SECTION O FIBER OPTICS



Similar documents
Intelligent Cable Management Systems

FiberGuide Fiber Management Systems. 4th Edition

SECTION COMMUNICATIONS OPTICAL FIBER OSP CABLING

SBC Companies Fiber Distribution Frame Interbay Management Panel Cross-Connect Procedures

SECTION J -- CABLING

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

800 Communications Circuits

ATT-TP Internet Services Cabinet Supported Cable Rack Requirements

Multiple Solutions for Connecting Multiple Dwelling Units (MDUs) WHITE PAPER

4RU High Density Shelf Installation Instructions

Multiple Solutions for Connecting Multiple Dwelling Units (MDUs)

Procedure for Cutting and Respooling Fiber Optic Cable

Underground Cable Installation

Sewing Methods Chicago Style Stitch

Intrabuilding Installation of Corning Cable Systems Fiber Optic Cable

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

Cabinets 101: Configuring A Network Or Server Cabinet

UT Southwestern Medical Center Information Resources Cable Installation Standard

Installation Instructions

BIX Termination Blocks

Patch Cords for Data Center Applications

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

Pretium EDGE HD Solutions

Installation of Rear View Camera in a 1995 Roadtrek 190 Popular

4 Installation Requirements

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Cat7/Class F New Installation Concept New infrastructure. Handbook

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

50 TO 60 INSTALLATION INSTRUCTIONS v1.0

TC Grounding and Bonding for Telecommunications Systems

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

1. Furnish and install faceplate and modular jacks at each single gang outlet as described below:

Data Center. Pre-terminated. Patch Panel System. Cabling Systems Simplified. Patch Panels. 10G + Gigabit. Patch Cords. Plug & Play Installation

Building Telecommunications Infrastructure Requirements

Part Name/Description Part Number Quantity. Power Cable

TubeTrace, ThermoTube

SECTION 22 LIGHTNING PROTECTION SYSTEM

METHOD STATEMENT FOR INSTALLATION OF CABLE TRAY/TRUNKING/LADDER

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

Whitepaper. Modular Substation Cable Termination Design. Author: Allan Bozek P.Eng, MBA, EngWorks Inc, Calgary, Canada

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENTAL SPECIFICATION 804 FIBER OPTIC CABLE FOR TRAFFIC SIGNAL INTERCONNECT JANUARY 19, 2007

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Electrical for Detached Garages: Updated Feb 19, 2016 for 2015 CE Code in force Jan. 1, Underground branch circuit feeding a detached garage:

Optical Cable Pre-Construction Survey. Keywords Stationary Reel Method, empty innerducts, sub-ducts, microducts, Intermediate-feed manholes

Specifying an IT Cabling System

SECTION FIBER OPTIC CABLE AND ACCESSORIES

InstaPATCH ZERO Solution Guide

ADDING AN ELECTRIC AUXILIARY FAN TO RADIATOR STACK ON 03 ALPINE COACH

Massoud Sadeghi: (425) Brett Portwood: (562) Transport Airplane Directorate; ANM-117

Arctic Leash Instruction Manual Alaskan Products Company LLC.

Fiber Optic Cable Installation

TABLE OF CONTENTS. I. TROUBLESHOOTING Section 1.01: Common Problems/Solutions... 2

AM/FM ANTENNA RELOCATION KIT

Reliable, Consistent, Quality

Organizing and Managing Equipment Rooms

The Optical Fiber Ribbon Solution for the 10G to 40/100G Migration

Terminating 25-Pair Cable and 4-Pair Cross Connects

Collocation Types In this document:

Portable Ladder Safety

Navico-Northstar 2kW JRC Radar Package, Scanner Cable Removal and Replacement

Pretium Connector Housings

INSTALL INSTRUCTIONS KK-C-HVAC-1 HVAC UNIT CHEVROLET/GMC VANS FOR

Cable Preparation and Pulling Procedure Best Practices for Fiber Optic Indoor Tight-Buffered Cable

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

SECTION TELECOMMUNICATION ROOMS

Cable management for rack-mounted systems

BID TABULATION Fiber Optic Cable Materials Bid # March 16, 2011 at 11:00 am CDT

Auto-belay Cable Replacement Process

Versatile, Scalable Cable Protection in Data Centers and Central Offices

Managing High-Density Fiber in the Data Center: Three Real-World Case Studies

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Application Note Optical Fiber Cable

BIX Cross-Connect System Distribution Connectors, Multiplying Connectors and Modular Jack Connectors

COYOTE PUP CLOSURE FOR UNDERGROUND, AERIAL, AND BURIED SPLICES 6.0" x 17" (152.4 mm x mm)

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

StorMax Cable and Interconnect Installation Instructions

Excerpts from the Canadian National Building Code (NBC)

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

User Manual. Instructions for installing the Sure Stitch on the Next Generation Quilting Frame. Parts Included:

AN IN-DEPTH LOOK AT 2011 NEC ARTICLE CABLE TRAY. (The following code explanations are to be used with a copy of the 2011 NEC.

Specifications for Communication Cabling Distribution Systems

Cable Routing System Versatile, Scalable Cable Protection in Data Centers and Central Offices

SECTION SIGNAL WIRE AND CABLE

Please check with your local inspection authority for any additional requirements before installation.

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

COMMERCIAL CONDUIT RULES AND REGULATION

TELECOMMUNICATIONS NETWORK STANDARDS AND GUIDELINES FOR THE NEW ADMINISTRATION BULDING

Cisco Aironet 2.4-GHz MIMO Wall-Mounted Omnidirectional Antenna (AIR-ANT2440NV-R)

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

Cabling Services (price per pull) Zone 1 Zone 2 Zone 3 Zone 4 Zone 5

1 Campus Cabling Systems Introduction

This presentation to be used in conjunction with:

Installing the Sno-free Standing Seam System for Metal Roofs

Transcription:

SECTION O FIBER OPTICS CONTENTS PAGE 1. GENERAL...O-2 1.1 Introduction...O-2 1.2 Definitions...O-2 1.3 Requirements...O-2 2. RUNNING, SECURING AND FIRESTOPPING FIBER OPTIC CABLE...O-3 2.1 Running Fiber Optic Cable...O-3 2.2 OFNR Cabling - Raised Floor Environments...O-5 3. FIBER OPTIC CABLING FROM VAULT TO FDF...O-5 4. FIBER OPTIC PATCHCORDS AND JUMPERS...O-6 4.1 Requirements...O-6 TABLE O-1 SUMMARY OF CHANGES IN SECTION O Revision Date Item Action Requirements Change Notification 03/11/2016 Entire Document Modification N/A; March 2016 TP76300 Rewrite 06/01/2016 4.1.11 Addition ATT-TP-76300-348 06/01/2016 2.1.4 Modification ATT-TP-76300-349 07/01/2016 2.1.4 Modification ATT-TP-76300-351 08/01/2016 2.1.4 Modification ATT-TP-76300-360 O-1

March, 2016 INSTALLATION REQUIREMENTS AT&T 1. GENERAL 1.1 Introduction 1.1.1 The Installation Supplier shall ensure, as part of the evaluation of the installation, that all equipment added, rearranged or modified is properly installed and in conformance with AT&T installation specifications. 1.1.2 The Installation Supplier shall ensure, as part of the evaluation of the installation, that all work has been done in accordance with the detail specifications or approved changes to the detail specifications. 1.1.3 This section covers AT&T requirements for running and terminating fiber optic cables and jumpers. 1.1.4 Changes in this issue of Section O are summarized in Table O-1. 1.2 Definitions 1.2.1 Fiber Optic Cable Premise Fiber Optic Cable is intended for indoor use within an environmental structure (i.e. home, commercial, or industrial building) to carry optical signals from place to place within the structure. There are two types of Premise cable and they are as follows: 1. Trunk Cable: Trunk cable is a stiff jacketed multi-stranded cable consisting of two or more fibers, typically used in a horizontal and distribution configuration, i.e. Optical Fiber Non-conductive Riser (OFNR) or Optical Fiber Non-conductive Plenum (OFNP). 2. Equipment Cord Cable: Equipment Cord cable is either one or two fibers often referred to as Simplex (a single fiber internal to one sheath) or Duplex (two individually sheathed fibers bonded together in a "zip cord" style), and is commonly refer to as either a jumper or a patch cord. The functional difference between a jumper and a patch cord is defined as follows: Patch Cord A connection between the rear of an FOT panel and a Network Element. Jumper A connection within the FDF complex between panels i.e. FOT to FOT, FOT to OSP, etc. 1.3 Requirements 1.3.1 The entire length of a polyethylene sheathed fiber optic cable run shall be placed on ladder type cable rack. 1.3.2 The Installation Supplier shall not install innerduct for use with polyethylene sheathed fiber optic cable in AT&T Equipment areas. 1.3.3 The AT&T approved Fiber Protection System (FPS) shall not be run through floor penetrations or fire rated walls. O-2

1.3.4 All fiber optic connections shall be made in a manner that provides proper operation and functionality of the equipment. 2. RUNNING, SECURING AND FIRESTOPPING FIBER OPTIC CABLE 2.1 Running Fiber Optic Cable 2.1.1 When the fiber optic cable enters the building in conduit, any slack shall be stored in the cable vault or cable entrance facility area, so that the cable can be pulled back and reterminated or spliced. 2.1.2 Whenever the building has no cable vault, any fiber optic cable slack shall be stored at the entrance facility. The stored length shall not exceed 50 feet. If the fiber optic cable has metallic strength members or a metallic shield, no more than fifty (50) feet of cable shall be pulled into the AT&T Equipment areas. 2.1.3 When the fiber optic cable is direct buried and does not enter the AT&T Equipment areas in conduit and, it cannot be pulled back into the first manhole, slack shall not be stored in the cable vault or cable entrance facility. 2.1.4 Fiber optic cable shall be run on either cable rack, basket rack or in metallic/terra cotta conduit throughout the AT&T facility. All horizontal cable rack shall be panned and horned which will allow the fiber to no longer be tied down on all new installations of cable racking and there is no need to upgrade any pre-existing racking with panning unless directed to do so by the IE. When cables are run on a vertical cable rack, cables shall be secured every strap (rung) and to the rungs only. When running cables on panned rack it is required that the cables be bundled together every 6 feet in order to keep the cables running straight. The use of Y / U horns and L brackets is no longer permitted except under the following conditions and when securing the fibers it should be done on every third horn: a) In smaller offices like Huts the use of compartment horns is permitted where installing cable racking is cost prohibitive b) In those locations such as Legacy-T offices that don t have any dedicated fiber cable racking and use the compartment horn exclusively for their routing needs. c) In those locations where there are pre-existing cable runs on compartment horns it is permitted to use these runs until they become exhausted. Note: In all locations where cable is still run on open ladder cable rack the previous method of securing the cable with wax cord every 4th rung shall still apply and used. 2.1.5 Polyethylene sheathed fiber optic cable (not to be confused with fiber optic patch cords or jumpers) shall not be placed in any fiber raceway/duct work of the fiber protection system. Note: Where cables have been run from the LGX to either the splice box or vault and the run is using a dedicated Fiber Protection System (FPS) it is permitted to follow the existing method and mark the FPS as (FIBER CABLES ONLY NO JUMPERS OR PATCH CORDS) O-3

March, 2016 INSTALLATION REQUIREMENTS AT&T AND NO WAIVER IS REQUIRED. The FPS should be inspected to insure that it has been supported properly to handle any additional weight of the cable. These cables are also subject to all bending radius standard requirements and to the capacity rules for an FPS. 2.1.6 All OSP cable entering a building, for more than 50 feet, that is not riser rated shall transition to an approved riser rated cable at the CEF or be placed in a fire stopped metallic or terra cotta conduit or approved fire rated inner duct prior to leaving the CEF. 2.1.7 Fiber cable shall not be run on dedicated primary power cable racks. 2.1.8 The cable shall be run straight on the cable rack and shall not hang off the side or run across an open area. 2.1.9 Fiber optic cable connectors shall be covered and protected with the manufacturer s dust caps during installation. 2.1.10 Fiber optic cables shall be installed and/or secured in a manner that protects them from damage. a) The Installation Supplier installing fiber optic cable (OFNR,OFNP, or equivalent) shall inspect and clean, if required, all connector fiber end-faces per the requirements detailed in the TP76417 prior to terminating connectors into bulkheads on FOT panels, Parking lot panels (PLP) or mating with another inspected (per the TP76417 provisions) fiber connector. 2.1.11 The Installation Supplier shall utilize cable clamps and grommets to secure all fiber optic cables terminating between Fiber Distributing Frames (FDF) or between FDFs and Network Elements. Clamps and grommets shall be attached to the terminating shelf if there is a designated place on the shelf itself to do so. If there is no designated place on the terminating shelf, then the clamp and grommet shall be placed on the bay upright. Multiple clamps and grommets may be used if necessary to facilitate proper cable slack management. When the bay/cabinet will not accept a clamp and grommet method it is permissible to use the wax cord and the fiber paper method of securing the cables. Note the first choice is always the use of clamps and there is no waiver required when using the wax cord method. Note-1: Multiple cables of like size counts can be placed under one clamp only if there is sufficient space for the two or more cables and the bending radius is not compromised, the cables are not crushed or pinched. Note-2: When using/running small count cables such as 2 & 4 count and a clamp cannot be obtained to secure such a cable then it is permitted to secure such cables using wax cord method. 2.1.12 Optical Fiber Non-conductive Riser (OFNR) cable leaving cable racks and entering frames, racks or other equipment shall be supported at least every 3 feet. 2.1.13 On vertical runs, the cable shall be secured at every strap. 2.1.14 Horizontal runs of cable on cable racks shall be secured at every 4th strap to maintain a straight run, and flow of the bends. 2.1.15 The cable shall be secured at points of break off from the cable rack. O-4

2.1.16 The maximum amount of fiber cables allowed to be secured i.e. stitched/strapped together are as follows: a) Fiber counts of 2 to 6 per cable are allowed to have up to 10 cables. b) Fiber counts of 8 to 36 per cable are allowed to have up to 5 cables. c) Fiber counts above 36 fibers per cable are allowed to have no more than 2 cables. d) The "micro" cables used with the T.E. connectivity Rapid Panel can have up to 12 cables. 2.1.17 Plastic tie wraps shall not be used to secure fiber optic cable inside the building. 2.1.18 No more than 10ft of slack is permitted for fiber cable runs over 100ft with the exception that the next rounded up 5ft increment is allowed to be added to the overall jumper length, (for example a 153ft or 154ft cable run is acceptable with an overall jumper length of up to 165ft). On fiber cable runs of less than 100ft, allowable slack shall be no more than 10% of the overall length of the run or rounded up to the next 5ft increment. This is especially true on cables of less than 50ft. 2.1.19 When securing OFNR cable, a minimum of two wraps of sheet fiber shall be placed around the fiber cable at each securing point. 2.2 OFNR Cabling - Raised Floor Environments 2.2.1 OFNR cable shall not be laid directly on a slab floor. 2.2.2 OFNR cable shall be run on or in its own dedicated medium. Acceptable mediums for OFNR cable in raised floor environments shall include but are not limited to cable racking, troughing, raceway, wire baskets or some other acceptable facsimile thereof which AT&T has approved. Note: In those locations where the OFNR cables were previously tied to the floor stanchion and there is no physical way to install a cable support medium then it is permitted to install the cables in the same manner, securing to the stanchions, without a waiver. 2.2.3 OFNR cable mediums shall be mounted to the floor stanchion or directly/indirectly to the slab floor. a) When mounting to floor stanchions, the medium shall be located 6 to 8 below the floor tile. 2.2.4 Fiber optic cabling paths shall be in 90 degree angle configurations and parallel to the floor stanchions and floor tiles. 3. FIBER OPTIC CABLING FROM VAULT TO FDF The following procedures apply to fiber cable run between the cable entrance facility and FDF: a) Traditional OSP Cable This cable shall be run in flexible, plastic, fire retardant innerduct, unless local fire or building codes dictate differently. Innerduct can be corrugated or smoothed walled. It is an NEC code requirement to install OSP cable in fire retardant inner duct when the cable enters a building. O-5

March, 2016 INSTALLATION REQUIREMENTS AT&T Note: when inner duct is used, it shall be properly fire stopped at the open ends and where it penetrates any fire rated wall, floor or cable penetration. b) OFNR Cable OFNR/OFNP Cable OFNR/OFNP cable shall not be run in innerduct. If OFNR/OFNP cable is installed in such a manner which causes the cable to free fall three or more floors, then a Kellum grip type of strain relief shall be used to support the cable. c) Indoor/outdoor cable shall follow the same guidelines outlined for OFNR/OFNP cable. Note: when securing this type of cable a fiber paper wrap is NOT required. d) FDF PANEL DIVERSITY When cabling from the vault into a location and the cables are routed diversely to the FDF, it is an acceptable practice to terminate these cables within the same bay as long as these cables are terminated in separate FDF shelves. These cables shall be routed on opposite sides of the bay. In the event a pre-terminated shelf is being used then there could be a situation where both cables will be running on the same side of bay. This is ok as long as the cables take diverse routes after leaving the bay. 4. FIBER OPTIC PATCHCORDS AND JUMPERS 4.1 Requirements 4.1.1 Fiber optic patch cords shall not be run on cable racks. 4.1.2 Fiber optic patch cords shall be run in AT&T approved fiber protection system (FPS). The following requirements apply to the installation of fiber protection systems: a) Solid-walled FPS shall be used for horizontal runs. Covers on horizontal sections of FPS are not required. All non-horizontal FPS shall have covers. End Caps shall be required at the ends of all FPS. b) Framework mounted vertical FPS shall be placed with covers facing the aisle. c) Drop options from an FPS to a N.E. frame shall only be accomplished via the use of a rigid arrangement or a corrugated split tube arrangement. d) Installation supplier shall maintain proper bend radius and cable management within the bay footprint. e) Split flex tube shall not extend more than 3 inches into any fiber management system. 4.1.3 Fiber optic equipment cords shall be ordered in the near correct lengths in order to interconnect between FDF panels or FDF panels and network elements. Fiber jumper slack shall be conditional as follows: a) No more than 10ft of slack is permitted for fiber runs over 100ft with the exception that the next rounded up 5ft increment is allowed to be added to the overall jumper length when necessary to account for adequate service loop slack (for example a 153ft or 154ft jumper run is acceptable with an overall jumper length of up to 165ft). b) On fiber runs of less than100ft, allowable slack shall be no more than 10% of the overall length of the run or rounded up to the next 5ft increment. This is especially true on jumpers/patch cords of less than 50ft. O-6

c) Excess fiber patch cord slack shall NOT be stored in the FPS. d) Under no condition, unless for testing or trouble shooting purposes, shall fibers be left UNTERMINATED at any Fiber Optic Termination Panel (FTP). Temporary patches or loop backs setup for testing or trouble shooting purposes shall remain in place at the discretion of GNFO. In these cases, a tag must be applied with the OTV name, order number and date. When any fiber is removed (unterminated) for testing or trouble shooting purposes, a dust cap shall be placed over the end of the fiber as well as in the vacated jack/port position. Spare fibers requested by the telco order are permitted and shall be left in place as appropriate. e) The following applies to spare fibers: 1. Spare fibers shall only be at the request of the IE via the TEO and shall be tagged, protected and secured as appropriate. OTV shall size the fiber cable to be as close to the desired number of fibers as possible. 2. The OTV shall never cut off spare fibers in a cable. 4.1.4 Protective/dust caps shall be placed on all unterminated fiber cables and fiber termination points. 4.1.5 Fiber inspection, cleaning, testing and documentation reporting requirements shall be adhered to per ATT-TP-76461 and ATT-TP-76417. 4.1.6 Vertical sections of FPS placed on frame upright shall have support brackets at the top, middle and bottom. 4.1.7 In the event a previously installed FPS that contains fibers must be cut, the section(s) involved shall be removed from their previously installed position and ALL fibers shall be supported and protected before any cutting can be done. 4.1.8 The cutting of installed FPS is to be considered Volatile Work Activity and shall be performed during the Maintenance Window. 4.1.9 There are no drop length requirements for unsupported patch cords transitioning from the FPS to the network element. 4.1.10 Mining of fiber from an FPS shall not be permitted unless the fibers can be readily identifiable with no risk to network service. A minimum of two individuals shall perform that removal operation. The utmost care and discretion shall be observed as any Fiber Protection System will always be carrying live service. At no time shall a jumper/patch cord be pulled through an FPS system with the connector still on it. O-7

March, 2016 INSTALLATION REQUIREMENTS AT&T 1. If it becomes necessary to remove jumpers or patch cords from the vertical of a bay or Fiber Distribution Bay (FDB) the following procedure shall be used. 2. The fiber shall be fully identified at both ends. 3. The fiber shall be removed from the vertical fiber manager and traced up and into the horizontal FPS. 4. While still holding onto the fiber, it shall be traced into the horizontal a minimum of 6 inches and then cut at that point. 5. The remaining end of the jumper or patch cord shall be left as flat as possible within the FPS, horizontal to the remaining fibers. 6. The remaining end of the jumper or patch cord shall not be looped back into the FPS. 7. The other end of the fiber shall be treated the same way as defined in steps 1 5. 4.1.11 Fiber optic patch cords shall be run in dedicated troughs of fiber protection systems. New fiber raceways shall be installed using the AT&T approved fiber protection system. The following requirements apply to the installation of fiber protection systems: a) Each vertical drop from the rigid downspout going to the bay shall be placed within two inches of the top of the bay. If the distance from the overhead FPS down to the bay level, either to a vertical FPS attached to the bay or to some other type of fiber management system, i.e. Glide or IMP, is greater than 2 inches, the installation supplier may utilize the methods out lined in the Section B. Note: The first choice is always a RIGID VERTICAL FPS. b) When utilizing corrugated split tubing as a drop option from the overhead FPS down to the bay level, either to a vertical FPS attached to the bay or to some other type of fiber management system, i.e. Glide or IMP, it shall be secured at both the entrance and exit points of the split tube. Where the corrugated split tube meets the vertical FPS on the side of the bay or at some other type of fiber management system, i.e. Glide or IMP, at the bay level, the split tube may be secured with pop rivets, nuts and bolts or waxed cord. When utilizing waxed cord, holes shall be drilled through the split tube and FPS and the wax cord shall be sewn on the inside of the split tube to secure the split tube. All of the above methods will allow the split tube to be used for ongoing growth (see Figure below for wax cord placement). Bolts shall be installed with the head of the bolt on the inside of the tubing and the nut on the outside of the FPS duct. Enough of the tubing must penetrate the FPS duct to eliminate any sharp bends; however, the tubing shall never be allowed to block any of the cable runs. When utilizing corrugated tubing (i.e. Split tube) as a drop option from the overhead FPS down to the bay level, either to a vertical FPS attached to the bay or to some other type of fiber management system, i.e. Glide or IMP, the overall length of split tube shall not exceed 36 inches. Split tube shall not be used with a trumpet flare. O-8

[ END OF SECTION ] O-9