Calculation of the Current Transformer Accuracy Limit Factor Application Note



Similar documents
Disturbance Recoder SPCR 8C27. Product Guide

Lifecycle Service Tool. Operator's manual

Voltage Regulator SPAU 341 C. Product Guide

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

PROPER SELECTION OF CONTROL CIRCUIT TRANSFORMERS WHITE PAPER BULLETIN 1497, 1497A, AND 1497B

Vrieswijk, T & Srinivasan,A Amerongen,NL, 25 januari 2012

CURRENT TRANSFORMERS INSTALLATION GUIDE

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

AC 800M. EtherNet/IP DeviceNet Linking Device LD 800DN. Power and productivity for a better world TM SP1134

Objectives 200 CHAPTER 4 RESISTANCE

Cable Size Selection for Energy Efficiency

Physics 3330 Experiment #2 Fall DC techniques, dividers, and bridges R 2 =(1-S)R P R 1 =SR P. R P =10kΩ 10-turn pot.

Capacitor Protection Relay SPAJ 160 C. Product Guide

Protect IT MNS Motor Management INSUM. MPU - Multi Purpose Unit. - Catalogue - ABB

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

Type SA-1 Generator Differential Relay

KOLMA and IHDA Indoor type Cable Current Transformers Catalogue ABB Power Distribution ABB Transmit 1 KKOLMA 1 GB

STUDY MATERIAL FOR CLASS Physics- CURRENT ELECTRICITY. The flow of electric charges in a particular direction constitutes electric current.

INSTRUCTION MANUAL. SIGNAL AMPLIFIER 4-20 ma

Transformer circuit calculations

Tape Wound, Split Core and Ebony Current Transformers

CT Application Guide for the 489 Generator Management Relay

Resistors. Some substances are insulators. A battery will not make detectible current flow through them.

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Current and Temperature Ratings

Instrument Transformers Application Guide

Tape Wound, Split Core and Ebony Current Transformers

Brush DC Motor Basics. by Simon Pata Business Unit Manager, Brushless DC

LOW-VOLTAGE CURRENT TRANSFORMERS

HIGH VOLTAGE LABORATORY INSTYTUT ENERGETYKI

CURRENT ELECTRICITY - I

Current Transformers

Enhanced Quality with a Touch of Style

EARTHING SYSTEM CALCULATION

The Electrical Properties of Materials: Resistivity

Resistivity. V A = R = L ρ (1)

Field Information Manager Product guide. Field Information Manager version 1.1

Vimpex Volt Drop Calculator

7. What is the current in a circuit if 15 coulombs of electric charge move past a given point in 3 seconds? (1) 5 A (3) 18 A (2) 12 A (4) 45 A

Transformers. Special transformers Reactors products

PREDICTING THE THERMAL CONDUCTIVITY OF ALUMINIUM ALLOYS AT CRYOGENIC TEMPERATURES. 1 Introduction. 2 The Problem

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

CT Analyzer: Coming to the Rescue. Introduction. Equivalent Circuit. Construction. Classification of a CT. Tony Porrelli, OMICRON, UK

DC RESISTANCE TEST AND WEIGHT MEASUREMENT TEST ON PRAGUE ACCC/TW CONDUCTOR STRANDED BY PT KMI WIRE AND CABLE Tbk COMPANY

CAP 501. User s Guide

Medium-voltage transformers

Using Current Transformers with the 78M661x

Measuring temperature with Resistance Temperature Detectors (RTD) (e.g., Pt100) and thermocouples

Assessment of Soil Resistivity on Grounding of Electrical Systems: A Case Study of North-East Zone, Nigeria

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

Current, Resistance and Electromotive Force. Young and Freedman Chapter 25

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

Substation Monitoring System SMS 510. Product Guide

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Temperature Rise Testing of Current Transformers: Improvement in Test Method

Pi LVDT and LVDT Amplifier APPLICATION NOTE

Waveguide Access Point WGA631. Product Guide

THE PER-UNIT SYSTEM. (2) The per-unit values for various components lie within a narrow range regardless of the equipment rating.

Relion. Power system protection and automation reference Fast substation busbar protection with IEC and GOOSE

T Substation Maintenance and Commissioning Test Equipment

AS COMPETITION PAPER 2007 SOLUTIONS

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

Pilot-wire differential relay for lines with two or more terminals

Modeling of Transmission Lines

6 ELECTRICAL PARAMETERS

Review Questions PHYS 2426 Exam 2

Guidance for upgrading to GB (IEC : 2005, MOD)

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

Resistance, Ohm s Law, and the Temperature of a Light Bulb Filament

Copyrights 2010 Victron Energy B.V. All Rights Reserved

Current transformer selection guide

RM4TG20 three-phase network control relay RM4-T - range V

DCMS DC MOTOR SYSTEM User Manual

ACTIV-8 PLUS Insulated Conductor Bar

WHITEPAPER CABLE CONDUCTOR SIZING

Ground Resistance Clamp-On Tester

3M High Flex Life Cable.050" 28 AWG Stranded, PVC 3319 Series

C13 User Manual Document ID: 2CMC486004M0201 Revision: A

Fault location on power cables. Fault location on power cables

vacon 100 vacon 100 flow vacon 100 hvac ac drives installation manual wall-mounted drives

ABB Drives. User s Manual. Pulse Encoder Interface Module RTAC-01

Remote Monitoring and REC 501 Control Unit Product Guide

Voltage Loss Formula s

Chapter 14: Inductor design

Product Data Sheet 3M Mini-Clamp II Plug and Socket Wiremount Connectors

Current Transformers Ratio / Polarity / Types


Modular I/O System Analog and Digital Interface Modules

Electrical Resistance Resistance (R)

Errors Related to Cable Resistance Imbalance in Three Wire RTDs

9. Force Measurement with a Strain gage Bridge

AC Transport constant current vs. low impedance modes

Low Voltage Switchgear MNS is with MSpeed

Subject: Glenair MIL-PRF Conduit Surface Transfer Impedance Test

ELECTRIC FIELD LINES AND EQUIPOTENTIAL SURFACES

How To Use A Cdm250 Digital Multimeter

Transcription:

Calculation of the Current Transformer Application Note kansikuva_bw

1MRS 755481 Issued: 09.11.2004 Version: A/09.11.2004 Calculation of the Current Transformer Application Note Contents: 1. Scope...4 2. Introduction...5 3. Technical implementation...6 3.1. Calculation of the CT burden...6 3.1.1. Resistance of a conductor...6 3.1.1.1. Resistance at higher temperatures...6 3.1.1.2. 4- or 6-wire connection...7 3.1.2. Burden of the relay...7 3.1.3. Example...8 3.2. Calculation of the actual accuracy limit factor...8 3.2.1. Example...8 3.2.2. Alternative method...9 4. References...10 5. List of symbols...11 Copyrights The information in this document is subject to change without notice and should not be construed as a commitment by ABB Oy. ABB Oy assumes no responsibility for any errors that may appear in this document. In no event shall ABB Oy be liable for direct, indirect, special, incidental or consequential damages of any nature or kind arising from the use of this document, nor shall ABB Oy be liable for incidental or consequential damages arising from use of any software or hardware described in this document. This document and parts thereof must not be reproduced or copied without written permission from ABB Oy, and the contents thereof must not be imparted to a third party nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license. Copyright 2004 ABB Oy All rights reserved. Copyright 2004 ABB Oy, Distribution Automation, Vaasa, FINLAND 3

Calculation of the Current Transformer 1MRS 755481 1. Scope This document describes the calculation of the actual accuracy limit factor (F a ) for protection-type (P) current transformers (CT). First, the calculation of the actual burden of the CT, including connection wires and protection relay impedance, is presented. Then, two alternative methods for calculating F a are shown. All calculation principles and equations are illustrated with an example. The rules presented are generally used and apply, for example, to protection calculation of SPACOM and RED 500 series protection relays. KEYWORDS: current transformer, accuracy limit factor, accuracy limit primary current. 4

1MRS 755481 Calculation of the Current Transformer 2. Introduction The rated accuracy limit factor (F n ) is the ratio of the rated accuracy limit primary current to the rated primary current. A protective current transformer type 5P10 has, for example, the accuracy class 5P and the rated accuracy limit factor 10. For protective current transformers, the accuracy class is determined by the highest permissible percentage composite error at the rated accuracy limit primary current specified for the accuracy class concerned, followed by the letter P (referring to protection). The CT accuracy primary limit current defines the highest fault current magnitude at which the CT will meet the specified accuracy. Beyond this level, the secondary current of the CT will be distorted, and this may have severe effects on the performance of the protection relay. In practise, the actual accuracy limit factor (F a ) differs from the rated accuracy limit factor (F n ) and is proportional to the ratio of the rated CT burden and the actual CT burden. For the reliable and correct operation of the protection relays, the current transformer (CT) has to be carefully chosen. The distortion of the secondary current of a saturated CT may endanger the operation, selectivity and co-ordination of the protection. A correctly selected CT, on the other hand, enables fast and reliable protection. 5

Calculation of the Current Transformer 1MRS 755481 3. Technical implementation 3.1. Calculation of the CT burden The actual burden is formed by the resistance of the pilot conductors and the protection relay(s). 3.1.1. Resistance of a conductor The resistance of a conductor (with a constant cross-sectional area) can be calculated from the equation: R = ρ x l/a (1) where ρ = resistivity of the conductor material (given typically at +20 C) l = length of the conductor A = cross-sectional area If the resistivity is given in µωm, the length in metres and the area in mm 2, the equation 1 will give the resistance directly in ohms. The resistivity and temperature coefficient for copper is given in table 3.1.1.-1 Table 3.1.1-1 3.1.1.1. Resistance at higher temperatures Resistivity and temperature coefficient for copper (Cu) Material Resistivity ρ (+20 C) Resistivity ρ (+75 C) Temp. coefficient α Copper 0.0178 µωm 0.0216 µωm 0.0039 1/K The resistance is temperature-dependent: when the temperature rises, the resistance will increase. Therefore, the resistance of a conductor should be calculated at the worst-case temperature. Normally +75 C is used for calculations. For pure metals like copper and aluminium the dependence is almost linear in quite a wide temperature range (-50...+200 C). The resistance at a certain temperature T 2 is calculated as follows: R 2 = R 1 x [1+α(T 2 -T 1 )] (2) where R 1 = resistance at temperature T 1 α = temperature coefficient of the conductor material T 1, T 2 = temperatures in Kelvin (20 C = 293.15 K) The resistance per cable length at +75 C for copper is given in the table 3.1.1.1-1 and in the figure 3.1.1.1-1. Table 3.1.1.1-1 Resistance per cable length (+75 C) for copper Material 2.5 mm 2 4 mm 2 6 mm 2 Copper 0.00865 Ω/m 0.00541 Ω/m 0.00360 Ω/m 6

1MRS 755481 Calculation of the Current Transformer Conductor wire resistance (copper) Resistance in 75 C (ohms) 0.20 0.15 0.10 0.05 0.00 2.5 mm 2 4 mm 2 6 mm 2 0 2.5 5 7.5 10 12.5 15 17.5 20 Length of the conductor (metres) Fig. 3.1.1.1.-1 Resistance per cable length (+75 C) for copper (Cu). 3.1.1.2. 4- or 6-wire connection If 6-wire connection is used, the total length of the wire, naturally, will be two times the distance between the CT and the relay. However, in many cases a common return conductor is used (figure 3.1.1.2-1). Then, instead of multiplying the distance by two, a factor of 1.2 is typically used. This rule only applies to the 3-phase connection. The factor 1.2 allows for a situation, where up to 20% of the electrical conductor length, including terminal resistances, uses 6-wire connection and at least 80% 4-wire connection. 3.1.2. Burden of the relay Fig. 3.1.1.2.-1 CT connections, 6-wire and 4-wire (common return conductor) If, for example, the distance between the CT and the relay is 5 metres the total length is 2 x 5 m = 10 metre for 6-wire connection, but only 1.2 x 5 m = 6.0 metre when 4- wire connection is used. The burden of the relay, i.e. the relay input impedance must be checked with the relay manufacturer (User s manual, Technical data). For SPACOM relays, for example, the input impedance is less than 0.020 Ω for a 5 A input (i.e. burden less than 0.5 VA) and less than 0.100 Ω for a 1 A input (i.e. less than 0.1 VA). 7

Calculation of the Current Transformer 1MRS 755481 3.1.3. Example The distance between the CTs and the protection relay is 15 metres, 4 mm 2 Cu conductors in 4-wire connection are used. The burden of the relay input is less than 20 mω (5 A input). Calculate the actual burden of the CT at 75 C: Solution: ρ = 0.0216 µωm (75 C) R = 0.0216 µωm x (1.2 x 15 m) / 4 mm 2 = 0.097 Ω Burden of CT = 0.097 Ω + 0.020 Ω = 0.117 Ω Note for rated secondary current As shown previously, the smaller the CT burden in voltamperes, the better (higher) the actual accuracy limit factor. When changing to 1A rated CT secondary current instead of 5 A, the burden in voltamperes will drop to a level of 1/25 of what it was. 3.2. Calculation of the actual accuracy limit factor The actual accuracy limit factor (F a ) is calculated from the following equation F a F n S S in in + S + S n a (3) 3.2.1. Example where F n = rated accuracy limit factor S in = internal burden of the CT secondary coil S n = rated burden of the CT S a = actual burden of the CT In equation 3, all burdens must be in VA, which can be calculated from the expression S = I 2 R by using the rated secondary current of the CT. The internal secondary coil resistance of the CT is 0.07 Ω, the secondary burden (including wires and relay) is 0.117 Ω and the CT is rated 300/5, 5P20, 10 VA. Calculate the actual accuracy limit factor F a. Solution: F n = 20 (CT data 5P20), S in = (5A) 2 0.07 Ω =1.75 VA, S n = 10 VA (from CT data), S a = (5A) 2 0.117 Ω = 2.925 VA F a 1.75 + 10 = 20 = 50.3 1.75 + 2.925 Note: Often, as in this example, the power factor (cosϕ) of the CT is ignored. 8

1MRS 755481 Calculation of the Current Transformer 3.2.2. Alternative method There is also an alternative method for calculating F a,, that is, by first calculating the voltage on the CT secondary side, using the rated values: U sat = F n x I n x (R in + R n ) (4) where F n = rated accuracy limit factor I n = rated secondary current of the CT R in = internal resistance of the CT secondary coil R n = rated resistance (burden) of the CT This voltage (secondary limiting e.m.f.) is independent of the CT burden. Thus, F a for the actual burden can be calculated as follows: F a = U sat /[I n x (R in + R a )] (5) where R a = actual resistance (burden) of the CT. By using the values from the previous example, the solution will be: 10VA U sat = 20 5A 0.07 Ω + = 47. 0V 2 ( 5A) F a = 47.0 V 5 A Ω + ( 0.07 0.117 ) Ω = 50.3 9

Calculation of the Current Transformer 1MRS 755481 4. References IEC 60044-1. Instrument transformers Part 1: Current transformers. 10

1MRS 755481 Calculation of the Current Transformer 5. List of symbols α ρ A F a F n I n l R temperature coefficient of the conductor material resistivity of the conductor material cross-sectional area actual accuracy limit factor rated accuracy limit factor rated CT secondary current length of the conductor resistance R 1 resistance at temperature T 1 R 2 resistance at temperature T 2 R a R in R n S a S in S n actual resistance (burden) of the CT internal resistance of the CT secondary coil rated resistance (burden) of the CT actual burden of the CT internal burden of the CT secondary coil rated burden of the CT T 1, T 2 temperatures in Kelvin (20 C = 293.15 K) U sat secondary limiting e.m.f. 11

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa FINLAND Tel. +358 10 22 11 Fax. +358 10 224 1094 www.abb.com/substationautomation 1MRS 755481 EN 11.2004