On-Demand Ventilation Energy Saving in Industrial Applications



Similar documents
Centrifugal Fans and Pumps are sized to meet the maximum

Energy Savings With Adjustable Frequency Drives. for Centrifugal Fans

NFPA Combustible Dust Compliance and the Industrial Ventilation System

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

Clearing the air A simple guide to buying and using local exhaust ventilation (LEV)

Demand Based Static Pressure Reset Control for Laboratories

Hybrid shunter locomotive

vacon ac drives for mining & minerals

Cooking at the Speed of light!

My Industrial Ventilation System Used to Work: The Role of System Documentation in Restoring System Performance

With the background of fulfilling public commitments for ECONO-PILOT ENERGY-SAVING SYSTEM FOR WATER PUMPS

Drives and motors. A guide to using variable-speed drives and motors in car parks

HEATER, AIR CONDITIONING AND VENTILATION

Case Studies: Infrared Heating in Industrial Applications

ENHANCED LABORATORY HVAC SYSTEM

Fan Applications & System Guide

OPERATION MANUAL. Total Heat Exchanger HRV (Heat Reclaim Ventilation) (Ceiling mounted duct type)

Electric Motor Brake Horsepower Calculations

WEEKLY SAFETY MEETING All Euramax Subsidiaries COMBUSTIBLE DUST. Safety Meeting Contents. Meeting Notice. Leaders Guide.

Energy Benchmarking Report for Lafayette Elementary School Bound Brook, NJ

factor max Delivering Electrical Efficiency INFORMATION PACK factor max

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM

Chapter 3.5: Fans and Blowers

Unico Inverter. Unique and efficient.

CITY OF LOS ANGELES PERSONNEL DEPARTMENT CAREER OPPORTUNITIES FOR MECHANICAL HELPER

Programmable Logic Controllers

VAV Laboratory Room Airflow The Lowdown on Turndown

9/15/2011. Presented by: Jason Reason, CIH, CSP, CHMM Senior Industrial Hygienist Indiana Occupational Safety and Health Administration

Direct Fresh Air Free Cooling of Data Centres

Type 1 dryers: Domestic dryers to be used primarily in a family living environment. Residences Individual apartments or condominiums

Achieving ENERGY EFFICIENCY with Standard Air-Conditioning Units. Mike West, PhD, PE Advantek Consulting, Inc

OSHA and Welding Exhaust

Development of Ventilation Strategy in Diesel Engine Power Plant by Using CFD Modelling

Design Information. Designing Your Dust Collection System. Typical dust or fume collection system

How To Save Energy On A Power Supply

Rainwater Harvesting

products 22 º C Ventilation Air Conditioning Refrigeration Energy & Cost Saving Products Inside PROVIDED BY HEINEN & HOPMAN

Airmanager Industrial HVAC retrofit results July Location Description:

Energy Audits Waste Water Treatment Plants

WHY AND HOW THE ENVIRONMENT HAS TO BE TAKEN INTO ACCOUNT AT THE WORLD SUMMIT ON THE INFORMATION SOCIETY, GENEVA 2003 TUNIS 2005

Spray Booth Guideline

Understanding Operations Management The Open University (2011)

Conserve Insight Energy Use Monitor. User Guide

Glossary of Heating, Ventilation and Air Conditioning Terms

HVAC Design Industrial Ventilation

Data Bulletin. Mounting Variable Frequency Drives in Electrical Enclosures Thermal Concerns OVERVIEW WHY VARIABLE FREQUENCY DRIVES THERMAL MANAGEMENT?

Energy Saving Ideas for Your Box Plant

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

ENERGY SAVING STUDY IN A HOTEL HVAC SYSTEM

CHAPTER 10: APPLIANCES AND LIGHTING

ENERGY AUDIT IN THE KACST BUILDING

Frequently Asked Questions Generators

Presented By: WALTER E. JOHNSTON, PE CEM, CEA, CLEP, CDSM, CPE

Rules of Thumb Energy Efficiency in Buildings

REFRIGERATED COMPRESSED AIR DRYERS

Duct Design. Presented by Dave Janquart

Basic Hydraulics and Pneumatics

Pellet Process - Uses and Exposures

HVAC Costs. Reducing Building. Building owners are caught between two powerful forces the need to lower energy costs. By Stephen J.

Do you remove fumes from robotic welding and laser cutting?

Information Technology Solutions

Fume Extraction: Guide to Safely Managing Solder Fumes in the Workplace

Printing and Publishing Energy Savings Guide

FPT FIAT POWERTRAIN TECHNOLOGIES PRESENTS ITS ENGINE RANGE FOR CONSTRUCTION APPLICATIONS AT INTERMAT 2009

Half the cost Half the carbon

Environmental Benefits of Thin Computing A comparison of the environmental impacts of conventional desktop and thin computing

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

PANDA SPRAY BOOTH FILTER INFORMATION

Resistors in Series and Parallel

USER S MANUAL HSC-24A

SENTRY AIR SYSTEMS, INC. PHARMACEUTICAL COMPOUNDING CONTAINMENT SYSTEMS SIMPLE SOLUTIONS FOR CLEANER AIR

NewAir AC-14100E / AC-14100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

Introduction. Motor Types

Dry Ice Cleaning. New opportunities with FerroČrtalič d.o.o.

VendingMiser. A: VendingMiser uses three different technologies to intelligently manage the power to a vending machine.

Q. Why have we set up an energy centre and heat network in Bunhill?

Remote Maintenance with Security Appliances FL MGuard RS2000 and RS4000. Economic and Reliable Service

MH 3M & 4M. High pressure washers with hot benefits

Steel Industry Systems with Integrated Mechanical and Electrical Control for High-quality Production and Energy Efficiency

Integrating Computerized Maintenance Management System and Energy Efficiency Management System A Modified Approach

Circulator Fan Performance Testing Standards BY CHRISTIAN TABER, BEMP, HBDP, MEMBER ASHRAE

FAILURE MODES AND EFFECT ANALYSIS (FMEA)

Dual Maximum VAV Box Controls

SWIMMING POOL HEAT PUMP

Heating your Building with Solar Energy

Types of Engineering Jobs

THE ELECTRIC HOOKUP. 1. Determine the wattage of various household appliances. 2. Calculate the number of kilowatt-hours used by appliances.

INDUSTRIAL AUTOMATION EQUIPMENT EDITION

Starting Current Reduction of Residential HVAC System and Peak-Load Impact of Power System: A Case Study

imagine SOLAR AIR CONDITIONING MADE EASY

Construction Indoor Air Quality Management Plans for LEED. Matt Gregg, PE, LEED AP

Antonio Jose Cumbane (PhD) Maputo, 31 st May 2011

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County

An overview of Euro VI for trucks over 3.5t. Brought to you by Mercedes-Benz

Transcription:

On-Demand Ventilation Energy Saving in Industrial Applications Ales Litomisky, Ecogate, Inc. ABSTRACT The purpose of this paper is to describe innovative on-demand industrial ventilation. These on-demand systems are already being used in the chemical, metal, and woodworking industries, achieving average electricity savings of 68% over unregulated, classical systems. Industrial Ventilation Classical Design Classically designed industrial ventilation systems utilize a large central fan and a system of ducts connecting each workstation to the fan (Fig 2). The typical fan motor size is between 50 and 350 HP, based on the number of connected workstations and the length of the duct system (losses). Larger factories use multiple systems that operate continuously for the whole shift time. Industrial ventilation is used everywhere where dust, fumes, or mist is created, such as the woodworking, metal working, food processing, and pharmaceutical industries. Systems are designed in a way that enables ventilation from all installed machines at the same time. Correspondingly, the appropriate size of the fan motor is chosen. However, data from real factories show that, typically, less than 50 % of machinery is working at any given time; therefore, 50% of machinery is not producing dust (fume, mist); despite this fact, suction continues from all machines. The Fan Law shows why electricity savings can be high. This law of physics says that at 50% reduction of air-flow which is achieved by automatically closing gates on non-operating machinery, fan motor will consume only 12.5% of electricity (an 87.5% saving) of what is required when suction is running at all workstations. Figure 1: Fan Law Power [H.P. %] Air volume [CFM %] 100 90 80 70 60 50 40 30 20 10 0 CFM = 50 % of blast gates are closed H.P. = 12.5 % of 100 % power 0 10 20 30 40 50 60 70 80 90 100 Air volume [CFM %] Power [H.P. %] 6-91

If the air volume is reduced by 50 %, then the electricity consumption of the fan motor will be reduced to 12.5% of the original power - an 87.5% saving. The laws of physics are on our side this time. The basic idea is simple: Let s equip each workstation with a sensor that detects when ventilation is necessary, and let s use a motorized gate to close the ventilation duct when ventilation is not necessary. Then the RPM of the fan can be adjusted to achieve proper air volume in the ducting (Fig. 3). However, there is a problem with this simple idea: if dust or other material is to be transported through the ducting, then it is necessary to maintain a set minimum velocity in the ducting to prevent the material from settling in ducts; also, minimum negative pressure should be maintained to overcome pressure losses in the duct system 1. When gates at non-working workstations are closed, air volume and, subsequently, air velocity in the main duct will drop and dust could settle. An on-demand dust collecting system solves this problem by using a PLC (industrial computer) that calculates the necessary air volume and the necessary negative pressure based on information from the sensors. The PLC adjusts the RPM of the fan accordingly, and it also opens additional gates at non-working machinery if this is necessary for maintaining proper air velocity. Duct diameters are smaller because they are optimized for example for 70% of air volume. The Duct Optimizer software (for Windows PC) is available to simulate and optimize the duct system for any given application. How the On-Demand System Works Each workstation is equipped with a sensor that detects when ventilation is necessary (Fig. 3). A motor-operated gate closes the ventilation duct when suction is not needed at a particular outlet. Both the sensors and the gates are connected to a central computer (industrial PLC). As a result, the computer continually receives information from the sensors and uses a software model of the ducting and fan to calculate the proper RPM (speed) of the fan and to determine the number and position of additional gates to be open whenever necessary for maintaining proper air velocity and negative pressure in the duct system. A serial line is used to communicate with the variable speed drive to adjust fan speed. Additional information for the computer is provided by a negative pressure sensor installed in the main duct. Every five minutes, the computer records the following: consumption of the fan motor, times when each workstation was switched on or off, system warnings, and errors. This data can be downloaded to any computer by a modem or via an Internet connection. Data are collected in an SQL database from which many different reports can be generated. Energy saving reports can be used for financing the Pay-by-Electricity-Savings program. Customers pay for such a system in monthly payments that do not exceed the measured cost of saved electricity. 1 This minimum negative pressure is not a constant value; it is a variable dependent on the number and position of open gates. An extreme example is when just one gate next to the fan is open: in this case, the losses in ducting are minimal, and the necessary negative pressure must exceed just the losses in the dust collector and fan. On the other hand, when the open gate is located at the far end of a long duct system, the minimum necessary negative pressure is substantially higher because it has to overcome the additional losses in a long duct system. 6-92

Figure 2: Unregulated (Classical) Ventilation System with Duct System Connected to each Work-Station, Central Dust Collector, Fan and Fan AC Motor Figure 3: On-Demand Ventilation System Note: each workstation is equipped with a sensor and a gate to close the ventilation duct when necessary. Both the sensors and the gates are connected to a central computer (PLC) that calculates the proper RPM (speed) of the fan and determines the number and position of additional gates to be open whenever necessary for maintaining proper air velocity and negative pressure in the duct system. 6-93

Figure 4: Motorized Gates for Different Duct Diameters Are Used to Close Ventilation on Non-Working Machinery Table 1: Cost of the Fan Operation at 3 Shifts and Electricity Cost $0.07-$0.20 per kwh Cost of Fan Operation Per Year 3 Shifts (24 hr. day / 7 days per week), 100% fan load $ per kwh $0.07 $0.12 $0.14 $0.16 $0.18 $0.20 Sys. Size 50 HP $21,168 $36,288 $42,336 $48,384 $54,432 $60,480 100 HP $44,272 $75,895 $88,544 $101,194 $113,843 $126,492 200 HP $88,405 $151,551 $176,810 $202,068 $227,327 $252,585 300 HP $124,161 $212,847 $248,322 $283,796 $319,271 $354,745 500 HP $221,372 $379,495 $442,744 $505,993 $569,243 $632,492 1000 HP $442,744 $758,990 $885,488 $1,011,987 $1,138,485 $1,264,984 By using an on-demand ventilation system, 50 to 80% of the fan operating cost can be saved. If air-conditioning or heating is used in a plant, then, in addition to the fan operation cost savings, additional savings are achieved because less air is ventilated outside the building, i.e. it is necessary to cool /heat less make-up air. Air conditioning/heating savings are typically two times higher than fan electricity savings (depending on geographical location, operating hours and energy cost). Figure 5: Savings by On-Demand Ventilation Systems Note: A. Fan operation electricity savings, B. air conditioning/heating savings (if used), and C. emission trading (where available). 6-94

Heating/air conditioning cost depends on geographic location and natural gas prices Typically, 2x higher savings (than fan operation cost savings) can be achieved by reducing make-up air volume Where Is Ventilation Used? Among industries using industrial ventilation are the automobile manufacturing, printing, food processing (flour, milk powder, salt, sugar, spices), chemical (solids, fumes), petrochemical & pharmaceutical industries, the woodworking industry, the metalworking industry, dental labs. Figure 6: Industries that Use Industrial Ventilation Example 1: Chemical Industry Battery Producer This example describes the system being used by a car/boat battery producer. This factory uses 24 workstations that produce lead battery grids. Production is planned in one-week intervals, based on the orders from dealers, seasonal changes, etc. Using this information, the factory makes a decision on how many workstations it will run during the different shifts of that one-week period. Any number out of those workstations (0-24) are then planned to be used during any particular shift. Each workstation uses supply-air as well as the ventilation system. Currently, both the supply-air and the ventilation system work for all workstations even if they are not in use. Implementing an on-demand air-supply and ventilation system could significantly reduce energy use. In our example, the factory was using 600 HP to operate the fan without the on-demand system. After installation of the on-demand system, only and average of 150 HP is required to run the fan, a 450 HP reduction. 6-95

Savings Over Current System Figure 7: Chemical Industry How Much kwh saved?* Heating / Air Conditioning Savings* 100 % $ 10 M 90 % 70 % 80 % 70 % 5 M kwh 10 M $ 1 M 60 % 1 M kwh 1 M $ 50,000 $ 100 K 50 % 50 % 40 % 100 K $ 10 K 30 % $ 5,000 20 % 10 K $ 1 K 10 % 0 % * represents per year savings Note: typical fan operation savings by on-demand systems compared to an unregulated design (left column), typical fan operation annual kwh savings (middle column) and how much can be saved on make-up air cost per year. (Heating/air conditioning is typically not used in the chemical industry.) Figure 8: Battery Producer Note: one large unregulated 600 HP system running 24/7/365 was used originally; the new system is divided into three sections that work on-demand (not all three sec-tions are working all the time; two sections and all workstations 1...24 are equipped with gates; the fan is equipped with a variable speed drive. 6-96

Example 2: Dental Lab Dental labs use industrial ventilation to collect dust during stages of making dental crowns, bridges and dentures. The company in this example runs 72 operating workplaces in their facility. Each workplace is equipped with a motorized gate and a sensor; in this application the sensor senses current to the hand-held tool used by dental technicians. A variable speed drive controls the fan motor (40 HP). The ventilation system is open only for workstations that are in use. The ventilation system significantly reduced noise and the amount of air ventilated outside of the building. Because the whole building is air-conditioned and less air is ventilated outside of the building, air conditioning costs have been significantly reduced. Percent [%] of Filter Time Figure 9: Dental Lab with 72 Workstations 55 50 45 40 35 30 25 20 15 10 5 0 123456789 11131517192123252729313335373941434547495153555759616365676971 Workstation Note: the chart shows activity time of individual work-stations as a percent of total shift time; workstation 44 is used max 55% of the shift time, several other workstations about 30% of the time, but the overall average is less than 10% of total shift time. Figure 10: Dental Labs Use Industrial Ventilation to Collect Dust Particles of Plaster, Metal Alloys, and Resins during Different Stages of Dental Production Note: the company in this example runs 72 operating workplaces in their facility. 6-97

Figure 11: Dental Lab Note: typical fan operation savings by on-demand systems over unregulated design (left column), typical fan operation annual kwh savings (middle column) and how much can be saved on heating/air conditioning annually. Example 3: Woodworking Industry Ventilation systems are commonly used in the woodworking industry (sawdust collecting). The amount of ventilated air is relatively high. For this example, a total of 900HP was required for the ventilating systems in one factory. It has a total of seven ventilation systems in the range from 100-200 HP in fan size. Woodworking machines are not cutting material all the time. According to our measurements, cutting time represents less than 50 percent of the total shift time. Average electricity savings in this particular installation are 67% compared to an unregulated system, with annual savings of $250,000 (fan operation savings). Percent [%] of Filter Time 55 50 45 40 35 30 25 20 15 10 5 0 Figure 12: Woodworking industry 1 2 3 4 5 6 7 8 9 10111213141516171819202122232425262728293031323334353637383940 Workstation Note: 200 HP dust collecting system with a total of 40 work-stations; chart shows percentage of shift time each workstation is active; the overall average is about 10% - a substantial opportunity to save on fan operation by using an on-demand ventilation system. 6-98

Figure 13: Woodworking Industry Note: a typical fan operation saving by on-demand systems over unregulated design (left column); a typical fan operation annual kwh saving (middle column); how much can be saved on heating/ air conditioning when used (right column). Example 4: Exhaust Ventilation Systems in Car Manufacturing After analyzing the performance and effectiveness of industrial ventilation systems in automobile manufacturing plants, we have identified several areas where ventilation systems are running even without a car present (see Fig 15). To optimize the efficiency of ventilation, we propose that an on-demand systems be implemented (at Toe-In operation and Dynamic Vehicle Testing) to prevent exhaust fan activity in workplaces without a car present, and to ensure optimum ventilation. (Note: other opportunities to implement on-demand ventilation in car manufacturing are in foundries, paint spray repair booths, assembly line, care lines, etc.). 6-99

Figure 14: Automobile Manufacturing Note: typical fan operation savings by on-demand systems over unregulated systems (left column); typical fan operation annual kwh savings (middle column); how much can be saved on heating/air conditioning annually per one factory annually (right column). Heating/air conditioning savings represent majority of savings achieved. Figure 15: Toe-In Operation TOE IN OPERATION 65 CARS/HOUR PRODUCTION LINE 65 CARS/HOUR (55 sec per car) CAPACITY = 30 CARS/HOUR TOTAL CAPACITY = 4 x 30 = 120 CARS/HOUR VENTILATION = 100,000 CFM ABOUT 65/120 = 54% IS NECESSARY ABOUT 46% IS WASTED 50,000 CPM WASTED = $ 100,000 SAVINGS ON HEATING ANNUALLY AVERAGE FANS LOAD REDUCTION ABOUT 50 kw Note: Toe-In operation uses four workplaces in parallel with a total capacity of 120 cars per hour; production line runs at 65 cars per hour, i.e. 46% of the time a car cannot be present but ventilation still runs; A substantial opportunity for an on-demand system because more than 50% of the air volume is wasted. Let s assume for this example that there are 65 cars coming on the conveyor to the Toe-In per hour. The Toe-In adjustment takes approximately 90-120 seconds (30-40 cars per hour; a conservative number of 30 cars per hour is used for the savings calculation at toe-in), so there must be several toe-in places working in parallel. Under ideal conditions, two working places 6-100

would be enough, but in real life there are four Toe-In working places for each plant (each conveyor) to compensate for possible equipment malfunction or various small delays. Nevertheless, it is obvious that the average use of these four working places is approximately 50%, and we therefore recommend that the on-demand ventilation system be implemented here because there is a substantial saving opportunity. Dynamic Vehicle Testing (DVT) Let s assume in this example that there are 65 cars coming to the DVT from the production line each hour. The DVT adjustment takes approximately 120-150 seconds (24-30 cars per hour; conservative number of 24 cars per hour is used for the savings calculation at DVT), so there are several DVT places working in parallel. Optimally, 2-3 working places would be enough, but in real life there would be five workplaces here on each production line (conveyor) to compensate for possible disruptions or equipment malfunction. Nevertheless, it is obvious that the average use of these five working places is approximately 50%. We therefore recommend that the on-demand system be implemented here because there is a substantial saving opportunity. Figure 16: Block Diagram of the On-Demand Ventilation System for Toe-In and Dynamic Vehicle Testing On-demand ventilation system for Toe-in and DVT operations Inputs (car presence obtained from Toe-In or DVT control systems) and gates are connected to a central computer (industrial PLC) The computer also regulates the speed of the fan via a variable speed drive unit 6-101

Conclusion Based on our studies over 100 factories average workstation use is 30-50% of total shift time. Because workstation utilization is low ventilation can be designed 50-80% more efficiently if an on-demand system is implemented. Potential energy savings in the USA is 26 billion kwh per year with potential savings of electricity cost $ 1.8 billion per year; pollution offset $ 33 billion Lb CO 2 per year. References Industrial Ventilation Statistics by Ales Litomisky 2005, IETC 2006, New Orleans New Saving Opportunity: On-demand Industrial Ventilation; Ales Litomisky, Energy Engineering Vol. 103, No.3, 2006 Ecogate Q&A for industrial designers The United Sates review, International Energy Agency, 9 rue de la Federation, 75739 Paris, France The Energy Factor, Energy User News, September 2002, Special report for senior executives Energy Star Article: Finding the money for energy efficient projects, published in Energy User News Richard R. Vaillencourt, PE: The Correct Formula for Using the Affinity Laws, When There Is a Minimum Pressure Requirement Industrial Ventilation, A Manual of Recommended Practice, 24 th Edition, published by American Conference of Governmental Industrial Hygienists 6-102