Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems)



Similar documents
The Permanent Link in Field Certification Reasons, Advantages, Testing Challenges

The Evolution of Copper Cabling Systems from Cat5 to Cat5e to Cat6 Copper Cabling Standards and Technical Aspects

INTERNATIONAL STANDARD

Session 2; Cabling Technology in the Data Centre Media Choices; Copper Twisted Pair

Copper Patch Cords. Impact On Network Performance and Reliability

Specifying an IT Cabling System

INTERNATIONAL STANDARD

01. HARTING RJ INDUSTRIAL RJ45 ETHERNET CONNECTORS

Performance Verification of GigaSPEED X10D Installations with Fluke Networks DTX 1800 CableAnalyzer

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Category 6 Solutions. 4. Category 6 Solutions. 09/ IN TrueNet Structured Cabling. Introduction Cable Patch Panels... 4.

AMP CO Plus Insert for Cat. 6 A Applications

Accelerating Light. Copper Cabling Solutions. Category 6A

Planning for 10Gbps Ethernet over UTP Questions to Ask When Planning the Cabling Plant WHITE PAPER

Cat 5, 6 or 7? Standards. Background. A University Standard for Structured Wiring. Network Points Installed. British Standards.

HARTING Ethernet Cabling 8-poles Overview

Copper Pre-terminated Assemblies

Cabling Standards Update 2014

R&Mfreenet Advanced Cat 6 A Unshielded Connection Module

ATT-TP Ethernet Copper Cable & Ethernet Copper Assembly Specification

APR 2016 Rev M

Patch Cords / Cable / Cable Assemblies. Patch. Cords/Cable/ Premise Connectivity Systems. Cable Assemblies

ADC Structured Cabling Solutions

ANSI/TIA/EIA A, Commercial Building Telecommunications Cabling Standard.

Total Solutions Verification

European Normative EN system

Simpler all over. Simpler all round. 500 MHz. 10 GB ether. fully shielded. Poe+ Cat.6 A. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug

Structured Cabling, Earthing & Equipotential Bonding

SMARTen 24 UTP Patch Panels

Communication, Signal & Data Cables

Panduit 28 AWG Patch Cords Installation Guideline

The Quality Connection. Industrial IT cabling ISO/IEC / EN

Mixed High-Speed Ethernet Operations over Different Categories of Bundled UTP Cable

HIGH SPEED COMMUNICATIONS PLENUM CABLE CATEGORY 5e CMP FEP JACKETED, PVC-FREE UNSHIELDED TWISTED PAIR (UTP)

The effect of temperature on the bandwidth of telecommunications cabling in commercial buildings. Focus on the IBDN System 4800LX from NORDX/CDT

Resolution of comments 242 and 267 on Insertion loss measurements of installed fiber cables. Steve Swanson May 5, 2009

Disclaimer This information is collected and composed by QUANG DUNG TECHNOLOGY from Cablingdb.com. All information is copyrighted by Cablingdb.com.

SUBJECT: CENELEC VOTE FINAL DRAFT PR EN INFORMATION TECHNOLOGY -GENERIC CABLING SYSTEMS PART 1:GENERAL REQUIREMENTS AND OFFICE AREAS

SMARTen 24 STP Patch Panels

HARTING Ethernet Cabling 4-poles Overview

TECHNICAL SPECIFICATION

Category 6 UTP - Cabling System

1.1 SYSTEM DESCRIPTION.1 Data system includes data outlets and wiring for office and school applications.

Specification SFTP CAT6 Network Cable 23AWG CU

SC8108-A. NetWork Cable Tester. User Operation Manual. Taking Its Source At Sanling Science & Technology Good helper to network

KVM - DVI, USB 2.0, Cat 5 Extender

This paper will explain some of the more important factors on how UTP wires work; specifically it will cover the following:

Evolution of Cabling Standards TIA/EIA ISO/IEC CENELEC. by Paul Kish NORDX/CDT Chair TIA TR 41.8

RADOX railway cables acc. to EN and EN Edition 2009

HARAX circular connector

An Engineer s Guide to Full Compliance for CAT 6A Connecting Hardware

Dlp-s & WIRING DEVICES. THE MAXIMUM FReeDOM OF ChOICe. SNAP-ON AND UNIVERSAL TRUNKING FOR high AND LOW CURReNt DIStRIBUtION

ISO 9001: 2008 Boosting quality to differentiate yourself from the competition. xxxx November 2008

Part 1: General Requirements TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Testing 10 Gb/s Performance of Category 6 and 6A Structured Copper Cabling Systems within the Unified Physical Infrastructure SM (UPI)

Cat. 6 A EL Incredibly fast Get more

E Series. E Series. Category 6 and 5e. Features

Standard Buccaneer - Ethernet

12 Fibre MTP Jumper, MTP (non-pinned) to MTP (pinned)

Ethernet Patch Cord Wiring

6000 Series Buccaneer

The High Cost of a Low-Cost Cable Certification Tester

Sealed Industrial Ethernet Circular IP67 Cat. 5e RJ45 Connector System

ANSI/TIA/EIA A A Revisited. Residential Telecommunications Cabling Standard (Draft 6/22/99) Larry L. Hamlin, RCDD

Copper Cabling Troubleshooting Handbook

HARTING Ethernet Cabling 4-poles Overview

Category-6 / Class-E Cabling

Simpler all over. Simpler all round. fully Ether. PoE+ shielded. MHz. Data Voice. MFP8 Cat.6 A Field assembly RJ45 plug

White Paper: DC Resistance Unbalance Testing: Easy, Low-Cost Insurance for Your PoE Systems

HARTING Ethernet Cabling 4-poles Overview

This draft amendment A1, if approved, will modify the Technical Basis for Regulation TBR 14 (1994)

INTRODUCTION KRONE HIGHBAND. KRONE has a long history as a market leader in the communications and information industry.

Safety & Performance in the Wire and Cable Industry

This amendment A1 modifies the Technical Basis for Regulation TBR 12 (1993)

High Speed Cables for Enterprise Data Solutions Business Unit Telecommunication Systems

Network Engineers Everywhere:

Screened cable and data cable segregation

Copper Systems Contents

Innovative Connectivity Solution for Maximum Performance and Security

How to Choose the Right Cable Category

IT Cabling Solutions

Guiding Principles for the contents of Particular Materials Appraisals (Version approved at the WGP on 21 November 2006)

LSA-PLUS Series 2 Connection and Disconnection Modules and Accessories

White Paper. Power over Ethernet Plus Update and Cabling Considerations

TENDER: Tf{/ A

Global cable expertise for rolling stock

Structured and Point to Point Network Cabling for Industrial Automation

Product Bulletin. One Enterprise. One Infrastructure. One Partner. Shielded Cabling Systems

Case Study. Molex PDS Delivers Voice and Data Streams around Shanghai Unicom Tower

428 MY HOME Structured cabling system for the home sector

Network Design. Yiannos Mylonas

IP 20 B.1 8 IP 65 / IP 67 B Cables B Tools B IP 20 B.2 8 IP 65 / IP 67 B Cables B Tools B IP 20 B.

If you want to get an official version of this User Network Interface Specification, please order it by sending your request to:

Enhanced Category 5 Cabling System Engineering for Performance

5-port / 8-port 10/100BaseTX Industrial Ethernet Switch User Manual

Transcription:

Requirements for Modular Patch Cords (e.g. RJ45 patch cords for Cat5 and Cat6 cabling systems) Introduction The purpose of this document is to: 1) provide background information beneficial to specifiers and users; 2) provide an overview of the relevant and applicable standards for modular patch cords; 3) explain the importance of specifying and using compliant modular patch cords; 4) indicate how modular patch cords should be specified; 5) detail the methods by which compliance can be shown; 6) recommend a course of action when non-compliant modular patch cords are uncovered. Modular patch cords are a vital component of cabling channels, the performance of which determines how efficiently applications operate. The performance of modular patch cords is fully specified in international cabling standards,. These specifications include transmission requirements, conditioning tests, and qualification test methodology the fundamental elements required to verify modular patch cord performance. The need for this advice has become increasingly important because market research and independent testing of modular patch cords being marketed in the UK indicates that a majority of modular patch cords purporting to be, and marked as, compliant to the cabling standards were found to be non-compliant. This is particularly true of modular patch cords at the cheaper end of the price spectrum. Definition Modular patch cord is a generic term that encompasses, where applicable, equipment cords, patch cords and work area cords that can be used in structured balanced cabling systems, as defined in cabling standards ISO/IEC 11801:2002, EN 50173-1 and TIA-568-B. The construction of these modular patch cords consists of 4-pair flexible cables (specified in IEC 61156 series, etc.) terminated with 8-way modular (a.k.a. RJ-45) plugs (specified in IEC 60603-7 series, etc.). The construction of the cable shall use either insulated stranded or solid conductors, dependent upon the referenced cabling standard and intended usage. The cables and connecting hardware shall be either unscreened or screened; mixing of unscreened and screened components within a modular patch cord is not standardised. Note: Balanced cord is a term that encompasses modular patch cord, but also includes a cord that may have different connecting hardware terminated at one or both ends, e.g. an equipment cord that has a non-modular patch at the equipment end that is compatible with the specified equipment, or a patch cord that has proprietary non-modular plugs at both ends that are compatible with the specified cross-connect connection system. Whilst this TIN specifically addresses specifications for modular patch cords, the requirements are generally applicable to all balanced cords. Specifications exist for Category 5 (Category 5e in TIA-568-B), Category 6 and Category 7 (ISO/IEC 11801:2002 and EN 50173-1 only) modular patch cords. The transmission performance requirements of these specifications are essentially equivalent; but there are differences resulting from the referenced standards therein that means that specifying only one of the referenced cabling standards does not ensure compliance to all.

Standards There are modular patch cord requirements in each of the above cabling standards. The testing of modular patch cords (cable assemblies) is covered by standards. The constituent parts of the modular patch cord cable and connecting hardware are both covered by standards. The relationship between these is detailed as follows. ISO/IEC 11801:2002 1) Balanced cords are specified in ISO/IEC 11801:2002, clause 13. a) The specification covers Category 5, Category 6 and Category 7 modular patch cords. b) The specification covers both unscreened (UTP) and screened (FTP, STP, etc.) constructions of modular patch cords. 2) Clause 13.1 (Introduction) defines the construction and the performance requirements of modular patch cords. a) The cable shall be as specified in IEC 61156 series. b) The cable shall meet the requirements of ISO/IEC 11801:2002 clause 9 (cable requirements). c) The modular patch shall be as specified in IEC 60603-7 series. d) The modular patch shall meet the requirements of ISO/IEC 11801:2002 clause 10 (connecting hardware requirements). e) The performance of modular patch cords is highly dependent upon the design and quality of the component parts (cable and connecting hardware), and the effect of the cable termination to the connecting hardware. It is recommended that modular patch cords be tested to determine the quality of the assembly. f) The performance requirements of modular patch cords shall be assessed, and show conformance: i) initially; ii) after being subjected to the mechanical stresses that are specified in IEC 61935-2. 3) Clause 13.2 (Insertion loss) specifies the maximum insertion loss (frequency dependent), achieved by design, and which is modular patch cord length dependent. 4) Clause 13.3 (Return loss) specifies the minimum return loss (frequency dependent), and which is modular patch cord length independent. 5) Clause 13.4 (NEXT) specifies the minimum near-end crosstalk loss (frequency dependent), and which is modular patch cord length dependent. EN 50173-1 1) Requirements for cords and jumpers are specified in EN 50173-1:2002, clause 9, Balanced cords are specified in EN 50173-1:2002, clause 9.2, and the Electrical performance requirements for patch cords is specified in EN 50173-1:2002. a) The specification covers Category 5, Category 6 and Category 7 modular patch cords. b) The specification covers both unscreened (UTP) and screened (FTP, STP, etc.) constructions of modular patch cords.

2) Clause 9.2.1 (General) defines the construction requirements of modular patch cords. a) The cable shall be as specified in EN 50288 series. b) The cable shall meet the requirements of EN 50173-1:2002 clause 7 (Cable requirements). c) The modular patch shall be as specified in EN 60603-7 series. d) The modular patch shall meet the requirements of EN 50173-1:2002 clause 8 (Connecting hardware requirements). e) Work area cords shall only be assembled using flexible cables of stranded construction. 3) Clause 9.2.2 (Cable attenuation) defines additional requirements for cables for modular patch cords. a) The insulated conductor diameter of the cable shall be 1.02mm. b) The maximum attenuation ratio of flexible cables shall be 1.5. c) Flexible cables of the correct attenuation ratio shall be used as defined by the implementation rules of EN 50173-1:2002, clause 6. 4) Clause 9.2.3.1 (Insertion loss) specifies the maximum insertion loss (frequency dependent), achieved by design, and which is modular patch cord length dependent. 5) Clause 9.2.3.2 (Return loss) specifies the minimum return loss (frequency dependent), and which is modular patch cord length independent. The return loss performance shall be conformant: b) after being subjected to the mechanical stresses that are specified in IEC 61935-2. 6) Clause 9.2.3.3 (Near-end crosstalk loss (NEXT)) specifies the minimum near-end crosstalk loss (frequency dependent), and which is modular patch cord length dependent. The NEXT performance shall be conformant: b) after being subjected to the mechanical stresses that are specified in IEC 61935-2. 7) Clause 9.2.4 (Identification) specifies that each modular patch cord shall be identified to indicate: a) Length. b) The design insertion loss ratio of the cable. c) Category of cable. d) Wire-map status where a direct pin-pin relationship does not exist (i.e. cross-over cords). TIA-568-B 1) TIA-568-B.1, with references to TIA-568-B.2 and including all associated addenda, specifies the following. a) Clause 4 (Horizontal cabling), which can include modular patch cords, and encompassing recognised cables. b) Clause 6 (Work area) including work area cords in clause 6.3. c) Clause 10 (Cabling installation requirements) including patch cords, equipment cords, work area cords and jumpers in clause 10.2.4.

2) TIA-568-B.2, clause 6 (Cords and cross-connect jumpers) specifies the requirements for Category 5e modular patch cords. a) The specification covers unscreened (UTP) and screened (ScTP) (by extension to TIA-568-B.2, annex K) constructions of modular patch cords. b) Clause 4.5 (Stranded conductor cable) specifies the requirements for cables used in modular patch cords. Stranded conductor cable is recommended for use for modular patch cords, but solid conductor cable is also allowed. c) Clause 5 (100 O balanced twisted-pair connecting hardware) specifies the requirements for connecting hardware used in modular patch cords. Reference is made to IEC 60603-7 series for modular plugs. d) Annex F (Testing of patch cords) specifies the requirements for qualification of modular patch cords. i) Test configurations and methodology are detailed. ii) The return loss shall be conformant after each step of a mechanical stress test. iii) New requirements for Category 6 modular patch cords, such as the Modular patch cord test procedure specified in TIA-568-B.2-1, annex J, are recommended for extension to Category 5e modular patch cords. 3) TIA-B.2-1, clause 6.3 (Cords) specifies the requirements for Category 6 modular patch cords. a) The specification covers unscreened (UTP) and screened (ScTP) by extension to TIA-568-B.2 constructions of modular patch cords. b) The specification details requirements for cable and connecting hardware, etc., by extension to TIA-568-B.2, clause 6. c) Clause 7 (Transmission requirements) specifies the performance of modular patch cords. d) Annex J (Modular patch cord test procedure) specifies the requirements for qualification of modular patch cords. Technical requirements For conformance to the appropriate cabling standards detailed above, the technical requirements for modular patch cords shall be met as follows. 1) Modular patch cords shall meet the H.F. transmission (insertion loss, return loss, NEXT, propagation delay, propagation delay skew) and d.c. electrical (wire map) requirements: b) after being subjected to a range of mechanical and environmental conditioning tests: i) tensile strength; ii) flexure; iii) bending and twisting; iv) crushing; v) dust ingress; vi) coiling and uncoiling; vii) climatic endurance.

2) Cables for modular patch cords shall meet the H.F. electrical and d.c. electrical requirements specified in the cable standards referenced above, at all temperatures at which the cable is specified. 3) Connecting hardware for modular patch cords shall meet the H.F. electrical and d.c. electrical requirements specified in the connecting hardware standards referenced above: b) after being subjected to a range of mechanical and environmental conditioning tests: i) climatic endurance; ii) mechanical operations; iii) corrosive gases; iv) vibration; v) temperature endurance. Testing Modular patch cords can be tested for transmission performance and mechanical / environmental robustness conformance against the requirements of the International Standards detailed above. Typically, initial verification is demonstrated by employing the services of a competent laboratory; where this is the manufacturer s own laboratory, a good manufacturer will typically demonstrate conformance by supporting documentation from an independent laboratory. This is especially true for transmission performance where the test methodology has only recently been agreed and standardised. The initial transmission performance characterisation of modular patch cords is usually completed by utilising a network analyser, suitable baluns, and the specified conforming mating test heads (sockets). Once initial product conformance is demonstrated, on-going verification of production can be assured through the use of appropriate portable test equipment, again fitted with the specified conforming mating test heads. The use of this portable test equipment typically, the current level III field testers that are used for measuring permanent links and channels also enables modular patch cords to be measured post manufacture e.g. on delivery to site or after installation. The transmission performance of structured balanced cabling channels is specified in ISO/IEC 11801:2002, EN 50173-1:2002 and TIA-568-B. The performance of channels is specified to enable support for a wide range of applications. Unless the uncommon channel design approach is adopted, conformance of channels to the above cabling standards is dependent upon the use of category conformant components (cable, connecting hardware, cords) with or without permanent link conformance testing. The installed link between the telecommunications room and the telecommunications outlet is inevitably commissioned by means of field tester acceptance testing. However, this cabling does not incorporate any balanced cords equipment, patch or work area cords. Thus, unless channel testing is further specified, the user of the channel is dependent solely upon category conformant balanced cords being used to ensure that the channel is conformant and will support the specified range of applications. It naturally follows that the use of non-conformant balanced cords (including modular patch cords) could produce non-conformant channels with resulting problems in supporting current, let alone future applications.

Recommendations 1) Manufacturers and suppliers of modular patch cords should ensure that: a) the modular patch cord conforms to the cabling standards as indicated on the product and its associated documentation; b) conformance is supported by a suitable test regime; c) there is clear product identification, with no misleading statements in regard to performance and usage; d) the product is fit for its intended purpose. 2) Procurement of modular patch cords should be realised only if the following are correctly specified: a) conformance to appropriate cabling standard(s), including: i) BS EN ISO 9000:2000 registration; ii) manufacturers support documentation (test reports, product marking, etc.); iii) on-going verification of conformance through a third party independent laboratory maintenance programme: b) category of transmission performance, including: i) designed insertion loss ratio (determined by conductor size); ii) conductor type (solid or stranded construction); c) additional requirements, such as: i) fire rating (IEC 60332 series); ii) sheath material (PVC, LSZH). 3) Manufacturers, specifiers, distributors, installers, maintainers and users all have a responsibility to ensure that the products that claim to be compliant are indeed so. The Trade Descriptions Act, 1968 states: a) The law requires that any description of goods and services given by a person acting in the course of trade or business should be accurate and not misleading. b) The Act makes it an offence to supply or offer to supply goods to which a false or misleading trade description is applied. c) These offences are strict liability offences i.e. it is possible for a trader to commit an offence without intending to do so. 4) If a non-compliant modular patch cord is uncovered, it is recommended that the supplier should be contacted so that any rogue modular patch cord can be replaced. However, if the problem appears more extensive, then a call to the supplier s local Trading Standards Office would seem appropriate. ACKNOWLEDGMENT Lynx Networks plc gratefully acknowledges the work undertaken by Mr Stuart Reeves, of ADC Krone for his research and preparation of this document. IMPORTANT NOTICE Whilst Lynx Networks has used every effort to ensure that the information above is accurate, it will not be held responsible in any way whatsoever for errors, omissions or misrepresentations.