Installation. Smart-UPS VT and MGE Galaxy 3500. Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V

Similar documents
Installation. Smart-UPS VT MGE Galaxy Maintenance Bypass Panel kva 400 V

Contractors Guide Central Inverter System Installation

Unpacking, Installation, and Customization

GENUINE PARTS INSTALLATION INSTRUCTIONS

TraceTek TTDM Series Leak Detection and Location Modules Replacement Parts Installation Instructions

Step 1. Item 6. Item 1

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

PS6500 Storage Arrays Rack Mount Instructions

LIEBERT VNSA Installation Sheet

Express5800/120Ed. Rack Mount Kit Installation Procedures PN:

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

TOYOTA TUNDRA 2015 Billet Grille w/led DRL

PowerFlex 700H and 700S AC Drives Frame 11 Main Fan Capacitor Replacement Kit

INSTALLATION INSTRUCTIONS

CoolWave r 2 Phase Control Board and Cable Replacement Kits

P150SC15. Designed for 2015 Ford F150 Super-Cab and Super-Crew vehicles without Sony System Stillwater Designs P150SC15-A

DCF Optimized Rack System

HP 16/18-Port Cable Management Kit Installation Guide

Elo Touch Solutions Wall-mounting Kit for the 5501L IDS Touchmonitors

Retrofit Instructions Installing a Sport Heated Steering Wheel - Leather, Multifunction BMW X5, E53,

Control Box Wiring For PRSstandard Tool

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

COOPER S PULLEY UPGRADE KIT INSTALLATION INSTRUCTIONS PART NUMBER NME5011

Wall-Mounting your HP computer. User Guide

Service Guide. Gateway M275

Installation Instructions Avalanche XUV Cap IMPORTANT! IMPORTANT!

INSTALL/REMOVAL INSTRUCTIONS: WINDOW REGULATOR

POWER LOCK KIT GENERAL INSTALLATION -J04427 REV Kit Number. Models. Additional Parts Required. Kit Contents

3. SEISCO PARTS & SERVICE REMOVAL AND REPAIR GUIDE

INSTALLATION INSTRUCTIONS

Table of Contents. What to Expect with. Preparation. Tools Needed. Wiring. Hanging the Fan. Blades. Motor Housing.

Uninterruptible Power Supply. 500 kva kva

Anthro Tablet Charging Cabinets

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family

PowerFlex 700S and 700H Frame 12 DC Bus Connector Kit

Smart-UPS RT External Battery Pack Stack/Rack-Mount 6U

Upgrading a GainMaker Line Extender from a Line-Powered Source to a 120 V AC-Powered Source Installation Instructions

430 Power/Electronics Replacement

Installation Guide Smart-UPS X External Battery Pack SMX120BP

INSTALLATION MANUAL ELECTRIC RANGE. Please read these instructions thoroughly before installing and operating the range.

CONTENTS TOOLS REQUIRED: Ratchet 13mm Socket 10mm Socket Phillips Screwdriver Pliers Panel Removal Tool. Amp Installation

TOYOTA Tundra BACK-UP CAMERA SYSTEM Preparation

INSTALLATION INSTRUCTIONS for Bifold Doors (JII103)

42U/45U 28" Wide Rack Installation & Service Guide

POLEMOUNT FIELD FIX ASSEMBLY INSTRUCTIONS

Installation Instructions

Installation. Basic Rack Power Distribution Unit AP9559

INSTALLATION AND OPERATING INSTRUCTIONS For Model GL1 Gate Locks

Triac Printed Circuit Board Replacement

SB-C-CTS/10TW3 SKU# & Up Cadillac CTS/CTS-V

Triple Expansion Chassis

5800 Temperature Sensor Cable Assembly

UPGRADING AND SERVICING GUIDE

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS MULTI-MOUNT KIT Part Number: Application: Warn HP PowerPlant P/N 71800

LIFT-505. BMF Lift Kit. Yamaha Drive Gas or Electric. Installation Instructions

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.

RAY-MAX Integrated Solar Power Strip

WARNING! REQUIRED TOOLS & SUPPLIES: HIGH VOLTAGE

MCR1900 Media Converter 19-Slot Chassis

1. SAFETY RULES. 8. Avoid placing objects in the path of the blades.

BMW E46 Convertible. Storage Compartment Lid Hydraulic Cylinder Removal

Smart-UPS VT kVA 400V. Site Preparation and Installation Manual

AutoDome Easy II. VEZ Series. Mounting Manual

About the BitStorm 6051 POTS Splitter

1. SAFETY RULES WARNING TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR PERSONAL INJURY, MOUNT FAN TO OUTLET BOX MARKED "ACCEPTABLE FOR FAN SUPPORT".

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Cooktop Low-Profile Ventilation Hoods

ZAPPY 3 OWNER S MANUAL. Read this manual completely before riding your Electric ZAPPY 3.

GTI VR6 Front Wheel Bearing DIY

SALEEN SPEEDLAB SERIES VI STANDARD SC UPGRADE KIT

SERVICE GUIDE For WARN PULLZALL 120v AC &100v AC P/N &

INTRODUCTION INTERLOCK KIT K-8110

TOYOTA TACOMA HANDS FREE BLU LOGIC Preparation

INSTALL/REMOVAL INSTRUCTIONS: WINDOW REGULATOR

Installation Instructions S

CP2 Buried Cable Pedestal Initial & Rehab Installation Instructions

QT Residential Blower Metal Residential Blower

6 inch A-Arm Lift Kit WARNING: / installation instructions. will fit CLUB CAR DS. included:

GreenWay Solar LED Path and Trail Lighting System. Installation and Owner s Manual

Check for deteriorated, shifting or missing tie-down pads. Replace if needed.

GPS AutoSteer System Installation Manual

Replacing a Vantage Vue Transmitter

RayClic Connection System Installation Instructions

Ford Focus Front Brake Rotors

Convertible Top Hydraulic Cylinder Removal Manual for W124 E-Class Convertibles Models 300CE (1993) and E320 ( )

Awning Instructions. Full Cassette 1.5m to 6m

MBSAW. Meat Cutting Band Saw With Meat Grinder Assembly & Operating Instructions

Installation Instructions For Slider Casement Air Conditioners

Power Management Module 2. Installation

Premier & Deluxe 3-Season Room Sliding Glass Door

DANGER DANGER. General Information. Safety Is Your Responsibility. Ordering Parts. Contact Information

Owner s Guide and Installation Manual. Vancouver Model Name , Model No. English Español

INSTALL/REMOVAL INSTRUCTIONS: WINDOW LIFT MOTOR

INSTALLATION INSTRUCTIONS

Speed-Mat Rectangle Cutter

Wiper Motor Marinco 2.5. Installation Instructions

INFRARED QUARTZ WALL HEATER

Transcription:

Installation Smart-UPS VT and MGE Galaxy 3500 Maintenance Bypass Panel with Power Distribution (wall-mount) 10-30 kva 208 V

Contents Safety... 1 SAVE THESE INSTRUCTIONS............................... 1 Safety warnings......................................... 1 Live maintenance precautions............................. 1 Product Overview... 3 Features................................................. 3 Internal components..................................... 4 Schematic.............................................. 5 Considerations... 6 Environmental........................................... 6 Installation... 7 Overview............................................... 7 Tools.................................................. 7 Panel board breakers..................................... 7 Removing the front door (optional).......................... 8 Mounting the MBP....................................... 9 Internal cable connections............................... 10 Making external cable connections........................ 11 Re-attaching the front door............................... 13 Installing Panel Board Breakers............................ 14 Appendix A: Changing Fuses... 15 Removing fuses........................................ 15 Replacing fuses........................................ 15 i

Safety SAVE THESE INSTRUCTIONS This manual contains important instructions for the Smart-UPS VT and MGE Galaxy 3500 series that should be followed when handling the Maintenance Bypass Panel with Power Distribution (wallmount). This UL-listed unit was designed to operate in conjunction with the Smart-UPS VT and MGE Galaxy 3500 10-30kVA, 208V UPS. Safety warnings Warning: Only APC by Schneider -trained personnel who are familiar with the construction and operation of this equipment, as well as the mechanical and electrical hazards involved, may perform this installation. Warning: This installation must comply with the requirements of ANSI/NFPA 75 and NEC/NFPA 79 Art. 645. Warning: All safety codes, safety standards, and other regulations must be strictly observed during installation and ongoing maintenance of this equipment. Warning: Prior to installing the Smart-UPS VT or MGE Galaxy 3500 Maintenance Bypass Panel, de-energize all external power being supplied to the UPS! Warning: Ensure that no electrical power is connected to the Maintenance Bypass Panel, and that all switches are in the OFF position before installing or servicing this unit! Warning: All wiring instructions must be followed precisely. Failure to comply could result in permanent damage to the equipment! Warning: When installing this unit to a wall, avoid contact with previously installed electrical wires and other potential hazards that might be embedded in the wall! 1

Live maintenance precautions APC does NOT recommend performing live maintenance to the MBP with Power Distribution. However, APC is aware that due to the critical nature of data center loads, live maintenance may occur. If providing live maintenance, observe the following precautions to reduce the risk of electrical shock. Caution: 1.Never work alone. 2.Only a certified electrician who is trained in the hazards of live electrical installation should perform the maintenance. 3.Know the procedure for disconnecting electricity to the MBP in the event of an emergency. 4.Wear appropriate protective clothing and other body equipment. Be sure to use rubberinsulated gloves and rubber-insulated boots. 5.Use double-insulated tools. If double-insulated tools are not available, insulate all tools with electrical tape. 6.Use electrical tape to insulate any non-insulated conductive parts. 7.Always follow local codes and site regulations when working on the MBP. 2

Product Overview Features The wall-mount version of the Smart-UPS VT and MGE Galaxy 3500 MBP combines bypass functionality with power distribution capability in a common enclosure.the lower section of the MBP contains switches that facilitate the transfer of power from the UPS to bypass operation to allow maintenance to be performed on the UPS. The upper section houses a 42-position panel board for distributing power to load. The unit weighs approximately 120 lbs [54.5 kg]. The MBP can be installed quickly and easily to almost any type of sturdy wall structure (refer to Mounting the MBP on page 9). Product SKU Input Output SBPSU10K30FC1M1-WP 81.3A, 208/120V, 3-Phase, 50/60Hz 83.3A, 208/120V, 3-Phase, 50/60Hz The MBP enclosure supports both top and bottom cable entry. The unit contains three 90A fuses that provide over-current and short-circuit protection. Space for Cutouts (both ends) Top Plate Knockouts (22) 37.36 in [949] 29.3 in [750] 7.48 in [190] 3

Internal components Ground Bar Neutral Bar Cable Connection Panel Board (42-position) Ground Bar Neutral Bar Neutral Bar Strain-relief Bar Strain-relief Bar Fuse Block ([3]90A Fuses) Ground Terminal Compression Lug Control Terminal Block Power Terminal Block UPS Inputs UPS Outputs Q1 Switch Q3 Switch Q2 Switch 4

Schematic 5

Considerations Environmental S The wall area selected for the MBP installation must be structurally sound and able to accommodate the size and weight of the unit. Refer to Mounting the MBP on page 9. The MBP should be kept in a climate-controlled environment having a temperature range of 0 to 40 C [32 to 104 F] and a relative humidity of 0% to 95%, non-condensing. The MBP must be protected at all times from excessive moisture, construction dirt, corrosive elements, and other contaminants. 36in [914mm] 18in [457mm] 6

Installation Overview Warning: Review Safety on page 1 before starting this installation. Pay strict attention to all safety warnings and caution notices! Tools ALL INTERNAL cable connections were made prior to shipment. EXTERNAL cable connections with the UPS need to be made on-site. EXTERNAL cable connections from the utility also need to be made on-site. EXTERNAL cable is not supplied. Control wire connections between the UPS and the MBP additionally need to be made on-site. Control wires are not supplied. Panel board breakers must be ordered separately. Tie-wraps are not supplied. The following tools are required for this installation: Dolly/hand-truck Tape measure Pliers Level Marker Drill M10 nut driver Standard (flathead) Phillips screwdriver T30 Torx screwdriver 4mm Allen wrench 1/2 socket with ratchet Panel board breakers The 42-position panel board supports the following Square D 1-, 2-, and 3-pole bolt-on circuit breakers. All of the circuit breakers listed below have been pre-tested and approved by APC. Breaker Type APC Part# Breaker Type APC Part# 1-pole, 20Amp PD1P20ABBSD 3-pole, 20Amp PD3P20ABBSD 2-pole, 20Amp PD2P20ABBSD 3-pole, 80Amp PD3P80ABBSD 2-pole, 30Amp PD2P30ABBSD 3-pole, 100Amp PD3P100ABBSD 7

Removing the front door (optional) Note: Front door removal is NOT a requirement for this installation. However, removing the door will allow better access to the internal components. 1. Place the MBP on its back such that its front door is facing straight up. 2. Use the enclosed keys to unlock and then open the front door. 3. Disconnect the internal ground cable from the ground stud on the door. Use an M10 nut driver to remove the M6 flange nut securing the cable to the stud. 4. Using your thumb and forefinger, pull the three rubber plugs off the bottom ends of the three hinge clips. 5. Using pliers, remove the three hinge clips connecting the door to the enclosure. 6. Remove the door. Store the door and all hardware in a safe location for later re-attachment. Front Door Locks (2) Rubber Plugs (3) Hinges (3) Hinge Clips (3) 8

Mounting the MBP APC by Schneider Electric recommends mounting the MBP to 3/4 inches plywood backing (36 in [914mm] high x 28 in [711mm] wide). 1. Attach the 3/4 inches plywood securely to the designated wall area. The wall should be strong enough to support the 120lb [54.5kg] MBP. Leave at least 18in [457mm] of space between the floor and the bottom of the plywood. Use appropriate hardware for the type of wall employed. 2. Measure and mark four (4) mounting-hole locations on the plywood backing. The locations will be in the shape of a rectangle measuring 25.94in [659mm] across and 33.86in [860mm] down. 3. Drill starter holes in each of the four marked locations. 4. At least three people are needed to lift the MBP and position it against the plywood backing. Line up the MBP s four mounting holes with the four drilled starter holes. 5. Screw four (4) 1/4 x 1 inches hex-head lag bolts, along with four (4) 1/4 inches flat washers, into the holes. Use a 1/2 inches socket with ratchet and tighten until rigid. 25.94 in [659] 1/4 x 1 in Lag Bolt (4) 1/4 in Flat Washer (4) 33.86 in [860] Minimum 18 in [457] from floor! 9

Internal cable connections For the convenience of the installer, ALL internal MBP cable connections were made prior to shipment. Check to make certain the following internal cable connections were completed: Power Terminal Block [L1, L2, L3, N, top-to-bottom] to Input Bus [L1, L2, L3, N, top-tobottom] Output Bus [L1, L2, L3, top-to-bottom] to Input Fuse Block [L1, L2, L3, top-to-bottom] Output Bus [N] to Neutral Bar [N] Output Fuse Block [L1, L2, L3, top-to-bottom] to Panel Board [L1, L2, L3, left-to-right] Neutral Bar [N] to Neutral Bar [N] (refer to Internal components on page 4) Control Terminal Block to optional customer contacts [1, 2, 3, 4, 5, 6] and UPS connections for Q3 [7, 8]. Note: The control wires from the UPS MUST be connected to the Normally Closed Auxiliary Contacts on Q3 [7, 8]. DO NOT use terminals 5 and 6 for these connections! Refer to Schematic on page 5 and to the appropriate wiring diagram in the UPS Installation Manual. Output Fuse Block to Panel Board [L1, L2, L3] Power Terminal Block to Input Bus [L1, L2, L3, N] Output Bus to Input Fuse Block [L1, L2, L3] Output Bus to Neutral Bar [N] 10

Making external cable connections Note: Utility cables can enter through the top or the bottom of the MBP. However, BOTTOM is recommended. External cables can enter the MBP through any of the available 1-inch [25.4mm] knockouts, or by making larger cutouts in the top or bottom plates of the enclosure. Each plate offers 22 knockouts and the ability to create up to four (4) 2-inch [50.8mm] cutouts. Prior to making any of the following external cable connections, establish an appropriate point of access by knocking out a 1-inch hole or cutting a larger hole in the top or bottom plate. The plate can be removed using a Phillips screwdriver to loosen the 12 screws securing it to the enclosure. An M10 nut driver is needed to remove the M6 flange nut securing the ground cable to the plate s ground stud. The cables are typically color coded: L1 = black, L2 = red, L3 = blue, N = white, and G = green. Utility connections. 1. Connect the four inputs [L1, L2, L3, N, top-to-bottom] from the Utility to the Power Terminal Block. Use a standard (flathead) screwdriver and torque to 60in-lbs [7Nm]. 2. Connect the one ground input [G] from the Utility to the Ground Terminal Compression Lug. Place the cable end in the bottom section of the compression lug, and then use a standard (flathead) screwdriver and torque to 240in-lbs [27Nm]. Utility to Ground [G] G Utility to Power Terminal Block [L1, L2, L3, N] 11

UPS connections. Note: UPS cables can enter through the top or the bottom of the MBP. However, BOTTOM is recommended. Refer to the Smart-UPS VT 10-30kVA or MGE Galaxy 3500, 208V Installation Manual for MBP cable connections at the UPS. 1. Connect the four UPS inputs [L1, L2, L3, N, top-to-bottom] to the Q1 Switch in the MBP. Use a 4mm Allen wrench and torque to 60in-lbs [7Nm]. 2. Connect the four UPS outputs [L1, L2, L3, N, top-to-bottom] to the Q2 Switch in the MBP. Use a 4mm Allen wrench and torque to 60in-lbs [7Nm]. 3. Connect the two UPS control wires to Pins 7 and 8 in the MBP Control Terminal Block. Use a standard (flathead) screwdriver and make the screws hand-tight. Control Wires [7, 8] UPS Inputs to Q1 UPS Outputs to Switch [L1, L2, L3, N] Q2 Switch [L1, L2, L3, N] 12

Re-attaching the front door Note: This section applies only if the front door was removed at the start of the installation process. If you chose not to remove the door, ignore this section. Re-attaching the front door requires at least two people: one to hold the door in place, and the other to make the necessary hardware connections. 1. Holding the door at an angle to the MBP enclosure, re-insert the three hinge clips into the three door hinges. 2. Using your thumb and forefinger, push the three rubber plugs onto the bottom ends of the three hinge clips. 3. Keeping the door open, re-connect the internal ground cable to the ground stud on the inside of the door. Place the M6 flange nut over the cable lug on the stud. Use an M10 nut driver and torque to 120in-lbs [14Nm]. 4. Close and lock the front door. Hinge Clips (3) Hinges (3) Rubber Plugs (3) 13

Installing Panel Board Breakers This section describes how to install breakers to the MBP s 42-position panel board. Electrical Hazard: Before installing breakers, make sure ALL MBP switches are in the OFF position. From normal operation, first switch Q2 OFF, and then switch Q1 OFF. 1. Use the enclosed keys to unlock and open the front door of the MBP. 2. Select the next available breaker position(s) on the panel board, and then snap the new 1-, 2-, or 3-pole breaker into the appropriate guard rail. Note: The panel board supports Square D bolt-on circuit breakers. For a listing of recommended breakers, refer to Panel board breakers on page 7. The top pole of a 3-pole breaker must always be placed in an L1 position on the panel board. Counting down from the top, these are positions 1, 7, 13, 19, etc. on the left side of the board and positions 2, 8, 14, 20, etc. on the right side of the board. 1. Make the bolt-on connections (those nearer the center of the panel board). Use a standard (flathead) screwdriver and torque to 24in-lbs [3Nm]. 2. Remove the corresponding plastic blanking plate(s) located directly in front of the newly installed breaker. The blanking plates can be accessed through the smaller, hinged panel board door at the front of the MBP. Use one of the front door keys to open this door. 3-pole Breaker (positions 1, 3, 5) 3-pole Breaker (positions 2, 4, 6) Bolt-on Connections Note: After installation, panel board breakers can be accessed by simply opening the panel board hinged door. 14

Appendix A: Changing Fuses Warning: Before changing fuses, make sure ALL MBP switches are in the OFF position. From normal operation, first switch Q2 OFF, and then switch Q1 OFF. Note: Replace ALL blown fuses with Bussmann Class J 90 Amp fuses (p/n JKS-90). Removing fuses 1. Open the front door of the MBP to access the fuse block. Use the enclosed front door keys. 2. Using a plastic or insulated fuse puller, tightly grasp the center section of the blown fuse. 3. Pull the fuse toward you, forcing its release from the two sets of spring clasps. Replacing fuses 1. Using a plastic or insulated fuse puller, tightly grasp the center portion of the replacement fuse. 2. Align the fuse s metallic ends with the two sets of spring clasps that will hold it in place. 3. Push the fuse into the two sets of clasps until the clasps snap around the metallic ends. 4. Close and lock the front door. Spring Clasps (top and bottom) Metallic End (top and bottom) 90A Fuse Fuse Block Fuse Puller Note: After changing fuses, the MBP can be returned to normal operation by first switching Q2 ON, and then switching Q1 ON. Q3 remains OFF. 15

APC Worldwide Customer Support Customer support for this or any other APC product is available at no charge in any of the following ways: Visit the APC Web site to access documents in the APC Knowledge Base and to submit customer support requests. www.apc.com (Corporate Headquarters) Connect to localized APC Web sites for specific countries, each of which provides customer support information. www.apc.com/support/ Global support searching APC Knowledge Base and using e-support. Contact the APC Customer Support Center by telephone or e-mail. Local, country-specific centers: go to www.apc.com/support/contact for contact information. For information on how to obtain local customer support, contact the APC representative or other distributors from whom you purchased your APC product. Entire contents copyright 2009 American Power Conversion Corporation. All rights reserved. Reproduction in whole or in part without permission is prohibited. APC, the APC logo, and TRADEMARK NAMES are trademarks of American Power Conversion Corporation. All other trademarks, product names, and corporate names are the property of their respective owners and are used for informational purposes only. 990-4198D-001 *990-4198D-001* 8/2009