Pressure Reducing Valve Calculation Example



Similar documents
SPRINKLER SYSTEM PLANS AND CALCULATIONS CHECK LIST

Pressure Limiting Driver (PLD)

Automatic Fire Sprinkler Submittal Requirements

WATER MEASUREMENT USING TWO INCH (50 mm) DRAIN TESTS

APPENDIX A RECOMMENDED RULES FOR SIZING THE WATER SUPPLY SYSTEM

SIZING OF WATER PIPING SYSTEM

Pacific Pump and Power

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13D

Clark County Fire Prevention

Design & Construction Standards, Revised January

ELECTRIC/DIESEL FIRE PUMP CHECK LIST

Pressure Drop Basics & Valve Sizing

CHAPTER. Standpipes and Hose Systems OVERVIEW. Standpipe and Hose Systems Defined

Operating, Installation, and Maintenance Instructions

Inspection and Testing of Water-Based Systems

Hydrant flow testing data provides important

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST RESIDENTIAL FIRE SPRINKLERS NFPA 13R

Firefighter Review. Instructor Guide

Automatic Sprinkler System Calculations

FIRE DEPARTMENT HYDRAULICS

Centrifugal Fans and Pumps are sized to meet the maximum

AKRON EDUCTORS TROUBLESHOOTING GUIDE OPERATION & THEORY OF EDUCTORS GENERAL OPERATING AND MAINTENANCE INSTRUCTIONS

Fire Pump Plan Review March 2010

Water Supply. Simulation of Water Distribution Networks. Mohammad N. Almasri. Optimal Design of Water Distribution Networks Mohammad N.

Toms River Fire Academy

One of the fundamental design elements that every

CHAPTER 2: The Plumbing System

Practice Problems on Pumps. Answer(s): Q 2 = 1850 gpm H 2 = 41.7 ft W = 24.1 hp. C. Wassgren, Purdue University Page 1 of 16 Last Updated: 2010 Oct 29

BOWL ASSEMBLY SELECTION Select impeller in exactly the same manner as for lineshaft type pump. Note comments under WELL SIZE.

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

The In-Line Gauge in Standpipe Operations

The Jockey Pump, an Important Part of a Fire Pump System.

Delta Power Company 4484 Boeing Drive - Rockford, IL 61109

Open Channel Diffusers

CENTRIFUGAL PUMP OVERVIEW Presented by Matt Prosoli Of Pumps Plus Inc.

Module 9: Basics of Pumps and Hydraulics Instructor Guide

Introduction to Water Pipe Sizing

Water hammering in fire fighting installation

Minor losses include head losses through/past hydrants, couplers, valves,

TECHNICAL DATA. 2. LISTINGS AND APPROVALS See Tables 1 & 2.

Index Page. Pumping Systems Intensifiers Gas Boosters High Pressure Generators

RAPID RESPONSE Model RSV-1 Residential Shut-Off Valve, 1 Inch and 2 Inch (DN25 and DN50) for Dual-Purpose Residential Water Supply General Description

CENTRIFUGAL PUMP SELECTION, SIZING, AND INTERPRETATION OF PERFORMANCE CURVES

Pipe Sizes For Water Distribution System Design

FAIRBANKS NIJHUIS PACKAGED FIRE PUMP SYSTEMS.

Springdale Fire Department Backup Driver Certification Program. Behavioral Objectives

Appendix B Forms for Inspection, Testing, and Maintenance

Pressure drop in pipes...

Design Criteria & Service Goals

10/9/2012. Poultry Farm Water Supply. Alabama Burglar & Alarm System. Industry Upgrades. Drinkers Fans Water Supply

REGULATORS 175/153 Series

Theory, Application, and Sizing of Air Valves

FIVE YEAR CERTIFICATION REPORT

FILLING AND PURGING THE SYSTEM

Gypsum Fire Protection District. Fire Sprinkler System Submissions

FIRE INSPECTION CHECKLIST

HYDROSTATIC TEST PUMPS

PLUMBING CODE REQUIREMENTS AND SIZING GUIDE FOR RESIDENTIAL WATER SOFTENERS. Second Edition. Prepared by

Chapter 8: Flow in Pipes

I. Introduction. 10 minutes

pvc well casing & drop pipe

In-Line Air Separators

Commercial & Municipal Retrofit 2015 VFD Rebate

Hydraulic Pump/Motor Division Hydraulic Pump/Motor Division

This document was scanned from hard copy to portable document format (PDF) and edited to 99.5% accuracy. Some formatting errors not detected during

REV. REL 1302 WEST BEARDSLEY AVENUE P.O. BOX 1127 ELKHART IN (574) FAX (574) ELKHART BRASS MFG. CO., INC.

Flygt Ball Check Valves

SECTION FIRE PROTECTION PIPING SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL

MERCER ISLAND FIRE DEPARTMENT FIRE COMMERCIAL SPRINKLER STANDARDS

Sta-Rite Industries Basic Training Manual

Slide 1. Slide 2. Slide 3 288,817,200,000. Thank you for attending the session on Hot Water Re-Circulation.

Roland Garcia Pearland Fire Department

Second Revision No. 106-NFPA [ Global Comment ] Supplemental Information. Submitter Information Verification. Committee Statement

FAIRBANKS NIJHUIS FIRE PUMPS.

Automatic Fire Sprinkler System Checklist

The conditions below apply to the curves shown on the following pages.

Irrigation Pump Variable Frequency Drive (VFD) Energy Savings Calculation Methodology. Public Utility District No. 1 of Chelan County

SPP Pumps Inc. Atlanta

! WARNING. Before using product, read and understand instructions.

Model SW-20 and SW K-factor Extended Coverage Ordinary Hazard Horizontal Sidewall Sprinklers (Standard Response) General Description

CHAPTER. Fire Pumps FIRE PUMP OVERVIEW. Fire Pump Unit Defined. Fire Pump Unit Responsibility

Spouts and Flow Regulators

TRAINING AND EQUIPMENT MANUAL HOSE PRACTICES EFFECTIVE: OCTOBER 2007

2.0 DESIGN CRITERIA FOR WATER DISTRIBUTION SYSTEMS

HYDRAULIC ANALYSIS OF PIPE LINED WITH MADISON S 100% SOLIDS STRUCTURAL POLYURETHANE COATINGS

Fiberstars Mini Lighted Laminar Flow Fountains

Selection Of Centrifugal Pumping Equipment 1

Overview of Hotel Fire Safety Requirements

Delta Fire manufacture and supply a comprehensive range of Marine Fire Fighting Equipment.

Division 21. Fire Suppression

HOUSTON FIRE DEPARTMENT HIGH-RISE SURVEY CHECKLIST

TECHNICAL DATA. 30a. September 18, /4-8 (DN32 - DN200)

1-1/2 Inch (DN40) 9 lbs. (4,1 Kg) 8 lbs. (3,6 Kg) Flange Groove* N/A N/A. Flange Flange N/A N/A

KODAK VERSAMARK, INC.

SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT

DESIGN GUIDE FOR INSTALLING PARTIAL SPRINKLER PROTECTION IN UNFINISHED BASEMENT AREAS

PERFORMANCE EVALUATION OF A DRINKING WATER DISTRIBUTION SYSTEM USING HYDRAULIC SIMULATION SOFTWARE FOR THE CITY OF OILTON, OKLAHOMA

C I T Y O F S E L M A F I R E D E P A R T M E N T

Transcription:

Pressure Reducing Valve Calculation Example Procedure to Calculate the Pressure Values required to factory set a Pressure Reducing Valve. 1) First calculate the maximum static pressure available on the supply side of the PRV at all levels. Calculate the Maximum Static Pressure at the Pump: Add the City Static Pressure to the Fire Pump Maximum Churn Pressure. The City Test and Fire Pump are at the same elevation so an elevation correction is not required. Maximum Static = 90 PSI + (150 psi x 1.18) = 90 + 177 = 267 PSI at the pump elevation. The Maximum Static Pressure at each PRV equals the Maximum Static Pressure at the Pump reduced by the elevation above the pump. The Fire Sprinkler Outlet on the 10th floor is 110 feet above the Fire Pump. Maximum Static = 267 PSI - (110 Ft x.4331 PSI/Ft) = 219.36 PSI The Hose Outlet on the 10th floor is 105 feet above the Fire Pump. Maximum Static = 267 PSI - (105 Ft x.4331 PSI/Ft) = 221.52 PSI Subtract the elevation pressure to determine the Maximum Static Pressure at each Outlet. See the chart below. 2) Then calculate the demand flow and pressure required on the system side of each PRV. a) Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Required Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. b) Calculate the sprinkler system demand. Use a flow of 225 GPM at 110 PSI at the PRV outlet - typical each level plus 100 GPM Inside Hose allowance. 3) Next calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. It will be easier to calculate the pressures for all Hose Outlets first and then the pressures for the sprinkler system outlets. For this calculation all Safety Margins are taken on the system side of the PRV and the remainder of the Standpipe and Supply Pipe will flow at the maximum pressure that the combined City and Fire Pump can provide. Calculate from the top Sprinkler System or Hose Outlets using the demand flow for each to the city supply leaving NO Safety Margin. (To find the maximum start residual pressure add the Safety Margin Pressure to your Start pressure.)

This is the Initial Input Screen used to calculate the maximum residual pressure available at the demand flow on the supply side of each PRV at all levels. Start with the Demand Flow (225 GPM) and Pressure (110 PSI + 10 PSI Safety). (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating.) Initial calculation is 83.8 PSI below curve. Add this to the start pressure (120 + 83.8) and recalculate. Adjust the start pressure until the safety margin is equal to or very close to 0.0 PSI. Note: A separate calculation is required to find the maximum pressure for the first floor Node FS1 as this is not an outlet along the hydraulic path we are currently calculating.

General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 09:25:02 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a 225.00 225.00 0.00 203.784 Pt 203.784 0.000 H10 n/a 100.00 100.00 0.00 208.174 Pt 0.000 208.174 Total K Factors.... 0 Total Fixed Flows... 2 Sum Actual Flow.... 325.00 Sum Required Flow... 325.00 Sum Delta Flow.... 0.00 Max Delta Flow.... 0.00 Max Delta Pressure.. 208.174 AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- FS10 2.469 203.784 2.216 0.000 225.00 15.08 FS10 <- H10 6.357 206.000 0.009 2.165 225.00 2.27 H10 <- FS9 6.357 208.174 0.024 3.032 325.00 3.29 FS9 <- H9 6.357 211.230 0.017 2.165 325.00 3.29 H9 <- FS8 6.357 213.413 0.024 3.032 325.00 3.29 FS8 <- H8 6.357 216.469 0.017 2.165 325.00 3.29 H8 <- FS7 6.357 218.652 0.024 3.032 325.00 3.29 FS7 <- H7 6.357 221.709 0.017 2.165 325.00 3.29 H7 <- FS6 6.357 223.892 0.024 3.032 325.00 3.29 FS6 <- H6 6.357 226.948 0.017 3.032 325.00 3.29 H6 <- FS5 6.357 229.997 0.024 2.165 325.00 3.29 FS5 <- H5 6.357 232.187 0.017 2.165 325.00 3.29 H5 <- FS4 6.357 234.370 0.024 3.032 325.00 3.29 FS4 <- H4 6.357 237.426 0.017 2.165 325.00 3.29 H4 <- FS3 6.357 239.609 0.024 3.032 325.00 3.29 FS3 <- H3 6.357 242.665 0.017 2.165 325.00 3.29 H3 <- FS2 6.357 244.848 0.024 3.032 325.00 3.29 FS2 <- H2 6.357 247.905 0.017 2.165 325.00 3.29 H2 <- SP1 6.357 250.088 0.151 2.382 325.00 3.29 SP1 <- TOR 6.357 252.621 0.184 0.000 325.00 3.29 TOR <- BOR 6.357 252.805 0.210 4.681 325.00 3.29 BOR <- PMPO 6.357 257.696 0.171 0.000 325.00 3.29 System Demand Pressure... 257.868 Safety Margin................ 0.016 Press. @ Pump Outlet 257.883 Press. From Pump Curve ( PMPI - PMPO )... -170.144 Press. @ Pump Inlet 87.739 PMPI <- UG1 6.357 87.739 0.103 0.433 325.00 3.29 UG1 <- TEST 6.160 88.275 0.820-0.433 325.00 3.50 Total Flow..................... 325.000 Pipe with highest velocity: PRV - FS10 (15.078) Water Supply Summary @ Point TEST Total Flow From Water Supply Curve........ 325.000 Pressure From Water Supply Curve......... 88.662 System Pressure Demand At Supply Curve...... 88.646 Safety Margin at Supply Curve......... 0.016

4) Fill in the Specification Chart with the required hydraulic information for the manufacturer. The maximum residual pressure available at the Fire Sprinkler system demand at the 10 th Floor PRV is shown below. The maximum residual pressure available at the Fire Sprinkler system PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Fire Sprinkler system node along the standpipe. Examples - (At node FS9 211.23-2.216 = 209.01 PSI) (At node FS2 247.905-2.216 = 245.69 PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer. Shown are values for the Fire Sprinkler System for the 10 th and 2 nd floors. Note: The actual required pressure on the system side of the PRV must include the safety margin desired. Therefore, the minimum pressure required is 120 PSI = 110 PSI as calculated + (10 PSI Safety). The Fire Sprinkler System Demand Flow is 225 GPM with a required Pressure of 120 PSI.

Repeat the calculation to determine the maximum residual pressure available at the Hose PRV for all the floors. Initial Input Screen used to calculate the maximum residual pressure available at the hose flow on the supply side of each PRV at all levels. The Standpipe Top hose outlet demands a flow of 250 GPM and Minimum Pressure of 100 PSI at the PRV outlet plus 250 GPM at the next outlet. (Any start pressure will do to begin with as we will be adding the safety margin back in and recalculating until there is no safety margin remaining.)

General Calculation Program Job - Pressure Reducing Valve Calculation Example Date - 03/21/12 File - F:\HES\HydraCALC\Ver50\Data\Jobs\Pressure Reducing Valve Calculation Example.wx1Time - 10:35:40 AREA CALCULATED - HEAD FLOW SUMMARY Actual Req. Delta Actual Req. Delta ID K-Factor Flow Flow Flow. Press. Press. Press PRV n/a 250.00 250.00 0.00 181.380 Pt 181.380 0.000 H9 n/a 250.00 250.00 0.00 189.296 Pt 1.000 188.296 Total K Factors.... 0 Total Fixed Flows... 2 Sum Actual Flow.... 500.00 Sum Required Flow... 500.00 Sum Delta Flow.... 0.00 Max Delta Flow.... 0.00 Max Delta Pressure.. 188.296 AREA CALCULATED - COMPLETE SUMMARY Start Finish Diam. Start Normal Pf Elev/Fixed Flow Vel Point Point Pres. Pres. Pres. PRV <- H10 2.469 181.380 2.693 0.000 250.00 16.75 H10 <- FS9 6.357 184.073 0.015 3.032 250.00 2.53 FS9 <- H9 6.357 187.119 0.011 2.165 250.00 2.53 H9 <- FS8 6.357 189.296 0.054 3.032 500.00 5.05 FS8 <- H8 6.357 192.382 0.039 2.165 500.00 5.05 H8 <- FS7 6.357 194.586 0.054 3.032 500.00 5.05 FS7 <- H7 6.357 197.672 0.039 2.165 500.00 5.05 H7 <- FS6 6.357 199.876 0.054 3.032 500.00 5.05 FS6 <- H6 6.357 202.962 0.039 3.032 500.00 5.05 H6 <- FS5 6.357 206.033 0.054 2.165 500.00 5.05 FS5 <- H5 6.357 208.253 0.039 2.165 500.00 5.05 H5 <- FS4 6.357 210.457 0.054 3.032 500.00 5.05 FS4 <- H4 6.357 213.543 0.039 2.165 500.00 5.05 H4 <- FS3 6.357 215.747 0.054 3.032 500.00 5.05 FS3 <- H3 6.357 218.833 0.039 2.165 500.00 5.05 H3 <- FS2 6.357 221.038 0.054 3.032 500.00 5.05 FS2 <- H2 6.357 224.124 0.039 2.165 500.00 5.05 H2 <- SP1 6.357 226.328 0.335 2.382 500.00 5.05 SP1 <- TOR 6.357 229.045 0.408 0.000 500.00 5.05 TOR <- BOR 6.357 229.454 0.466 4.681 500.00 5.05 BOR <- PMPO 6.357 234.601 0.380 0.000 500.00 5.05 System Demand Pressure... 234.981 Safety Margin................ 0.002 Press. @ Pump Outlet 234.983 Press. From Pump Curve ( PMPI - PMPO )... -150.000 Press. @ Pump Inlet 84.983 PMPI <- UG1 6.357 84.983 0.228 0.433 500.00 5.05 UG1 <- TEST 6.160 85.644 1.819-0.433 500.00 5.38 Total Flow..................... 500.000 Pipe with highest velocity: PRV - H10 (16.753) Water Supply Summary @ Point TEST Total Flow From Water Supply Curve........ 500.000 Pressure From Water Supply Curve......... 87.030 System Pressure Demand At Supply Curve...... 87.028 Safety Margin at Supply Curve......... 0.002

The maximum residual pressure available at the Standpipe demand at the 10th Floor Hose PRV is shown below. The maximum residual pressure available at the Hose PRV for all the other floors can be quickly found by subtracting the friction loss of the 2 ½ pipe from the pressure available at each Standpipe Hose node along the standpipe. Examples - (At node FS9 187.119-2.693 = 184.43 PSI) (At node H2 226.328-2.693 = 223.64 PSI) All the maximum residual pressures can now be supplied to the PRV manufacturer.

Below is an example of a field adjustable PRV made by Elkhart Brass Fire Fighting Equipment. Follow the manufacturer s guide for proper field adjustment of the pressure reducing valves. Similar hydraulic pressure information is required in order to factory set or to field adjust a PRV.