Tank Heating Solutions. For Oil Spill Response Vessels



Similar documents
Marine Boilers. From a world class boiler manufacturer

Range Tribune HE Solar Unvented Direct and Indirect Cylinders

Steam Generator Boilers Compact Steam Boilers. Rapid Start-Up Safe in Operation

INTEC Engineering GmbH Heating Solutions for the Marine Industry

5.2. Vaporizers - Types and Usage

FLASH TANK ECONOMIZER PRODUCT GUIDE

MH 3M & 4M. High pressure washers with hot benefits

Fuel Treatment and Conditioning Systems

Electric Flow Boiler

1. A belt pulley is 3 ft. in diameter and rotates at 250 rpm. The belt which is 5 ins. wide makes an angle of contact of 190 over the pulley.

Laddomat Charging unit

Session 2: Hot Water Supply

Cooking at the Speed of light!

Heavy Fuel Oil supply units. The world s best selling HFO supply unit. The right choice for any conditions

Boiler & Pressure Vessel Inspection discrepancies and failures

Hot water supply, distribution and use

ELECTRODE BOILERS VAPOR POWER INTERNATIONAL

Description of functions

Sulfur Tail Gas Thermal Oxidizer Systems By Peter Pickard

DIRECT STEAM INJECTION HOT WATER SYSTEMS FOR JACKETED HEATING

QPM3 Low pressure pump for circulation of oil in hydraulic and lubricating systems

LG Electronics AE Company, Commercial Air Conditioning

I. STEAM GENERATION, BOILER TYPES

CONTENTS. ZVU Engineering a.s., Member of ZVU Group, WASTE HEAT BOILERS Page 2

WASHING PROCESS OF CARGO TANKS ON TANKERS FOR TRANSPORTATION OF CRUDE OIL

ASPE Seminar Water Heater Piping Strategies. Presented by Joe Kalarickal, EIT Regional Sales Manager AERCO International

How Ground/Water Source Heat Pumps Work

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

Efficiency on a large scale CFB Steam Boilers

The soot and scale problems

PLATE HEAT EXCHANGER. Installation Manual. Customer Name: Serial number: Purchase order number: Project:

STEAM HEATING SYSTEM TROUBLESHOOTING GUIDE

Alfa Laval in brief Alfa Laval is a leading global provider of specialized products and engineering solutions.

Waste Heat Recovery through Air Conditioning System

NFPA31FuelOilPiping 1 Revised

Fully Pumped Systems

ECOCIAT. Domestic hot water heat recovery unit

LNG Storage and Fuel Gas Systems. LNG: Fuel for Shipping, London 15-Feb Carriers & Offshore Units. Jürgen Harperscheidt Sales Manager

The Worcester Greenstar System Filter. An innovative solution for reducing system contaminants

Energy Saving Fact Sheet Boilers

SWIMMING POOL HEAT PUMP Owners Manual

R&D on Oil-Burning, Environment-Friendly, High-Efficiency Boiler

Sizing and Selection of Hot Water Generating Plant. Presentation by: Rob Larner & David Dutch

Indirect-Fired Storage Water Heater Models WH-30 through WH-80 INSTALLATION AND OPERATING INSTRUCTIONS

Norwegian Clean Seas Association for Operating Companies (NOFO)

LNG BUNKERING LNG AS A SHIP S FUEL GREEN SHIP TECHNOLOGY, OSLO 23-MAR Carriers & Offshore Units. Jürgen Harperscheidt Sales Manager

CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER

Solar Hot Water Heaters

Link-Up. Solid Fuel Association Guide to Central Heating.

Lessons Learned, Best Practices and Observations Plant Winterization Visits

MU Cooling System. Hi-Pres. Low sulphur fuel cooling system. System specifications HI-PRES MARINE & OFFSHORE

Air Eliminators and Combination Air Eliminators Strainers

PELLEXIA COMFORT ENVIRONMENT COMPATIBLE

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

Indirect fired heaters

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

Overview of Heat Recovery Boiler Systems and Operating Costs Factors Effecting Blowdown Blowdown Heat Recovery The Energy Tank

Strong partners offer perfect solutions. Automatic filtration and maintenance of engine lubricating oil in diesel locomotives

Torino Nord. Cogeneration Plant. The gas turbine. The steam generator. The Torino Nord cogeneration plant produces electricity and heat for district

Designed for multi-injector endurance testing, the

Vicot Solar Air Conditioning. V i c o t A i r C o n d i t i o n i n g C o., l t d Tel: Fax:

Laundry Hot Water Systems

IGEMA BOILER LEVEL & TDS CONTROLS

Technical data. Danfoss DHP-A

ECOplus Solar Cylinder

Quik Lining Systems Heater Owners Guide

Natural Convection. Buoyancy force

Delivering exceptional performance and Ecovalue. Ecocent

ITE. Indirect calorifier ITE - 400/500/600/750/1000. Installation, User and Service Manual. Innovation has a name.

SIOUX HYBRID WATER HEATER

DIESEL-FUELED, BLOWN AIR, DUCTABLE HEATERS

Saeid Rahimi. Effect of Different Parameters on Depressuring Calculation Results. 01-Nov Introduction. Depressuring parameters

HEAVY DUTY STORAGE GAS

UNITOR ULTRASONIC cleaning

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Take the complication out of cooling. Data center cooling equipment and service from Alfa Laval

In-Line Air Separators

Hot Water Boilers and Controls Why Condensing Boilers are Different. Presented Oct. 14, 2008 Long Island Chapter, ASHRAE

Floor Heating Warehouse.co.uk

Energy Efficient Operations and Maintenance Strategies for Boilers

Backup Fuel Oil System Decommissioning & Restoration Plan

UNDERSTANDING CENTRAL HEATING SYSTEMS

Marine after-treatment from STT Emtec AB

Supply, storage and handling of LNG as ship s fuel Björn Munko LNG 17, Houston

Energy Efficiency HOSPITALITY.

Evaluate, Clean, and Tune Guidance

Visions become real. Temperature control and cooling systems. The innovative and reliable solution

Signature and ISX CM870 Fuel System

Operating instructions

Solar air collectors for industry and larger halls S Ø. Efficient dehumidification and air heating for free...

Natural geothermal energy.

Static Electricity. A Health and Safety Guideline for Your Workplace. What Are Some Sources of Static Electricity? What is Static Electricity?

Hybrid heat pumps. saving energy and reducing carbon emissions

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

A Guide to Trouble-Free Cooling Towers

Investigations of a Long-Distance 1000 MW Heat Transport System with APROS Simulation Software

High-efficient gas boiler CompactGas

High efficiency, cast-iron gas boiler

Heating Water by Direct Steam Injection

MICRO-COGENERATION AND DESALINATION USING ROTARY STEAM ENGINE (RSE) TECHNOLOGY

Transcription:

Heating Solutions For Oil Spill Response Vessels

A chain is only as strong as its weakest link Oil spill incidents are unplanned and unwanted events that can have dire consequences for the environment and fragile ecosystems around the globe. Fast response combined with the correct equipment able to cope with any type of hydrocarbon emulsion is vital to minimize the risk involved in extracting, processing and transporting petrochemicals outside our coastlines. PARAT Halvorsen, in close cooperation with yards and ship owners, has developed a system that strengthens one vital part of the response value-chain in a very cost efficient way. A heating system that is fully integrated into the response vessels utility and heat recovery loop and that in moments can be re-mobilized to deliver steam through specially engineered injection nozzles into the tanks that carry recovered hydrocarbons. PARAT Halvorsen is a Norwegian technology company providing state of the art solutions for steam- or other heated medium based processes. PARAT has delivered boilers and heaters to the marine and offshore markets since 1970.

Theory Exploration and production of hydrocarbons off coastlines around the world is increasing. Reliable oil spill response solutions are essential, and the focus on this type of technology is constantly growing. PARAT has been working on the transportation aspects of this problem for years now. Ships store the oil recovered from the sea in tanks, and the oil needs to stay viscous so the tanks can be emptied. This is done by injecting steam into the emulsion during transport. During the Prestige oil spill incident in the Bay of Biscay in 2002 it was discovered that the recovered oil settled quickly in the storage tanks and became too thick to be pumpable. The only way to get it out was mechanically. In order to increase the viscosity, steam was injected directly into the tanks. In the aftermath, NOFO (Norwegian Clean Seas Association for Operating Companies), developed a basic standard for vessels to be approved for oil spill recovery operations which specifically requires tank heating to be part of the vessels basic equipment. When presented with such an opportunity, PARAT Halvorsen worked closely together with the yards and owners to find and develop the most space and cost efficient solution available. This involves integrating the vessel hot water loop with the contingency steam injection tank heating system. Permanent installation The multi nozzle steam lance will be designed and optimized for each tank. For tanks where entrance is not allowed, the lance must be installed permanently. To enable permanent installation the nozzle heads are fitted with rupture discs that ensure that there will be no ingress of pollution to the nozzle head when the lance is not in operation. Various basic concepts : Multi nozzle lance STEAM BACKUP dedicated steam boiler installed as a 100% backup system, which will only be in operation when the vessel is in Oil Recovery mode. STEAM BOILER WITH TWO PHASE HEAT EXCHANGER steam boiler provides heat to the vessels hot water loop through a steam/hot water heat exchanger. In Oil Recovery mode, a small flow is still routed through the heat exchanger to provide sufficient heat for the critical HVAC consumers. In case of oil pollution to the sea surface, the oil will be recovered and stored in tanks in the oil recovery ships until it can be delivered for processing. Experience from such situations has shown that the oil must be heated to maintain a sufficient viscosity for offloading. To ensure that the recovery vessels can operate efficiently, NOFO has made regulations requiring a sufficient heating system for the tanks on board. Presently, such oil tanks are heated by steam from a boiler on board. The steam is in many cases delivered to several nozzles installed around the perimeter of the tank. To achieve an adequate distribution of steam and heat in the tank multiple nozzles must be installed. Such an installation has several drawbacks. One is the necessity of many openings in the tank. Another is the need of a manifold to distribute the steam. Both these features lead to a lot of couplings and gaskets that may develop leaks, and which are costly. Even with several nozzles installed, the heat distribution may be insufficient, leaving spaces such as the area around the tank outlet in the bottom in a cold shadow. There may also be insufficient space around the tank for such a large installation. Often the tank is accessible only in a small sector of its circumference, making it difficult to provide a sufficient number of steam inlets. PARAT Halvorsen has developed a multi nozzle arrangement that ensures a better distribution of heat in the oil recovery tank and at a lower cost than previously mentioned alternatives. This is achieved with a distribution system which is capable of heating the whole tank from one insertion point. The arrangement reduces the need for complicated assemblies in the tanks, and also ensures that it is sufficient with one nozzle system per tank. COMBINED STEAM AND HOT WATER BOILER boiler fully integrated in the vessel hot water and heat recovery loop. When in Oil Recovery mode the boiler is dedicated to supply steam for tank heating, and the HVAC-loop is maintained with a bypass system. The system is patented by PARAT Halvorsen.

Normal Operation (Figure 1) (Figure 2) Oil Recovery Mode ORO s Steam Lance on Deck Double Block & Bleed arrangement Steam Nozzle in ORO s Flow Control Valve Flow Control Valve Expansion Circulation Pump Domestic Heater Hot Water HVAC Back-up Heater Expansion Circulation Pump Domestic Heater Hot Water HVAC Boiler in Hot Water Mode Boiler in Steam Mode Softening Filter Engine Heat Recovery Engine Heat Recovery < Make up Water Hot Water Loop Cold Water Return Feed Water Pump Feed Water Steam Feed Water Hot Water Loop Cold Water Return Integrated Solution To save space, cost and to ensure proper functioning of the boiler equipment, it is smart to ensure that the boiler is in constant operation and part of the overall vessel HVAC system. PARAT Halvorsen has solved this as illustrated above. NORMAL OPERATION: During normal operation the boiler is part of the vessel hot water loop. When the heat demand is higher than the heat recovered from the engines, the boiler will start and supply the additional energy required, as shown in figure 1. OIL RECOVERY MODE: If an emergency should occur, the boiler is isolated from the hot water loop. Heating for critical HVAC consumers is maintained by a compact back-up heater. The water level is lowered and the boiler is switched to steam mode. Steam is then supplied directly to the tanks that contain recovered oil. This is shown in figure 2.

Heating Solutions For Oil Spill Response Vessels 12 1 6 2 3 5 7 8 9 10 11 4 1. Boiler with Back-up heater 2. Water Treatment System 3. Engine Heat Recovery 4. Feedwater Pump 5. Expansion 6. Circulation Pumps 7. Domestic Heater 8. Heating 9. HVAC 10. Block & Bleed System 11. Multi Nozzle Steam Lance 12. Hand Held steam lance The Combined steam and hot water boiler, which is patented by PARAT Halvorsen, is in daily use as it is fully integrated in the vessels hot water loop. Typical duty: 1250kW The multi nozzle steam lance is installed through a flange connection in the tank, and should be installed as close to the tank suction outlet as possible. When steam is required for tank heating, a small back-up heater keeps up the temperature in the hot water loop. Typical duty: 200kW. The heater is normally placed on top of the boiler. PARAT Halvorsen has developed a handheld steam lance for connection to a steam outlet on the vessels deck. The hand held steam lance can be used for removal of oil spill on deck and equipment and for de-icing. The lance is delivered with an 25m insulated steel hose.

Steam vs Hot Water When evaluating tank heating concepts for the NOFO standard it was determined through both theoretic assessment and empirical testing that steam injection was the ideal way to ensure sufficient heat distribution in the recovered oil. However, in later years warm water based solutions have been introduced to the market. PARAT Halvorsen decided to evaluate the feasibility of this method and performed numerous theoretical and practical tests. Martin Løvland (MSc Heat and Combustion Engineering) explains the theory behind transfer of heat in petrochemicals during the Oil Spill Response seminar held at PARAT Halvorsen. Test results show that transferred heat in oil is approximately 10% of that with the coil in water. This shows that the effect measured in water must be reduced by a factor of 10 to give a correct representation of the capacity when immersed in oil. We based our tests on the specific requirements in the NOFO 2009 requirements. All the vessel s ORO tanks must be equipped with a permanent system for heating recovered oil/emulsion. The system must make it possible to raise the temperature 15 C for a volume of 1000m 3 within a period of 12 hours; calculated for a sea temperature of 5 C and an air temperature of 0 C. The calculations set a specific heating capacity at 3.44 kj/kg/ C which is the typical value for a 50% mix of oil and water. It must be possible to use the entire capacity of the heat source in a random maximum combination of 3 tanks. Based on this the required energy input can be calculated as follows: Q = (1.000.000 * 1.0kg/l * 3440J/kgK *15 C) (12hrs * 3600s/hr) Q = 1194kW (1790 kgs/h) This means that you need 400kW of heat input in each tank to fulfil the requirements. The warm water solutions currently on the market are based on compact coils installed in flanged connections in the side of the tanks. To achieve the sufficient heat transfer from the coils to the oil, you theoretically need to circulate the medium over the heating surfaces with a significant velocity. Initial tests performed with this concept were done in water. Water is a medium with very good heat transferring properties, through natural convection. The reason for this is the low viscosity and high conductivity of water. For hydrocarbons, viscosity is far higher and conductivity far lower. The high viscosity will lead to the accumulation of heated emulsion around the coil that isolates the mass from further heat transfer because the ΔT is reduced. In theory, we therefore expect a large reduction of heat transfer with the coil in question when used in hydrocarbons. In order to test this out we first tried the coil in water to document the coil s energy output. Then we tested it in a more adequate hydrocarbon based medium to measure the relative reduction in heat transfer. The purpose of installing a heat source in the tank is to facilitate pumping of the medium. It is therefore the heat source s ability to break the wax bonds that determines the flow needed from the circulation pump inside the tank.

Assumptions for our calculation of velocity for the medium in relation to the coil: Heat capacity for the medium: Cp = 2.0 kj/kgk Required temperature increase: ΔT = 20 C (5..25 C) Heat input: Q = 400kW cross-section for a storage tank with a diameter of 4m: A = 12.6m 2 Calculated flow: Q = m x Cp x ΔT m = Q / (Cp x ΔT) = 400 / (2 x 20) = 10 kg/s = 36m 3 /h Calculated velocity over the heating coil inside the tank: F = u x A u = F/A = 36 / (3600 x 12,6) = 0.0008 m/s To achieve the sufficient heat transfer from the coils to the oil you theoretically need to circulate the medium over the heating surfaces with a significant velocity. Calculations show that velocity is so low that heat transport will not be influenced, so natural convection is therefore the only useful heat transfer mechanism. This velocity is so low that heat transport will not be influenced, so natural convection is therefore the only useful heat transfer mechanism. Even if the medium was sufficiently viscous to be pumped, a pump capacity of 200m 3 /h gives a velocity of only approximately 0.004m/s. This is still too low to influence the heat transfer. Resistance to heat transfer occurs in the thin layer of oil film on the coil s surface. An effective heat exchanger with small flow cross sections is needed if you want to increase the heat transport when using circulation. This type of exchanger cannot be used in viscous impure mediums because it will most likely be blocked after only a short period of time. When testing the system a coil with the same dimensions as the coils available on the market was used. Stated output of such a coil is 200kW, but calculation shows that without constant circulation the output with natural convection is about 100kW. When performing testing of the coil in both water and oil, we get the following results: Average effect in water: 68kW Average effect in oil: 7kW Transferred heat in oil is approximately 10% of that with the coil in water. This shows that the effect measured in water must be reduced by a factor of 10 to give a correct representation of the capacity when immersed in oil. The temperature measurements in the oil were taken from the centre of the coil and 50mm and 250mm above the coil. These measurements all had similar temperatures, which shows that the resistance against heat transfer is found at the surface of the coil and no heat pocket is formed around the whole coil. Circulation of the medium inside the tank will therefore not influence heat transfer to any significant degree. Calculation of the thickness of the heated oil film: Q = K/L * A * (T1-T2) Q = transferred energy output A = Heat surface area K = Conductivity L = Layer thickness T1 = Surface temperature of the coil T2 = Bulk oil temperature in the tank L = K/Q * A * (T1-T2) = 0,12W/m C / 7000W * 1.4m 2 * (88 C - 15 C) = 1.8mm The figure illustrates the difference between heat distribution from a Hot Water Coil and a Steam Injection Lance. Injection of steam results in an efficient heat distribution. The oil emulsion works as an insulating layer on the heat surface of the coil, thus limiting heat distribution to the entire tank volume. If the effectiveness of the coil is to increase significantly, the layer thickness must be reduced equivalently. This is only possible if we use heat exchangers with very small gaps between the plates. General circulation inside the tank will not influence heat transport so near the surface of the coil. No measurements were done in a mixture of hydrocarbon and water. Since the resistance of the transferred heat is found alongside the film near the coil's surface, we assume that when the coil is contaminated with hydrocarbon heat transport will be much lower, even in an oil/water mixture. Using a hot water coil of this magnitude for tank heating will not work because the transferred effect in oil is not even close to satisfying NOFO s requirements.

Oil-fired or Electrical boiler Retrofit PARAT Halvorsen can deliver both electrical and oil-fired boiler alternatives as part of the integrated solution. There are advantages and disadvantages with both technologies, which is illustrated in the table below. For existing vessels that do not have a tank heating system installed, PARAT Halvorsen can deliver complete retrofit packages. Either by replacing the existing hot water boiler with a new combined steam and hot water system, or with a containerized boiler system placed on deck. PARAT MEL-C, 1250kW, Electrical Combined Steam / Hot water boiler ELECTRICAL PARAT MSH, 1250kW, Oil-fired Combined Steam / Hot water boiler OIL-FIRED + - + - Compact size Requires sufficient High fuel efficiency Size and weight power supply References PARAT Halvorsen AS has more than 100 deliveries to OSR vessels, both oil-fired and electrical boilers. The deliveries include complete Heating System. A few selected reference projects are listed below. Very low turn down Lower overall fuel Low electrical Turn-down 1:3 1:100 efficiency power consumption Minimal maintenance Additional effect panel Robust design Maintenance Vessel: Viking Fighter Capacity: 1250kW, Type: Electrical Vessel: Vestland Mistral Capacity: 1600kW, Type: Electrical Vessel: REM Hrist Capacity: 1600kW, Type: Electrical No need for More cable routing Additional fuel tank flue gas ducting in vessel required No need for additional fuel tank No need for fuel supply arrangement Vessel: Troms Sirius Capacity: 1250kW, Type: Electrical Vessel: REM Fortune Capacity: 1250kW, Type: Electrical Vessel: North Pomor Capacity: 1600kW, Type: Oil-fired

Parat Halvorsen AS P.O. Box 173 N-4402 Flekkefjord Norway Tel +47 99 48 55 00 Fax +47 38 32 44 71 office@parat.no www.parat.no