Operating instructions Mechatronic flow sensor. SBY33x 704465/06 03/2011



Similar documents
Operating instructions Diffuse reflection sensor with background suppression O1D101 O1D / / 2012

Operating instructions Switching amplifier for fibre optics. OBF5xx / / 2010

Operating instructions Capacitive sensors

Operating instructions Diffuse reflection sensor. OJ50xx / / 2004

Operating instructions Optical distance sensor O1D100 O1D / / 2012

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Electronic Pressure Switch EDS 300

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

How To Use A Flowmeter

Electronic Pressure Switch EDS 3000

Conductive Level Switch FK 2 Technical Data:

Product data sheet. JUMO MIDAS Pressure Transmitter. Sales No. Order code JUMO AS /

DALI RC BASIC SO. Control unit Operating instructions

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

Overview of types. Technical data

Security. Alarm central unit. Ref.-No. KNX Alarm central unit EAM 4000

VSO MAX HP High Flow Proportional Valve

Instruction Manual Differential Pressure Transmitter

VP23, 3-way proportional pressure control valves Seat valve with μp-driven pressure control

Compact pressure switch Flameproof enclosure Ex d Model PCA

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

EASIDEW PORTABLE HYGROMETER INSTALLATION, OPERATION AND MAINTENANCE MANUAL

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Ball valve C 16 valve ball completely moulded in place, extremely low clearance volume, high k v value

E4E PILOT OPERATED DIRECTIONAL CONTROL VALVE WITH ELECTRIC PROPORTIONAL CONTROL SERIES 51

3/2-, 5/2- and 5/3-way Solenoid Valves for process pneumatics

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

AIR-AIR PRESSURE MULTIPLIER (BOOSTER)

Assisted lift operated 2/2-way solenoid valves Type EV250B

Typical Aluminum GFM Mass Flow Meter

Turbine Flow Sensor Series VTR

Dimensional drawing. Connection type IME08-1B5NOZT0S IME08-1B5NSZT0S IME08-1B5POZT0S IME08-1B5PSZT0S. 3 x 0.14 mm². brn. L+ Schließer/ Öffner M.

Battery Powered Thermal Mass Flow Meters for Gases

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

Flow switches Series AD/VH

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

MANTA Piston Distributor for Oil and Fluid Grease

ELECTROMAGNETIC FLOWMETER COMPACT

Relative and absolute pressure switch type 529

Battery Powered Thermal Mass Flow Meters for Gases

Digital inductive conductivity transmitter

Magnetic proximity switches

Battery Powered Digital Mass Flow Meters for Gases

Electronic pressure switch with display Model PSD-30, standard version Model PSD-31, with flush diaphragm

Cable Plug acc. to DIN EN , Form A

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

3/2, 5/2, 5/2 bistable and 5/3 way pneumatic solenoid valve

DMP 331. Industrial Pressure Transmitter for Low Pressure. Stainless Steel Sensor

OEM Pressure Transmitters for heavy-duty applications, Type MBS 1200 and MBS 1250

DXPE*J /215 ED. DIRECtIONAL CONtROL VALVE PILOt OPERAtED, WItH OBE AND FEEDBACK. Q max (see performance table) SERIES 30

HERZ-Thermal Actuators

VEO. V4PF480Y/277VSYTK02 Art.Nr.: V4PF480Y/277VSYTK02P Art.Nr.: TECHNICAL DATA

Oil and Coolant Circulating Heating System. Model - OCSM

Data Sheet PS1B Pressure Switch

E2EL Ø 6,5 M8 / Plug M8 M8 / Plug M12 E2EL

3/2, 5/2, 5/2 bistable and 5/3 way pneumatic solenoid valve

Valve series MN-06 acc. to NAMUR, 3/2-way G1/4 750 Nl/min (0.762 Cv)

Operating Instructions for Plastic Flow Meter. Model: KSK

ELECTRIC INSTANTANEOUS WATER HEATER

Quick Connect. quick - simple - efficient.

Thermal flow sensors TA10-ZG8c and TA10-ZG9c for exact and stable, long-term measuring of lower flow velocities (Laminar Flow)

DN [mm] [m 3 /h] Characterizing disk Dimensions / Weights see «Dimensions and weights», page 3 Motorizing

SunMaxx Solar Filling Station Operating Instructions

FMA 3100/3100ST/3300/3300ST Series Thermal Mass Flow Sensors and Meters

Cross-beam scanning system to detect slim objects. 100 mm in

How To Read A Pipe From A Sensor

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Adsorption air dryers ADS 1 215

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Clear Glass Sensor. Ordering Information E3S-CR67/62. Optimum Sensor for Detecting Transparent Glass and Plastic Bottles

OPERATING INSTRUCTIONS

PIEZOMETER AIRFLOW MEASURING RING

Technical Data. Dimensions

Proportional pressure regulators VPPE

4 Posiflow Proportional Solenoid Valves

AS-i 3.0 PROFIBUS Gateways with integrated Safety Monitor

Analogue Input, 4-fold, MDRC AE/S 4.1, GH Q R0001

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Chapter 5: Flow Valves

DCS Input/Output Relay Card Series

1/11 CO2 DOSAGE SYSTEMS. CO2 dosage system consists of following parts;

Overheating limit control

Online data sheet PET-1CB010N10SVMC PET PRESSURE SENSORS

Technical Information RIA14

Preset Counter signo 721

FLOAT SWITCHES FLOW SWITCHES FOR LIQUIDS PRESSURE SWITCHES

FREEZE Canopy. Canopy lighting. QCS Quick-Connection-System. Daylight. Neutral White. Fresh Meat. Packed Meat

Pluggable interface relays CR-P Pcb relays

servo-controlled 3-WaY vacuum solenoid valves WiTH

4/2-Way Pneumatic Solenoid Valve

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Features. Picture. Specifications

Infrarot-Bewegungsmelder IP44

Multifunction devices

System 8. ü ( System 8

AS-i 3.0 Gateways, PROFIsafe via PROFINET or PROFIBUS

Ferrostat Speed Sensor Series DSF Explosion Proof Versions EEx

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

alpha DSL WTM EG Instructions for use ADSL-Modem alpha DSL WTM EG

Transcription:

Operating instructions Mechatronic flow sensor SBY33x 7065/06 03/2011

Contents 1 Safety instructions...2 2 Functions and features...3 3 Installation...3 Electrical connection... 5 Switch point setting... 5.1 Definition of requested value...5 5.2 Adjustment to existing flow...5 6 Operation...6 7 Maintenance, repair and disposal...6 8 Scale drawing...7 9 Technical data...8 1 Safety instructions Please read the product description prior to set-up of the unit. Ensure that the product is suitable for your application without any restrictions. Improper or non-intended use may lead to malfunctions of the unit or to unwanted effects in your application. That is why installation, electrical connection, set-up, operation and maintenance of the unit must be carried out by qualified personnel authorised by the plant operator. Check the compatibility of the product materials (see technical data) with the media to be monitored in all applications. The device shall be supplied from an isolating transformer having a secondary Listed fuse rated either a) max 5 amps for voltages 0~20 V (0~28.3 Vpeak), or b) 100/Vp for voltages of 20~30 V (28.3~2. Vpeak). Flow Operated Switches shall be connected only by using any R/C (CYJV2) cord, having suitable ratings. 2

2 Functions and features The unit monitors liquid media (water, glycol solutions, oils). It detects the volumetric flow quantity to the principle of differential pressure and switches the output: Output closed (LED = ON), if volumetric flow quantity switch point. Output open (LED = OFF), if volumetric flow quantity < switch point. The switch point is adjustable. 3 Installation Ensure that the system is free of pressure during installation. Ensure that no media can leak at the mounting location during installation. Install the unit according to the marked flow direction into a pipe RP ¾ and tighten firmly. IN Rp 3 Rp 3 OUT IN = inlet OUT = outlet 3

Electrical connection The unit must be connected by a qualified electrician. The national and international regulations for the installation of electrical equipment must be adhered to. Voltage supply to EN 50178, SELV, PELV. Disconnect power. Connect the unit as follows: 2 1 3 1 3 L+ L- For information about available sockets/connectors see: www.ifm.com Products Accessories 5 Switch point setting There are 2 possibilities: Definition of requested value 5.1. Adjustment to existing flow 5.2. 1 2 A B C D A: LED; B: setting screw; C: lock screw; D: setting scale Do not turn the setting screw beyond the maximum value of the setting range ( Technical data) to avoid faulty switching.

5.1 Definition of requested value Loosen the lock screw. Turn the setting screw until the requested value just becomes visible on the setting scale. Example in figure 2: requested value = 10 l/min. Tighten the lock screw. 5.2 Adjustment to existing flow Let the normal flow circulate in the installation. Loosen the lock screw. Set the switch point with the setting screw. -- If the LED lights before setting: turn the setting screw in the direction [+] until the LED goes out. Then turn in the opposite direction [-] until the LED lights. -- If the LED does not light before setting: turn the setting screw in the direction [-] until the LED lights. Tighten the lock screw. Correlation between number of the turns of the setting screw (SET) and switch point in l/min: One complete turn corresponds to approx. 2 l/min for SBY332 approx. 3 l/min for SBY333 approx. 6 l/min for SBY33 Q [l/min] 60 50 0 30 20 10 0 1 2 3 5 6 7 8 9 SBY33 SBY333 SBY332 SET The diagram shows the typical course of the measurement curves for water at 20 C. 5

6 Operation After power on the unit is ready for operation. It detects the volumetric flow quantity and switches the output according to the setting. Function diagram Q A B t C 1 0 A = requested flow; B = switch point; C = switching output 7 Maintenance, repair and disposal In case of correct use no maintenance and repair measures are necessary. In case of strongly polluted media: mount a filter in front of the inlet (IN). Recommendation: use a 50-micron filter. Only the manufacturer is allowed to repair the unit. After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations. 6

8 Scale drawing 32 97...105,5 Rp 3 Rp 3 13 76,5 13 113...123,5 dimensions are in millimeters 7

9 Technical data Setting range [l/min] - SBY332...1...15 - SBY333...1...25 - SBY33...2...50 Flow range max. [l/min]...100 Operating voltage [V]... 2 DC (-15 % / +10 %) Current rating [ma]... 100 Protected against short circuits, reverse polarity and overload Voltage drop [V]...< 2.5 Current consumption [ma]...< 15 Hysteresis [l/min] - SBY332...0.2...1 - SBY333...0.5...2 - SBY33...1...3 Repeatability [% of value of measuring range]...1 Accuracy [% of value of measuring range]...± 5 Response time [s]...< 0.01 Pressure loss (dp) / flow rate (Q) dp [bar] 1,0 0,9 0,8 0,7 B A C 0,6 0,5 0, 0,3 0,2 0,1 0 0 5 10 15 20 25 30 35 0 5 50 55 60 65 Q [l/min] A: SBY332 B: SBY333 C: SBY33 8

Housing materials...brass chemically nickel-plated; aluminium anodised; PP Materials (wetted parts)... stainless steel (30S15); brass chemically nickel-plated; PP; O-ring: FPM (Viton) Protection... IP 67 III Switching cycles min.... 10 million Medium temperature [ C]... 0...85 Operating temperature [ C]... 0...60 Pressure resistance [bar]... 25 Further information at www.ifm.com 9