White rust on galvanized and galvanized pre-painted steel. Technical Information

Similar documents
Protecting Galvanized Steel Sheet Products from Storage Stain Rev 2.1 Aug-03

BLACK JACK ALL WEATHER ROOF COATING

THE USE OF STEEL BUILDING PANELS FOR ANIMAL CONFINEMENT

Metal Rescue Rust Remover Technical Data

VC 104+ Rigid Grade / Rigid Grade Imagine VC 104 Rigid Grade Commercial Customised

COATING & WRAPPING OF UNDERGROUND PIPING

ApplicatorTrainingBulletin. The Galvanized Surface. Surface Preparation of New Galvanizing

PAINTING OVER HOT DIP GALVANIZED STEEL

Chromadek for Roofing Applications Pre-painted hot-dip galvanised steel sheet

Standard Method for Sampling and Analysis of. of Chlorine Containing Bleaches. Soap Products

Durability of aluminium

Approved. Property Test/Standard Description. matt (0-35) Flash point ISO 3679 Method 1 27 C calculated IED (2010/75/EU) (calculated)

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

METAL ROOF RESTORATION SAMPLE DESIGN GUIDELINES

The Owners Coated Coil, Cleaning and Maintenance Service Manual.

Spandrel Glass Types and Recommendations

September 3, Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901

A. Work on this project shall consist of, but is not limited to, the following:

Chapter 2 Basis of design and materials

Introducing an All New Line of Cleaning Chemicals

ELASTOCEM. Technical features. Applications. Two-component flexible, waterproofing and protective cementitious grout.

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007

RECOATING AND RENEWING SPF ROOFING SYSTEMS

Property Test/Standard Description. gloss (70-85) Flash point ISO 3679 Method F (100 C) calculated VOC-US/Hong Kong. US EPA method 24 (tested)

NEOGARD. Preventive Maintenance Manual

IMO Approved Tank Cleaning Chemicals

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

PHOENIX Product Data Sheet (Updated on 14-Jan-2012)

Why is my air conditioner dripping on my customers?

BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION

K2 STONE NATURAL VENEER

Property Test/Standard Description. semi gloss (35-70) Flash point ISO 3679 Method 1 34 C IED (2010/75/EU) (calculated)

Tractor Painting Tips

Points of Construction

Evaluating Protective Coatings for Ballast Tanks

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

Building and Grounds Maintenance Checklist

SCENIC VIEW SV 10 SECTION SOLAR CONTROL FILMS

SIGMAFAST 210. PRODUCT DATA SHEET December 12, 2014 (Revision of April 1, 2013) DESCRIPTION

The Rooflight Company s Operations & Maintenance Guide

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER POLYSOCYANURATE SYSTEM DESCRIPTION TORCH SYSTEM OVER POLYISO (15,17,19 YR) TH/BS-TH/CS

Additional Information. Paint Application

Approved. Property Test/Standard Description. matt (0-35) Flash point ISO 3679 Method 1 28 C calculated VOC-US/Hong Kong. US EPA method 24 (tested)

Minor Cracks in Horizontal Surfaces

Sto Specification No. RC100 Guideline Specifications for Cleaning Wall Surfaces

PAINT REMOVAL SYSTEM PAINT REMOVAL SPECIFICATION SAFE WORK METHOD STATEMENT FOR LEAD PAINT REMOVAL

WARRANTY VINYL SIDING CERTAINTEED CORPORATION LIFETIME LIMITED

WATERPROOFING FOR CONCRETE STRUCTURES

Advice to consumer Reference 50.1 May Condensation. Some causes, some advice.

One Year Limited Guarantee on VIOLET Watches

BEST PRACTICE GUIDE. Fibrelime Premixed Universal Plaster and Render

Installation Instructions

ACO Cleaning principles for drainage

SIGMACOVER 300. PRODUCT DATA SHEET December 12, 2014 (Revision of November 1, 2013) DESCRIPTION

Stucco Repair and Maintenance No. 1.01

SEAMS SEAMING USING SEAM TAPE

Keeping Your Swimming Pool and Spa Healthy Environmental Health Guide

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

Residential Roofing Guide

RAPTOR TRUCK BED LINER - BLACK

ABSeam Panel Overview and Installation Instructions

SECTION PREFORMED METAL STANDING SEAM ROOFING

CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN Fax: Re-Roofing: Asphalt Shingles

PRETREATMENT TECHNICAL DATA SHEET WATER EMULSIFIABLE RUST PREVENTATIVE PRODUCT DESCRIPTION

Solvent Cementing Instructions For Plastic Pipe & Fittings

Roof Inspection. Summary Report

Mineral waterproof coating PCI Dichtschlämme

CONTENTS. 1 cooling technology white paper

VINYL SIDING CERTAINTEED CORPORATION L I M I T E D

GUIDELINE SPECIFICATIONS

Cedar Impressions Siding LIFETIME LIMITED

Test Methods for the Colour Fastness of Leather & Dyes. TFL Leather Technology Ltd. Quality and Environment February 2004 Version 1.

The history of brick in Scotland Signs of deterioration in brickwork Causes of deterioration Repair and maintenance of brick structures

LIMITED LIFETIME CERTAINTEED CORPORATION VINYL SIDING PRODUCTS

GUIDELINES FOR HANDLING FABRICATION INSTALLATION AND CLEANING

THERMOTEK MODIFIED BITUMEN TORCH MEMBRANE OVER

PREPARING HOT-DIP GALVANIZED STEEL SURFACES FOR PAINTING OR POWDER COATING: A PRIMER

Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.

Housing Services Guidance for tackling condensation, damp and mould in your home

CREATING A SYMPATHETIC ENVIRONMENT FOR ARCHIVAL MATERIAL MADHU RANI ICKPAC, BANGALORE

Anodizing Reference Guide

INDUSTRIAL FLOORING INSTALLATION CHALLENGES. James C. Ziegler, ArmorSeal Product Manager Sherwin Williams Cincinnati, Ohio, USA

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

Application of Exterior Wood Finishes

PRODUCT DATA SHEET DESCRIPTION:

Warranty. 1/5. Warranty

Araldite AV 170. Advanced Materials. One component epoxy adhesive. Structural Adhesives. Key properties. Description. Product data.

Best Management Practices

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

Pilkington Reflite Handling and Processing Guidelines Solar Control

How to Install Hardwood Flooring Over a Sub Floor

HVAC Schedule. Contract # GS-07F-9452S Contract # GS-06F-0091S 2008 NCH CORPORATION 2009 NCH CORPORATION

CONDENSATION IN REFRIDGERATED BUILDINGS

WOLVERHAMPTON WASTE SERVICES GUIDANCE FOR THE SAFE REMOVAL, COLLECTION AND DISPOSAL OF MATERIALS CONTAINING ASBESTOS OR ASBESTOS CEMENT

RBS detergents for laboratories

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

Activ ActivTM self-cleaning glass Activ

Guidelines for Durable Driveways, Carports Patios, Walks, Garage Floors

Note: Minor color change may occur in exposed service, but corrosion protection will not be compromised

CATHODIC PROTECTION SYSTEM DESIGN

Transcription:

Technical Information

White rust on galvanised steel Prevention It is easier to prevent white rust than to cure it! Reasonable precautions to protect steel during both transport and storage can considerably reduce the risk of white rust. Storage should be indoors if possible, preferably in a clean, dry area away from any source of chemical pollution. Since rapid changes in temperature may cause condensation leading to white rust, storage should, as far as possible, be at an even temperature above the dew point. In particular, storage of coil or sheet on site can be improved by a few simple precautions, viz: Always stack the packs on metal or wooden skids to keep them from direct contact with the ground. 'Where possible, do not leave uncovered coil or sheet stacks lying in the open. Store them under cover and away from open doorways. However, if it is absolutely necessary to store material out-of-doors, then the following simple precautions are essential: If stacks or coils cannot be kept under cover, erect a simple scaffolding around them and cover it with a waterproof sheet, tarpaulin or polythene. Leave space between the cover and the stacks or coils to allow air to circulate. Store off the ground and on a slope so that any rain penetrating the cover will drain away. Inspect the storage site regularly to ensure that, despite these precautions, the steel has not become wet. Be aware that sheets in the stack, not only the top but also in-between, get wet due to condensation at night and that the condense water connate evaporate. The period of outdoor storage should be kept as short as possible. Particularly during the summer period, higher temperatures speeds up the rust process very much. What is white rust? How is it caused? White rust is a complex, hydrated zinc carbonate/zinc hydroxide. It is a corrosion product of zinc formed under certain specific conditions of exposure. The most common causes of white rust are: 1. Ingress of water, due to rainwater, between the adjacent surfaces in a stack of galvanised or per-painted steel or sheets or components or within windings in a galvanised coil during transport or storage. 2. Condensation within a coil, a stack of sheets or components caused by rapid changes in temperature. 3. Condensation from the drying out of new buildings or the laying and drying out of wet concrete screed. 4. The combined effect of weather and site dust on the components of a building frame before the application of the weather skin. 5. The combined effects of weather and site dust on roof decking before the application of insulation and weather proofing. It is important to note that white rust, since it can be transparent when wet, may not always be visible until the steel dries. 1

Is white rust harmful? What action is required? Because of the large volume of white rust often apparent, it frequently gives the misleading impression of extensive corrosion. However, in the vast majority of cases, white rust does not indicate serious degradation of the zinc coating nor does it necessarily imply any likely reduction in the expected life of the product. Unless the sheets or components are to be over-painted later, superficial white rusting can be safely ignored. In most cases, when exposed to natural, acceptable environmental conditions, superficial deposits of white rust will gradually 'tone-in' and eventually disappear. However, heavy deposits, especially when combined with other corrosion phenomena, should be regarded with caution. The advice applies particularly to continuously galvanised steel, but in many respects relates also to products galvanised after manufacture. However, in the latter case, specific advice should be sought from the supplier involved. Figures A1, A2, B1, B2, and C each show an area of galvanised steel affected by products of corrosion. Note Where subsequent over-painting is required, white rust deposits must always be removed, otherwise they will impair paint adhesion (see note 3, page 4). The remedial actions recommended assume that the galvanised steel is not to be painted or otherwise coated. Light white rust Visible effect: thin, white, powdery deposit (fig. A1 and A2) Cause Caused by moisture trapped between sheets or components during transport or storage, or by condensation. None required. The protective properties of zinc are not impaired by the presence of superficial white rust. Existing white rust deposits will slowly convert to protective basic zinc carbonate. 2

Removal Where it is essential to remove white rust deposits, this can be achieved by using special proprietary cleaners or simple chemical solutions which can be made up on site. A suitable solution could be: 1 % solution of trisodium phosphate (NA3PO4) or 1 % solution of potassium or sodium dichromate slightly acidified with sulphuric acid (PH not less than 6). This solution may leave a stained surface. N.B. In all cases, affected sheets should be thoroughly washed and allowed to dry after treatment. Heavy white rust Visible effect: thick, crusty deposit (fig. B1 and B2) Cause Prolonged, adverse storage or inadequate protection during transport allowing considerable water ingress between stacked sheets or components. In buildings, this can also occur where normal cycles of wetting and drying are combined with a corrosive atmosphere, before completion of the weather skin. Remove small area of white rust by brushing with a stiff-bristled brush (not a wire brush). Check residual zinc coating thickness with magnetic gauge (note 1). An average of at least 3 point determinations should be taken in each case. If within specification (note 2), and if the sheet or component is to be used in reasonably dry or freely exposed conditions, no action is required. However, if the sheet or component is to be exposed to excessive condensate or to conditions where moisture can be retained, the deposits must be removed. If below specification, clean the area (note 3) and treat with an inorganic zinc-rich paint to a minimum dry film thickness of 25µm (note 4). 3

Notes 1. Simple hand-held magnetic thickness gauges suitable for the on-site or factoryfloor measurement of residual zinc coating thickness are available from a number of companies. 2. Coating weight should correspond to the relevant specification according EN 10346, Continuously hot-dip zinc coated structural steel strip and sheet. 3. Small areas of white rust can be removed by abrading with a stiff-bristled brush. Large areas can be treated with a proprietary product or with simple chemical solutions which can be prepared on site. 4. Where wet conditions are likely to persist, over-painting with a suitable paint system should be considered as an added protection. Red rust Visible effect: thick, red rust (fig. C) Cause Corrosion of steel substrate where zinc coating has broken down completely. Should not be confused with superficial rust staining caused, for example, by small amounts of drilling swarf on the zinc surface or by wash from adjacent mild steel fixings. In general, sheets or components showing this defect should not be used. In circumstances where there is no alternative but to use the defective material, a repair procedure may be undertaken if the purchaser agrees. Expert advice should be sought first. 4

White rust on pre-painted steel Prevention For pre-painted material the same precautions counts as for galvanized steel, stated on page one. Storage should be indoors if possible, preferably in a clean, dry area away from any source of chemical pollution. Pre-painted material is also sensitive for rapid changes in temperature which may cause condensation leading to white rust. Storage should, as far as possible, be at an even temperature above the dew point. In particular, storage of coil or sheet on site can be improved by a few simple precautions, viz: Always stack the packs on metal or wooden skids to keep them from direct contact with the ground. 'Where possible, do not leave uncovered coil or sheet stacks lying in the open. Store them under cover and away from open doorways. However, if it is absolutely necessary to store material out-of-doors, then the following simple precautions are essential: If stacks or coils cannot be kept under cover, erect a simple scaffolding around them and cover it with a waterproof sheet, tarpaulin or polythene. Leave space between the cover and the stacks or coils to allow air to circulate. Store off the ground and on a slope so that any rain penetrating the cover will drain away. Inspect the storage site regularly to ensure that, despite these precautions, the steel has not become wet. Be aware that sheets in the stack, not only the top but also in-between, get wet due to condensation at night and that the condense water connate evaporate. The period of outdoor storage should be kept as short as possible. Particularly during the summer period, higher temperatures speeds up the rust process very much. Strippable film applied on pre-painted steel does not diminish the risk. Sooner or later water will penetrate through the film. Especially during summertime when rapid changes in temperature occur which may cause condensation within the stack of sheets or within the coil white rust could start within days when storage on site is not appropriate. 5

Light white rust Visible effect: thin, white deposit (fig. D1 and D2) Maybe not required for walls. The protective properties of zinc are not impaired by the presence of superficial white rust. Existing white rust deposits will slowly convert to protective basic zinc carbonate. However, for aesthetic reasons, light stains are in general easy to remove by cleaning with warm water and soap by means of a low pressure spray or brush, max 60ºC, max 60 Bar. Heavier stains may be cleaned with a basic solution which as well can be used to remove fungal growth, dirt and debris. A basic solution may be applied to a pre-washed surface by means of a low pressure spray or brush containing: Household detergent - 0.5% Trisodium Phosphate - 3.0% 5% Sodium Hypochlorite solution - 25.0% Clean, fresh water - 71.5% This should be rinsed thoroughly with clean water after treatment. Over spraying is possible by specialized firms. Regarding to roofs, remedial action will be required in most cases due to the more demanding conditions. Specific advice should always be sought for both the wall and roof utilization from the supplier involved. 6

Heavy white rust Visible effect: thick, crusty deposit (fig. E) In general, sheets or components showing this defect should not be used. In circumstances where there is no alternative but to use the defective material, a repair procedure may be undertaken if the purchaser agrees. Expert advice should be sought first. 7