Industrial Steam System Process Control Schemes



Similar documents
Mixing Valves. ARGUS Application Note: Mixing Valves

Schematic Symbols Chart (Design Hydraulic and Pneumatic circits)

Heating Water by Direct Steam Injection

Chapter 10. Control Design: Intuition or Analysis?

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

Commercial Semi-Instantaneous Water Heaters

Basic Symbols. Lines. Circular. Square. Diamond. Miscellaneous Symbols. -continuous line - flow line. -dashed line - pilot, drain

TABLE OF CONTENT

REGULATING VALVE APPLICATIONS

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

COUNTERBALANCE VALVES

How To Clean Up A Reactor Water Cleanup

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

Why and How we Use Capacity Control

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

Example. Fluid Power. Circuits

In-Line Electronic Flow Switches

PROCESS CONTROL SYSTEM DESIGN Process Control System Design. LECTURE 6: SIMO and MISO CONTROL

Frequently Asked Questions

Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing

IGEMA BOILER LEVEL & TDS CONTROLS

Aeration Air & Digester Gas Flow Metering Using Thermal Mass Technology. HWEA 2011 Conference Craig S. Johnson

Steam System Best Practices Condensate System Piping

Basic Hydraulics and Pneumatics

F ox W hi t e Paper. Reduce Energy Costs and Enhance Emissions Monitoring Systems

100DHP TM CCI DRAG Control Valve For High Pressure Turbine Bypass

Pressurized Water Reactor B&W Technology Crosstraining Course Manual. Chapter 9.0. Integrated Control System

Guidelines for operation of minimum flow control valves

Applying Pressure Independent Control Valves in H.V.A.C. Systems. A Presentation to: Orange Empire ASHRAE Santa Ana Nov. 17, 2009

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

VAD. Variable Area Desuperheaters

Material taken from Fluid Power Circuits and Controls, John S. Cundiff, 2001

Process Analysis and Control P&ID Handout Page 1 P&ID SYMBOLS. ISA Symbols and Loop Diagrams

Michael Montgomery Marketing Product Manager Rosemount Inc. Russ Evans Manager of Engineering and Design Rosemount Inc.

CGC s Hybrid System Loop Control

Daniel. Liquid Control Valves Technical Guide. Technical Guide DAN-LIQ-TG-44-rev0813. DAN-LIQ-TG-44-rev0208. February 2008.

The Secret of Hydraulic Schematics. BTPHydraulics

Tips for burner modulation, air/fuel cross-limiting, excess-air regulation, oxygen trim and total heat control

VAD Variable Area Desuperheaters

hance the application of specific components, such as pumps, motors, accumulators, filters, and airline lubricators.

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

REGULATORS D& HD Series

Unit 24: Applications of Pneumatics and Hydraulics

C. starting positive displacement pumps with the discharge valve closed.

Signature and ISX CM870 Fuel System

Pressure and Temperature Controls

VARIABLE VOLUME / VARIABLE SPEED SYSTEMS APPLICATIONS

Building Commissioning

Turbo Tech 101 ( Basic )

Design guidelines for hybrid boiler systems.

Systems Engineering/Process Control L10

Unit 24: Applications of Pneumatics and Hydraulics

Introduction to Process Control Actuators

Electronic Flow Switches

Chapter 5. Components, Symbols, and Circuitry of Air-Conditioning Wiring Diagrams

Sanitary Type Electronic Flow Switches

Improved Modern Control Station for High Pressure Bypass System in Thermal Power Plant

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

SAMPLE CHAPTERS UNESCO EOLSS PID CONTROL. Araki M. Kyoto University, Japan

Using Building Energy Management Systems (BEMS) Best Practice for Energy and Carbon Savings.

EcoDesign & Labelling Directive (ErP)

QNET Experiment #06: HVAC Proportional- Integral (PI) Temperature Control Heating, Ventilation, and Air Conditioning Trainer (HVACT)

HOW TO SELECT A LOW VOLUME (L.V ) BOILER

Using meters to measure steam flow

Tadahiro Yasuda. Introduction. Overview of Criterion D200. Feature Article

TRAINING, EXAMINATION AND CERTIFICATION

HVAC Processes. Lecture 7

HEAT INTERFACE UNITS (Modular)

ISA108 Intelligent Device Management (IDM)

HC900 for Boiler Control Applications

PLC Control Unit for a CSM-C Steam Compact Clean Steam Generator

Grant Agreement No SFERA. Solar Facilities for the European Research Area SEVENTH FRAMEWORK PROGRAMME. Capacities Specific Programme

VOLTAGE REGULATOR AND PARALLEL OPERATION

Commercial Boiler Systems and Controls

1 DESCRIPTION OF THE APPLIANCE

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

Water for Injection (WFI) and Pure Steam Production in a Lean Manufacturing Environment. Larry Zanko Project Manager STERIS Corporation

The Piping System Model a New Life Cycle Document. Elements of the Piping System Model

HOT WATER SYSTEMS CONTENTS

Indirect fired heaters

Water Efficiency. Water Management Options. Boilers. for Commercial, Industrial and Institutional Facilities. Boiler Water Impurities

Perform Common Process Loop Control Algorithms

CCST Exam Preparation Course Syllabus

Enhancing Process Control Education with the Control Station Training Simulator

stable response to load disturbances, e.g., an exothermic reaction.

Printing and Publishing Energy Savings Guide

Fault codes DM1. Industrial engines DC09, DC13, DC16. Marine engines DI09, DI13, DI16 INSTALLATION MANUAL. 03:10 Issue 5.0 en-gb 1

Sizing and Selection of Hot Water Generating Plant. Presentation by: Rob Larner & David Dutch

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R EN - Edition 01-26/10/2009

AN INSTRUMENT FOR GRAVIMETRIC CALIBRATION OF FLOW DEVICES WITH CORROSIVE GASES. J. O. Hylton C. J. Remenyik Oak Ridge National Laboratory *

Dynamic Process Modeling. Process Dynamics and Control

Select the Right Relief Valve - Part 1 Saeid Rahimi

Model 43AP Pneumatic Controller, Style B

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

heat transfer solutions Steam to Water Heat Transfer Packages for Domestic Hot Water

Float and Thermostatic Traps Series H, C and X

Sensing and Control. A Process Control Primer

Chapter 11 SERVO VALVES. Fluid Power Circuits and Controls, John S.Cundiff, 2001

Transcription:

Industrial Steam System Process Control Schemes This paper was developed to provide a basic understanding of the different process control schemes used in a typical steam system. This is however a fundamental overview and the reader should be aware that more in-depth knowledge is required to get the ultimate process control result. The process control schemes that will be discussed are: I. Feedback II. Feedforward III. Back-pressure IV. Ratio V. Cascade VI. Differential Some control systems will have one or more of the above schemes to achieve process control. The applications of the various control schemes are detailed in the typical application examples defined in this fact sheet. The above control schemes can be applied to the following generic applications: I. Temperature II. Flow III. Level IV. Pressure In any control scheme that is applied, there are three elements that must be defined by the user for the control process. I. Process Variable (Sensing device) a.) Flow transmitter b.) Level transmitter Steam System Information 1-1

c.) Pressure transmitter d.) Differential transmitter e.) Temperature transmitter II. Controller a.) Self contained b.) Proportional and Integral (PI) c.) Proportional. Integral, Derivative (PID) III. Output control signal (Final controlling mechanism) a.) Control valve b.) Actuator c.) Or another device This review focuses on control valves, which are used the majority of the time as the final element. The control valve has several classifications. I. Regulating design valve a.) Self contained b.) External pilot operated II. Pneumatic actuated valve a.) Globe design b.) Caged trim c.) Ball In any process control selection, it is important to understand the advantages and disadvantages of each selection. The regulating control valve (regulator) is a device that has a 20 to 1 turndown and limited selections of flow trim characteristics. Steam System Information 1-2

The globe style control valve has 30 to 1 turndown and is a device that can provide a limited number of selections of flow trim characteristics. Flow trim characteristics can be linear, non-linear, or modified equal percentage. Flow trim selection can enhance control of steam flow at varying load demands. The cage trim control valve is the most flexible and probably is the most commonly used for precise steam process control. This valve provides the largest selection of different flow trim characteristics and the highest turn down capabilities (40 to 1). The ball valve has a number of different flow characteristics that can be provided. The flow profile can be changed by the design of the ball (standard, V ball, etc.) The ball valve turn down can be as high as 25 to 1. Symbol Definitions PT = Pressure transmitter FT = Flow transmitter TT = Temperature transmitter CT = Controller R = Ratio CS = Cascade Feedback Control One of the simplest process control schemes used in steam applications is the feedback control scheme (shown below). The advantage of this control scheme is that it is the simplest. It s disadvantage are that it is dependent on a single transmitter sensing a change in flow, pressure, or level to provide the response back to the controller or valve. This control scheme does not take into CT consideration any of the other variables in the process. PT Feedback Control Steam System Information 1-3

Feedback Control (Back pressure application) Feedback control for a steam system backpressure control scheme utilizes another parameter to provide the controller with information on process changes. Backpressure control is used to maintain inlet steam pressure above a predetermined setpoint. Pressure transmitters are located on the inlet and outlet piping which will notify the control that changes are occurring. Consequently, backpressure control is used in conjunction with feedback control. The most common application for a steam system is the elimination of instant high demand for steam from a process that will effect the boiler operation. CT PT PT Feedback for a back pressure application Feed Forward Control Feed forward control uses a secondary input from another variable to assist or provide the controller with the knowledge that various changes are occurring in the process. Flow measurement in pressure reducing applications adds instant identification that a change is occurring. This allows the controller to make corrective actions before a significant temperature or steam pressure change has occurred. Consequently, feed forward control is used in conjunction with feedback control. The feedback loop is used to maintain setpoint control and feed forward is used to compensate for any errors and unmeasured disturbances. One of the most common applications is a pressure transmitter that is used on a shell and tube heat exchanger to sense and feed forward a change in steam pressure. The steam pressure change on the shell side is the CT PT T Feed forward control Steam System Information 1-4

first indication that the temperature (process variable) will change in a very short period of time. Ratio Control Ratio control is a duplex form of feedback control that has two sets of variables, for which the controller calculates a setpoint from the two variables for the control scheme. The object of a ratio control scheme is to keep the ratio of two variables at different values depending on the final objective of the control system. As diagram below indicates, on a pressure control system, the control output to the different valves is ratio depending on the percentage of travel (0-100%) and the pressure transmitter. This type of control scheme is applied when two or more control valves are used in a pressure reducing application. CT R PT Ratio Control Cascade Control Cascade control is widely used within steam process industries. The conventional cascade scheme has two distinct functions with two control loops. Cascade control is used to improve the response of the single feedback strategy. A heat exchanger varying process flow will have different steam requirements depending on the flow. Cascade control understands the requirements and adjusts the output to FT Process flow To a heat exchanger Cascade control CT TT Temperature output Steam System Information 1-5

the control valve according to process flow. The main objective is to achieve the desire output temperature of the process, which is the lead process variable. The idea is similar to that of the feed forward control scheme. Differential Control Differential control is used typically on rotating cylinder dryers because differential pressure is required across the siphoning joint to assist in evacuating the condensate. The use of rotating cylinders is the only process where gravity drainage of condensate is not possible. Therefore, using differential control identifies the parameters of inlet and outlet process pressures and maintains a lower outlet steam pressure, thus achieving the differential. Differential control is also used on other limited heat transfer applications. CT PT PT Differential control Control Actions The controller s output to the final control element (valve or actuator) is accomplish by different methods I. On/off a.) Simplest b.) Least accurate c.) PI (proportional and integral) d.) Medium cost factor e.) Medium accuracy Steam System Information 1-6

II. PID (proportional, integral and derivative) a.) Highest cost b.) Highest accuracy On/Off Control Control schemes using a feedback control parameter can use on/off control. On/off control is the simplest control scheme with the highest degree of inaccuracy. The controller has setpoint with high and low control action points, similar to a home air conditioning or heating system. The thermostat has a desired setpoint and the system is actually operated between two temperature points (on/off). A desired outlet temperature is 180 F and the on/off control would activate the steam valve to heat the product to 185 F. At 185 F, the steam valve would be deactivated and this would allow the process to cool down to 175 F (lower setpoint). The steam would be activated and deactivated between the high and low process setpoints. PI Control PI control will use proportional (proportional to the difference between a setpoint and a process variable) and integral (a totalizing function) algorithm, which provides a continuous control process output to meet the desired setpoint. This is similar to a light dimmer switch versus an on/off light switch. The dimmer mechanism provides a light variable from off to full brightness or anywhere in between. PI controls the steam flow from zero to full flow or anywhere in between on a continuous basis. PID Control PID control has proportional, integral, and derivative algorithms available for use to maintain the setpoint of the process. Steam applications use the proportional and integral part of the PID. The derivative algorithm is used very seldom and then only by someone very experienced in control algorithms. If the heat transfer equipment, control valve, and the controller are properly selected, then proportional and integral are the only parameters required to maintain a highly accurate process result. Applications of Control Schemes Steam Pressure Control Steam System Information 1-7

The majority of industrial steam systems will have a pressure-reducing valve application. High pressure steam is reduced to lower pressure steam for a process or heating application. Used throughout all types of industries, some plants will have from one to over one hundred different pressure-control valves. The feedback control scheme is simply a pressure transmitter or a sensing line coming back to the valve. In a simple regulator type control system for pressure control (shown below), a sensing line is providing the feedback to the external pilot, which is the controlling device. The main valve is the final controlling element. Regulating valve using a feedback control scheme A control valve layout using a pressure transmitter as the feedback sensing device and the controller provides the correct control action (shown below). The pneumatic valve is the final controlling element. Controller using feedback to control a valve Steam System Information 1-8

Many applications require the use of one or more valves to achieve the necessary turndown. Control valves that are used in any type of control scheme should utilize a secondary pressure drop if the control valve is in a sub-critical flow operation. The diagram below shows the use of a simple orifice plate after the control valve to provide a secondary pressure drop. This type of installation has been used for over 60 years. The inlet pressure to the control valve is P1, the pressure between the control valve and the orifice is P2, and the final control point or outlet pressure to the control valve is P3. Orifice plates, when properly sized and installed, prevent the valve from operating at a subcritical flow and causing premature failure. Feedback control with muffling orifice P1 P2 P3 Backpressure Control The backpressure control is a type of feedback control scheme. The typical application is smaller boilers without large steam reservoir capabilities for instant steam load demands. High instantaneous demands for steam can cause unwanted shutdowns of the boiler. Using backpressure control prevents the shut down. A transmitter sensing the inlet pressure to the valve identifies a reduction of pressure beyond the predetermined setpoint and the valve begins to close down to maintain the steam set pressure on the inlet of the valve. This action overrides any pressure requirements or needs on the downstream side of the valve. Backpressure control Steam System Information 1-9

Feedforward Control The following drawing shows a feedforward/feedback control system. The orifice steam flow meter is providing the feedforward information to the controller. The pressure transmitter is providing the feedback to the controller. The pneumatic control valve is the final element. Feedforward control Ratio Control Another way to accomplish the goal of meeting large steam flow requirements is the use of multiple valves. Multiple valves can provide better control in meeting the process requirements. In a two-stage pressure control scheme, the stages use a feedback control scheme and then ratio the controller output to the valves. In the diagram below, the system is the ratio or position of the primary and secondary valve depending on the required flow rates. Parallel positioning valves are quite commonly used in process heating applications where load conditions vary greatly from the very coldest part of the season to the very warmest time of the season. Ratio control Steam System Information 1-10

Differential Control Differential control as shown below provides the condensate removal of a rotating cylinder dryer. This goal is accomplished by maintaining a lower steam pressure (pressure transmitter no. 2) than the inlet steam pressure (pressure transmitter no. 1) Differential control Inlet pressure before dryer outlet pressure after the dryer before receiving tank Heat Transfer Feedback Control Probably the most simple and most common control scheme used in heat transfer is simple feedback control. This is the simplest system, but this control scheme does not account for any upsets or disturbances or unknown factors that might occur in the system and affect the heat transfer process. Steam System Information 1-11

Feedback control on a shell and tube heat exchanger Heat Transfer Feedforward Control This control scheme uses feedback to control temperature, and uses pressure as the feedforward. A disturbance or change in process immediately causes a pressure drop to occur in the heat transfer due to the collapsing of the steam. The steam pressure feedforward anticipates the temperature change at the outlet product flow prior to this occurring. This provides anticipation of process changes. Feedforward control for heat transfer Steam System Information 1-12

Heat Transfer Feedback, Feedforward, Cascade Control The control system in heat transfer can have feedback (temperature) feedforward (steam pressure) and cascade in the product flow into the control scheme. Using all possible variables in the heat transfer control can provide the highest degree of accuracy. Feedback, feedforward, cascade control Feedback Condensate Control Condensate feedback control scheme is used in condensate removal and is typically a simple level transmitter, controller, and control valve. This system is used on a heat transfer application as shown below. In process flow operations where condensate flow rates are 8,000 lbs/hr or higher, steam traps are not recommended. The recommendation is to use a level transmitter, controller, and control valve with a feedback control scheme. This feedback control Feedback condensate control Steam System Information 1-13

scheme gives you the ability to remove the condensate from the heat transfer process on a continuous basis. In these high flow rates, a control valve provides a high degree of accuracy and control in the removal of condensate from heat transfer. Control vs. Cost The ultimate process control scheme is one that provides the system the most information possible, but to do this there is also a cost factor that must be evaluated. The more information being provided to the control scheme, the more cost for the field devices and the more complex the controller, control strategy, wiring, etc. Therefore, the user must understand there is cost justification to consider in identifying the correct control scheme for the process application. Conclusions Control strategies, when evaluated from basic inputs and outputs, are simple and straightforward. Control schemes should be determined based on the control necessary, the cost, and the process. Recommendations 1) Outline your objectives and goals clearly before starting the selection process; 2) Select the correct control scheme for the process; and 3) Select the proper equipment for the application. Steam System Information 1-14