a.c. and 1500 d.c.- Equipment for testing, measuring or monitoring of protective measures - Part 1: General requirements. [3] IEC 61557-8 (1997-02): Electrical safety in low voltage distribution systems up to 1000 a.c. and 1500 d.c.- Equipment for testing, measuring or monitoring of protective measures - Part 1: Insulation monitoring devices for IT systems. [4] IEC 60664-1 (2000-04): Insulation coordination for equipment within low-voltage systems - Part 1: Principles, requirements and tests. [5] IEC 60255-5 (2000-12): Electrical Relays - Part 5: Insulation coordination for measuring relays and protection equipment - Requirements and tests. [6] Directive 73/23/EEC - Low voltage equipment. [7] Protective Measures with insulation monitoring, Wolfgang Hofheinz, 2nd edition, DE verlag Berlin, ISBN 3-8007-2516-9 [8] P. an Tichelen, Dominique Weyen, Gilbert Decat, 'DC bus integration and electrical safety in electric vehicles', ES 18 conference proceedings, October 2001 Berlin. [9] IEC 60364-7-712(2002-05): Electrical installations of buildings- Part 7-712: requirements for special installations or locations- Solar photovoltaic (P) power supply systems [10] IEC 61140 (2001-10): Protection against electric shock - Common aspects for installation and equipment [11] IEC 60364-1 (2001-08): Electrical installations of buildings- Part 1: Fundamental principles, assessment of general characteristics, definitions. [12] IEC 61200-413(1996-03): Electrical installation guide - Part 413: Protection against indirect contact - Automatic disconnection of supply. [13] P. an Tichelen, D. Weyen, G. Meynen, 'How to organise electrical insulation safety in grid coupled systems'', will be published in proceedings of 20 th European Photovoltaic Solar Energy Conference, 2005. [14] Paul J.L.an Tichelen, Dominique Weyen, Guy K.J. Meynen, ' A comparison of residual current devices with insulation resistance monitoring devices when considering safety in DC systems', Proceedings of the 4th IASTED conference on Power and Energy systems, June 2004 Greece. [15] European Patent EP 1265076, ' Safety device for monitoring a DC bus insulation'.