Formal Interpretation NFPA 10. Portable Fire Extinguishers. 2013 Edition



Similar documents
Model Safety Program

PLAN SUBMITTAL REQUIREMENTS FOR KITCHEN HOOD AND DUCT EXTINGUISHING SYSTEMS

FIRE EXTINGUSIHER INSPECTION, MAINTENANCE, AND TESTING PROCEDURES

UL 300 Standard. RS 1021 (9/13) 2013 Nationwide Mutual Insurance Company Page 1 of 6 All Rights Reserved

Automatic fire-extinguishing systems for commercial cooking

Commercial Kitchen Fire Safety

PLAN SUBMITTAL REQUIREMENTS FOR SPRAY BOOTHS AND SPRAYING ROOMS EXTINGUISHING SYSTEMS

presents Cooking With Fire Fixed Fire Suppression & Exhaust Systems for Cooking Environments Monday, 17 June, 13

INFORMATION BULLETIN Bulletin No Bureau of Fire Prevention Date: June 10, 2005 Revised: March 8, 2007

EXETER TOWNSHIP DRY OR WET CHEMICAL FIRE SUPPRESSION SYSTEMS

GUIDELINE 5. CLASSES OF FIRE, TYPES OF PORTABLE FIRE EXTINGUISHERS, INSPECTION & MAINTENANCE OF FIRE EXTINGUISHERS IN UNIVERSITY BUILDINGS

All You Ever Wanted to Know About Fire Extinguishers...

Errata has been identified as follows:

The Mission Critical Fire Protection Experts

2014 Limited Plan Submittal Checklist

Code Compliance Guideline: Swimming Pool Chemicals

MONARCH FIRE PROTECTION DISTRICT

Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment

Name Of Occupancy Date. Yes No Describe

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

How To Write A Fire Risk Assessment

Six Monthly Servicing of Fire Extinguisher on Commercial Vessels.

Portable Fire Extinguisher Presentation

Fire Extinguishers. A Health and Safety Guideline for Your Workplace. Fire Extinguishing Methods. Introduction. Types of Extinguishers

Fire Extinguishing Systems -- OSHA Standards

General Fire Code Requirements Within Commercial Tenant Spaces

Maintaining Fire Protection Systems

NATIONAL FIRE ALARM AND SIGNALING CODE

INSPECTION, TESTING AND MAINTENANCE OF FIRE PROTECTION SYSTEMS AND EQUIPMENT

G SPECIFICATION: GAS METER AND REGULATOR INSTALLATION REQUIREMENTS. 3 and Gas Yellow Book. REVISIONS: (See ) 1/15/14 5 Years

(1) Acceptable means having been inspected by the Commissioner or his/her representative and approved for the intended usage.

FIRE CODE INTERPRETATION

FIRE RISK ASSESSMENT

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

Winnipeg Fire Department Fire Prevention Branch

Hydrostatic Testing of Aviation Components

MEANS OF EXIT / ESCAPE / EGRESS SELF INSPECTION CHECKLIST

REGULATORY REFORM (FIRE SAFETY) ORDER Fire Risk Assessment. 145 Drury Lane Covent Garden London WC2B 5TA

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

NMSU FIRE DEPARTMENT Commercial Kitchen Fire Suppression Worksheet

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Fire Safety PROCEDURES January 2011

EACH CLASS of fire A, B, C, or D has a different source. Some

FIRE RISK ASSESSMENT

Notes. Material 1. Appropriate Flammable Liquids

Vehicle Fire Protection. An Ownerʼs Manual for ANSUL Fire Suppression/Detection Systems

Busting the UL 300 Money Myth

OCFRD TENT STANDARD This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

SPECIAL CLAUSES/WARRANTIES THESE ARE OPERATIVE ONLY IF SHOWN IN THE SCHEDULE OR IN AN ENDORSEMENTFORMING PART OF THE SCHEDULE

Queen's University Environmental Health and Safety

Waste Oil Collection / Storage

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS November 2011

Minnesota State Department of Public Safety

Georgia State Amendments to the International Fire Code (2012 Edition)

Fire Extinguishers Water Extinguishers

OREGON FIRE CODE Interpretations and Technical Advisories

SELF-INSPECTION PROGRAM FOR FIRE PROTECTION EQUIPMENT

NFPA31FuelOilPiping 1 Revised

FIRE SAFETY RECORD OF TESTS LOGBOOK

Greater Manchester Fire and Rescue Service

TYPICAL FIRE SAFETY INSPECTION VIOLATIONS

ANSUL. Restaurant Fire Suppression Systems ANSUL UL 300 ANSUL. LOW ph

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

Name of Business. Record 1- Approved Food Suppliers List

THE GAS UTILITIES S AND THE JAPAN GAS ASSOCIATION S EFFORTS TO IMPROVE SAFETY

Zurich Small Business - Restaurant Supplemental Information Bailey-Yorkshire Insurance Associates

Permit Application for Mobile Food Truck

EXTINGUISHER. The purpose of this module is to sensitize firefighters on the subject of extinguishers.

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS

Important Ontario Fire Code Information for Building Owners in the City of Windsor

Building Permit, Fire Inspection and Operating Permit Fee Schedule

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

MOBILE FOOD A GUIDE TO PERMITTING IN ALBUQUERQUE

Fire Safety Risk Assessment

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

The terms hazard and risk are often used, which we define as the following:

Section III Hazardous Materials Management

MAINTENANCE OF SMALL WATER SUPPLY, SANITATION AND IRRIGATION SCHEMES

ALVERNIA UNIVERSITY OSHA REGULATION: 29 CFR WELDING, CUTTING, AND BRAZING ( HOT WORK ) SECTION: 3600

PACKAGED FIRE TUBE BOILER

Restaurant & café guide

OPERATIONS & MAINTENANCE (O&M) FOR PROPANE STORAGE FACILITIES

Building Code Clarifications - 7. Fire Resistance

Formal Interpretation NFPA 30. Flammable and Combustible Liquids Code Edition

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

HOT WORK PERMIT PROCEDURES

CIBSE Guide M: Maintenance engineering and management Statutory compliance legislation and guidance

SUBCHAPTER 17 FIRE ALARM, DETECTION AND EXTINGUISHING EQUIPMENT

An inventory of hazardous materials used in your workplace will prove useful.

SARATOGA FIRE DISTRICT EARLY WARNING FIRE ALARM SYSTEM STANDARDS AND REQUIRMENTS CONTENTS

Fire Safety Log Book

The following definitions apply with regard to requirements specified in this document:

Restaurant and Café Risk Management Guide. Don t Risk It!

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Transcription:

Reference: 5.5.5 and 6.6.1 F.I. No.: 10-02-2 Background:, subsection 5.5.5 requires that fire extinguishers be provided for the protection of cooking appliances that use combustible cooking media (vegetable or animal oils and fats) be listed and labeled for Class K fires. Subsection 6.6.1 requires class K fire extinguishers be provided for hazards where there is a potential for fires involving combustible cooking media (vegetable or animal oils and fats). Based on these two requirements, there is confusion with regard to requiring class K extinguishers for stove top cooking. Questions No. 1: Do subsections 5.5.5 and 6.6.1 require class K extinguishers to be installed for commercial fryers employing combustible cooking media (vegetable or animal oils and fats)? Answer: Yes Questions No. 2: Do subsections 5.5.5 and 6.6.1 require class K extinguishers to be installed for a griddle? Answer: Yes Questions No. 3: Do subsections 5.5.5 and 6.6.1 require class K extinguishers to be installed for a stove top frying pan? Answer: Yes Issue Edition: 2002 Reference: 4.2.3 and 5.7.1 Issue Date: July 7, 2005 Effective Date: July 27, 2005 Copyright 2013 All Rights Reserved

Reference: 5.5.5.3 F.I. No.: 10-98-3 Background: 5.5.5.3 Where a hazard is protected by an automatic fire protection system, a placard shall be conspicuously placed near the extinguisher that states that the fire protection system shall be actuated prior to using the fire extinguisher. Question: Is it the intent of the Committee that the instructions on this placard apply to all Class K fires including those other than the deep fryer fires? Issue Edition: 1998 Reference: 2-3.2.1 Issue Date: January 22, 2002 Effective Date: February 11, 2002 Copyright 2013 All Rights Reserved

Reference: 6.2.1.1, 6.2.1.2, 6.2.1.5 F.I. No: 84-2 Background: During regular maintenance of fire extinguishers in an apartment building, it was found that extinguishers were provided on the main or ground level floor and not on the second floor or basement level. The apartment proprietors explained that the rationale for not providing extinguishers on the second or basement level was that the extinguishers on the main level are within the 75-ft maximum travel distance, if the stairway is included in the calculations. Question: Does prohibit the inclusion of a flight(s) of stairs in the calculation of travel distance? Travel distance is intended to reflect the time it takes to respond with an extinguisher to a fire emergency. A staircase slows down response time. Furthermore, there could well be interference to obtaining and transporting the extinguisher from tenants vacating the premises. Paragraph 6.1.3.1 states, Fire extinguishers shall be conspicuously located where they will be readily accessible and immediately available in the event of fire, and 6.1.3.3.1 states, Fire extinguishers shall not be obstructed or obscured from view. Extinguishers located on another floor do not meet the intent of these paragraphs. Issue Edition: 1984 Reference: 3-2.1, 3-2.3 Date: October 1984 Copyright 2013 All Rights Reserved

Reference: 7.1.2.1, 7.1.2.2, 7.3.1, 7.3.2 F.I. No.: 10-98-1 Background: Some people claim that a maintenance procedure that does not require internal maintenance is essentially the same as a monthly inspection procedure, so only minimal knowledge is required and no special training. Some people claim persons performing the external examination required by 7.3.2 need special training, the manufacturer s maintenance manual, repair parts, and appropriate servicing equipment. Question: Subsection 7.3.2 requires all extinguishers be examined externally on an annual basis. Subsection 7.3.3 requires certain extinguishers to be examined only internally. Are individuals conducting only the external maintenance required to be trained and certified in accordance with 7.1.2.1 and 7.1.2.2? Issue Edition: 1998 Reference: 4-1.4, 4-4.1, and 4-4.2 Issue Date: December 15, 1998 Effective Date: January 4, 1999 Copyright 2013 All Rights Reserved

Reference: 7.3.1.1.1 F.I. No.: 10-98-2 Background: Some people interpret 7.3.1.1.1 to mean that it is acceptable either to do maintenance at yearly intervals or to do maintenance when an inspection specifically indicates the need. Either program will satisfy requirements. Question: Is it the intent of 7.3.1.1.1 that all fire extinguishers should be subjected to maintenance at a maximum interval of not more than 1 year? Issue Edition: 1998 Reference: 4-4.1 Issue Date: December 15, 1998 Effective Date: January 4, 1999 Copyright 2013 All Rights Reserved

Reference: 7.3.1 F.I. No: 84-5 Background: Subsection 7.3.1 states: Where required by another section of this standard, maintenance procedures shall include the procedures detailed in the manufacturer s service manual and a thorough examination of the basic elements of the fire extinguisher, including the following: (1) Mechanical parts of all fire extinguishers (2) Extinguishing agent (3) Expelling means (4) Physical condition Referring now to Annex I, Table I.1(a), Mechanical Parts Maintenance Checklist, calls for a check of Gas Tube and Siphon or Pickup Tube and Table I.1(b ), Agent and Expelling Means Maintenance Checklist, calls for a check of Agent Condition (contamination, caking, or wrong agent). Question: To do the above two check points, is it the intent to require emptying, annually, a cartridgeoperated dry chemical extinguisher? Answer: No. Issue Edition: 1984 Reference: 4-4.2 Date: March 1986 Copyright 2013 All Rights Reserved

Reference: 7.9.2, 7.9.3 F.I. No: 84-3 Background: A system has been submitted to a laboratory for listing that is intended for the rebuilding of 2 ½-gallon, stainless steel, stored-pressure, water fire extinguishers that were manufactured in 1964 or later. The extinguishers would be thoroughly inspected and tested, fitted with a new hose and solid AFFF cartridge nozzle, and relabeled. No modifications would be made to the internal parts of the extinguisher, and the extinguisher charge remains exactly as originally designed. The entire operation would be subjected to follow-up inspections by the testing laboratory and accomplished only at locations authorized by the laboratory. The rating of the extinguisher is upgraded from 2-A to 3-A:40-B, thus providing the owner of the extinguisher with a significant increase in fire extinguishing capability. A laboratory has accepted the system for test but is unlikely to list it until the question of possible conflict with 7.9.2 and 7.9.3 is answered. Question 1: Is it the intent of 7.9.2 and 7.9.3 to prohibit field alteration or conversion of listed portable extinguishers from one type to another? Issue Edition: 1984 Reference: 4-5.3.8 Date: January 1985 Reissued to correct error: January 1986 Copyright 2013 All Rights Reserved

Reference: 8.3.1 F.I. No: 84-1 Background: A 12-year testing interval has been used when portable CO 2 fire extinguishers have not been discharged. Consequently, this procedure has saved a considerable amount of time and money. Question: Is it the intent of 8.3.1 that all portable CO 2 fire extinguishers be hydrostatically tested every 5 years, regardless of whether or not they have been discharged? Issue Edition: 1984 Reference: 5-2 Date: June 1984 Copyright 2013 All Rights Reserved