Capacitor Protection Relay SPAJ 160 C. Product Guide



Similar documents
Voltage Regulator SPAU 341 C. Product Guide

Disturbance Recoder SPCR 8C27. Product Guide

Remote Monitoring and REC 501 Control Unit Product Guide

Arc Protection Relay REA 10_. Product Guide

Combined overcurrent & earth-fault relay. Type SPAJ 140 C

SPAM 150 C. Motor protection relay SPAM 150 C. User s manual and Technical description. U aux V NC. θ>θ t. θ [ % ] 9 EXT.TRIP I >> / I.

REA 10_ 1MRS MBG

Current and voltage measuring relays

Relion 605 series. Self-powered feeder protection REJ603 Product Guide

Trip circuit supervision relay. Type RXTCS

Overcurrent and earth-fault relay

Circulating Current Relay. Type IRXm

Three-phase monitoring relay CM-PFE

Waveguide Access Point WGA631. Product Guide

Quick Connect. quick - simple - efficient.

RM4TG20 three-phase network control relay RM4-T - range V

REA 101 Arc protection relay. Operator s manual

Electronic timer CT-VBS OFF-delayed without auxiliary voltage, for DC contactors Data sheet

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

Safety technique. Emergency stop module BO 5988 safemaster

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

Relion 605 series. Feeder protection and control / Feeder protection REF601 / REJ601 Product Guide

RM17TE V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC

ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories

Pilot-wire differential relay for lines with two or more terminals

38 Series - Relay interface modules A

80 Series - Modular timers 16 A. Features

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument D

MasterINTERFACE 39 Series - Relay interface modules

Low Voltage Products. Switches Automatic Transfer Switches

Analog signal converters CC-E I/I Current / current isolators

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

T Substation Maintenance and Commissioning Test Equipment

38 Series - Relay interface modules A

Arc Protection Relay REA 101. Operator s Manual

DRTS 33. The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

ABB i-bus KNX SA/S Switch Actuators Product Manual

Thermistor motor protection relays CM-MSS.22 and CM-MSS.23

Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous

48 SERIES Relay interface modules 10 A

Thermistor motor protection

MasterINTERFACE 39 Series - Relay interface modules

Digital Pressure Measuring Instrument MDR480

Electronic overload relay EF65, EF96 and EF146

FREJA 300 Relay Testing System

MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1

Electronic overload relay EF19 and EF45

Power Meter Series 700

AC3200 INTELLIGENT BROADBAND AMPLIFIER

A project to optimise quality and energy efficiency must include metering

60 Series - General purpose relays 6-10 A. Features

ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x , 2CDG 110 1xx R0011

instabus KNX / EIB System System E F G H

80 Series - Modular timers 16 A. Features

HSP GmbH Zum Handwerkerhof Wendelstein Tel / Fax: / Web: HSP@hsshsp.de NTG-3000.

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

RM35UA13MW. range V. Main. Product or component type. Relay monitored parameters

Bulletin 150 SMC Flex Smart Motor Controller Specifications

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER

Pluggable interface relays CR-P Pcb relays

Portal Software GSM-PRO Run LED displays module activity Com LED displays activity on the GSM network GSM-PRO

Thermal-Magnetic Circuit Breaker M1-..

Energy Management Energy Meter Type EM23 DIN

Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.

Technical data. General specifications. Indicators/operating means. 30 Hz Multiplex operation 30 Hz / n, n = number of sensors, n 5

MICROSENS. Central 48 V DC Power Supplies for PoE-Components. Description. Features

Instruction Bulletin. MCS025 Sync-Check Module Installation Sheet

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in

Thyristor-controlled power supplies and battery chargers

ELR: ABB range of front panel residual current relays Protection device according to IEC/EN Annex M

Rack mounted telephone- and leased line modem for industrial applications

Number 1 in efficiency

TRACTION NETWORK MONITORING AND PROTECTION SYSTEM SMTN-3 CITY ELECTRIC TRANSPORT RAILWAYS METRO INDUSTRY

Technical catalogue. Modular DIN rail components Installation contactors

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N

49 Series - Relay interface modules A. Features

Feeder Protection Relay. Technical Reference Manual - ANSI Version

Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...

Installation manual. Generator Paralleling Controller GPC multi-line C

Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs

LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A V AC coil

Feeder protection. for overhead lines and cables in isolated neutral or compensated networks. Specification

Applications. diris_826_a_1_gb_cat

Technical data. General specifications. Indicators/operating means. Electrical specifications Operating voltage U B Power consumption P 0 Interface

Relés e Contatores de Estado Sólido SIRIUS

Transcription:

Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase overload stage with inverse (ANSI) time characteristic Phase unbalance protection stage with definite time characteristic Phase unbalance protection stage with inverse time characteristic Undercurrent protection for detection of capacitor disconnection. Reconnection time with wide setting range Compensation for natural unbalance current Fully user-selectable output relay configuration Easy selection of appropriate operational scheme for various applications Numerical display of setting values, measured current values, memorized values, etc. Continuous self-supervision of hardware and software Serial interface for connecting the relay to the fibre-optic SPA bus and further to higher-level data acquisition, reporting and/or control systems Powerful software support for parameterization of the relay, for reading measured and recorded values, events, etc., and for storing readings Member of the SPACOM product family and ABB s Distribution Automation system CE marking according to the EC directive for EMC Application The numerical capacitor relay is an integrated current measuring multi-function relay designed to be used for the protection of capacitor banks. Capacitor banks are used in the power system for compensating the reactive power and for filtering harmonics. The capacitor banks are usually protected against overload caused by harmonic currents and overvoltage caused by internal faults in the bank. Protection against unintentional reconnection of a charged capacitor to an energized network is also to be included. All these functions are incorporated in the capacitor protection relay. A complete protection system for capacitor banks should also include overcurrent, short circuit and earth-fault protection. The capacitor protection relay is easily supplemented with adequate overcurrent and earth-fault relays from the SPACOM product range. 3

Design The capacitor protection relay includes a three-phase, two-stage overload unit, a twostage unbalance unit, an undercurrent unit and a reconnection inhibit timer. The relay measures the phase currents of the capacitor bank. The relay also measures the unbalance current of a split capacitor bank. The current transformer output can be adapted to the rated current of the relay by means of a matching setting. Equally, the unbalance unit is provided with a compensation feature which allows the natural unbalance current of a capacitor bank to be eliminated from the calculations. The phase currents measured by the relay are transformed to voltage images describing the voltages of the capacitor bank. Because harmonic components cause overloading of capacitor banks the relay measures harmonic components up to and including the 13th harmonic. The overload unit protects the capacitors against overvoltage. The first stage of the overload unit operates with inverse time operation characteristic, whereas the second overload protection stage has a definite time characteristic. The inverse time curve is based on ANSI/IEEE C37.99 and IEC 871-1 recommendations for voltage withstand related to time for capacitor banks. The slope of the curve is adjustable. The unbalance unit is also provided with two operation stages. i.e. an inverse time stage according to BS 142 and a definite time stage. The former is normally used for tripping and the latter for signalling. The purpose of the undercurrent protection unit is to detect disconnection of the capacitor bank and to prevent a charged capacitor bank from being switched to the network. The start value, the operate time and the reconnection inhibit time are adjustable. The capacitor protection relay is provided with one external control input. The control input can be used for blocking one or more of the protection stages, for carrying out an external trip command, for inhibiting a reconnection attempt and/or for resetting a latched output relay in the manual reset mode of operation. Data communication The feeder protection relay is provided with a serial interface on the rear panel. By means of a bus connection module type SPA-ZC 21 or SPA-ZC 17 the feeder protection relay can be connected to the fibre-optic SPA bus. The bus connection module SPA-ZC 21 is powered from the host relay, whereas the bus connection module type SPA-ZC 17 is provided with a built-in power unit, which can be fed from an external secured power source. The relay communicates with higher-level data acquisition and control systems over the SPA bus. Self-supervision The relay incorporates a sophisticated selfsupervision system with auto-diagnosis, which increases the availability of the relay and the reliability of the system. The selfsupervision system continuously monitors the hardware and the software of the relay. The system also supervises the operation of the auxiliary supply module and the voltages generated by the module. When a permanent internal relay fault is detected, the IRF indicator on the relay front panel is lit. At the same time the output relay of the self-supervision system operates and a fault message is transmitted to the higherlevel system over the serial bus. Further, in most fault situations, a fault code is shown in the display of the protection relay module. The fault code indicates the type of the fault that has been detected. Auxiliary supply voltage The auxiliary supply of the relay is obtained from an internal plug-in type power supply module. Two auxiliary power module versions are available: type SPTU 240R2 for the supply voltage range 80 265 V ac/dc and type SPTU 48R2 for the supply voltage range 18 80 V dc. The power supply module forms the internal voltages required by the protection relay and the I/O module. 4

Technical data Table 1: Energizing inputs Phase current inputs 1-3, 4-6, 7-9 1-2, 4-5, 7-8 Unbalance current inputs 25-27 25-26 Rated current I n 1 A 5 A Thermal current continuously 4 A 20 A withstand for 1 s 100 A 500 A Dynamic current Half-wave value 250 A 1250 A withstand Input impedance <100 mω <20 mω Phase current monitoring range 0 8.5 x I n Phase unbalance current monitoring range 0 212% I n Rated frequency f n 50 Hz or 60 Hz Table 2: Output contact ratings Type of contact Tripping Signalling Terminals 65-66, 74-75 70-71-72, 68-69, 77-78, 80-81 Rated voltage 250 V ac/dc Thermal withstand Carry continuously 5 A 5 A capability Make and carry for 0.5 s 30 A 10 A Make and carry for 3 s 15 A 8 A Breaking capacity for dc, 220 V dc 1 A 0.15 A when the control circuit 110 V dc 3 A 0.25 A time constant L/R 40 ms, at the control voltage levels 48 V dc 5 A 1 A Table 3: External control input Blocking and control input 10-11 External control voltage level 18 265 V dc or 80 265 V ac Typical control current of activated input circuit 2 20 ma Table 4: Data communication Transmission mode Data code Transfer rates, selectable Optional bus connection for plastic core cables module, powered from for glass fibre cables an external power source Optional bus connection for plastic core cables module, powered from for glass fibre cables the host relay Fibre-optic serial bus ASCII 4800 or 9600 Bd SPA-ZC17BB SPA-ZC17MM SPA-ZC21BB SPA-ZC21MM 5

Technical data (cont d) Table 5: Capacitor protection relay module SPCJ 4D40 Overload stage I b > Start current I b > 0.30 1.50 I n Start time <80 s Operation characteristic Time multiplier k Reset time ANSI inverse 0.2 2.0 <100 ms Drop-off/pick-up ratio, typically 0.95 Operate time accuracy Operation accuracy ±3% of set value ±3% of set value Overload stage I a > Start current I a > 80 120% of I b > Undercurrent stage I< Phase unbalance I 1 > Phase unbalance I 2 > Unbalance compensation Operate time Reset time 0.5 100 s <250 ms Drop-off/pick-up ratio, typically 0.95 Operate time accuracy ±2% of set value Operation accuracy ±3% of set value Start current I< 0.10 0.70 I n Operate time 1.0 100 s Reconnection inhibit time t rec 0.5 100 min Reset time <80 ms Drop-off/pick-up ratio, typically 1.1 Operate time accuracy ±2% of set value or ±75 ms Operation accuracy within the range of 0.25 0.70 I n ±3% of set value Start current I 1 > 1.0 100% of I n Operate time t 1 1.0 300 s Reset time <100 ms Drop-off/pick-up ratio, typically 0.90 Operate time accuracy ±2% of set value or ±75 ms Operation accuracy within the range of 1.5 100% I n ±3% of set value Start current I 2 > 2.0 80.0% of I n Start time <70 s Operation characteristic Inverse time characteristic Time multiplier k 2 0.1 1.0 Reset time <100 ms Drop-off/pick-up ratio, typically 0.90 Operate time accuracy of theoretical characteristic 7.5% or ±35 ms Operation accuracy ±3% of set value Shortest possible operate time ~100 ms Compensation current I cs 0.0 20.0% of I n Operation accuracy <3% of I n Table 6: Auxiliary supply modules Supply and output relay operative voltage range module SPTU 240R2 Supply and output relay operative voltage range module SPTU 48R2 Power consumption, quiescent/operation conditions 80 265 V ac/dc 18 80 V dc ~4 W/~6 W 6

Technical data (cont d) Table 7: Tests and standards Test voltages Dielectric test voltage (IEC 60255-5) 2.0 kv, 50 Hz, 1 min Interference tests Impulse test voltage (IEC 60255-5) Insulation resistance (IEC 60255-5) High-frequency (1 MHz) disturbance test (IEC 60255-22-1), common mode 5 kv, 1.2/50 µs, 0.5 J >100 MΩ, 500 V dc 2.5 kv High-frequency (1 MHz) disturbance 1.0 kv test (IEC 60255-22-1), differential mode Fast transients (IEC 60255-22-4, class 4 kv, 5/50 ns III and IEC 61000-4-4), power supply inputs Fast transients (IEC 60255-22-4, class 2 kv, 5/50 ns III and IEC61000-4-4), other inputs Electrostatic discharge 8 kv (IEC 60255-22-2 and IEC 61000-4-2), air discharge Electrostatic discharge 6 kv (IEC 60255-22-2 and IEC 61000-4-2), contact discharge Environmental conditions Service temperature range -10 55 C Transport and storage temperature -40 70 C range (IEC 60068-2-8) Damp heat test (IEC 60068-2-3) <95%, 40 C, 56 d/a Degree of protection by enclosure IP 54 when panel mounted Weight ~3.5 kg 7

Block diagram L1 L2 L3 0 - - I I 0 Rx Tx 63 1 23 4 56 7 89 25 26 27 11 10 61 62 (~) Uaux - (~) IRF 70 71 72 SIGNAL SIGNAALI 1 1 68 69 LAUK. TRIP 65 66 SPA-ZC_ UUDELLEEN- RECONNECTION KYTKENNÄN START HAVAHT. SIGNAALI SIGNAL 2 2 ENABLE SALLIMINEN 74 75 77 78 80 81 CONTROL OHJAUS- INPUT TULO BS SERIAL SARJA- PORTTI 5 A 1 A 5 A 1 A 5 A 1 A 5 A 1 A @ _ U3 - U2 SPTU_R2 F E D C B A TS1 SS1 SS2 SS3 TS2 1 LAUK. TRIP R 1 1 1 1 1 SGB1/6 SGB1/7 SGB_/1 IRF 3Ia> 3Ib> T8 SGR1/1 SGR1/2 SGR1/3 SGR1/4 SGR2/1 SGR2/2 SGR2/3 SGR2/4 SGR2/5 SGR2/6 SGR2/7 SGR1/5 SGR1/6 SGR1/7 SGR1/8 SGR2/8 T2 SGF/1 T1 T3 SGB_/2 ÐI ÐI T4 T5 SGF/2 T6 SGB_/3 SGB_/4 SGB_/5 SGB_/8 3I< UUDELL.KYTK. RECONN.INHIBIT ESTO EXTERNAL ULK. LIIPAISU TRIP RELAY RELEENRESET KUITTAUS I/O U1 T7 T9 SPCJ 4D40 Fig. 1 Block diagram and sample connection diagram SJAJ160C_BLOCK.FH7 SPAJ160C_block 8

Mounting and dimensions Flush mounting 142 30 250 216 186 34 129 ±1 162 136 139 ±1 Panel cutout dim100 Fig. 2 Flush-mounting relay case (dimensions in mm) Semi-flush mounting a b Raising frame SPA-ZX 111 SPA-ZX 112 SPA-ZX 113 a 176 136 96 b 74 114 154 SFM100_1 Fig. 3 Semi-flush mounting relay case (dimensions in mm) Mounting in 19 inch cabinets and frames An ancillary mounting plate, height 4U (~177 mm), is recommended to be used when the protection relays are to be mounted in 19 inch frames or cabinets. The ancillary mounting plate type SPA-ZX 104 accommodates three relays, type SPA-ZX 105 two relays and type SPA-ZX 106 one relay. Projecting mounting When projecting mounting is preferred, a relay case type SPA-ZX 110 is used. The relay case for projecting mounting is provided with front connectors. SPA-ZX104 SPA-ZX105 SPA-ZX106 0,4 482,6 0 (19") SPA-ZX110 SPA-ZX115 10 158 115 ø6 263 312 292 101,6 21,5 7 0,4 177 0 (4U) 115 6 98 104_6_10 Fig. 4 Mounting cabinets and frames as well as projecting mounting (dimensions in mm) 9

Ordering When ordering, please specify: Ordering information Ordering example 1. Type designation and quantity, 5 pieces 2. Order number RS 611 051-AA 3. Rated values I n =5 A, f n =50 Hz 4. Auxiliary voltage U aux =110 V dc 5. Accessories - 6. Special requirements - Order numbers Capacitor protection relay without test adapter Capacitor protection relay including test adapter RTXP 18 The last two letters of the order number indicate the rated frequency f n and the auxiliary voltage U aux of the relay as follows: RS 611 051-AA, CA, DA, FA RS 611 251-AA, CA, DA, FA AA equals f n = 50 Hz and U aux = 80 265 V ac/dc CA equals f n = 50 Hz and U aux = 18 80 V dc DA equals f n = 60 Hz and U aux = 80 265 V ac/dc FA equals f n = 60 Hz and U aux = 18 80 V dc References Additional information Manual Capacitor bank overload and unbalance protection relay 1MRS 750064-MUM EN 10

ABB Oy Distribution Automation P.O. Box 699 FI-65101 Vaasa, FINLAND Tel 358 10 22 11 Fax 358 10 224 1094 www.abb.com/substationautomation