Voltage Regulator SPAU 341 C. Product Guide



Similar documents
Capacitor Protection Relay SPAJ 160 C. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide

Arc Protection Relay REA 10_. Product Guide

REA 10_ 1MRS MBG

Current and voltage measuring relays

Waveguide Access Point WGA631. Product Guide

Quick Connect. quick - simple - efficient.

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

Combined overcurrent & earth-fault relay. Type SPAJ 140 C

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Three-phase monitoring relay CM-PFE

Analog signal converters CC-E I/I Current / current isolators

Trip circuit supervision relay. Type RXTCS

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

RM4TG20 three-phase network control relay RM4-T - range V

MasterINTERFACE 39 Series - Relay interface modules

Safety technique. Emergency stop module BO 5988 safemaster

REA 101 Arc protection relay. Operator s manual

T Substation Maintenance and Commissioning Test Equipment

Circulating Current Relay. Type IRXm

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

MasterINTERFACE 39 Series - Relay interface modules

48 SERIES Relay interface modules 10 A

Low Voltage Products. Switches Automatic Transfer Switches

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

38 Series - Relay interface modules A

80 Series - Modular timers 16 A. Features

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

38 Series - Relay interface modules A

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

MHCO MHCO-RI. Transmitter The Transmitter, connected to the system, acquires the inputs and througth a fiber optic transmits it to the receiver.

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Pilot-wire differential relay for lines with two or more terminals

FREJA 300 Relay Testing System

Digital Pressure Measuring Instrument MDR480

Control Devices Catalogue. Control Devices. Preferred and Standard Products

Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start * see variants. Applications.

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Energy Management Energy Meter Type EM23 DIN

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Power Meter Series 700

Bulletin 150 SMC Flex Smart Motor Controller Specifications

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

HERZ-Thermal Actuators

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

80 Series - Modular timers 16 A. Features

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Installation manual. Generator Paralleling Controller GPC multi-line C

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

49 Series - Relay interface modules A. Features

E-STOP relays, safety gate monitors

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Preset Counter signo 721

SPAM 150 C. Motor protection relay SPAM 150 C. User s manual and Technical description. U aux V NC. θ>θ t. θ [ % ] 9 EXT.TRIP I >> / I.

Arc Protection Relay REA 101. Operator s Manual

OZW30. Central Unit SYNERGYR

mecotron Safety relay ESTOP-2 For emergency stop monitoring

PNOZsigma - Base units

pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2, /0.65/0.

Overcurrent and earth-fault relay

A project to optimise quality and energy efficiency must include metering

15 Series - Electronic step relay and dimmer. Features SERIE

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

ABB i-bus KNX SA/S Switch Actuators Product Manual

Thermistor motor protection

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

H/L = Power supply. FN = Nominal Frequency. RN = Rated value of output burden. UN = Nominal input voltage. IN = Nominal input current.

Everything you need for protection scheme testing

Safety Relays ESM/ESM-F

Vario-Series Accessories

Digital input modules

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Rack mounted telephone- and leased line modem for industrial applications

Technical catalogue. Modular DIN rail components Installation contactors

MCR-VDC-UI-B-DC. Voltage Transducer for DC Voltages. INTERFACE Data Sheet _en_01. 1 Description

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Modular I/O System Analog and Digital Interface Modules

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

Transcription:

Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations 1 A and 5 A tappings on the energizing phase current inputs Selectable rated energizing input voltage of phase-to-phase voltage measurement: 100 V, 110 V, 120 V Three-phase overcurrent and undervoltage blocking Line-drop compensation Maximum three transformers can be operated in parallel when the minimizing circulating current principle is used. Master/slave and negative reactance principles can be used with an unlimited number of transformers in parallel. Tap changer position measurement Local man-machine communication via push-buttons and digital display on the front panels of the regulator modules Serial interface for connecting the regulator to higher-level data acquisition systems, local/remote control systems or other host systems High immunity to electrical and electromagnetic interference Continuous self-supervision of regulator hardware and software for enhanced system reliability Auto-diagnostic fault indication to facilitate fault location and repair Powerful software support for parameterizing the regulator, for reading measured values, events, etc., and for storing set values CE marking according to the EC directive for EMC 3

Application The voltage regulator is intended to be used in distribution substations for automatic and manual voltage regulation for power transformers with on-load tapchangers. The regulator can be used in association with a single power transformer by measuring voltage alone. When two or three power transformers are run in parallel and more sophisticated regulating principles are used the voltage regulators need to measure both voltage and current. Further, a means of communication between the regulators must be provided. When two transformers are running in parallel three operating principles can be selected, i.e. the master/slave principle, the negative reactance principle or the minimizing circulating current principle. Design The fully equipped voltage regulator includes four modules: a connection module, an I/O module, an automatic voltage regulating module and a manual voltage regulating module. The regulator modules are multi-functional microprocessor-based plug-in units. The voltage regulator is available in two versions: with or without the manual voltage regulating module. The regulator modules are provided with local man-machine communication interfaces. Automatic voltage regulator module SPCU 1D50 The automatic voltage regulator module is used for automatic control of the tap changers of power transformers. The module can control parallel transformers in three different ways, i.e. using the master/slave, the negative reactance and the minimizing circulating current principle. When the master/slave principle is used the number of parallel power transformers is unlimited. One regulator acts as the master and calculates the voltage drop on the basis of its own measurements, assuming that the power transformers are equally loaded. In this application a direct wiring is required between the voltage regulators. When the negative reactance principle is used the module compares the actual phase shift with the set load phase shift and by measuring the current the compensating value that affects the regulator control voltage, can be calculated. The negative reactance principle can be used for controlling power transformers with different ratings and step voltage values. Since, in this principle, no connection is required between the regulators, even transformers located in different substations can be operated in parallel. When the minimizing current principle is used the number of parallel power transformers maximum is three. Each voltage regulator module transmits its own current and phase shift values to the other modules operating in parallel. The modules calculate the total value of the busbar current and the phase shift and compare this value with their own values. Manual voltage regulating module SPCU 1D56 When the voltage regulator is set for manual operation the tap changer of the power transformer can be controlled via the push-buttons of the manual voltage regulating module. If a raise or lower command cannot be executed because of an overcurrent situation or external blocking, the operator will be notified by means of the LED indicators marked I> or BLOCK. The display of the module shows setting values, tap-changer positions and measured values. Data communication The relay is provided with a serial interface on the rear panel. By means of a bus connection module type SPA-ZC 17 or SPA-ZC 21 the relay can be connected to the fibre-optic SPA bus. The bus connection module type SPA-ZC 21 is powered from the host relay, whereas the bus connection module SPA- ZC 17 is provided with a built-in power unit, which can be fed from an external secured power source. The relay communicates with higher-level data acquisition and control systems over the SPA bus. When several voltage regulators are to be operated in parallel, bus connection modules type SPA-ZC 100 are used. Self-supervision The regulator incorporates a sophisticated self-supervision system with auto-diagnosis, which increases the availability of the equipment and the reliability of the system. The self-supervision system continuously monitors the hardware and the software of the device. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. 4

When a permanent internal relay fault is detected, the IRF indicator on the relay front panel is lit. At the same time the output relay of the self-supervision system operates and a fault message is transmitted to the higherlevel system over the serial bus. Further, in most fault situations, a fault code is shown in the display of the protection relay module. The fault code indicates the type of the fault that has been detected. Auxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPGU 240A1 for the supply voltage range 80 265 V ac/dc and type SPGU 48B2 for the supply voltage range 18 80 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module. Technical data Table 1: Energizing inputs, voltage inputs Rated voltage U n, selectable 100 V (110 V, 120 V) Terminal numbers X0/13-14 Continuous voltage withstand 2 U n Rated burden of voltage input at U n <0.5 VA Rated frequency f n, according to order 50 Hz or 60 Hz Table 2: Energizing inputs, current measuring inputs Rated current I n 1 A 5 A Terminal numbers X0/1-3, 4-6, 7-9 X0/1-2, 4-5, 7-8 Thermal current continuously 4 A 20 A withstand for 10 s 25 A 100 A for 1 s 100 A 500 A Dynamic withstand half-wave value 250 A 1250 A Input impedance <100 mω <20 mω Table 3: Output contact ratings Type of contact Tap-changer control Signalling Terminal numbers X2/1-2, 3-4 X2/5-6, 7-8, 9-10-11, 14-15-16 Nominal voltage 250 V ac/dc Thermal withstand Carry continuously 5 A 5 A capability Make and carry for 0.5 s 30 A 10 A Make and carry for 3 s 15 A 8 A Breaking capacity for dc, 220 V dc 1 A 0.15 A when the control circuit 110 V dc 3 A 0.25 A time constant L/R 40 ms, at the control voltage levels 48 V dc 5 A 1 A Table 4: External control inputs Terminal numbers X1/1-2, 3-4, 5-6, 7-8, 9-10, 11-12, 13-14 External control voltage 18 250 V dc or 80 250 V ac Typical control current of input circuit 2 20 ma Table 5: External ma input Terminal numbers External control current Input resistance X1/15-16 0 20 ma 300 Ω 5

Table 6: Auxiliary supply modules Power module SPGU 240A1 Power module SPGU 48B2 rated voltages U n operative voltage range rated voltages U n operative voltage range Power consumption, quiescent/operation conditions 110/120/230/240 V ac 110/125/220 V dc 80 265 V ac/dc 24/48/60 V dc 18 80 V dc ~10 W/~15W Table 7: Automatic voltage regulating module SPCU 1D50 Operate time setting range Operate time accuracy at definite time characteristic Operate time accuracy at inverse time characteristic Minimum operate time at inverse time characteristic 0.0 300 s ±1% of set value or ±250 ms Table 8: Manual voltage regulating module SPCN 1D56 Accuracy, ma input signal Output pulse duration, selectable Table 9: Data communication Transmission mode Data code Data transfer rate, selectable ±250 ms and the inaccuracy appearing when the measured voltage varies ±0.3% 1 s ±1% of FSR 0.50 10 s in 0.1 s steps Fibre-optic serial bus ASCII 4800 or 9600 Bd Optical bus connection module for plastic core cables SPA-ZC 21BB for glass fibre cables SPA-ZC 21MM Optical bus connection module powered from the for plastic core cables SPA-ZC 17BB internal power source for glass fibre cables SPA-ZC 17MM Optical bus connection module for parallel operation for plastic core cables SPA-ZC 100BB for glass fibre cables SPA-ZC 100MM 6

Table 10: Tests and standards Test voltages Insulation resistance voltage (IEC 60255-5) >100 MΩ, 500 V dc Interference tests Impulse test voltage (IEC 60255-5) Dielectric test voltage (IEC 60255-5) High-frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode High-frequency (1 MHz) disturbance test (IEC 60255-22-1), differential mode 5 kv, 1.2/50 µs, 0.5 J 2 kv, 50 Hz, 1 min 2.5 kv 1.0 kv Fast transients (IEC 60255-22-4, class III and 4 kv, 5/50 ns IEC 61000-4-4, level 4), power supply inputs Fast transients (IEC 60255-22-4, class III and 2 kv, 5/50 ns IEC 61000-4-4, level 4), other inputs Electrostatic discharge 8 kv (IEC 60255-22-2 and IEC 61000-4-2, class III), air discharge Electrostatic discharge 6 kv (IEC 60255-22-2 and IEC 61000-4-2, class III), contact discharge Environmental conditions Service temperature range -10 +55 C Transport and storage temperature range -40 +70 C (IEC 60068-2-8) Temperature influence voltage measurement <0.025%/ C Temperature influence tap-changer position <0.025%/ C measurement Temperature influence current measurements <0.1%/ C Damp heat test (IEC 60068-2-30) 93 95%, +55 C, 6 cycles Degree of protection by enclosure of flush IP 54 mounting regulator case according to IEC 60529 Weight of fully equipped regulator ~5.5 kg 7

Block diagram Fig. 1 Block diagram and sample connection diagram BSPAU341 8

Mounting and dimensions Flush mounting 226 30 293 259 229 34 214 ±1 162 136 139 ±1 Panel cut-out dim300 Fig. 2 Flush-mounting relay case (dimensions in mm) Semi-flush mounting a b Raising frame SPA-ZX 301 SPA-ZX 302 SPA-ZX 303 a 219 179 139 b 74 114 154 SFM300_1 Fig. 3 Semi-flush mounting relay case (dimensions in mm) Mounting in 19 inch cabinets and frames An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 304 accommodates two size 300 relays and type SPA-ZX 305 one size 300 relay. Projecting mounting When projecting mounting is preferred, a relay case type SPA-ZX 317 is used. The relay case for projecting mounting is provided with front connectors. SPA-ZX304 SPA-ZX305 SPA-ZX201 SPA-ZX306 SPA-ZX307 SPA-ZX317 SPA-ZX318 +0,4 482,6 0 (19") 242 197 ø6 306 312 292 6 197 98 21,5 101,6 7 +0,4 177 0 (4U) 304_5_6 Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm) 9

Ordering When ordering, please specify: Ordering information Ordering example 1. Type designation and quantity 1, 5 pieces 2. Order number RS 488 003-AA 3. Rated frequency I n =5 A, U n =110 V, f n =50 Hz 4. Auxiliary voltage U aux =110 V dc 5. Accessories - 6. Special requirements - Order numbers Voltage regulator _ without test adapter 1, incl. modules SPCU 1D50 and SPCN 1D56 3, incl. module SPCU 1D50 The last two letters of the order number indicate the rated frequency f n and the auxiliary voltage U aux of the relay as follows: RS 488 003-AA, CA, DA, FA RS 488 005-AA, CA, DA, FA AA equals f n = 50 Hz and U aux = 80 265 V ac/d CA equals f n = 50 Hz and U aux = 18 80 V dc DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc Voltage regulators _ including test adapter RTXP18 1, incl. modules SPCU 1D50 and RS 488 203-AA, CA, DA, FA SPCN 1D56 3, incl. module SPCU 1D50 RS 488 205-AA, CA, DA, FA The last two letters of the order number indicate the AA equals f n = 50 Hz and U aux = 80 265 V ac/d rated frequency f n and the auxiliary voltage U aux of CA equals f n = 50 Hz and U aux = 18 80 V dc the relay as follows: DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc References Additional information User s manual and technical description Voltage regulator 1MRS 750110-MUM EN 10

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel +358 10 22 11 Fax +358 10 224 1094 www.abb.com/substationautomation