SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade



Similar documents
Universal Serial Bus (USB) to DH-485 Interface Converter

MicroLogix 1100 Embedded Web Server

Stratix 5700 Network Address Translation. Quick Start

Logix5000 Controllers Nonvolatile Memory Card

ControlNet Standard and High-flex Coax Cable

RSLogix Guard PLUS! Programming Software

Hard Disk Drive (HDD)

Cloning Utility for Rockwell Automation Industrial Computers

User Manual. DeviceNet Network Configuration

USER GUIDE. Ethernet Configuration Guide (Lantronix) P/N: Rev 6

Micro800 Programmable Controllers. Bulletin 2080 Selection Guide

Logix5000 Controllers Nonvolatile Memory Card

Stratix 5700 Switch Configuration

Installation Guide. FactoryTalk Batch Material Manager Installation Guide

Allen-Bradley/Rockwell

USB-to-Data Highway Plus Cable

Technical Note. Setting ACS drive IP address automatically with Rockwell BOOTP/DHCP Server. Contents

Logix5000 Controllers Security

ControlLogix Remote I/O Communication Module

Hypercom Key Loading and Management (HKLM) RS232 PPP Key Injection PC Setup Guide

Allen-Bradley/Rockwell

CompactLogix Power Supplies Specifications

Fiery Clone Tool For Embedded Servers User Guide

DriveTools SP v5.04 Software Patch

Easy Setup Guide for the Sony Network Camera

Time Recorder Extension Module for the Dynamix 2500 Data Collector

LabelWriter. Print Server. User Guide

TFTP Firmware upgrade

TCP/IP MODULE CA-ETHR-A INSTALLATION MANUAL

ACU-1000 Manual Addendum Replacement of CPM-2 with CPM-4

Application Technique. Safety Function: Magnetic Door Switch Monitoring

MicroLogix 1400 Embedded Web Server

Installation. The product model shown in this QIG is TD-W8961ND, as an example.

CompactLogix 5370 L1 Controllers

Allen-Bradley/Rockwell

Ultra Thin Client TC-401 TC-402. Users s Guide

FactoryTalk ViewPoint Quick Start Guide

Safety Function: Door Monitoring

PowerFlex 20-HIM-A3/-A5/-C3S/-C5S Series C HIM Firmware 6.001

Fiber Optic Cable Installation

Smart Control Center. User Guide. 350 East Plumeria Drive San Jose, CA USA. November v1.0

BiPAC 7404V series. VoIP/(802.11g) ADSL2+ (VPN) Firewall Router. Quick Start Guide

Modicon M340 Firmware

Logix5000 Controllers Function Block Diagram

1-Port Wireless USB 2.0 Print Server Model # APSUSB201W. Quick Installation Guide. Ver. 2A

DATACARD Firmware Update Instructions. Contents. Firmware Update Application for Windows Operating Systems. What You Need

TECHNICAL BULLETIN. Configuring Wireless Settings in an i-stat 1 Wireless Analyzer

VIVA 4G LTE Mini Router. Quick Start Guide

Introduction 1-1 Installing FAS 500 Asset Accounting the First Time 2-1 Installing FAS 500 Asset Accounting: Upgrading from a Prior Version 3-1

Installation. Note The product model shown in this QIG is TD-W8951ND, as an example.

Honeywell Internet Connection Module

Product Compatibility and Download Center

AXIS Camera Station Quick Installation Guide

User Manual. EtherUSB

Quick Installation Guide Network Management Card

Table of Contents. FleetSoft Installation Guide

RouteFinder SOHO. Quick Start Guide. SOHO Security Appliance. EDGE Models RF825-E, RF825-E-AP CDMA Models RF825-C-Nx, RF825-C-Nx-AP

Safety Precautions WARNINGS

Deployment Guide: Transparent Mode

Additional Requirements for ARES-G2 / RSA-G2. One Ethernet 10 Base T/100 Base TX network card required for communication with the instrument.

Cloning Utility for VersaView Industrial Computers

Logix5000 Controllers Import/Export Project Components

UDS2100 Quick Start Guide

Applies to: F1PG200ENau Belkin Analogue Telephone Adapter (ATA) Firmware release notes

Installing an Omnicast System Omnicast version 3.5

Fiery E100 Color Server. Welcome

DeviceNet Communication Card

User Manual. Onsight Management Suite Version 5.1. Another Innovation by Librestream

HWg-STE HWg-STE PoE MANUAL

Modbus RTU (RS-485) TCP/IP (Ethernet)

A6210 WiFi USB Adapter ac USB 3.0 Dual Band User Manual

EPSON Scan Server & EPSON TWAIN Pro Network

Table of Contents. Hardware Installation...7 Push Button Security Using the Setup Wizard Configuration...11 Main Security...

Deposit Direct. Getting Started Guide

Reference Manual. Pressure/Temperature Compensated Flow (P_PTComp) Version 3.1

ON HOLD ANNOUNCER. Once you receive your audio announcer, check the packaging to ensure that all of the following items are enclosed:

N600 WiFi USB Adapter

ControlFLASH Firmware Upgrade Software

FX-BTCVT Bluetooth Commissioning Converter Commissioning Guide

Configuration Manager Wizard

Installation & Licensing Guide. AquiferTest Pro. An Easy-to-Use Pumping Test and Slug Test Data Analysis Package

PL-1, Pocket Logger B

Windows Vista / Windows 7 Installation Guide

VMware Horizon FLEX User Guide

Welch Allyn Vital Signs Monitor 300 Series

EPSON USB/Parallel Adapter User s Guide

FileMover 1.2. Copyright Notice. Trademarks. Patents

Table of Contents. Chapter1. Introduction Before Installation System Requirements... 1

1 Installation. Note: In Windows operating systems, you must be logged in with administrator rights to install the printer driver.

BASLER ACE QUICK INSTALLATION GUIDE

NetDisk & NetDisk Mini

Parallels Transporter Agent

Network/Floating License Installation Instructions

The Wireless LAN (Local Area Network) USB adapter can be operated in one of the two following networking configurations :

Transmitter Interface Program

Wireless-N. User Guide. PCI Adapter WMP300N (EU) WIRELESS. Model No.

COMPRESS Installation Guide

Caplio Utility for Windows

About This Guide SolarEdge Configuration Tool Software Guide. About This Guide

NOTE: PLEASE DO NOT ATTEMPT TO INSTALL THE SOFTWARE BEFORE READING THIS DOCUMENT.

Transcription:

Installation Instructions SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Catalog Numbers 1747-DU501 Topic Page System Requirements 3 Install ControlFLASH 3 Prior to Running ControlFLASH 3 Return the SLC 5/05 Processors to Initial Factory Conditions 4 Use ControlFLASH 5 After Successfully Updating Your SLC 5/05 Processor 16 About This Publication This document provides instructions on how to install the ControlFLASH utility, setup prerequisites for preparing the system for upgrade, and instructions for upgrading your processor to the latest firmware. It does not provide information on how to configure or run applications on the following device: 1747-DU501.

2 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss. ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences. SHOCK HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures. IMPORTANT Identifies information that is critical for successful application and understanding of the product.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 3 Related Publications For Refer to this Document Publication A more detailed description on how to install and use your SLC 500 Modular Hardware Style Control System. A more detailed description on how to install your SLC 500 Modular Processors. A more detailed description on ControlFLASH installation. SLC 500 Modular Hardware Style User Manua SLC 5/03, SLC 5/04, and SLC 5/05 Modular Processors Installation Instructions ControlFlash Firmware Upgrade Software User Manual 1747-UM011 1747-IN009 1756-UM105 To view and download PDF files, go to the Literature Library at http://www.rockwellautomation.com/literature. To order printed copies, contact your Allen-Bradley Distributor or Rockwell Automation Sales Office. System Requirements Personal computer with at least a 486 processor Windows NT, 2000, or XP operating system At least 32 MB of memory or the minimum required by the operating system Ethernet connection to SLC processor Install ControlFLASH Insert the CD-ROM of the ControlFLASH Firmware Upgrade Kit into your CD-ROM drive. The Setup Wizard appears to guide you through the installation process. If a ControlFLASH directory does not yet exist, one is created in your Program Files directory. IMPORTANT If an error is encountered during installation, uninstall the previous ControlFLASH firmware from the computer and try again. Prior to Running ControlFLASH For OS501 Series C FRN 9 and later, the SNMP Server must be enabled for the upgrade to occur. The ability to disable the SNMP Server that was added in Series C FRN 9 and later, requires RSLogix 500 version 6.30 or higher.

4 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 1. Save the current SLC 5/05 processor program. IMPORTANT The user program is cleared as part of the operating system upgrade process. You must restore your program after successfully loading the operating system upgrade. 2. Note the IP address assigned to the SLC 5/05 processor. When updating the processor, use BOOTP or fixed IP address, not DHCP. The IP address may be read from the processor when you are online with RSLogix 500 software. In the Channel Configuration dialog box select the Chan. 1 System tab. If BOOTP Enable is selected and the IP Address is 0.0.0.0, then note the Ethernet Hardware Address (located on the Ethernet Daughtercard) of the 5/05 processor, which begins with 00:00:BC). IMPORTANT Refer to the following Rockwell Automation publications for more information on the Ethernet Communication Protocol: SLC 500 Instruction Set Reference Manual, publication 1747-RM001 SLC 500 Modular Hardware Style User Manual, publication number 1747-UM011 IMPORTANT If you are not sure whether an IP address is assigned or cannot determine what the IP address is, return the 5/05 processor to initial factory conditions. Return the SLC 5/05 Processors to Initial Factory Conditions IMPORTANT If you return the processor to the initial factory conditions, the user program and communication configurations are returned to their default settings. To return the processor to initial factory conditions. ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is removed from the SLC 500 power supply. 1. Remove power from the SLC 500 power supply. 2. Remove the processor from the chassis. 3. Disconnect the battery by removing the battery connector from its socket. 4. Locate the VBB and GND connections on the back of the motherboard. 5. Place a small bladed screwdriver across the VBB and GND connections and hold for 60 seconds.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 5 This returns the processor to the initial factory conditions. GND VBB Use ControlFLASH ATTENTION: Do not interrupt the flash procedure. Once you have begun to download the firmware for either the daughtercard (step 18) or the motherboard (step 24), the SLC 5/05 is put into an unrecoverable state if you lose power or communications for any reason. 1. Launch the ControlFLASH application under Programs>Flash Programming Tools. 2. Verify that the J4 jumper of the SLC 5/05 processor being upgraded is set to Protect. The daughtercard firmware can only be updated when the J4 jumper is set to Protect. SLC 500 PROCESSOR UNIT CAT SER FAC SERIAL NO. PROC. REV. PLACE FRN UPGRADE LABEL HERE OPERATING SYSTEM INFO WHITE OS # SER FRN RED PROTECT + 1-3 PROGRAM BATTERY J4 ) U LISTED IND. CONT. EQ. L FOR HAZ. LOC. A196 SA ) CURRENT REQUIREMENTS: 1A @ 5 VDC 200mA @ 24 VDC CLASS 1, GROUPS A, B, C AND D, DIV. 2 OPERATING TEMPERATURE CODE T3C MADE IN USA

6 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 3. Insert the SLC 5/05 processor into an SLC chassis. 4. Attach an Ethernet cable to the processor from your computer (or a hub). IMPORTANT If you are connecting to the SLC 5/05 processor through a hub, you can use a standard Ethernet patch cable. If you are connecting directly to the SLC 5/05 processor from your computer, you need to use an Ethernet crossover cable. 5. Apply power to the chassis. 6. Verify that the SLC 5/05 processor key switch is in the PROG or REM PROG (RUN LED indicator not illuminated) mode. The Welcome to ControlFLASH dialog box appears. 7. Click Next.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 7 8. Select the appropriate catalog number from the Catalog Number dialog box and click Next. For Series C Processors, select catalog numbers that are followed by a /C. The AB_SNMP.DLL Enter IP Address dialog box appears. 9. Enter the IP address for the processor. IMPORTANT Use the IP address that was noted in step 2 of the section, Prior to Running ControlFLASH on page 3. If the processor has been reset to Initial Factory Conditions, use an available IP address assigned by your network administrator.

8 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 10. Click the Get Info button. If the IP address was previously configured in the processor, go to step 12. The AB_SNMP BOOTP Server dialog box appears, indicating that this IP address has not been configured into the processor. 11. Enter the hardware address of the SLC 5/05 processor that is being upgraded and click OK. The hardware address is noted in step 2 of the section, Prior to Running ControlFLASH, on page 3. The AB_SNMP BOOTP Server Running dialog box may take several seconds or minutes to appear. You may need to wait several seconds or minutes before you are returned to the AB_SNMP.DLL Enter IP Address dialog box. Within a few seconds, the Device Identification box displays the processor s current revision information.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 9 12. Click OK. 13. Select the appropriate revision from the Firmware Revision dialog box and click Next.

10 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade The Summary dialog box appears. 14. Click Finish. The ControlFLASH dialog box appears. 15. Click Yes. If your PC has more than one Ethernet interface installed, the following dialog box displays the assigned IP addresses of each of the listed Ethernet interfaces. Proceed to the next step. If your PC does not have more than one Ethernet interface installed, go to step 18. 16. Highlight the IP address of the PC Ethernet interface that connects to the Ethernet network hosting the target processor.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 11 17. Click OK. 18. You may need to wait several seconds before the Progress dialog box appears. A typical sequence is shown below. While the download is in progress, the ENET LED changes from a solid green to flashing green to solid red and then turns solid green again. When the daughtercard update is complete, the ENET LED flashes green. The download process of the daughtercard firmware can take up to approximately two minutes. 19. When the message Waiting while module burns flash and all progress bars are displayed, check the AB_SNMP dialog box. Open it from your taskbar if it does not appear automatically. The AB_SNMP dialog box prompts you to turn off power, remove the processor, move the jumper to Program, re-insert the processor, and apply power. ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is removed from the SLC 500 power supply 20. Wait for the ENET LED to turn solid green.

12 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 21. Click OK. 22. If your PC has more than one Ethernet interface installed, then the following dialog box displays the assigned IP addresses of each of the listed Ethernet interfaces. Proceed to the next step. If your PC does not have more than one Ethernet interface installed, go to step 24. 23. Highlight the IP address of the PC Ethernet interface that connects to the Ethernet network hosting the target processor. Click OK. 24. The AB_SNMP BOOTP Server Running dialog box may appear. A Progress dialog box is displayed again. A typical sequence is shown starting below. While the download is in progress, the RUN and FLT LED indicators remain off. The other four LED indicators RS232, ENET, FORCE, and BATT turn on and off in a walking bit sequence. When

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 13 the update is complete, these four LED indicators remain on together. The download process of the firmware takes approximately 3 minutes. 25. Open the AB_SNMP dialog box from the task bar if it does not appear automatically. Follow the dialog box prompts to do the following: Verify the LEDs have stopped flashing. Turn off power to the chassis. Remove the processor. ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is removed from the SLC 500 power supply.

14 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Set the motherboard jumper J4 back to Protect. Re-insert the processor. Apply power to the chassis. 26. Once you have re-applied power, wait for the ENET LED indicator to turn solid green. Click OK. The AB_SNMP BOOTP Server Running dialog box may appear. The Update Status dialog box appears. If the update was successful, the status text box is green and has an appropriate message.

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 15 If the update was not successful, the status text box is red and has an appropriate message. 27. Click OK and you are returned to the Welcome to ControlFLASH dialog box. 28. You may either continue upgrading additional SLC 5/05 processors by clicking Next, or you may exit the program by clicking Cancel. If you click Cancel, you are asked to verify that you want to end the update session.

16 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade After Successfully Updating Your SLC 5/05 Processor 1. Remove power from the SLC 500 power supply and remove the processor from the chassis. ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is removed from the SLC 500 power supply. 2. Apply the enclosed operating system upgrade label to the SLC 5/05 processor nameplate. 3. Re-insert the processor into the chassis and apply power. 4. Restore your program to the processor. ControlFLASH Error Messages There are three error messages you can receive. Invalid Catalog Number Target Module Not in Proper State for Programming Failed to Receive Initial TFTP Request from Target Invalid Catalog Number The following error message is displayed if: the ControlFLASH tool is unable to match the processor to the catalog number that was selected in the catalog Number dialog box, or the tool is unable to identify the processor type selected because the J4 jumper is in the Program position. To clear this error: 1. Click OK. 2. Click Cancel to go to the Catalog Number dialog box. You may either: select the correct catalog number in the dialog box, and proceed with the update, or

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 17 power down the processor and check the J4 jumper position. ATTENTION: Do not remove the processor from the SLC 500 chassis until all power is removed from the SLC 500 power supply. 3. Restart the firmware upgrade procedure in the Use ControlFLASH section. Target Module Not in Proper State for Programming The following dialog box appears when this error occurs: To clear this error: 1. Place the SLC 5/05 processor into PROG mode. 2. Ensure that DHCP is not selected. 3. Restart the firmware upgrade process at the beginning of the Use ControlFLASH section. If the error occurs again, power-cycle the SLC 5/05 processor and restart the firmware upgrade process. Failed to Receive Initial TFTP Request from Target The following dialog boxes appear in the sequence shown when this error occurs. To clear this error: 1. Connect the processor s Ethernet port directly to the PC Ethernet port using a crossover cable, or disable or uninstall any firewall VPN or virus protection software running on the PC. 2. Power-cycle the processor. 3. Restart the firmware upgrade process.

18 SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade Notes:

SLC 5/05 Processors Firmware/Operating System ControlFLASH Upgrade 19 Notes:

Rockwell Automation Support Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools. For an additional level of technical phone support for installation, configuration and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/. Installation Assistance If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running. United States or Canada 1.440.646.3434 Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative. New Product Satisfaction Return Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures. United States Outside United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process. Please contact your local Rockwell Automation representative for the return procedure. Documentation Feedback Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Automation, SLC, SLC 500, RSLogix 500, ControlFLASH and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. PN 40071-111-01(7) Supersedes Publication 1747-IN019F-EN-P - August 2008 Copyright 2011 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.