B. Reference ASME A17.1 for elevator sumps and sump pump requirements. D. ASSE 1003 Performance Requirements for Water Pressure Reducing Valves.

Similar documents
STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL Purpose:

Fire Pump Plan Review March 2010

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

1. Conductivity < 15 micro ohms/cm 2. ph of 6.0 to Nonvolatile TOC content < 1.0 ppm

Element D Services Plumbing

DARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES

DIVISION 22 PLUMBING PLUMBING EQUIPMENT Domestic Water Heaters

Pump Specifications 2448LSG, 2448LSGX Series Omnivore 2HP Simplex Grinder Packages

FAIRBANKS NIJHUIS FIRE PUMPS.

Constantemp Double Wall Low pressure steam-water Heater F-340LDW,F-640LDW, F-940LDW and F-1240LDW

SECTION FACILITY STORM DRAINAGE PIPING

DIVISION 22 PLUMBING PLUMBING EQUIPMENT Domestic Water Heaters

DESIGN STANDARDS SECTION

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Medical Air Systems: Scroll

PLUMBING ROUGH IN INSPECTION

PLUMBING VALVES HOUSTON ORLANDO GREENVILLE 800/ / / TOTAL MAINTENANCE SOLUTIONS

2006 Codes. Please verify the following before calling for inspection

AURORA AND 1040 Series SUCTION DIFFUSERS, COMBINATION AND TRIPLE DUTY VALVES

BERMAD Waterworks. Quick Active Check Valve. 700 Series. Model 740Q. Features and Benefits. Major Additional Features

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

A. This Section includes the following for soil, waste, and vent piping inside the building:

Jay R. Smith Mfg. Co.

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

Morrison Bros. Co. General Product Specifications

Model 763 AURORA. 750/760 Series APCO-PM CONSTANT PRESSURE BOOSTER SYSTEMS

77 ILLINOIS ADMINISTRATIVE CODE, PART 890 (NEW) ILLINOIS PLUMBING CODE (02/04) SUBPART I: WATER SUPPLY AND DISTRIBUTION

Utility Distribution Systems

SJT / SJM / SJP Large Vertical Pumps

Style 07 Zero Flex Rigid Coupling. Style 75 Flexible Coupling. Style 77 Flexible Coupling 11. Description

INSTALLATION, OPERATING, AND MAINTENANCE INSTRUCTIONS PARTS LIST

ASME/ANSI B Cast Iron Pipe Flanges and Flanged Fittings ASME/ANSI B Malleable Iron Threaded Fittings ASME/ANSI B16.

Axial and Mixed Flow Pumps for Large Volume Pumping

In-Line Air Separators

RMF Engineering

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

American- Darling 5¼" B-84-B-5.

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

Model 362A AURORA. 340A/360A Series SINGLE STAGE END SUCTION PUMPS.

Commercial Semi-Instantaneous Water Heaters

MODEL INSTALLATION INSTRUCTIONS

SECTION SOIL AND WASTE SYSTEMS

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

SECTION DUCTILE IRON PIPE AND FITTINGS

CONSTRUCTION CHECKLIST Residential Plumbing Rough-In September 2004

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PLUMBING SPECIALTIES

PRESSURE REDUCING CONTROL VALVE

BOWIE PUMPS OPERATION - MAINTENANCE

TABLE 1. Rugged cast aluminum alloy casing,celcon waterways with nichrome parts White (unless stainless steel housing)

OUR PRODUCTS TRH-TRS-TRM-TRV. LIQUID RING VACUUM PUMPS AND COMPRESSORS Capacity up to 2100 ACFM Vacuum to 29 Hg. Our Other Products.

FLASH TANK ECONOMIZER PRODUCT GUIDE

PLAN CHECK CORRECTION SHEET FOR PLUMBING SYSTEMS 2014 LAPC

NAVIEN AMERICA INC FITCH AVENUE

BLADDER SURGE CONTROL SYSTEM

BERMAD Waterworks. Pressure Relief/Sustaining Valve. 700 Series. Model 730. Features and Benefits. Major Additional Features

SPECIFICATION DIVISION 22 SECTION DESCRIPTION DIVISION 22 PLUMBING SECTION THERMOMETERS, PRESSURE GAUGES, AND ACCESSORIES

Electronic Wallmount Faucet 1500T4 & 1501T4 Series

FACILITY POTABLE WATER STORAGE TANKS

Element D Services Plumbing

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

Vertical Pumps for the Oil & Gas Industry

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

CROSS-CONNECTION CONTROL MANUAL

TANKLESS WATER HEATER INSTALLATION DIAGRAMS

SunMaxx Solar Filling Station Operating Instructions

TECHNICAL BROCHURE B5-33GB 5GB, 7GB, 10GB, 18GB, 25GB, 33GB HIGH PRESSURE MULTI-STAGE BOOSTER PUMP

THE JERSEY CITY MUNICIPAL UTILITIES AUTHORITY REQUIREMENTS FOR FIRE AND DOMESTIC WATER LINE AND METER INSTALLATIONS

JOB or CUSTOMER: ENGINEER: CONTRACTOR: SUBMITTED BY: SPECIFICATION REF: QUANTITY TAG NO. MODEL NO. GPM FEET LEAD LENGTH COMMENTS.

SPECIFICATIONS FOR THE INSTALLATION OF FIRE ALARM SYSTEMS, SPRINKLER SYSTEMS, AND MASTER BOXES IN THE POQUONNOCK BRIDGE FIRE DISTRICT

NFPA31FuelOilPiping 1 Revised

Series 1510 Centrifugal Pumps Technical Bulletin. Bulletin B-207G Bell & Gossett

What to Expect From the Examination. How to Study the Plumbing Codes

INSTALLATION AND OPERATION INSTRUCTIONS - (LOW FLOW MODELS) (Before installation, compare electrical needed for the model of heater selected)

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Float and Thermostatic Traps Series H, C and X

LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459

Plumbing Installations A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

SRA-125/SRAX-125 Double-Rail Lift-Out Rail System Installation & Service Manual with Parts List

Amendments to the 2012 International Plumbing Code

Backflow Bulletin #1

Mustang Series PRESSURE REDUCING CONTROL VALVE WITH PRESSURE SUSTAINING FEATURE. M115-2 (Globe) M (Angle) Schematic. Standard Components

GENERAL PLUMBING REQUIREMENTS

Copper and Copper Alloy Tube, Pipe and Fittings

FIRING RANGE PHASE 1 DESIGN

Oil and Coolant Circulating Heating System. Model - OCSM

Plumbing Installations. A homeowner guide to the City of Winnipeg plumbing requirements for a single-family dwelling

Horizontal Split Case Fire Pumpset Electric Motor Driven 50 Hz

GOLD Plus 30/40/60/80

A. Accessible Fixture: Emergency plumbing fixture that can be approached, entered, and used by people with disabilities.

ECOCIAT. Domestic hot water heat recovery unit

THERMOSTATIC MIXING VALVE TRIM K-T9493, K-T9494

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

CHAPTER 11 STORM DRAINAGE

Nominal Life Expectancy for Building Components

4" SUBMERSIBLE PUMPS

Transcription:

PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is to apply the principles of this section so that the University may achieve a level of quality and consistency in the design and construction of their facilities. Deviations from these guidelines must be justified through LCC analysis and submitted to the University for approval. B. Reference ASME A17.1 for elevator sumps and sump pump requirements. 1.02 Codes and Standards A. Plumbing Code Compliance: Comply with applicable portions of International Plumbing Code pertaining to selection and installation of Plumbing materials and products. Note that the City of Austin (COA) follows the Uniform Plumbing Code and all systems that interface with COA infrastructure must comply accordingly. B. Plumbing and Drainage Institute: WH-201. C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers. D. ASSE 1003 Performance Requirements for Water Pressure Reducing Valves. E. ASME Boiler and Pressure Vessel Code. F. HI Compliance: Design, manufacture, and install plumbing pumps in accordance with Hydraulic Institute Standards. G. UL Compliance: Design, manufacture, and install plumbing pumps in accordance with UL 778 Motor Operated Water Pumps. H. SSPMA Compliance: Test and rate sump and sewage pumps in accordance with SUMP and Sewage Pump Manufacturers Association (SSPMA) and provide certified rating seal. I. ANSI 2l.22 Relief Valves for Hot Water Supply Systems. 1.03 Requirements A. Provide water hammer arrestors, complete with accessible isolation valve, in hot and cold water lines at the end of each battery of plumbing fixtures and at each plumbing fixture location remote from a battery of fixtures. Size in accordance with PDI WH-201. B. Isolate domestic water lines for building services from cross connection by means of two code-approved backflow preventer in for each water feed to the building. Provide additional backflow prevention devices in process water connections and fire system connections off the main building service. C. Provide backflow preventers at any connection between potable and non-potable water systems. D. Provide clean-out capability for domestic hot water return piping in recirculating loops. Provide a capped Design & Construction Standards, Revised September 2012 5.22.10-1

tee fitting at each ninety-degree turn in the piped return system. E. Route groups of pipes parallel to each other with spacing to allow for insulation and valve service. F. Provide dielectric couplings at connections between dissimilar metals. G. Provide sectional valves on each branch and riser, close to main, where branch or riser serves 2 or more plumbing fixtures or equipment connections. H. Provide shutoff valves installed on inlet of each plumbing equipment item and on inlet of each plumbing fixture. I. Provide drain valves at equipment, bases of risers, and low points in system to completely drain potable water system. J. Provide soft-seat check valves on discharge side of each pump. K. Provide balance cocks in each hot water recirculating loop. L. In all cases, Designer shall evaluate system conditions and select the optimum pump type and configuration based on pump efficiency and characteristics. M. Recommend in-line circulating pumps or close-coupled end suction pumps for low flow (up to 50 GPM) circulating systems. N. Recommend base-mounted end suction pumps for circulating systems with flow rates between 50 and 500 GPM. O. Pumps furnished as part of factory-fabricated equipment, such as a part of booster pump skids, are to be end-suction, if available. P. Provide all booster pumps with a valved bypass line to facilitate maintenance. Q. Cleanouts for fixture banks shall be located above fixture flood level. R. Provided dedicated shutoff valve for outdoor hose bibs and fixtures. PART 2: PRODUCTS 2.01 Pipes and Pipe Fittings A. Pipe Size 2" and Smaller 1. Copper tube; Type "L", hard-drawn wrought-copper fittings, solder-joints. Use Dutch Boy or Silvabrite 100 lead-free solder, Composition 95/5, Solder Filler Metals: ASTM B 32, Solder containing lead is not permitted. 2. Copper Tube; Type "L" with copper Press Fittings with rubber O-rings made with hydraulic compression tool, Viega ProPress or approved equal. 3. Piping smaller than ¾ shall not be allowed. B. Pipe Size 2 1/2 and Larger: 1. Copper tube; Type "K", hard-drawn wrought-copper fittings, brazed sil-fos-joints manufactured by Design & Construction Standards, Revised September 2012 5.22.10-2

Sil-fos, Solder Filler Metals: Solder containing lead is not permitted. 2. Copper Tube 2-1/2 to 4 ; Type "K", with copper Press Fittings with rubber O-rings and stainless steel grip ring made with hydraulic compression tool, Viega ProPress or approved equal. C. Piping 6 and larger shall be ASTM A53 galvanized steel pipe, schedule 40, with rolled grooved ends and mechanical couplings. D. Exterior below grade or below concrete slab equipment or fixture supply feeds: Piping shall be Type K copper, soft-annealed temper, with wrought copper fittings and lead free jointing. E. Below building concrete slab - Tube size ¾" and larger: type "K" soft - annealed copper coil tubing. Copper tubing installed below building concrete slab on grade shall be installed without solder joints. F. Underground water main piping systems: All pipe used for underground water piping mains shall be Class 50 ductile iron pipe, arranged with bell and spigot mechanical joints, fully restrained with retaining glands. Class 51 for 3 and 4 and Class 50 for 6 and larger, 2.02 Piping Specialties A. Provide basket strainers with cast-iron body, 125-psi flanges, bolted type or yoke type cover. Furnish with removable, non-corrosive perforated strainer basket, with 1/8" perforations and lift-out basket handle. 2.03 Bibbs and Faucets A. Hose Bibbs shall be threaded end, bronze body, renewable composition disc, tee handle, ¾" NPT inlet, and ¾" hose outlet. Provide with vacuum breaker. B. Sill Faucets shall be bronze body, renewable composition disc, wheel handle, ¾" solder inlet, ¾" hose outlet. Provide with vacuum breaker. 2.04 Hydrants A. Recessed Non-Freeze Wall Hydrants: Case-bronze casing, length to suit wall thickness, vacuum breaker, hinged locking cover, ¾ inlet, and hose outlet. B. Project Non-Freeze Wall Hydrants: Cast-bronze hydrant, chrome plate face, tee handle key, bronze casing, length to suit wall thickness, vacuum breaker, ¾ inlet, hose outlet. C. Projected Non-Freeze Wall Hydrants: Cast bronze hydrant, chrome-plated face, tee handle key, bronze casing, length-to-suit wall thickness, vacuum breaker, ¾ inlet, hose outlet. D. Floor Level Non-Freeze Hydrants: Bronze hydrant, rough bronze box, tee handle key, bronze casing, length to suit depth of bury, drain hole, vacuum breaker, hinged locking cover, ¾ inlet, hose outlet. E. Non-Freeze Post Yard Hydrants: Bronze hydrant, tee handle key, bronze casing with cast-iron casing guard, length to suit depth of bury, drain hole, vacuum breaker, ¾ inlet, hose outlet. 2.05 Backflow Preventers A. Shall be of the reduced pressure zone (RPZ) type. The assembly shall include shutoff valves on inlet and Design & Construction Standards, Revised September 2012 5.22.10-3

outlet, and strainer on inlet. Backflow preventers shall include test cocks, and pressure-differential relief valve located between 2 positive seating check valves. Construct in accordance with ASSE Standard 1013. Coordinate the exact model of the backflow preventer with the University prior to incorporation into the design. B. Provide backflow preventers at any connection between potable and non-potable water systems. Refer to Products section. 2.06 Pressure Regulating Valves A. Shall be single seated, direct operated type, bronze body, integral strainer, complying with requirements of ASSE Standard 1003. Provide inlet and outlet shutoff valves and throttling bypass valve. Provide pressure gauge on valve outlet. 2.07 Relief Valves 2.08 Pumps A. The standard relief valves shall be manufactured in accordance with ASME Boiler and Pressure Vessel Code. Valves shall be combined pressure-temperature relief valves with bronze body, test lever, thermostat and shall comply with ANSI 2l.22 listing requirements for temperature discharge capacity. Provide temperature relief at 210 F and pressure relief at 150 psig. A. In-Line Re-Circulation Pumps 1. Provide maintenance-free circulator pumps designed for 125 psig working pressure 225 F continuous water temperature and specifically designed for quiet operation. 2. Body: Stainless steel fitted construction with iron body. 3. Shaft: Steel, ground and polished, metal impregnated carbon thrust bearing. 4. Motor: Non-overloading at any point on pump curve, open, drip proof, sleeve bearings, quiet operating, rubber mounted construction, built-in thermal overload protection. 5. Coupling: Self-aligning, flexible coupling. B. Water Pressure Booster System 1. General: Provide factory-fabricated and tested water pressure booster system consisting of diaphragm type water tank, centrifugal pumps, power and control panels, instrumentation, and operating controls. It is a University Standard to provide pumps with a valved bypass to facilitate maintenance. 2. Pumps: Provide two (2) constant speed, single stage, end-suction design, cast-iron; bronze fitted centrifugal pumps with mechanical shafts seals. Mount pumps on vibration insulators. Provide temperature probe and electric purge valve immediately upstream of each PRV. Provide drip-proof motors. 3. Water Tank: Provide factory pre charged diaphragm type water tank with replaceable flexible membrane. Construct in accordance with ASME Code and provide ASME stamp for 125-psi minimum. 4. System Controls: Maintain system pressure with pilot-operated diaphragm type combination pressure regulating and non-slam check valve on each pump discharge line. a) Provide low system pressure switch located on discharge header to sense drop in system pressure, and to activate alarm and automatically start standby pump. b) Provide adjustable vane type flow switch to sequence lag pump. C. Control Panel Enclosure: 1. Provide UL-listed, NEMA l, hinged door, and lockable control panel enclosure. Design & Construction Standards, Revised September 2012 5.22.10-4

D. Duplex Pedestal Type Sump Pumps: 1. Pump: Duplex, centrifugal, semi-open impeller type sump pump, complete with galvanized steel strainer, cast-iron base plate, suction plate and casing, and cast-iron or bronze impeller. 2. Shaft: Stainless steel of length to suit depth of basin, connected with flexible coupling to motor, and intermediate sleeve bearing for lengths over 4'. 3. Motor: Open drip-proof, electrical characteristics as scheduled. 4. Basin: Fiberglass construction of indicated dimensions, with inlet connections of size and location as indicated. Maintain minimum of 3' depth below lowest inlet invert. 5. Cover: Cast-iron or steel circular cover with manhole or hand hole opening, depending on diameter. Provide openings for pump, control rod, and discharge piping. 6. Controls: Pump controls shall include float switch with gas-tight seals, bronze or stainless steel floats and rods, alternator, high level automatic alarm switch with gas-tight seals Auxiliary BAS alarm contacts and provisions for activation of a remote alarm light. Control panel shall be a factory-wired NEMA Type 1 (non-metallic) enclosure and shall include (HOA) two hand-off-auto switches, electric auto alternator circuit, combination motor controller with circuit breaker, control power transformer, and pump running lights. Alarm switch and all controls shall operate on 120 VAC (fuse protected circuit), 60 hertz, U.L. 508 listed industrial controls label. 7. Provide main disconnect switch. E. Submersible Sump Pumps: 1. Pump: Cast-iron shell, bronze impeller, stainless steel shaft, factory-sealed grease lubricated ball bearings, ceramic mechanical seal, and perforated steel strainer. 2. Motor: Hermetically sealed, capacitor-start, with built-in overload protection, electrical characteristics as scheduled. Provide 20' of 3-conductor PVC cord and molded grounding plug. 3. Controls: Float-operated mercury switch. 4. Provide with stainless steel safety/lifting chain or slide rail system. 5. Provide connections points in piping to facilitate rapid tie-in of temporary pumps during emergency situations. 6. Controls: Pump controls shall include float switch with gas-tight seals, bronze or stainless steel floats and rods, alternator, high level automatic alarm switch with gas-tight seals Auxiliary BAS alarm contacts and provisions for activation of a remote alarm light. Control panel shall be a factory-wired NEMA Type 1 (non-metallic) enclosure and shall include (HOA) two hand-off-auto switches, electric auto alternator circuit, combination motor controller with circuit breaker, control power transformer, and pump running lights. Alarm switch and all controls shall operate on 120 VAC (fuse protected circuit), 60 hertz, U.L. 508 listed industrial controls label. 7. Provide main disconnect switch. F. Duplex Sewage Ejector Pumps: 1. Pump: Duplex (Two) centrifugal, self-priming, solids handling pumps with a cast iron body and cast iron or ductile iron impeller. 2. Shaft: Carbon steel, connected with flexible coupling to monitor. 3. Motor: Open drip-proof, electrical characteristics as scheduled. 4. Basin: Fiberglass construction of indicated dimensions, with inlet connections of size and location as indicated. Maintain minimum of 4 depth below lowest inlet invert. 5. Cover: Cast-iron or steel circular cover with manhole or hand hole opening, depending on diameter. Provide openings with gas tight seals for controls, vent, and suction piping. 6. Controls: Pump controls shall include float switch, bronze or stainless steel floats and rods, alternator, high level automatic alarm switch, Auxiliary BAS alarm contacts and provision for activation of a remote alarm light. Control panel shall be a NEMA Type 1 (non-metallic) enclosure and shall include (HOA) two hand-off-auto switches, electric auto alternator circuit, combination motor controller with circuit breaker, control power transformer, and pump running lights. Alarm switch and all controls shall operate on 120 VAC (fuse protected circuit), 60 hertz, U.L. 508 listed industrial controls label. 7. Provide main disconnect switch. Design & Construction Standards, Revised September 2012 5.22.10-5

PART 3: EXECUTION 3.01 Pipe Testing Procedures: A. Refer to 6.02.10 Appendix: Pipe Testing Procedures for plumbing pipe testing procedures. END OF STANDARD Design & Construction Standards, Revised September 2012 5.22.10-6