RTD and thermocouple circuits, with millivolt calculations



Similar documents
Basic voltmeter use. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Parallel DC circuits

Lab 3 - DC Circuits and Ohm s Law

Series and Parallel Circuits

DC mesh current analysis

DC Circuits (Combination of resistances)

Physics 3330 Experiment #2 Fall DC techniques, dividers, and bridges R 2 =(1-S)R P R 1 =SR P. R P =10kΩ 10-turn pot.

Transformer circuit calculations

Ohm's Law and Circuits

Electrical Fundamentals Module 3: Parallel Circuits

Preamble. Kirchoff Voltage Law (KVL) Series Resistors. In this section of my lectures we will be. resistor arrangements; series and

Inductors. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws

Simple circuits worksheet

Basic circuit troubleshooting

Resistors. Some substances are insulators. A battery will not make detectible current flow through them.

V out. Figure 1: A voltage divider on the left, and potentiometer on the right.

Elementary circuits. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

AC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Objectives 200 CHAPTER 4 RESISTANCE

Conversion Between Analog and Digital Signals

Resistance, Ohm s Law, and the Temperature of a Light Bulb Filament

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Resistors in Series and Parallel Circuits

CHAPTER 28 ELECTRIC CIRCUITS

Capacitors. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Experiment 8 Series-Parallel Circuits

Monolithic Thermocouple Amplifiers with Cold Junction Compensation AD594/AD595

Tristan s Guide to: Solving Series Circuits. Version: 1.0 Written in Written By: Tristan Miller Tristan@CatherineNorth.com

Experiment NO.3 Series and parallel connection

Kirchhoff s Laws Physics Lab IX

Chapter 7 Direct-Current Circuits

Current, Resistance and Electromotive Force. Young and Freedman Chapter 25

Lab E1: Introduction to Circuits

Series-parallel DC circuits

Nodal and Loop Analysis

Users Manual. Temperature Calibrator

Potentiometers. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Experiment 4 ~ Resistors in Series & Parallel

Experiment #3, Ohm s Law

TECH TIP # 37 SOLVING SERIES/PARALLEL CIRCUITS THREE LAWS --- SERIES CIRCUITS LAW # THE SAME CURRENT FLOWS THROUGH ALL PARTS OF THE CIRCUIT

Parallel DC circuits

The Electrical Properties of Materials: Resistivity

Parallel Circuits. Objectives After studying this chapter, you will be able to answer these questions: 1. How are electrical components connected

Ammeter design. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Building the AMP Amplifier

FB-DC3 Electric Circuits: Series and Parallel Circuits

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Design Project: Power inverter

Soldering. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

# 2. Selecting and Using Thermistors for Temperature Control

1. The diagram below represents magnetic lines of force within a region of space.

Which Bulb Burns Brighter? One is a 60-watt bulb and the other a 100-watt bulb, and they are connected in an electric circuit.

HOW ACCURATE ARE THOSE THERMOCOUPLES?

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

Module 2. DC Circuit. Version 2 EE IIT, Kharagpur

DET Practical Electronics (Intermediate 1)

6 Series Parallel Circuits

EXPERIMENT 7 OHM S LAW, RESISTORS IN SERIES AND PARALLEL

TT-1000A TURBINE TEMPERATURE TEST SET USER INSTRUCTION MANUAL M/N: TT-1000A P/N: Doc. P/N: Revision D April 24, 2013

Measuring Electric Phenomena: the Ammeter and Voltmeter

(Issued 1 Dec. 1965) CRD-C METHOD OF TEST FOR THERMAL CONDUCTIVITY OF LIGHTWEIGHT INSULATING CONCRETE 1

STUDY MATERIAL FOR CLASS Physics- CURRENT ELECTRICITY. The flow of electric charges in a particular direction constitutes electric current.

The Fundamentals of Thermoelectrics

WHITE PAPER How to Prevent Temperature Measurement Errors When Installing Thermocouple Sensors and Transmitters

Circuit symbol. Each of the cells has a potential difference of 1.5 volts. Figure 1. Use the correct answer from the box to complete the sentence.

Lesson Plan. Parallel Resistive Circuits Part 1 Electronics

Fig. 1 Analogue Multimeter Fig.2 Digital Multimeter

= (0.400 A) (4.80 V) = 1.92 W = (0.400 A) (7.20 V) = 2.88 W

Energy, Work, and Power

Current and Voltage Measurements. Current measurement

USB TC-08. Temperature Logger. User's Guide. usbtc08.en r7 Copyright Pico Technology Limited. All rights reserved.

Current Electricity Lab Series/Parallel Circuits. Safety and Equipment Precautions!

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Basic RTD Measurements. Basics of Resistance Temperature Detectors

Microcontroller to Sensor Interfacing Techniques

Using LabVIEW to Measure Temperature with a Thermistor

Physics, Chapter 27: Direct-Current Circuits

Loop Calibration and Maintenance

Wires & Connections Component Circuit Symbol Function of Component. Power Supplies Component Circuit Symbol Function of Component

Tristan s Guide to: Solving Parallel Circuits. Version: 1.0 Written in Written By: Tristan Miller Tristan@CatherineNorth.com

Wire types and sizes

Episode 126: Capacitance and the equation C =Q/V

Chapter 22 Further Electronics

= V peak 2 = 0.707V peak

APPLICATION NOTES OF SIGNAL ISOLATORS

IC Temperature Sensor Provides Thermocouple Cold-Junction Compensation

Lab 3 Rectifier Circuits

NTE923 & NTE923D Integrated Circuit Precision Voltage Regulator

Resistors in Series and Parallel

Series and Parallel Resistive Circuits Physics Lab VIII

ECEN 1400, Introduction to Analog and Digital Electronics

Your Multimeter. The Arduino Uno 10/1/2012. Using Your Arduino, Breadboard and Multimeter. EAS 199A Fall Work in teams of two!

CURRENT ELECTRICITY - I

7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A

Alternating Current and Direct Current

DC generator theory. Resources and methods for learning about these subjects (list a few here, in preparation for your research):

Thermistor Basics. Application Note AN-TC11 Rev. A. May, 2013 Page 1 WHAT IS A THERMISTOR?

Analysis of a single-loop circuit using the KVL method

Transcription:

RTD and thermocouple circuits, with millivolt calculations This worksheet and all related files are licensed under the Creative Commons ttribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/, or send a letter to Creative Commons, 559 Nathan bbott Way, Stanford, California 94305, US. The terms and conditions of this license allow for free copying, distribution, and/or modification of all licensed works by the general public. 1

Question 1 Questions Calculate the voltage across the bridge ( B ) at the following RTD temperatures, assuming a 604 Ω nickel-iron RTD with an alpha value of 0.00518: 1k5 4k7 22 m + B RTD 2k2 T = 0 o C ; B = T = 81 o C ; B = T = -45 o C ; B = T = 320 o F ; B = millivolts millivolts millivolts millivolts file i00600 Question 2 Suppose you need to determine the temperature of a fluid inside a pipe. Installed in this pipe is a 2-wire 100 Ω RTD inside a thermowell, not connected to a transmitter or any other circuit. You happen to have a multimeter with you to measure resistance at the RTD leads. Touching the two test leads of your multimeter together, you measure 0.3 Ω. Then, connecting those same leads to the RTD s wires, you measure 184.6 Ω. You do not happen to have an RTD table with you, but you do carry a calculator. Calculate the approximate temperature of the fluid in this pipe, assuming the most common α value for 100 Ω RTDs. file i00602 2

Question 3 Determine the temperature of the RTD, given a measured voltage of 59.7 millivolts between test points C and D in this circuit: R wire = 1.7 Ω C RTD R 0 = 100 Ω α = 0.00392 R wire = 1.6 Ω 0.54 m B D ssume a 100 Ω RTD with α = 0.00392. file i00166 Question 4 Determine the temperature of the RTD, given a measured voltage of 89.2 millivolts between test points C and D, and 88.7 millivolts between test points E and D: R wire = unknown C RTD R 0 = 100 Ω α = 0.00385 R wire = unknown E 0.41 m B R wire = unknown D ssume a 100 Ω RTD with α = 0.00385, and all wire resistances to be equal to each other. file i00601 3

Question 5 Suppose you need to measure the temperature of an operating oven using nothing but a 1000 Ω RTD (α = 0.00385), a 1.75 kω precision resistor, and a battery of unknown voltage: 1.75 kω precision resistor + - Wht Wht Red Red 1 kω RTD α = 0.00385 OFF COM Oven Turning the switch on, you measure 1.32 volts across the resistor and 1.22 volts across the RTD. Calculate the oven temperature based on these measurements, and also explain why it is important to quickly take these measurements once the switch is turned on. file i00632 4

Question 6 Determine the temperature of the RTD, given CD = 140.5 millivolts and EF = 140.1 millivolts: R wire = unknown C RTD R 0 = 1 kω α = 0.00385 R wire = unknown R wire = unknown E F 0.12 m B R wire = unknown D ssume a 1 kω RTD with α = 0.00385, and all wire resistances completely unknown (not assumed to be equal). file i00631 Question 7 Suppose someone builds a dual-junction thermocouple circuit using type T thermocouple wire (copper and constantan metals), then measures voltage between the two junctions with a voltmeter: OFF COM Copper (+) Copper (+) 105 o F 77 o F Constantan (-) Constantan (-) Calculate the voltage read by the voltmeter, using a type T thermocouple table to find millivolt potentials for each of the junctions. file i03172 5

Question 8 When a type T thermocouple (copper/constantan) is connected to a voltmeter made of copper wires, two active junctions are formed: one at the point of measurement (the measurement junction) and one at a terminal near the voltmeter (the reference junction). The copper-to-copper junction at the top screw of the terminal block is of no consequence because it is a junction of identical metals, and as such generates no thermoelectric voltage: Process + - Measurement junction Field Copper Constantan Instrument room Terminal block Copper Copper Reference junction oltmeter The amount of voltage sensed by the voltmeter in this thermocouple circuit is equal to the difference in voltages produced by the measurement and reference junctions: E meter = E meas E ref Now consider a type J thermocouple connected to a copper-wire voltmeter. Here we see there are not two but three active junctions of dissimilar metals: Process + - Field Iron Constantan Instrument room Terminal block Copper Copper oltmeter Measurement junction Reference junction 1 Reference junction 2 Upon first observation it would appear this circuit is more complicated than the type T thermocouple circuit, owing to the existence of the additional dissimilar-metal junction. However, a principle called the Law of Intermediate Metals allows us to consider the two reference junctions (iron-copper and constantancopper) as electrically equivalent to a single reference junction of iron-constantan, such that the type J 6

thermocouple circuit becomes just as simple as the type T circuit with one measurement junction and one reference junction in opposition to each other. Explain what the Law of Intermediate Metals is, and how it may be used to simplify the two active reference junctions of the type J circuit. lso, explain why it is important that the terminal block be isothermal in nature. file i03628 Question 9 Suppose someone builds a dual-junction thermocouple circuit using type T thermocouple wire (copper and constantan metals), then measures voltage in the loop using a voltmeter: OFF COM Copper (+) Copper (+) 59 o F Constantan (-) Constantan (-) 193 o F 102 o F Constantan (-) Copper (+) Constantan (-) 71 o F Copper (+) Calculate the voltage read by the voltmeter, using a type T thermocouple table to find millivolt potentials for each of the junctions. file i02948 7

Question 10 Calculate the amount of voltage seen by the voltmeter given the following measurement and reference junction temperatures: T 1 Type B thermocouple T 2 OFF T 3 Type B cable COM T 1 = 589 o F ; T 2 = 63 o F ; T 3 = 70 o F ; meter = T 1 = 821 o F ; T 2 = 69 o F ; T 3 = 73 o F ; meter = T 1 = 1524 o F ; T 2 = 91 o F ; T 3 = 105 o F ; meter = T 1 = 1922 o F ; T 2 = 102 o F ; T 3 = 135 o F ; meter = file i02947 m m m m 8

Question 11 Calculate the amount of voltage seen by the voltmeter given the following measurement and reference junction temperatures: T 1 Type E thermocouple T 2 Type EX cable OFF T 3 COM T 1 = 233 o C ; T 2 = 31 o C ; T 3 = 25 o C ; meter = T 1 = 348 o C ; T 2 = 40 o C ; T 3 = 16 o C ; meter = T 1 = 161 o C ; T 2 = 4 o C ; T 3 = 23 o C ; meter = T 1 = 836 o C ; T 2 = 34 o C ; T 3 = 19 o C ; meter = file i02945 m m m m 9

Question 12 Suppose three different voltmeters are connected to a thermocouple, with each voltmeter having a different ambient temperature: Chromel 71 o F 85 o F 60 o F 1050 o F oltmeter oltmeter oltmeter lumel Calculate the amount of voltage registered by each of the three voltmeters, as well as answer the following questions: If a fourth voltmeter were connected to this same thermocouple, would it affect the readings of the other three? If a thermocouple transmitter were connected to this thermocouple, would it affect the readings of the voltmeters? Would it matter whether or not this transmitter were equipped with reference junction compensation? file i00873 Question 13 type K thermocouple is inserted into a process, with a digital multimeter connected to its terminals. The ambient temperature at the DMM s test lead connections is 84 o F. Calculate the thermocouple s measurement junction temperature at the following millivolt measurements (rounding to the nearest degree Fahrenheit): 2.55 m ; T = deg F 6.21 m ; T = 10.93 m ; T = 18.83 m ; T = file i00390 deg F deg F deg F 10

Question 14 type J thermocouple is inserted into a process, with a digital multimeter connected to its terminals. The ambient temperature at the DMM s test lead connections is 17 o C. Calculate the thermocouple s measurement junction temperature at the following millivolt measurements (rounding to the nearest degree Celsius): 5.05 m ; T = deg C 17.82 m ; T = 31.44 m ; T = 40.29 m ; T = file i00379 deg C deg C deg C Question 15 Suppose you walk up to this thermocouple, installed to measure the temperature of an enclosed process vessel, and connect a sensitive voltmeter to the terminals at the junction head: Head (long length of extension cable) Transmitter Z S 4-20 m cable Blu Red m Process vessel Temp =??? OFF COM Determine the process temperature if you read 7.825 millivolts with the voltmeter connected to the screw terminals inside the thermocouple head. ssume a head temperature of 92 o F. Suppose at some later time you connected the voltmeter to the transmitter s input terminals and read 8.332 millivolts. Calculate the process temperature at this time, assuming an ambient temperature of 66 o F at the transmitter. file i03972 11

Question 16 Calculate the appropriate millivoltage values and potentiometer resistances to simulate a thermocouple at the desired temperatures, assuming the ambient temperature at the transmitter is 72 o F and the transmitter has cold junction compensation enabled: Transmitter Z S 4-20 m cable (Configured for type J) 510 kω 1 kω pot 10.000 volts DC power supply T simulate = 550 o F ; input = m ; R pot = Ω T simulate = 300 o F ; input = m ; R pot = Ω T simulate = 150 o F ; input = m ; R pot = Ω file i03657 12

Question 17 Calculate the voltage sensed by the analog-to-digital converter inside the temperature transmitter: Temperature transmitter 75 o F nalog-digital converter Copper cable Type NX cable 1847 o F Type N thermocouple 93 o F file i00357 13

Question 18 Part of this solar-heating control system uses a dual-thermocouple circuit to compare the temperature inside the solar collector against the temperature inside the house, preventing the circulation fan from running if the house is ever warmer than the collector: Sun House Collector Heated air Fan 119 o F 68 o F TC Cold air return TE TE Blu Red Blu Red Red TT nswer the following questions about this subsystem: Identify the thermocouple type used in this application, and determine whether or not this type is a good choice. Calculate the voltage measured at the input terminals of the transmitter, and also determine whether or not this transmitter needs to be enabled for reference junction compensation. Identify the meaning of the diamond-shaped PID symbol labeled TC. file i00377 14

Question 19 This thermocouple is installed improperly: 31 o C Head Red Yel (long length of extension cable) Yellow-colored jacket Transmitter Red Yel Z S 4-20 m cable Yel Red 23 o C Process vessel 592 o C Identify the nature of the problem, and then calculate the millivoltage seen at the screw terminals of the temperature transmitter given the temperatures shown. fter that, calculate the temperature interpreted by the transmitter assuming it has cold junction compensation (CJC) enabled. file i00633 15

nswer 1 nswers ll answers shown here based on tabulated values for the RTD s resistance (rather than values calculated by formula): T = 0 o C ; B = -0.6989 millivolts T = 81 o C ; B = 0.9568 millivolts T = -45 o C ; B = -1.6215 millivolts T = 320 o F ; B = 2.4831 millivolts nswer 2 The α value is most likely 0.00385, resulting in a calculated temperature of 218.96 o C or 426.13 o F. nswer 3 R RTD = 107.256 Ω T = 65 degrees Fahrenheit (from table) T = 65.32 degrees Fahrenheit (from formula) nswer 4 RTD = 88.2 m wire = 0.5 m (each current-carrying conductor) R RTD = 215.12 Ω T = 309 degrees Celsius (from table) T = 299.02 degrees Celsius (from formula) nswer 5 R RTD = 1.617 kω T oven = 160.4 o C = 320.7 o F (calculated from formula, not from a table) The voltage measurements must be taken very soon after the switch is thrown to avoid measurement errors due to self-heating of the RTD. nswer 6 RTD = 140.1 m R RTD = 1167.5 Ω T = 43.5 o C = 110.31 o F (both values calculated from formula, not table) nswer 7 The voltmeter should read -0.643 millivolts, because the 105 o F junction has a potential of 1.635 millivolts, the 77 o F junction has a potential of 0.992 millivolts, and the two junctions voltages are opposing one another in polarity with the positive terminal of the voltmeter connected to the negative-most copper wire. 16

nswer 8 The Law of Intermediate Metals tells us that a series chain of dissimilar metal junctions at the same temperature are electrically equivalent to a single junction comprised of the outer two metals (ignoring all the intermediate metal types between) at that temperature. Thus, the iron-copper-constantan reference junction pair is electrically equivalent to a single iron-constantan reference junction, so long as both screw terminals are at the same temperature (isothermal). This principle renders the meter s metal type irrelevant. nswer 9 The voltmeter should read 3.908 millivolts. Counting all the junction voltages (with polarities shown in reference to whether they match or oppose the meter s test lead polarity): 193 o F junction = 3.789 m 71 o F junction = +0.857 m 102 o F junction = 1.565 m 59 o F junction = +0.589 m Loop total voltage = 3.908 m Hint: any junction pushing conventional flow in a counter-clockwise direction is regarded here as a positive figure. ny junction pushing in a clockwise direction is regarded as a negative figure. The last junction (at 59 o F) may be treated as a single copper-constantan junction because the metal type of the meter s test leads acts as an intermediate metal. The fact that both the copper-testlead and constantantestlead junctions are at the same temperature allows us to disregard the test lead metal altogether and treat it as a single copper-constantan junction at 59 o F. nswer 10 ll answers based on ITS-90 thermocouple table values: T 1 = 589 o F ; T 2 = 63 o F ; T 3 = 70 o F ; meter = 0.463 m T 1 = 821 o F ; T 2 = 69 o F ; T 3 = 73 o F ; meter = 0.953 m T 1 = 1524 o F ; T 2 = 91 o F ; T 3 = 105 o F ; meter = 3.378 m T 1 = 1922 o F ; T 2 = 102 o F ; T 3 = 135 o F ; meter = 5.294 m Note: all temperatures at T 2 are irrelevant because this is a junction between similar metals (type B wires connecting to corresponding type B wires). The reference (cold) junction is where the type B wires connect to copper, at temperature T 3. nswer 11 ll answers based on ITS-90 thermocouple table values: T 1 = 233 o C ; T 2 = 31 o C ; T 3 = 25 o C ; meter = 14.395 m T 1 = 348 o C ; T 2 = 40 o C ; T 3 = 16 o C ; meter = 23.856 m T 1 = 161 o C ; T 2 = 4 o C ; T 3 = 23 o C ; meter = 9.039 m T 1 = 836 o C ; T 2 = 34 o C ; T 3 = 19 o C ; meter = 62.701 m Note: all temperatures at T 2 are irrelevant because this is a junction between similar metals (type E wires connecting to corresponding type EX extension wires). The reference (cold) junction is where the type EX wires connect to copper, at temperature T 3. 17

nswer 12 Each voltmeter forms its own reference junction where the copper wires of each voltmeter connect to the chromel and alumel thermocouple wires. Each voltmeter s reference junction produces its own voltage, opposed in polarity to the voltage of the measurement junction (at 1050 o F). This means we must perform a separate voltage calculation for each voltmeter based on each meter s reference junction temperature. n equivalent schematic diagram shows how the four dissimiar metal junctions relate to one another, and to the three voltmeters: Equivalent circuit showing three voltmeters and the measurement junction: + + 71 o 85 o + 60 o meas + oltmeter oltmeter oltmeter The chromel and alumel wire types identify this as a type K thermocouple, and so we may use a type K thermocouple table to look up voltages for all four junction temperatures: Type K at 1050 o F = 23.439 m Type K at 71 o F = 0.865 m Type K at 85 o F = 1.181 m Type K at 60 o F = 0.619 m Since we know the measurement and reference junctions stand opposed to one another in each voltmeter loop, we may calculate each voltmeter s reading by subtracting the reference junction s voltage from the measurement junction s voltage for each voltmeter: oltage registered by the left-hand voltmeter (at 71 o F): 23.439 m 0.865 m = 22.574 m oltage registered by the center voltmeter (at 85 o F): 23.439 m 1.181 m = 22.258 m oltage registered by the right-hand voltmeter (at 60 o F): 23.439 m 0.619 m = 22.820 m The voltage read by each voltmeter is a simple function of Kirchhoff s oltage Law, with the measurement junction and the voltmeter s reference junction being the only voltage sources in the KL loop. Therefore, connection of a fourth voltmeter will have no effect whatsoever on the other three voltmeters. Likewise, connection of a thermocouple transmitter to this same chromel/alumel wire pair will have no effect on the voltmeters readings, with or without reference junction compensation. 18

nswer 13 ll answers based on ITS-90 thermocouple table values: 2.55 m ; T = 195 deg F 6.21 m ; T = 357 deg F 10.93 m ; T = 567 deg F 18.83 m ; T = 904 deg F nswer 14 ll answers based on ITS-90 thermocouple table values: 5.05 m ; T = 112 deg C 17.82 m ; T = 346 deg C 31.44 m ; T = 586 deg C 40.29 m ; T = 732 deg C 19

nswer 15 n equivalent circuit diagram shows the relationships between the thermocouple measurement junction (in the process), the two reference junctions formed where thermocouple wire meets copper wire, the digital multimeter, and the temperature transmitter (when the DMM is connected at the head): Equivalent circuit with digital multimeter (DMM) connected at head: + + 92 o 66 o process + + comp DMM DC Transmitter T process = 388 deg F at 7.825 millivolts (measured at 92 o F head) nother equivalent circuit diagram shows the relationships between the thermocouple measurement junction (in the process), the two reference junctions formed where thermocouple wire meets copper wire, the digital multimeter, and the temperature transmitter (when the DMM is connected at the transmitter): Equivalent circuit with digital multimeter (DMM) connected at transmitter: + + 66 o 66 o process + + comp DMM DC Transmitter T process = 385 deg F at 8.332 millivolts (measured at 66 o F transmitter terminals) nswer 16 T simulate = 550 o F ; input = 14.516 m ; R pot = 741.39 Ω T simulate = 300 o F ; input = 6.815 m ; R pot = 347.80 Ω T simulate = 150 o F ; input = 2.278 m ; R pot = 116.20 Ω 20

nswer 17 oltage at DC: 35.948 millivolts ccording to an ITS-90 table for type N thermocouples, the measurement junction will generate 36.577 m at 1847 o F, while the reference junction (at the NX-copper cable junction) will generate 0.629 m at 75 o F. Since we know these two junctions voltages are opposed to each other, the voltage seen at the transmitter terminals will be 35.984 m. nswer 18 These are type T thermocouples, sending 1.174 millivolts to the transmitter s input. Cold junction compensation (CJC) should not be enabled in the transmitter, because we want to measure the difference in temperature between the collector and the house, not compensate for one of those thermocouples voltages! The diamond symbol is a logic device most likely a PLC used for on/off control of the fan. nswer 19 The extension wire has been connected backwards to the thermocouple. Yellow should connect to yellow, and red to red! Seeing how the four junctions voltages interact is best done by drawing the circuit with each junction explicitly labeled as to polarity. You will see that the process and reference (transmitter) junctions are aiding each other, and the two junctions formed at the head are opposing the first two (but aiding each other). The formula for calculating voltage at the transmitter screw terminals then becomes: terminals = 592o C + 23o C 31o C 31o C terminals = 24.565 m + 0.919 m 1.244 m 1.244 m terminals = 22.996 m If the transmitter has CJC enabled, it will add 0.919 m to compensate for the reference junction, making the interpreted (measurement junction) voltage equal to 23.915 m. This equates to 577 o C, which is substantially cooler than the real process temperature. 21