Closed Circuit Cooling Towers



Similar documents
VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

Overview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations

A Guide to Trouble-Free Cooling Towers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

AIR CONDITIONING TECHNOLOGY

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

HVAC Systems: Overview

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

1.2 Refrigerant Equipment. General

Chilled Water HVAC Systems

RPV - RP - RA air handling units

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

ECOCIAT. Domestic hot water heat recovery unit

Commissioning - Construction Documents (Page 1 of 6)

SECTION MORTUARY REFRIGERATORS

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

COMMISSIONING OF HVAC SYSTEMS

Element D Services Heating, Ventilating, and Air Conditioning

HVAC Processes. Lecture 7

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SWIMMING POOL AIR-HANDLING UNITS KU-DB Series

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Why and How we Use Capacity Control

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Oil and Coolant Circulating Heating System. Model - OCSM

AIR-COOLED CHILLERS APPLIED SYSTEMS. EUWA*5-24KAZW - EUWY*5-24KAZW -

Lesson 36 Selection Of Air Conditioning Systems

SECTION HEAT PUMPS

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Steam System Best Practices Condensate System Piping

State of the Art Energy Efficient Data Centre Air Conditioning

Cooling Systems 2/18/2014. Cooling Water Systems. Jim Lukanich, CWT ChemCal, Inc. Grapevine, TX

Diesel Engine Driven Generators Page 1 of 6

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

Center for Energy Education Laboratory

300 Series PA Pump and Cooler Assemblies

ASTACEA4 Inspect complex/central air conditioning systems

Bring the fresh in. Dedicated Outside Air Systems

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Glossary of Heating, Ventilation and Air Conditioning Terms

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

MAC-120HE-01 Air-Cooled Chiller

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

Mechanical Rooftop Custom Capabilities

Liebert Hiross HPW The High Performance Wallmount Cooling Solutions for Telecom Mobile Remote Access Nodes

Optimization of Water - Cooled Chiller Cooling Tower Combinations

- White Paper - Data Centre Cooling. Best Practice

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

2006 APC corporation. Cooling Solutions and Selling Strategies for Wiring Closets and Small IT Rooms

Tim Facius Baltimore Aircoil

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

HEATING AND COOLING SYSTEMS THAT FIT COMFORTABLY WITHIN YOUR BUDGET.

Johnson Air-Rotation Systems

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Cool Design for Homes and Offices

Maintenance for Energy Efficiency

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

How To Clean Up A Reactor Water Cleanup

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

The Different Types of Air Conditioning Equipment for IT Environments

HEAVY DUTY STORAGE GAS

NYC Department of Education Building Condition Assessment Survey BROADWAY EDUCATION CAMPUS - MANHATTAN, 26 BROADWAY, MANHATTAN, NY, 10004

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

NSN

APC APPLICATION NOTE #112

USER S MANUAL HSC-24A

Evaluate, Clean, and Tune Guidance

DUCT TYPE AIR CONDITIONER

Heating Water by Direct Steam Injection

Glossary of HVAC Terms

SECTION GENERAL PROVISIONS FOR HVAC WORK

PBX Series Quick Fit Connector Bimetallic Steam Traps

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

BPW32 DN15, DN20 and DN25 Balanced Pressure Wafer Steam Trap

21.1 Functions, Basic Configuration, and Interfaces

INFO HTK. Hybrid dry cooler. The reference for hybrid dry cooling ,000 kw

WINDOW ROOM AIR CONDITIONER

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

2A.1 Features of Chiller Control Components A.3 Chilled-Water Supply Temperature Control A.4 Cooling-Water Supply Control...

How To Use A Water Source Heat Pump

How Ground/Water Source Heat Pumps Work

Energy Efficiency in Industrial HVAC Systems

Condensing unit type EPSILON-ECHOS LE Technical information manual

White Paper #10. Energy Efficiency in Computer Data Centers

/ Marley NC Class Cooling Tower /

Building Energy Systems. - HVAC: Heating, Distribution -

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Offshore Substation. HVAC System. ETS-09 Rev. 2. technical standards. Dok Sag 09/1437

Dealer Sales & Service Guide

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Select Radiators Installation Guide

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

Product Data Bulletin

Transcription:

CCCT - C Product Group Detail General Information... C Principle of Operation... C Configuration... C Fan System... C3 Capacity Range... C3 Maximum Entering Fluid Temperature... C4 Typical Applications... C4 Product Line Table... C4 Advantages of... C6 Engineering Considerations... C9

CCCT - C General Information Closed circuit cooling towers provide evaporative cooling for many types of systems, and the specific application will largely determine which BAC Closed Circuit Cooling Tower is best suited for a project. The Product Line Table is intended as a general guide. Specialized assistance is available through your local BAC Balticare Representative. Principle of Operation Closed circuit cooling towers operate in a manner similar to open cooling towers, except that the heat load to be rejected is transferred from the process fluid (the fluid being cooled) to the ambient air through a heat exchange coil. The coil serves to isolate the process fluid from the outside air, keeping it clean and contamination free in a closed loop. This creates two separate fluid circuits: () an external circuit, in which spray water circulates over the coil and mixes with the outside air, and () an internal circuit, in which the process fluid circulates inside the coil. During operation, heat is transferred from the internal circuit, through the coil to the spray water, and then to the atmosphere as a portion of the water evaporates. Configuration BAC manufactures two types of closed circuit cooling towers: combined flow and counterflow. Combined Flow Combined flow is the use of both a heat exchange coil and wet deck surface for heat transfer in a closed circuit cooling tower. The addition of wet deck surface to the traditional closed circuit cooling tower design reduces evaporation in the coil section, reducing the potential for scaling and fouling. BAC s combined flow closed circuit cooling towers utilize parallel flow of air and spray water over the coil, and crossflow air/water flow through the wet deck surface. In parallel flow, air and water flow over the coil in the same direction. The process fluid travels from the bottom to the top of the coil, increasing efficiency by bringing the coldest spray water and air in contact with the process fluid at its coldest temperature. Combined Flow: Parallel flow of air and water over the coil in counterflow with the fluid inside the coil Combined Flow: Crossflow configuration over the wet deck Baltimore Aircoil

CCCT - C 3 Counterflow In a counterflow closed circuit cooling tower design, the flow of the air is in the opposite direction of the spray water. In BAC s counterflow closed circuit cooling towers, air travels vertically up through the unit while the spray water travels vertically down over the coil. Fan System The flow of air through most factory assembled evaporative cooling equipment is provided by one or more mechanically driven fans. The fan(s) may be axial or centrifugal, each type having its own distinct advantages. Counterflow Configuration Axial fan units require approximately half the fan motor kilowatt of comparably sized centrifugal fan units, offering significant life-cycle cost savings. Centrifugal fan units are capable of overcoming reasonable amounts of external static pressure ( 5 Pa), making them suitable for both indoor and outdoor installations. Centrifugal fans are also inherently quieter than axial fans, although the difference is minimal and can often be overcome through the application of optional low sound fans and/or sound attenuation on axial fan units. Fans can be applied in an induced draft or a forced draft configuration. Centrifugal Fans Axial Fans Induced Draft The rotating air handling components of induced draft equipment are mounted in the top deck of the unit, minimizing the impact of fan noise on near-by neighbors and providing maximum protection from fan icing with units operating in sub-freezing conditions. The air being drawn through the unit hereby discharges over the inducing fan. The use of corrosion resistant materials ensures long life and minimizes maintenance requirements for the air handling components. Forced Draft Rotating air-handling components are located on the air inlet face at the base of forced draft equipment whereby fresh air is blown through the unit. This base fan position facilitates easy access for routine maintenance and service. Additionally, location of these components in the dry entering air stream extends component life by isolating them from the corrosive saturated discharge air. Capacity Range In the Product Line Table, product capacities are called out in terms of a flow rate. This refers to the fluid flow rate that the unit can cool from a 30ºC entering water temperature to 5 C leaving water temperature at a ºC entering ambient wet-bulb temperature. All capacities shown are for a single cell; multiple cell units can be applied to achieve larger capacities.... because temperature matters

CCCT - C 4 Maximum Entering Fluid Temperature All BAC are capable of withstanding entering fluid temperatures as high as 8ºC. Typical Applications A list of typical applications is provided in the Product Line Table for your reference. Product Line Table Principle of Operation 7 VXI 8 0 3 4 0 VFL 7 8 4 3 6 9 6 9 Configuration Counterflow Counterflow Fan System Centrifugal Fan, Forced Draft Centrifugal Fan, Forced Draft Capacity Range (Single Cell) Maximum Entering Fluid Temperature,5 tot 00 l/s to 65 l/s 8 C 8 C Typical Applications Small to medium HVAC & industrial applications such as water source heat pump loops and air compressor cooling Indoor installations High temperature applications Tight enclosures & installations requiring a single air inlet Extremely sound sensitive applications Small to medium HVAC & industrial applications Installations with extremely low height requirements Indoor installations High temperature industrial applications Extremely sound sensitive applications. Air In;. Air Out; 3. Fluid In; 4. Fluid Out; 5. Wet Deck Surface; 6. Cold Water Basin; 7. Water Distribution System; 8. Coil; 9. Spray Water Pump; 0. Eliminators;. Optional Extended Surface. HFL, HXI and DFC water saving and hybrid wet-dry closed circuit products are available to meet specific design requirements. Refer to the "Water Saving Products" section for more details on these products. Baltimore Aircoil

CCCT - C 5 FXV - Single Air Inlet Models 0 0 7 Combined flow Axial Fan, Induced Draft S500 FXV-D Dual Air Inlet Models Combined flow Axial Fan, Induced Draft 3 to 49 l/s 00 to 300 l/s 8 C 8 C Small to medium HVAC & industrial applications such as water source heat pump loops and air compressor cooling Tight enclosures & installations requiring a single air inlet Unit replacements 8 5 6 4 3 9 4 3 7 8 5 0 0 6 9 Medium to large HVAC & industrial applications such as electric arc furnaces and pharmaceutical plants 4 3... because temperature matters

CCCT - C 6 Advantages of Open cooling towers expose process cooling water to the atmosphere, typically as part of a chiller system loop (see Figure ). These open towers use an efficient, simple, and economical design. All components in an open system must be compatible with the oxygen introduced via the cooling tower. Closed circuit cooling towers completely isolate process cooling fluid from the atmosphere. This is accomplished by combining heat rejection equipment with a heat exchanger in a closed circuit tower (see Figure ). A closed loop system protects the quality of the process fluid, reduces system maintenance, and provides operational flexibility at a slightly higher initial cost. When deciding which system is best for an application, several factors should be considered. Figure : Chiller Loop w/open Tower Figure : Chiller Loop w/closed Circuit Tower Performance If an application must produce full capacity throughout the year, maintaining a clean, reliable system loop is critical. Isolating the process fluid in a closed loop system prevents airborne Baltimore Aircoil

CCCT - C 7 contaminants from entering and fouling the system. Sustaining optimum performance in an open loop system will require regular maintenance to assure similar efficiency. High efficiency chillers and heat exchangers rely on clean process water to function properly and are significantly impacted by even small amounts of fouling. Expense The initial equipment cost of an open loop system will be less than a comparably sized closed loop system, since the open system does not include the intermediate heat exchanger component. However, the higher first cost of a closed loop system will be paid back during years of operation through the following savings: Cleaner process fluid results in a cleaner internal surface area, and higher efficiency components in the system (e.g. chiller) Reduced system maintenance costs Reduced water treatment costs for evaporative equipment Operating in free cooling mode during the winter to save energy consumption Maintenance Since the process fluid of a closed loop system is completely isolated from the environment, routine maintenance is only required on the heat rejection equipment itself. The need to shut down the system periodically to clean the heat exchanger is dramatically reduced, if not entirely eliminated. Providing clean process fluid to the system will extend the life of other components in the system (condenser bundles, compressors, etc.). Water Treatment Maintaining proper process fluid quality in a system may involve several steps, such as chemical treatment, filtration equipment and the addition of clean make-up water. A closed circuit cooling tower can provide the following advantages over an open cooling tower: Lower volume of recirculating water to treat Process loop requires minimal treatment During periods of dry operation, the need for make-up water is eliminated Operational Flexibility Closed circuit cooling towers allow for the following modes of operation not possible with open cooling towers: Free cooling operation without the need for an intermediate heat exchanger: Chiller turned off Dry operation: Conserve water and treatment chemicals, prevent icing and eliminate plume Variable pumping: Closed condenser water loop allows for variable speed pumping to conserve energy... because temperature matters

CCCT - C 8 Closed Circuit Tower versus Open Tower / Heat Exchanger Sometimes, an open cooling tower is paired with a heat exchanger (see Figure 3) to capture some of the benefits of closed loop cooling. Choosing closed circuit cooling towers over this open tower/ heat exchanger combination may still be a better choice for the following reasons: Total cost: Addition of a heat exchanger (pump, piping, etc.) to the open tower loop brings the initial cost much closer to that of the closed circuit tower system Single piece of equipment: Compact design of the closed circuit tower conserves space in a self-contained package, compared to multiple locations for the tower/heat exchanger arrangement Maintenance: Narrow spacing in heat exchanger (e.g. plate and frame) may trap solids introduced by the open tower, requiring frequent, time consuming cleaning to assure optimum performance Dry operation: Open tower/heat exchanger system cannot be run dry in the winter These guidelines provide some general information to help decide whether a closed circuit cooling tower is better suited for a particular application than an open tower, with or without a heat exchanger. For additional assistance with a project, please contact your local BAC Balticare Representative. Figure 3 : Chiller Loop w/open Tower/Heat Exchanger Combination Note : BAC offers heat exchanger skids in combination with most of his open cooling tower products. These skids are available for both new installations or to retrofit on existing installations. The heat exchanger skid consists of a plate heat exchanger with pump and interconnecting piping and appendages. The skids are delivered on a heavy duty frame and with steel panel enclosure. Refer to your BAC Balticare representative for more details and selections. Baltimore Aircoil

CCCT - C 9 Engineering Considerations Location Units must have an adequate supply of fresh air to the air inlet(s). When units are located adjacent to building walls or in enclosures, care must be taken to ensure that the warm, saturated discharge air is not deflected off surrounding walls or enclosures and drawn back to the air inlet(s). Warning: Each unit should be located and positioned to prevent the introduction of the warm discharge air and the associated drift, which may contain chemical or biological contaminants including Legionella, into the ventilation systems of the building on which the unit is located or those of adjacent buildings. Note: For detailed recommendations on layout, please consult your local BAC Balticare Representative. For VL and VX products, bottom screens or solid bottom panels may be desirable or necessary for safety, depending on the location and conditions at the installation site. Piping and Valves Piping must be sized and installed in accordance with good piping practice. All piping should be supported by pipe hangers or other supports, not by the unit. Some installations may require flow balancing valves (supplied by others) at the coil inlets to balance the flow to individual coils and cells. External shutoff valves on the closed circuit loop (supplied by others) may also be required if the system design necessitates the isolation of individual cells. Although equalizing lines can be used to balance water levels between multi-cell closed circuit cooling towers, the spray water for each cell must be treated separately, and a separate make-up must be provided for each cell. Note that a common remote sump for multi-cell installations can simplify make-up and water treatment see "Technical Resources, Remote Sump Tank Selection" for details. See the appropriate Operating and Maintenance Instruction Manual for more information on water treatment. Capacity Control Variable Frequency Drives (VFD) Installations which are to be controlled by Variable Frequency Drives (VFD) require the use of an inverter duty motor as designed IEC 34., which recognizes the increased stresses placed on motors by these drive systems. Inverter duty motors must be furnished on VFD applications in order to maintain the motor warranty. Fan motors must be furnished with thermal protection (either PTC sensors or coil thermostats normally open, or normally closed). The motor protection consists of temperature sensitive cutout devices embedded in the motor windings (minimum 3 per motor). The minimum fan motor speed during normal operation should be not below 30% of the speed indicated on the motor nameplate. This corresponds with 5 Hz for a 50 Hz supply and 8 Hz for a 60 Hz supply. BAC offers factory installed motor control packages including VFD drives. Refer to the section "Technical Resources, Motor Controls". Check with your local BAC Balticare representative for availability. Warning: When the fan speed is to be changed from the factory-set speed, including through the use of a variable speed control device, steps must be taken to avoid operating at or near fan speeds that cause a resonance with the unit or its supporting structure. At start-up, the variable frequency drive should be cycled slowly between zero and full speed and any speeds that cause a noticeable resonance in the unit should be locked out by the variable speed drive. Fan Cycling Fan cycling is the simplest method of capacity control. The number of steps of capacity control can be increased using the Baltiguard Fan System, the independent fan motor option, or two-speed fan motors in conjunction with fan cycling (see the Custom Features & Options section of the appropriate product line to determine whether the Baltiguard Fan System or the independent fan motor option are available; two-speed motors are available for all products). These options provide substantial energy savings when compared to simple fan cycling. Warning: Rapid on-off cycling can cause the fan motor to overheat. It is recommended that controls be set to allow a maximum of 6 on-off cycles per hour.... because temperature matters

CCCT - C 0 Note: Spray water pump cycling should not be used for capacity control. This method of control often results in short cycling of the pump motor as capacity changes substantially with pump cycling. In addition, alternate wetting and drying of the coil promotes scaling of the heat exchanger coil surface. Capacity Control Dampers (VFL and VXI models only) On centrifugal fan models, modulating capacity control dampers are available to provide close control of the leaving temperature. See Section "Accessories" or contact your local BAC Balticare representative. Vibration Cutout Switch Vibration cutout switches are recommended on all axial fan installations. Vibration cutout switches are designed to interrupt power to the fan motor and/or provide an alarm to the operator in the event of excessive vibration. BAC offers both electronic and mechanical vibration cutout switches on all closed circuit cooling towers. Water Treatment As water evaporates in the unit, the dissolved solids originally present in the water remain in the system. The concentration of these dissolved solids increases rapidly and can cause scale and corrosion. In addition, airborne impurities and biological contaminants, including Legionella, may be introduced into the circulating water. To control all potential contaminants, a water treatment program must be employed. In many cases, a simple bleed-off may be adequate for control of scale and corrosion. However, biological contamination, including Legionella, can be controlled only through the use of biocides. Such treatment should be initiated at system startup, after periods of equipment shutdown, and continued regularly thereafter. Accordingly, it is strongly recommended a biocide treatment be initiated when the unit is first filled with water and continued regularly thereafter. For more information, consult the appropriate Operating and Maintenance Manual. When a water treatment program is employed, it must be compatible with construction materials. Batch feeding of chemicals into the unit is not recommended. If units are constructed with optional corrosion resistant materials, acid treatment may be considered; however, the water quality must be maintained within the guidelines set forth in the Operating and Maintenance Instructions. Note: Unless a common remote sump is utilised, each cell of a multi-cell installation must be treated as a separate entity, even if the cold water basins are equalized. For complete Water Quality Guidelines, see the appropriate Operating and Maintenance Instruction Manual, available at www.baltimoreaircoil.com. For specific recommendations on water treatment, contact a competent water treatment supplier. Wet Deck Surface Compatibility (FXV and FXV-D models only) The standard wet deck surface in FXV and FXV-D is constructed of a plastic material This wet deck surface is compatible with the water found in most evaporative cooling applications. For applications where the entering fluid temperature exceeds 8 C, contact your local BAC Balticare Representative to confirm that the standard wet deck is acceptable. Sound Levels Sound rating data are available for all BAC models. When calculating the sound levels generated by a unit, the designer must take into account the effects of the geometry of the tower as well as the distance and direction from the unit to noise-sensitive areas. Whisper Quiet fans and intake and discharge sound attenuation can be supplied on certain models to provide reduced sound characteristics (see the Custom Features and Options section of the appropriate product line for details). The Baltiguard Fan System, two-speed motors, or variable frequency drives can also be used to reduce sound during periods of non-peak thermal loads. For more information on sound and how it relates to evaporative cooling equipment, see Section "Technical Resources, Fundamentals of Sound". For detailed low sound selections, please consult your local BAC Balticare Representative. Baltimore Aircoil

CCCT - C Winterization When a unit is shut down in freezing weather, the basin water must be protected by draining to an indoor auxiliary remote sump tank or by providing supplementary heat to the cold water basin. Supplementary heat can be provided by electric immersion heaters or in some cases, hot water, steam coils, or steam injectors. All exposed water piping, make-up lines, and spray pumps (if applicable) that do not drain at shutdown should be traced with electric heater tape and insulated. When dry operation is planned for low ambient conditions, centrifugal fan units should be supplied with oversized fan motors to prevent motor overload when the spray water is not operating. For remote sump applications, the spray water pump must be selected for the required flow at a total head which includes the vertical lift, pipe friction (in supply and suction lines) plus the required pressure at the inlet header of the water distribution system (4 kpa). A valve should always be installed in the discharge line from the pump to permit adjusting flow to the unit requirement. Inlet water pressure should be measured by a pressure gauge installed in the water supply riser at the spray water inlet, and adjusted to the specified inlet pressure. Indoor Installation (applicable to VXI and VFL models only) Many indoor installations require the use of inlet and/or discharge ductwork. Units installed with inlet ductwork must be ordered with solid-bottom panels. Generally, intake ducts are used only on smaller units while the equipment room is used as a plenum for larger units. Discharge ductwork will normally be required to carry the saturated discharge air from the building. Both intake and discharge ductwork must have access doors to allow servicing of the fan assembly, drift eliminators, and water distribution system. All ductwork is supplied and installed by others and should be symmetrical and designed to provide even air distribution across the face of air intakes and discharge openings. Such ductwork may increase the external static pressure on the unit, requiring a larger fan motor to be installed. This external static pressure must be quantified (in Pa) to BAC to allow for suitable fan motor sizing. Warning: The discharge opening must be positioned to prevent the introduction of discharge air into the fresh air intakes serving the unit or the ventilation systems of adjacent buildings. Note: Axial fan units are not suitable for indoor installations. Safety Adequate precautions, appropriate for the installation and location of these products, should be taken to safeguard the public from possible injury and the equipment and the premises from damage. Operation, maintenance and repair of this equipment should be undertaken only by personnel qualified to do so. Proper care, procedures and tools must be used in handling, lifting, installing, operating, maintaining, and repairing this equipment to prevent personal injury and/or property damage. Fluid Compatibility The fluid to be cooled must be compatible with the coil material (standard serpentine are carbon steel, hot-dip galvanized on the outside only). Fluids not compatible with coil materials can lead to corrosion and tube failure. Certain fluids may require occasional pressure cleaning or mechanical cleaning of the inside of coil tubes. In such cases the coil must be designed to provide this capability. Open / Closed System The standard galvanised steel serpentine and coils are carbon steel, hot-dip galvanised on the outside only, and are intended for application on closed, pressurised systems which are not open to the atmosphere. Stainless steel coils or cleanable coil units (with tubes hot-dip galvanized inside and out) are available to cool corrosive fluids or water and ethylene/propylene glycol solutions in systems open to the atmosphere Protection Against Coil Freezing At below freezing ambient conditions, the unit can experience heat loss even without the recirculating spray water pump and fans in operation. Without a heat load on the circulating fluid,... because temperature matters

CCCT - C coil freezing can occur even at full flow. Protective means are readily available to avoid potential freeze problems. Where the system will permit, the best protection against coil freeze-up is the use of an industrially inhibited anti-freeze solution. When this is not possible, the system must be designed to meet both of the following conditions:. Maintain minimum recommended flow through the coil at all times, as per the table below:. Maintain a heat load on the circulating fluid so that the temperature of the fluid leaving the coil will not be below 7ºC. If the process load is extremely light, or if the process is periodically shut off entirely, then an auxiliary heat load must be applied to the circulating fluid when below freezing ambient temperatures exist to prevent damage to the coil. Refer to the Heat Loss Data table (see the product section for applicable heat loss data) for the auxiliary heat load requirement. The amount of auxiliary heat necessary to prevent coil freezing can be further reduced by the use of a positive closure damper hood and insulation. Draining the coil is not recommended as a normal method of freeze protection. However, draining is acceptable as an emergency method of freeze protection. Frequent draining can promote corrosion inside the coil tubes. If the coil is not protected by an industrially inhibited anti-freeze solution, an automatic drain valve and air vent is recommended to drain the coil if flow stops or fluid temperature drops below 7ºC when the ambient temperature is below freezing. Note that cold water basin heaters will not provide freeze protection for the coil. The coil of dry and TrilliumSeries coolers can never drain completely. If a minimum heat load can not be guaranteed on the dry coil during the winter period, then the use of an anti-freeze solution is the only available protection against coil freezing. Model Minimum Flow (l/s) VFL 4X - 48X 4, VFL 7X - 96X 7,9 VXI 9, 8, 7, 36 3,5 VXI 50 5 VXI 70, C7 7 VXI 95, 45, C08 8 VXI 44, 5 3 VXI 80 VXI 90, 90 6 VXI 88, 430 6 VXI 360 FXV 4X, 43X 3 FXV 44X 5 FXV Q44X 0 FXV 5XX 6 FXV Q5XX FXV 64X, 66X 7 FXV Q6XX 4 FXV D88X, D364X 8 FXV D88XQ, D364XQ 36 Warranties Please refer to the Limitation of Warranties applicable to and in effect at the time of the sale/ purchase of these products. Baltimore Aircoil