CALCULATED VS. ACTUAL SHORT CIRCUIT CURRENTS FOR VRLA BATTERIES



Similar documents
Effects of AC Ripple Current on VRLA Battery Life. A Technical Note from the Experts in Business-Critical Continuity

Charger Output AC Ripple Voltage and the affect on VRLA batteries

Constant Voltage Charger Selection for VRLA Batteries

THE PROPER CHARGING OF STATIONARY LEAD-ACID BATTERIES. (YOUR BATTERY IS ONLY AS GOOD AS HOW YOU CHARGE IT.)

LEAD ACID BATTERY working LIFETIME STUDY

OHMIC MEASUREMENTS: THE HISTORY AND THE FACTS

NorthStar Battery (NSB) Telecom Installation and Operation Guide

Substation Battery & Charger Maintenance

Conductance Testing as an Integral Element in Battery Management

If you accidentally get battery acid on your skin, flush it with lots of water

Experiment #3, Ohm s Law

LEAD-ACID STORAGE CELL

LEAD CRYSTAL. User Manual. Valve-regulated lead-crystal batteries Energy storage Cells

Using Thermocouple Sensors Connecting Grounded and Floating Thermocouples

Line Reactors and AC Drives

Capacity Testing of VRLA Batteries (20 to 200 Ampere-Hours Capacity)

The Time Constant of an RC Circuit

Basic RTD Measurements. Basics of Resistance Temperature Detectors

Wet vs Sealed Batteries A detailed explanation of the differences between charging "Wet" Batteries and charging "Sealed" Batteries.

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Lead Acid Battery Terminology Glossary

NP Series VALVE REGULATED LEAD-ACID BATTERIES

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören

Application Note. So You Need to Measure Some Inductors?

EE 1202 Experiment #4 Capacitors, Inductors, and Transient Circuits

2. Add the following definitions to 3.3 General Definitions and renumber 3.3 as required:

TRANSPORT OF DANGEROUS GOODS

Chapter 11. Inductors ISU EE. C.Y. Lee

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

PS-6.2 Explain the factors that determine potential and kinetic energy and the transformation of one to the other.

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Aircraft Electrical System

Battery Technology for Data Centers and Network Rooms: Lead-Acid Battery Options

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

Electrical Resonance

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

DC GROUND FAULT DETECTION PROVIDED FOR UNINTERRUPTIBLE POWER SUPPLIES

Measurement of Capacitance

Fuse Selection Guide

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

Experiment #11: LRC Circuit (Power Amplifier, Voltage Sensor)

Thyristor-controlled power supplies and battery chargers

Solar Wind Microhydro Water Pumping Inverters Batteries Professional system design and installation

11: AUDIO AMPLIFIER I. INTRODUCTION

Lab E1: Introduction to Circuits

Introduction to Electricity & Magnetism. Dr Lisa Jardine-Wright Cavendish Laboratory

Bourns Resistive Products

WINDING RESISTANCE TESTING

UPS Applications and VRLA Battery Sizing

Battery Handbook. By: RON SMITH

Ametek Prestolite Power AC power / Charger / Battery terms

SYNCHRONOUS MACHINE TESTING WITH MOTOR CIRCUIT ANALYSIS INSTRUMENTATION

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Frequency Response of Filters

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

E. K. A. ADVANCED PHYSICS LABORATORY PHYSICS 3081, 4051 NUCLEAR MAGNETIC RESONANCE

Life Cycle Testing of Series Battery Strings with Individual Battery Equalizers

Temperature Compensated Charging of Lead Acid Batteries

Fox-2 MPPT Unit Testing

CALIBRATION OF A THERMISTOR THERMOMETER (version = fall 2001)

EXTENDING THE LIFE OF POWER FACTOR CAPACITORS

UN Manual of Tests and Criteria, Sub-section 38.3, Amendments to the 5 th edition, effective 2014 January 1 st

Inrush Current. Although the concepts stated are universal, this application note was written specifically for Interpoint products.

DIRECT CURRENT GENERATORS

Using NTC Temperature Sensors Integrated into Power Modules

SOC Understanding Overcurrent Circuit Protectors

AAV003-10E Current Sensor

A Practical Guide to Dielectric Testing

SYNCHRONOUS MACHINES

Selecting IHLP Composite Inductors for Non-Isolated Converters Utilizing Vishay s Application Sheet

LM3940 1A Low Dropout Regulator for 5V to 3.3V Conversion

WHY DIFFERENTIAL? instruments connected to the circuit under test and results in V COMMON.

Inductors in AC Circuits

6 ELECTRICAL PARAMETERS

Charge Regulator SCR 12 Marine

Lab 3 - DC Circuits and Ohm s Law

13 ELECTRIC MOTORS Basic Relations

Understanding Power Impedance Supply for Optimum Decoupling

ES250: Electrical Science. HW7: Energy Storage Elements

LAB 7 MOSFET CHARACTERISTICS AND APPLICATIONS

TESTS OF 1 MHZ SIGNAL SOURCE FOR SPECTRUM ANALYZER CALIBRATION 7/8/08 Sam Wetterlin

MULTIPLE CHOICE. Choose the one alternative that best completes the statement or answers the question.

USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG

What is PWM? Why is there so much excitement about PWM?

A Comparison of Various Bipolar Transistor Biasing Circuits Application Note 1293

BJT Characteristics and Amplifiers

Bosch C3 and C7 Battery Chargers: Smart, safe and simple to use

ACHIEVING CHARGE QUALITY FOR LEAD ACID BATTERIES IN INDUSTRIAL MOTIVE APPLICATIONS

Experiment #5, Series and Parallel Circuits, Kirchhoff s Laws

Chip Diode Application Note

The full wave rectifier consists of two diodes and a resister as shown in Figure

Renewable Energy Test Station (RETS) TEST PROCEDURES FOR SOLAR TUKI

SMT POWER THERMISTORS

RGB for ZX Spectrum 128, +2, +2A, +3

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

GENERAL SCIENCE LABORATORY 1110L Lab Experiment 6: Ohm s Law

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Introduction to the Smith Chart for the MSA Sam Wetterlin 10/12/09 Z +

Automotive Sensor Simulator. Automotive sensor simulator. Operating manual. AutoSim

Transcription:

CALCULATED VS. ACTUAL SHORT CIRCUIT CURRENTS FOR VRLA BATTERIES Scott D. Gerner Manager, Product Development Paul D. Korinek Director, Product Engineering C&D Technologies Milwaukee, WI 53212 Tom E. Ruhlmann Manager, Technical Services INTRODUCTION A shorted lead acid battery has the capability of delivering an extremely high current, 1 to 1 times the typical discharge current used in most applications. Electrical systems using batteries must be properly protected to avoid potentially dangerous fault conditions. In this paper, we compare the short circuit currents as predicted using generally accepted estimation methods versus actual measured values for individual batteries and battery systems. Practical considerations such as the effects of temperature, state of charge and type of circuit protection device are also presented. A battery s short circuit current is typically estimated by dividing its open circuit voltage by its internal resistance. While the true DC internal resistance can be determined using a series of discharge tests, it is often simpler to directly measure the battery s impedance or conductance using an AC test signal; several test units are commercially available. Due to differences in resistance versus impedance values, the calculated short circuit currents will naturally be different from those obtained using traditional DC test methods. OBJECTIVES In this paper, the following topics regarding short circuit current are presented: - Comparison of values obtained using estimation methods versus actual measurements for a range of VRLA battery designs - Comparison of resistance, impedance and conductance measurements as a predictive tool - Effects of temperature, state of charge and circuit resistance BATTERY DESIGN In DC systems, a shorted battery has the potential to deliver an extremely high current in a short amount of time. The magnitude of the current is dependent upon the battery s internal resistance and the external circuit resistance. The battery s internal resistance is related to product design attributes such as plate surface area, inter-plate spacing, separator material type, electrolyte type (gel or absorbed liquid), acid gravity and saturation, connecting strap/weld/terminal post diameters and grid design. For new batteries, both state of charge and temperature can have modifying effects on the internal resistance. As a VRLA battery ages, the resistance often rises due to corrosion of the positive grid, changes in active material structure and electrolyte dry out. The total resistance of the battery string is the sum of the battery internal resistances plus the resistance of external components such as inter-connection hardware and circuit protection devices. The amount of time to achieve maximum current depends upon such factors as the capacitive and inductive reactance of the battery and the external circuit, as well as the battery s electrochemical response 1. Often, the peak short circuit current occurs within 5 to 15 milliseconds. Without some form of protection such as a fuse or breaker, a short circuit condition can cause permanent damage to the battery. In effect the battery can itself becomes the fuse. If the weakest link is within the battery, melting and opening of an internal connection has the potential to ignite the hydrogen/oxygen gas mixture contained within the battery headspace, resulting in a potentially dangerous situation. Melting of the external inter-battery connections may occur, particularly if the terminal connections are loose. While an external failure typically results in a more benign open circuit condition, severe and/or prolonged overheating may lead to permanent battery and equipment damage, including the potential for fire. 7 1

SHORT CIRCUIT CURRENT ESTIMATION Using Ohm s law, the potential maximum, zero voltage short circuit current can be calculated by dividing the battery s nominal open circuit voltage by its resistance (I = V/R). By discharge testing over a wide range of currents and measuring the battery s voltage response, its internal resistance can be calculated from the slope of the voltage versus current (R = dv/di). Extrapolating this line back to zero volts yields the resistance-free or zero voltage short circuit current. As the range and magnitude of discharge currents increase, the accuracy of the resistance and short circuit current values increase. In IEC896-2 Stationary Lead-Acid Batteries, Part 2: Valve Regulated Types, the estimated short circuit current is obtained by discharging a battery at 4 times and 2 times its rated 1 hour discharge current (I 1 at 25 o C to 1.75 volts per cell). At the 4X rate, the battery voltage is measured at 2 seconds. After a 5 minute rest without recharge, the battery is discharged at the 2X rate and the voltage is measured after 5 seconds. From these two points, a line is extrapolated back to zero volts to calculate the short circuit current. A rule of thumb estimation method suggests multiplying the 1 minute rate by 1 to obtain the short circuit current; however, there may be a wide variation between estimated and actual values depending on battery design. TEST METHOD AND EQUIPMENT Standard production C&D Dynasty Division VRLA batteries were tested. Products spanned the full range of product sizes, from 33 to 2 AH (2 hour AH capacity), including batteries using gelled and absorbent glass mat (AGM) construction. All the battery models are multi-cell, nominal 12 volt design, with the exception of the 6 volt 2 AH product. Typically, three samples of each type were tested. Batteries were boosted to full state of charge and allowed to rest for 72 hours before measuring the open circuit voltage (OCV), impedance and conductance. The following commercially available test equipment was used to measure impedance or conductance: Manufacturer Model Type Frequency Hewlett Packard HP4328A Impedance 1 Hz Biddle Bite Impedance 6 Hz Alber Cellcorder Resistance N/A Midtronics Micro Celltron Conductance unknown Each battery was constant current discharged at 25 o C at 4X its rated AH capacity for 2 seconds with voltage and current readings taken at.1 second intervals and at 2X for 5 seconds at.5 second intervals, per the IEC standard. The voltage and current was recorded using an Agilent 3497 data-logger. Some batteries were given additional discharges at 1X and 2X for 3 seconds with readings taken at.5 second intervals to obtain additional current and voltage points for a trendline fit and extrapolation to zero volts. After testing, batteries were recharged. Finally, each battery was dead shorted, connected to a shorting circuit consisting of a shunt (5A+.25%), Hall effect transducer [model LEM LT 4T (4A+.5%)], 26 feet of MCM-55 cable and a knife switch. A 2 channel Fluke 19 Scopemeter with automatic triggering was attached to the Hall effect transducer and to the battery terminals. Current and voltage readings were recorded at.2 millisecond time intervals from to.2 seconds. An Agilent 3497 data-logger was used to monitor the shunt current and battery terminal voltage at 4 millisecond time intervals from to 3 seconds. The shorting circuit had a resistance of 1.8 milli-ohms, as measured with a Biddle DLRO micro-ohmmeter. The inductance of the circuit was not measured. To determine the effect of temperature, sets of UPS12-14 (12V-33AH) batteries were float charged at 13.65V (2.275 volts/cell) for 48 hours at 2, 11, 24, 33 and 4 o C in a temperature-controlled environment. OCV, impedance and conductance readings were measured and each battery was dead short tested using the test method described above. To measure the effect of state of charge (SOC%), similar dead short tests were conducted on a set of nine UPS12-17 batteries (12V-5AH). Individual batteries were constant current discharged at the 5 hour rate (8.66A) for, 1.25, 2.5 and 3.75 hours at 25 o C to achieve respective SOC values of 1, 78, 57 and 35% based on the 2 hour AH capacity. 7 2

DISCUSSION Discharge Voltage versus Time A typical series of discharge voltage versus time curves are shown in Figure 1. This specific example is for a battery discharged at a constant current rate 4, 2, 1 and 2 times its 1-hour discharge rate from an open circuit condition. Similar results are obtained if the battery discharge starts from float charge. Once a load is applied to the battery, the voltage quickly falls to a steady state level where the voltage slowly decreases with increasing time and depth of discharge. The initial voltage drop primarily consists of two components, a resistive loss (V = IR) and an electrochemical voltage loss, also called polarization. Both terms are dependent upon the load current. Note that for these discharges, the time interval between voltage readings was 5-1 milliseconds. For comparison, typical voltage and current versus time curves for a battery that was shorted using the shorting circuit are displayed in Figure 2. For this test, sample measurements were recorded at.2 millisecond intervals in order to capture the rapid change in values. Note that steady state minimum voltage and maximum current conditions were attained within 5 to 1 milliseconds. The time constant for this circuit, the time for current to reach 63% of steady state is approximately 4 milliseconds. With a 1.8 milliohm external resistance, the battery voltage dropped to approximately 3. volts. The jagged current line is due to signal noise as opposed to variations in the actual short circuit current. For comparison to the 4X to 2X rates used previously, the short circuit current of 1745A at 1 milliseconds in this example is approximately 64 times the 1 hour discharge rate (2.73A at the 1 hour rate). 13. 12.5 12. 11.5 11. 1.5 1. Figure 1 Voltage versus Time for R ange ofdischarge C urrents 1X 2X 9.5 9. 2X 8.5-2 2 4 6 8 1 12 14 16 18 2 22 S econds 4X 2 18 16 14 12 1 8 6 4 2 Figure 2 D ead ShortVoltage and Currentvs.Time Current 5 1 15 2 25 3 35 4 45 5 Milliseconds 2 18 16 14 12 1 8 6 4 2 Short Circuit Estimation Methods The IEC method of estimating the short circuit current is based on discharging the battery at 4x its rated 1 hour discharge rate for 2 seconds, rest for 5 minutes, followed by a 2x discharge for 5 seconds. The discharge times are long enough to allow the voltages to reach a steady state value (Figure 1). The IEC method specifies to use these two discharge points to draw a line back to zero volts to estimate the short circuit current. The slope of the line is equivalent to the battery s true DC resistance. This method was used to derive the short circuit currents and resistances for three samples (TEL12-3, 12 volt 3AH battery) shown in Figure 3. Because the two voltage and current points are so close together and significantly less than the short circuit value, even small variations in voltage can lead to gross estimation errors. As the test discharge current increases (and load voltage decreases), the estimated resistance and short circuit current values improve. Discharging at 1X and 2X for 3 seconds allows the battery to achieve a steady state voltage (Figure 1). Using the 3 second voltages at the 1 and 2X discharge rates for these same three samples, the predicted short circuit current increases significantly over just the 4 and 2X rates. Using the shorting circuit, which produces an even higher current and lower voltage, approaching the true zero voltage point, an even better estimate of short circuit current and internal battery resistance will be obtained. The shorting circuit test results for the three TEL12-3 samples are shown in Figure 4. Increasing the range and magnitude of discharge currents (and voltages) significantly helps to improve the accuracy of estimating the battery s short circuit current and internal resistance values. A comparison of the average values obtained using each test method is summarized in Table 1 for the specific battery model (TEL12-3) used in Figures 1 to 4. A comparison of the zero voltage short circuit currents predicted by the IEC versus the shorting circuit method for the entire C&D Dynasty product line is shown in Figure 5. This graph shows the test values for individual batteries, not averaged results for a given battery model. Typically, three samples of each battery model were tested; the three point data clusters in 7 3

Figure 5 are representative of battery and test method consistency. All of the IEC method data points fall considerably below the corresponding values measured using the shorting circuit. Underestimating the true short circuit current may result in improper sizing of the circuit protection device. In this program, all tested products had a 1 hour discharge current that ranged from 2.7 to 18.2 amps. The 4X and 2X rates are relatively common discharge rates and most test laboratories have test equipment to handle this range of currents. However, 1X and 2X rates may be beyond the capabilities of some discharge test equipment, particularly for batteries with large amp-hour capacities. The zero voltage short circuit current is the absolute maximum potential current at theoretically zero resistance. In actual applications, the resistance of the external circuit will reduce the actual short circuit current. With the shorting circuit, which had a relatively low external resistance of 1.8 milli-ohms, the short circuit current was significantly reduced from the zero voltage value. In the example with the three TEL12-3 models (Figure 4), the average zero voltage short circuit current was 232A; however, with the shorting circuit, the current was only 17A. 14 Figure 3 Short Circuit CurrentEstim ated fro m 4X and 2X Rates 3 Figure 4 C u rre n ts Estim ated fro m "S h o rting C ircuit" Test 12 1 8 6 4 2 # m O hm s 1 916 13.4 2 1329 8.9 3 1121 1.8 2 4 6 8 1 12 14 2X 4X 25 2 15 shorttest 1 # m O hm s 2X 1 2383 4.9 1X 2X 5 2 2318 5.1 4X 3 2262 5.2 2 4 6 8 1 12 14 Table 1. Estimated TEL12-3 Short Circuit Current and Internal Resistance by Test Method Value Units 4-2X (IEC Method) 4, 2, 1, 2X 4X-Shorting Circuit Current Amps 1122 2 232 Resistance Milli-ohms 11. 6. 5.1 IE C P redicted Current(A m p s ) 4 35 3 25 2 Figure 5 IE C P redicted versus "S h o rting C irc u it" - Zero Voltage Current FullP roductline 15 Trendline 1 1 2 3 4 5 6 "S h o rting Circ u it" Current(A m p s ) Im pedance 12 1 8 6 4 2 C orrection Factor R 2 Alber.65.943 Biddle.88.967 H P 1.1.979 M idtronics 4.31.95 Figure 6 Im pedance M easurem ents vs.d C Resistance 2 3 4 5 6 7 8 Calculated DC Resistance (m illi-ohm s) Alber (X/1) Biddle 1:1 C orrelation HP M idtronics (1/X) 7 4

Resistance Measurements While the short circuit current value at zero volts is indicative of the maximum potential current, the internal resistance of the battery is actually a more important value for application purposes where the actual short circuit current may be a significantly smaller value. The short circuit current (I SC ) for a battery system can be predicted using Ohm s law, as follows I SC = V BATT / R TOTAL, where R TOTAL = R BATT + R EXTERNAL V BATT R BATT = Nominal battery system voltage, 2. volts per cell x number of cells in series string = Internal battery resistance, nominal resistance per battery x number of batteries in series string R EXTERNAL = External system resistance, including all cables, circuit breaker/fuse and fault From short circuit tests, the internal battery resistance can be calculated from the slope of the load voltage vs. current line, as demonstrated in Figures 3 and 4. Prior to its final shorting circuit test, the impedance (or conductance) of each battery was measured. A plot of the true DC resistance (milli-ohms) as calculated from the shorting circuit test versus impedance and conductance is shown in Figure 6 for all 12 volt battery models. The Alber resistance values were divided by 1 to obtain proper scaling. The Midtronics unit measures battery conductance. For graphical and scaling purposes, the Midtronics values shown in Figure 6 are expressed as 1 divided by the measured value. All of the direct reading values correlate with the calculated DC resistance, following a similar trend; however, there is a wide range in offsets between the various manufacturers test equipment and the absolute DC resistance. In order to provide a better correlation between each manufacturer s test unit and DC resistance, a correction factor has been calculated to fit the test data to the 1:1 correlation line. The multiplication correction factor and correlation coefficient (R 2 ) is shown in the key on Figure 6. The test technique, including AC frequency portion of the test signal may account for the differences in offset. Although there was a good correlation with 12V batteries, direct reading values for the 6 volt battery model (UPS6-62) did not correlate well with calculated DC resistance for any test equipment with the exception of the Hewlett Packard unit. 48V String Application Tests A 48 volt string consisting of 4 UPS12-2 batteries was assembled for short circuit testing in a typical UPS style cabinet system with a thermal magnetic breaker (ABB 1A, 3 pole, model S3N1TW). Similar equipment to the prior shorting circuit tests was used with the exception that the knife switch was replaced with a pressurized bolt switch to minimize arcing. Data was collected at.1 millisecond intervals. Resistance measurements of the interconnect hardware, breaker and external test equipment were measured using a Biddle micro-ohmmeter. Using the equation above, we predicted a short circuit current of 255 amps [48V / (.16 +.28)], which compares reasonably with the actual measured average steady state test result of 253 amps during the first 5 milliseconds where the current level was relatively stable. During the first millisecond, the current spiked nearly instantaneously to 5A, then rapidly dropped to the steady state value. These results are unlike similar tests with single 12 volt batteries using the shorting circuit (Figure 2), where the current increased to a steady state value over the initial 4 milliseconds. The differences may be due to the relative length of cabling for each system and their inductive properties. Note that the actual string voltage does not drop to zero volts but rather from 51 down to 9 volts due to the circuit resistance. Between 5 and 9 milliseconds the thermal magnetic breaker started to open, resulting in a steady decline in current, not an abrupt current drop. By 9 milliseconds, the current was down to zero. The current and voltage vs. time plots are shown in Figure 7. This test was repeated three times, with ~3 minutes rest time in between each short test, without recharge; the thermal magnetic breaker functioned properly and in a very consistent manner, producing nearly identical voltage and current versus time traces. The batteries were protected by the thermal breaker and remained fully functional. Figure 7 48V String ShortCircuitTest- Therm alm agnetic Breaker Figure 8 48V String ShortCirc u ittest- Fused 6 6 6 5 5 5 4 4 4 3 3 3 2 2 2 1 1 1-2 2 4 6 8 1 12 14 Time (m s ) -2 2 4 6 8 1 12 14 Tim e (m s ) 7 5

For comparison, the same 48V string was set up with using a fuse (Ferraz A7F4, 7V, 4A semi-conductor fuse) rather than a thermal breaker. Data was collected at.2 millisecond intervals. Similar to the prior test, the initial current instantly spiked to 5A and decreased to a relatively steady state value after approximately 1 millisecond. Unlike the thermal magnetic breaker tests, there was a step change in current and voltage when the fault was cleared; however, the entire event lasted ~9 milliseconds. See Figure 8 for the current versus time plot. Using the equation above, we predicted a short circuit current of 262 amps [48V / (.16 +.23)] versus the actual steady state average of 268 amps. The batteries were protected by the fuse and remained fully functional. State of Charge In most applications, the battery is on constant trickle or float to keep it at 1% state of charge. However, the potential exists for a short circuit condition to occur after the batteries have been discharged, perhaps at initial installation before the batteries have received a freshening charge. To determine the effect of state of charge on short circuit current, a set of nine UPS12-17 batteries (12V-5AH) were discharged to different states of charge prior to a dead short test. Absolute current values were normalized in Figure 9 to show relative decrease in short circuit potential correlating with state of charge. The short circuit current stays relatively high even for low states of charge; for example, currents exceeded 9% of nominal even at ~6% state of charge. Although there is a reduction in positive (PbO 2 ) and negative (Pb) active material with discharge, there remains ample material for a short duration, high rate discharge. Following the discharge, the rest time before the dead short test will also allowed higher gravity acid to diffuse from the separator into the pores of the plates, somewhat replenishing the battery s capacity. C u rre n t (% ) 11 1 9 8 7 Figure 9 Relative S hortcirc u itc u rre n t vs.s tate ofc harge 6 3 4 5 6 7 8 9 1 State ofc harge (% ) C u rre n t (% ) 12 1 98 96 94 92 9 Figure 1 Nom inalshortcircuitc urrentvs.tem perature 25C = 1% 88 5 1 15 2 25 3 35 4 45 Tem perature (C ) Temperature Effects In many applications, the ambient temperature is not a perfectly controlled at 25 o C. Sets of three UPS12-14 (12V-33AH) were placed on float at 2.275 volts/cell at each test temperature point for 48 hours for conditioning. Prior to conducting the dead short test on each battery, the impedance and conductance were measured. Current values for each temperature were averaged and then normalized based on 1% capacity at 25 o C to obtain the results shown in Figure 1. Over the range from 2 to 25 o C, the nominal current only changes ~1%, with virtually no change as the temperature increases from 25 o C up to 4 o C. Acid conductivity versus temperature follows a similar trend; however, conductivity values nearly halve as the temperature decreases from 4 to 2 o C. In an equivalent circuit model of a battery, the terminals, straps, plates, separator and electrolyte all act as resistors in series. Estimates of the contribution of each component indicate the acid may account for ~15% of the total resistance of a typical VRLA battery at 25 o C. At low temperatures, the decrease in acid conductivity and chemical reaction rates accounts for the reduction in short circuit current. Resistance versus Temperature As part of the short circuit temperature testing, impedance and conductance readings were measured at each test temperature immediately before the dead short test. The relationship between impedance and temperature for each type of test equipment is shown in Figure 11. A least squares trend-line was fit through each set of data points to calculate a value of micro-ohms per degree Celcius from the slope of the line. For scaling purposes, the Alber resistance values were divided by 1; the Midtronics values were converted from conductance to resistance by taking the inverse and multiplying by 1. For this temperature range, the slopes are fairly linear. Although there is only a slight decrease in impedance versus temperature, the Alber and Biddle units show a much stronger relationship with a negative slope of 19 u-ohms/c versus only.3 to.8 u-ohms/c for the Midtronics and HP units. The difference between the test unit s measurement techniques and AC frequencies may be responsible. 7 6

Resistance and Product Design Battery design can have a significant effect on its resistance and short circuit current. Plate count and the type of electrolyte retention (gelled or AGM construction) are two primary contributors to battery resistance. The multiplied product of plate height, plate width and positive plate count yield the opposed positive surface area per cell. Similar to resistors in parallel, as the plate count and corresponding surface area increase, the resistance decreases. Grid design attributes such as frame and wire cross sectional area, grid conductivity and wire pattern (radial, rectilinear) all have modifying effects as well. The type of separator and electrolyte (polyethylene/gel or absorbent glass mat/liquid) also play a major role in product resistance. A comparison of current versus load voltage and corresponding short circuit currents and resistances for three products that use the same case size and have the plate height and width, but have differing plate counts and separator systems is shown in Figure 12. The UPS12-37 (AGM 1) is designed for UPS high rate discharge applications, with 1AH capacity at the 2 hour rate. This product has a high plate count, 8 positives/9 negatives per cell and AGM construction, responsible for its low resistance and very high zero voltage short circuit current (2.2 milliohms, 545A). By comparison, the TEL12-9 is also AGM construction, but with only 6 positives and 7 negatives per cell, designed for lower, telecom discharge rates, it still has a 2 hour rating of 1AH. With the reduced plate count and increased inter-plate spacing, resistance increased and short circuit current decreased substantially (2.9 milliohms, 41A). Finally, the BBG18 is a gelled product with the same plate count and surface area as the TEL12-9. The polyethylene separator and the gelled acid itself account for the significant change in resistance and short circuit current (4.5 milliohms, 27A). Although all three batteries have the same external dimensions and similar sized plates, and the AGM products have the same 2 hour AH capacity, the products resistance and short circuit values can vary significantly due to internal design differences. 8. Figure 11 Im pedance versus Tem perature,u P S 12-14 Slope = m icro-ohm s/c 6 Figure 12 P roductd esign and Resistance Im pedance (m illi-o h m s ) 7. 6. 5. 4. 3. 2. 1.. 5 1 15 2 25 3 35 4 45 Tem perature (C ) Alber Biddle HP M idtronics Unit u-ohm /C Alber 19.3 Biddle 18.5 HP.8 M idtronics.3 C urrent(a m ps ) 5 4 3 2 1 Type Plates m -ohm s AGM 1 8+/9-2.2 AGM 2 6+/7-2.9 GEL 6+/7-4.5 2 4 6 8 1 12 14 Voltage AGM 1 AGM 2 GEL CONCLUSIONS Accurate battery system short circuit current and resistance values are required to properly size and select the proper circuit protection device. Estimated short circuit values can vary widely depending upon the test method and measurement technique. Multi-stepped discharge test methods that use a large span in current and voltage provide the best accuracy in estimating battery short circuit current and resistance. Equipment that directly measures a battery s resistive properties can provide a reasonable alternative to discharge tests, with the use of correction factors. Battery system circuit resistance, state of charge and temperature can reduce the nominal zero-voltage short circuit currents. Potentially dangerous short circuit conditions can be prevented with a better understanding of battery and circuit protection operation. Acknowledgements The authors wish to thank Mark Beutler for his efforts in instrumenting and conducting the short circuit tests. References 1. C&D Technologies, Battery Short Circuit Current Publication RS 1468 3/1996 7 7