Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ s MOVIDRIVE MDX61B DCS31B Option Edition 04/2007 11553812 / EN Manual
SEW-EURODRIVE Driving the world
1 Structure of the Safety Notes... 5 2 Safety Notes... 6 2.1 General... 6 2.2 Target group... 6 2.3 Designated use... 7 2.4 Transportation, putting into storage... 7 2.5 Installation... 7 2.6 Electrical connection... 7 2.7 Operation... 8 2.8 Terminology... 8 2.9 Other applicable documents... 8 2.10 TÜV certificate... 9 3 Unit Design... 10 3.1 Unit designations and characteristics... 10 3.2 Nameplate... 11 3.3 DCS31B unit design... 12 4 Installation... 13 4.1 General installation information... 13 4.2 Installation of the DCS31B option card... 13 4.3 Connection and terminal description of the DCS31B option... 15 4.4 Measures to ensure electromagnetic compatibility (EMC)... 16 4.5 External DC 24 V voltage supply... 17 4.6 Connecting binary inputs DI1 to DI8... 17 4.7 Connecting position and velocity sensors... 23 4.8 Wiring of binary outputs... 31 5 Startup... 36 5.1 General startup instructions... 36 5.2 Parameter descriptions... 37 5.3 Switch-on sequence... 39 5.4 Validation report... 40 6 Validation... 41 6.1 Procedure... 41 7 Maintenance... 42 7.1 Maintenance during operation... 42 7.2 Changing / handling changes on the unit... 42 7.3 Disposal... 42 Manual MOVIDRIVE MDX61B DCS31B Option 3
8 Local Diagnostics... 43 8.1 Meaning of the status LEDs... 43 8.2 Error and alarm classes... 44 8.3 Error messages... 44 8.4 Alarm messages... 47 9 Technical Data... 54 9.1 Plug connectors... 54 9.2 Response times of DCS31B option... 56 10 Appendix... 57 10.1 Description of the input elements... 57 10.2 List of encoders recommended by SEW-EURODRIVE... 59 11 Index... 60 4 Manual MOVIDRIVE MDX61B DCS31B Option
Structure of the Safety Notes 1 Operating Instructions 1 Structure of the Safety Notes The safety notes in this manual are designed as follows: Pictogram SIGNAL WORD! Type and source of danger. Possible consequence(s) if the safety notes are disregarded. Measure(s) to prevent the danger. Pictogram Signal word Meaning Consequences in case of disregard Example: DANGER! Imminent danger Severe or fatal injuries General danger WARNING! Possible dangerous situation Severe or fatal injuries CAUTION! Possible dangerous situation Minor injuries Specific danger, e.g. electric shock STOP! Possible damage to property Damage to the drive system or its environment NOTE Useful information or a tip Simplifies the handling of the drive system CAUTION! A requirement of fault-free operation and fulfillment of any rights to claim under limited warranty is that you adhere to the information in the manual. Therefore, read the manual before you start operating the unit! Make sure that the manual is available to persons responsible for the plant and its operation, as well as to person who work independently on the unit. You must also ensure that the documentation is legible. Exclusion of liability: You must comply with the information contained in this manual to ensure safe operation of the DCS31B option and to achieve the specified product characteristics and performance requirements. SEW-EURODRIVE assumes no liability for injury to persons or damage to equipment or property resulting from non-observance of this manual. In such cases, any liability for defects is excluded. Manual MOVIDRIVE MDX61B DCS31B Option 5
Safety Notes 2 General 2 Safety Notes The following basic safety notes must be read carefully to prevent injury to persons and damage to property. The operator must make sure that the basic safety notes are read and observed. Make sure that persons responsible for the plant and its operation, as well as persons who work independently on the unit, have read through the operating instructions carefully and understood them. If you are unclear about any of the information in this documentation, or if you require further information, please contact SEW- EURODRIVE. 2.1 General Never install damaged products or take them into operation. Submit a complaint to the shipping company immediately in the event of damage. During operation, drive inverters can have live, bare and movable or rotating parts as well as hot surfaces, depending on their enclosure. Removing covers without authorization, improper use as well as incorrect installation or operation may result in severe injuries to persons or damage to machinery. Consult the documentation for additional information. 2.2 Target group Only qualified personnel are authorized to install, startup or service the units or correct unit faults (observe IEC 60364 or CENELEC HD 384 or DIN VDE 0100 and IEC 60664 or DIN VDE 0110 as well as national accident prevention guidelines). Qualified personnel in the context of these basic safety notes are: All persons familiar with installation, assembly, startup, programming, parameter setting and operation of the product who possess the necessary qualifications. Furthermore, they must also be familiar with the applicable safety regulations and laws, particularly with the requirements of category 4 to EN 954-1 and all other standards, guidelines and laws specified in this documentation. The staff responsible for this work must be given express permission from the company to startup, program, configure, label and ground units, systems and circuits in accordance with the standards of the safety technology. All persons involved in any other work, such as transportation, storage, operation and disposal, must have suitable training. 6 Manual MOVIDRIVE MDX61B DCS31B Option
Safety Notes Designated use 2 2.3 Designated use The DCS31B option is designed for installation in the MOVIDRIVE MDX61B drive inverter, size 1 to 6. In case of installation in machines, startup of the DCS31B option (i.e. start of designated operation) is prohibited until it is determined that the machine meets the requirements stipulated in the EC Directive 98/37/EC (machine guideline); observe EN 60204. Startup (i.e. start of designated operation) is only permitted with adherence to the EMC guideline (89/336/EEC). The EMC test specifications EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-6 and EN 61000-6-2 must be taken into account during startup. Technical data and information on the connection requirements are provided on the nameplate and in the documentation; these must be observed under all circumstances. 2.4 Transportation, putting into storage Observe the notes on transportation, storage, and proper handling. Observe the climatic conditions in accordance with the section "Technical Data." 2.5 Installation The units must be installed and cooled in accordance with the guidelines listed in the corresponding documentation. Protect the DCS31B option from improper strain. Do not bend components or alter insulation spaces, particularly during transportation and handling. Avoid touching electronic components and contacts. The DCS31B option contains components that can easily be damaged by electrostatic energy and improper handling. Prevent mechanical damage or destruction of electric components (may pose health risk!). The following applications are prohibited unless measures have been expressly taken for them to be carried out: Use in potentially explosive atmospheres Use in areas exposed to harmful oils, acids, gases, vapors, dust, radiation, etc. In non-stationary applications 2.6 Electrical connection Observe the applicable national accident prevention guidelines when working on live DCS31B options (e.g. BGV A3). Perform electrical installation according to the pertinent regulations (e.g. line cross sections, fusing, protective conductor connection). For any additional information, refer to the applicable documentation. You will find notes on EMC-compliant installation such as shielding, grounding, arrangement of filters and routing of lines in the documentation of the safety monitor. The system or machine manufacturer is responsible for maintaining the limits established by the EMC legislation. Preventive measures and protection devices must meet the regulations in force (e.g. EN 60204). Manual MOVIDRIVE MDX61B DCS31B Option 7
Safety Notes 2 Operation 2.7 Operation Systems with integrated MOVIDRIVE MDX61B with DCS31B option must be equipped with additional monitoring and protection devices, if necessary, according to the applicable safety guidelines, such as the law governing technical equipment, accident prevention regulations, etc. Keep all covers and doors closed during operation. The fact that the status LED and other display elements are no longer illuminated does not indicate that the unit has been disconnected from the power supply and no longer carries any voltage. Mechanical blocking or internal safety functions of the unit can cause a motor standstill. Eliminating the cause of the problem or performing a reset can result in the drive re-starting automatically. If, for safety reasons, this is not permitted for the driven machine, disconnect the unit from the mains before correcting the fault. 2.8 Terminology The designation MOVISAFE is the generic term for all design variants in the MOVISAFE 100B product series. If a particular design variant is referred to in the operating instructions, the complete designation is used. The term "safe" in this context refers to the classification as a safety function based on EN 954-1. The configuration software "MOVISAFE CONFIG" is a programming and configuration tool for MOVISAFE. 2.9 Other applicable documents Description Configuration of MOVISAFE (without fieldbus) using the "MOVISAFE CONFIG" configuration software. Validation report of the implemented configuration Reference MOVISAFE CONFIG online help ( MOVISAFE software ROM, edition 02/2007, item number 1156 6604) Technical safety check. This check can be generated using the MOVISAFE CONFIG configuration software and serves as an acceptance protocol. Approval TÜV certificate for DCS31B ( MOVISAFE software ROM, edition 02/2007, part no. 1156 6604) 8 Manual MOVIDRIVE MDX61B DCS31B Option
Safety Notes TÜV certificate 2 2.10 TÜV certificate 60048AXX Manual MOVIDRIVE MDX61B DCS31B Option 9
Unit Design 3 Unit designations and characteristics 3 Unit Design 3.1 Unit designations and characteristics DCS31B Velocity monitoring: Speed monitoring Standstill monitoring Direction monitoring Emergency stop monitoring Position monitoring: Position range monitoring Travel range monitoring Target position monitoring 8 digital inputs 2 clock outputs 6 digital auxiliary outputs SSI / incremental / sin/cos encoder interface Diagnostics and configuration interface 10 Manual MOVIDRIVE MDX61B DCS31B Option
Unit Design Nameplate 3 3.2 Nameplate DCS31B nameplate MOVIDRIVE MDX61B with built-in DCS31B option is supplied with two nameplates. The first nameplate ( following figure) is attached to the contact spring strip of the DCS31B option. It lists the part number and the serial number of the DCS31B option. 59493AXX MOVIDRIVE nameplate The second nameplate ( following figure) is attached to the MOVIDRIVE MDX61B. It contains the following information: Unit designation Part number Serial number Input data Version status Reference to the response times in the manual Permitted standards 59492AXX NOTE If the DCS31 option is supplied as a separate unit, attach the enclosed nameplate to the MOVIDRIVE MDX61B. Manual MOVIDRIVE MDX61B DCS31B Option 11
Unit Design 3 DCS31B unit design 3.3 DCS31B unit design [1] [2] [3] [4] [5] [6] [7] [8] 59385AXX [1] Status LED: Alarm / error Status LED: Watchdog Status LED: System B Status LED: System A [2] X80: Connection for voltage supply DC 24 V [3] X81: Connection binary inputs DI1... DI8 and clock signals P1, P2 [4] X82: Connection binary outputs DO0 / DO1 [5] X83: Connection binary output DO2 [6] X84: Connection incremental, sin/cos, absolute encoder (SSI) [7] X85: Connection incremental, sin/cos, absolute encoder (SSI) [8] X87: Connection service interface 12 Manual MOVIDRIVE MDX61B DCS31B Option
Installation General installation information 4 4 Installation 4.1 General installation information NOTES Route the signal cables for connection of the binary inputs separately from those for contact monitoring. It is essential that you route power cables separately from signal cables. The cables connected to outputs X82 and X83 may not exceed 30 m. 4.2 Installation of the DCS31B option card NOTES The DCS31B option card can only be installed in MOVIDRIVE MDX61B sizes 1 to 6, not in size 0. The DCS31B option card must be inserted in the expansion slot. Before you begin Read the following notes before installing or removing an option card: STOP! Electrostatic charge. Damage to electronic components. Disconnect the inverter from the power. Switch off the DC 24 V and the supply voltage. Take appropriate measures to protect the option card from electrostatic charge (use discharge strap, conductive shoes, etc.) before touching it. Before installing the option card, remove the keypad ( MOVIDRIVE MDX60B/61B operating instructions, Sec. "Removing/installing the keypad") and the front cover ( MOVIDRIVE MDX60B/61B operating instructions, Sec. "Removing/installing the front cover"). After having installed the option card, replace the front cover ( MOVIDRIVE MDX60B/61B operating instructions, Sec. "Removing/installing the front cover") and the keypad ( MOVIDRIVE MDX60B/61B operating instructions, Sec. "Removing/installing the keypad"). Keep the option card in its original packaging until immediately before you are ready to install it. Hold the option card by its edges only. Do not touch any of the components. Manual MOVIDRIVE MDX61B DCS31B Option 13
Installation 4 Installation of the DCS31B option card Basic procedure for installing/removing an option card (MDX61B, sizes 1-6) 2. 1. 2. 1. 3. 3. 3. 4. 4. 60039AXX 1. Remove the retaining screws holding the card retaining bracket. Pull the card retaining bracket out evenly from the slot (do not twist). 2. Remove the retaining screws of the black cover plate on the card retaining bracket. Remove the black cover plate. 3. Position the option card onto the retaining bracket so that the retaining screws fit into the corresponding bores on the card retaining bracket. 4. Insert the retaining bracket with installed option card into the slot, pressing slightly so it is seated properly. Secure the card retaining bracket with the retaining screws. 5. To remove the option card, follow the instructions in reverse order. 14 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connection and terminal description of the DCS31B option 4 4.3 Connection and terminal description of the DCS31B option Part numbers DCS31B option: 1820 958 0 NOTES The DCS31B option can only be installed in connection with MOVIDRIVE MDX61B sizes 1 to 6. The DCS31B option must be inserted in the expansion slot. The DCS31B option must be supplied with 24V DC. The total current consumption is 2A DC. Front view of DCS31B DCS31B X84 X85 A/F WD B A 9 6 9 6 X83 X82 X81 X80 5 1 5 1 Description LED Alarm / error LED Watchdog LED System B LED System B LED/ terminal LED A/F LED WD LED B LED A X80: Voltage supply connection X80:1 X80:2 X81: Connection binary inputs X81:1 P1 X81:2 DI1 X81:3 DI2 X81:4 DI3 X81:5 DI4 X81:6 P2 X81:7 DI5 X81:8 DI6 X81:9 DI7 X81:10 DI8 X82: Connection binary inputs DO0, DO1 X82:1 DO0_P X82:2 DO0_M X82:3 DO1_P X82:4 DO1_M X83: Connection binary output DO2 X83:1 DO2_P X83:2 DO2_M X84: Connection incremental, sin/cos, absolute encoder (encoder 1) X85: Connection incremental, sin/cos, absolute encoder (encoder 2) X84:1 X84:2 X84:3 X84:4 X84:5 X84:6 X84:7 X84:8 X84:9 X85:1 X85:2 X85:3 X85:4 X85:5 X85:6 X85:7 X85:8 X85:9 Function The LEDs show the status of the DCS31B option. ( Sec. "Local Diagnostics") DC 24 V Reference potential 0V24 Clock signal 1 for safe inputs; DC 24 V clocked Input 1 Input 2 Input 3 Input 4 Input 5 Clock signal 2 for safe inputs; DC 24 V clocked Input 6, fixed assignment 'Reset' Input 7 Input 8 HISIDE - output 0 LOSIDE - output 0 HISIDE - output 1 LOSIDE - output 1 HISIDE - output 2 LOSIDE - output 2 Assignment depends on connected encoder ( Sec. "Technical Data") Assignment depends on connected encoder ( Sec. "Technical Data") X87: Connection service interface X87 interface Baud rate: 38,4 kbaud For point-to-point connection only X87 59387AXX Manual MOVIDRIVE MDX61B DCS31B Option 15
Installation 4 Measures to ensure electromagnetic compatibility (EMC) 4.4 Measures to ensure electromagnetic compatibility (EMC) The DCS31 option is designed for industrial applications (based on the EMC test specifications EN 61800-3). Prerequisite for safe installation is that the electromagnetic compatibility of the entire system must be ensured by taking appropriate measures. The following measures ensure the designated operation of the DCS31B: Make sure that the voltage supply lines of the DCS31B option and the "switching cables" of the MOVIDRIVE MDX61B are routed separately. Route the inverter s signal cables and power cables in separate cable ducts. The cable ducts must be at least 10 mm apart. Only use shielded cables to connect the position and velocity sensors. The cable used to transfer signals must be suitable for the EIA485 standard (formerly RS485). Make sure the shield in the 9-pin sub-d connector for the position and velocity sensors is applied correctly. The shielding on the sensor side must also be applied correctly. Only use metal or metallized connectors. Make sure the installation of the inverter is EMC-compliant in the vicinity of the DCS31B. Check the routing and design of the shielding for the motor cable and braking resistor connection. All contactors in the vicinity of the DCS31B option have to be equipped with suitable suppressors. 16 Manual MOVIDRIVE MDX61B DCS31B Option
Installation External DC 24 V voltage supply 4 4.5 External DC 24 V voltage supply The DCS31B option requires a DC 24 V voltage supply (SELV or PELV, EN 50178). During project planning and installation of the power supply unit, the following conditions must be taken into account: Make sure you adhere to the minimum and maximum tolerance of the supply voltage. Tolerance Minimum ( 15 %) Maximum (+15 %) Nominal voltage = DC 24 V DC 24 V 15 % = DC 20.4 V DC 24 V +15 % = DC 27.6 V To keep the residual ripple of the supply voltage as low as possible, we recommend using a 3-phase power supply unit or an electronically-controlled unit. The power supply unit must meet the requirements in EN 61000-4-11 (voltage dip). The external DC 24 V supply of the DCS31B option also powers the internal electronics and the external velocity and position sensors. These components are not protected separately against short circuits. The current consumption of the installed encoder should not exceed DC 300 ma. When using encoders with higher operating currents, the encoder voltage supply must be provided separately. You must ensure the external DC 24 V voltage supply is isolated from the voltage supply system (e.g. AC 230 V). To do so, choose power supply units that meet the guidelines stipulated in DIN VDE0551, EN 60742 and DIN VDE0160. When selecting a suitable unit, make sure there is equipotential bonding between PE and DC 0 V on the secondary side. Provide external protection for the DCS31B option by installing a 2 A fuse. Observe local guidelines when configuring the connection cables. The maximum external voltage that can be connected to the DCS31B option is DC 32 V. 4.6 Connecting binary inputs DI1 to DI8 The DCS31B option has 8 binary inputs (DI1... DI8). They are suitable for connecting single or dual-channel sensors with or without pulsing. NOTE To be able to acknowledge error messages, the binary input DI6 must be configured as reset input. The connected signals must have a "high" level of DC 24 V (DC +15 V... DC +30 V) and a "low" level of DC 0 V (DC 3 V... DC +5 V). The inputs are fitted with input filters. An internal diagnostic function checks cyclically whether the binary functions and the input filters are working properly. If an error is detected, the DCS31B option switches to alarm status and displays the error ( Sec. "Local diagnostics"). Manual MOVIDRIVE MDX61B DCS31B Option 17
Installation 4 Connecting binary inputs DI1 to DI8 Using clock outputs P1 and P2 In addition to the binary inputs DI1 to DI8, the DCS31B option has two clock outputs P1 and P2. Clock outputs P1 and P2 are switching DC 24 V outputs installed for monitoring binary inputs (DI1... DI8) only. Clock outputs may not be used for other functions of the application. The switching frequency is 240 Hz (stand-alone) for each clock output. For project planning, note that the maximum total current permitted for the outputs is 300 ma. NOTE Without changing the pulse, the binary inputs can be used with single-channel, selfmonitoring sensors in applications according to EN 954-1 to category 2. With dualchannel sensors and a function test performed within 24 hours, two-channel sensors without pulsing can achieve category 4. If a function test is not performed within 24 hours, the sensors can achieve category 3. Note that external measures, particularly suitable cable routing, must be taken to prevent short circuits in the external wiring between different inputs and against the supply voltage of the DCS31B option. Each binary input of the DCS31B option can be configured separately for the following signal sources: Binary input is assigned to pulse P1 Binary input is assigned to pulse P2 Binary input is assigned to DC 24 V continuous voltage NOTE The following sample circuits assume that the switching elements are configured in accordance with the required EN 954-1 category and that safety approval has been granted for the application in question. 18 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting binary inputs DI1 to DI8 4 Single-channel sensor, unchecked X81 P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 DC 24 V DC 0 V Figure 1: Single-channel sensor, unchecked 59258AXX NOTE The single-channel sensor is connected to the DCS31B option without pulsing. The DCS31B option cannot detect cross faults or interruptions in the signal line. Note that this configuration is not permitted for safe applications without external measures. Manual MOVIDRIVE MDX61B DCS31B Option 19
Installation 4 Connecting binary inputs DI1 to DI8 Dual-channel sensor, unchecked Before using dual-channel sensors (homogeneous or diversified) check whether they have been approved for the intended purpose. P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 X81 DC 24 V DC 0 V Figure 2: Dual-channel sensor (homogeneous), unchecked 59259AXX Using dual-channel homogeneous sensors without a pulsing can lead to problems. Short circuits cannot be detected in the supply line of the dual-channel sensor, e.g. in the cable. Safe operation can only be achieved by routing the cables separately and making sure the terminals cannot short circuit. P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 X81 DC 24 V DC 0 V Figure 3: Dual-channel sensor (diversified), unchecked 59260AXX The DCS31B option can operate safely with dual-channel diversified sensors without pulsing. NOTE Category 3 in accordance with EN 954-1 can be achieved with both circuits. 20 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting binary inputs DI1 to DI8 4 Single-channel sensor, checked Check whether the sensor is approved for use in fail-safe applications. X81 P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 P1 P2 DC 24 V DC 0 V 1 2 3 4 5 6 7 8 9 10 Figure 4: Single-channel sensor with pulsing 59261AXX When using a single-channel sensor with pulsing, the sensor must be connected to the clock output P1 or P2. The clock cycle must then be assigned on the DCS31B option. The following errors are detected if you use a single-channel sensor with pulsing: Short circuit in the DC 24 V supply voltage Short circuit on DC 0 V Cable interruption (power interruption is a safe state!) However, a short circuit in the cable between the two sensor connections is not detected. A short circuit between P1 and DI1 is also not detected. With a suitable switching element and careful cabling for the sensor, category 3 to EN 954-1 can be achieved. NOTE Category 3 is achieved when there is no possibility of a short circuit between DI1 and P1 or between the sensor connections. Faults can be excluded in accordance with EN ISO 13849-2, table D8. Manual MOVIDRIVE MDX61B DCS31B Option 21
Installation 4 Connecting binary inputs DI1 to DI8 Dual-channel sensor, checked All cross fault connections and connections to DC 24 V and DC 0 V can be detected when two independent clock signals are used on a homogeneous sensor. Only use NC contacts for safety applications. X81 P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 P1 P2 DC 24 V DC 0 V Figure 5: Dual-channel homogeneous sensor with pulsing NOTE 59262AXX Note that when connecting a diversified sensor ( following figure), only the NO contact is tested regularly. As with the homogeneous sensor, all types of faults are detected in the supply line. P1 1 DI1 2 DI2 3 DI3 4 DI4 5 P2 6 DI5 7 DI6 8 DI7 9 DI8 10 X81 P1 P2 DC 24 V DC 0 V Figure 6: Dual-channel diversified sensor NOTE 59263AXX Category 4 to EN 954-1 can be achieved in both cases when using permitted, positive opening switching elements. 22 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting position and velocity sensors 4 4.7 Connecting position and velocity sensors Before you begin STOP! Do not plug in or remove encoder connections during operation. Doing so can cause irreparable damage to the electrical components on the encoder. Disconnect the connected encoders and the DCS31B option before plugging in or removing the encoder connections. The DCS31B option has two encoder interfaces for connecting standard incremental, sin/cos and absolute encoders. NOTE SEW-EURODRIVE recommends using the encoders listed in the appendix. Incremental, sin/cos or absolute encoders (binary or Gray Code) can be connected and operated via the same encoder interface. The internal encoder simulation can be used via backplane bus as well. The sin/cos encoders operate in the same way as incremental encoders. Please read the following notes carefully: The DCS31B option usually provides the connected sensors with the voltage supply. This voltage is monitored by a diagnostic process. If the sensors are powered by an external voltage supply. you must include the possibility of a voltage supply failure in the possible sources of error for the whole system. Particularly with shared external voltage supplies, you must document that this fault will be detected when the minimum operating voltage of the encoder system is not maintained. Check that EMC measures, such as shielding, etc., have been applied. The two encoders must not impact on each other. This refers to both the electrical and mechanical part. If both encoders are connected to the monitoring system with the same mechanical parts, the connection must be positive and may not include any parts that are subject to wear (chains, toothed belts, etc.). However, if parts subject to wear are used, you must install additional monitoring systems to check the mechanical connection of the sensors (e.g. monitoring function for a toothed belt). If position processing is activated, you must use at least one absolute encoder. If you only use one absolute encoder, connect it to X85 (encoder 2) on. Encoder 1 functions as a process sensor and encoder 2 as a reference sensor. If you are using encoders with different resolutions, configure the encoder with the higher resolution as "Encoder 1" (X84) and the encoder with the lower resolution as "Encoder 2" (X85). An internal number format is used in the input fields "Position", "Velocity" and "Acceleration" when the monitoring functions are configured. This can cause the values to be rounded up. Manual MOVIDRIVE MDX61B DCS31B Option 23
Installation 4 Connecting position and velocity sensors The following also applies to the use of absolute encoders: Absolute encoders can be read in in the data format SSI binary or SSI Gray Code. This setting is made in the encoder dialog box in the configuration software. The data length is 24 Bit. Combining different encoder types Encoder types can be combined depending on the specific application. Note the following limitations: If monitoring functions are used with position processing, at least one sensor must be assigned as an absolute encoder. When combining an absolute encoder with an incremental encoder, connect the incremental encoder to X84 and the absolute encoder to X85. If the internal encoder value of the inverter is to be used, the internal encoder has to be configured in the MOVISAFE CONFIG program as "encoder 1". If you change the encoder configuration at a later date, the existing parameters for the monitoring functions may no longer be compatible with the new encoder configuration. In this case, check the parameter settings and value ranges of all the monitoring functions in use. SEW-EURODRIVE recommends using the encoders listed in the appendix. Configuring the measuring types The most important input parameters for the monitoring functions of the DCS31B option are: Position Velocity Acceleration These input parameters are generated in a dual-channel from the connected encoder systems. Two independent encoder systems are required to achieve category 4 in accordance with EN 954-1. One encoder system can be sufficient for certain applications to achieve category 3 in accordance with EN 954-1 (e.g. only velocity monitoring). Travel types A and B must be configured accordingly for internal signal processing. This can be done using the encoder dialog box in the programming interface. Note the following parameters when configuring the travel type: Measuring type You can choose "linear" or "rotary" as the travel type. Units of the travel type For a linear measuring type, you can choose "mm/sec" or "m/sec" as the unit for velocity. For rotary travel, you can choose "mgrad/sec", "rps" or "rpm" as the unit for velocity. The selected resolution should correspond to the physics of the travel type to prevent rounding problems in the configuration. 24 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting position and velocity sensors 4 Positioning range The positioning range is used to determine the permitted range during positioning processes. If you do not define a positioning range, only monitoring functions with velocity processing properties will be activated during configuration. Monitoring functions with position processing properties will be deactivated in the dialog box. Once you have activated the positioning range window, i.e. allowed position processing, note that the current position of the drive must be within the measuring length window. The positioning range has a range of 1... 1000000 and is normalized with the unit specified for the travel type. Encoder type The following encoders can be used: Absolute encoder: SSI data interface with a constant data length of 24 Bit Binary or Gray Code data format Encoder with signal level to RS422 If the measuring channel is operated in slave mode, i.e. as a listener, the maximum external clock rate is 150 khz. The pulse break between the pulse clusters must be greater than 30 µs and less than 6 ms. Incremental encoder: Encoder with signal level to RS422 Measuring signal A/B track with 90 degree phase difference Maximum frequency of the input pulses 200 khz Sin/cos encoder: Encoder with AC 1 V ss Measuring signal A/B track with 90 degree phase difference Maximum frequency of the input pulses 200 khz Internal encoder simulation via backplane bus: The signals of the motor encoder can be used as encoder 1. The number of pulses of the encoder simulation via backplane bus is 4096 pulses per revolution after starting up the encoders in MOVIDRIVE. NOTE If the internal encoder simulation via backplane bus is used for reference travel of MOVIDRIVE B, the DCS31B option issues the error message "Plausibility position detection" (F109, subcode 036/037). Acknowledge the error message via the binary input DI6 with fixed "Reset"assignment ( Sec. 4.6). Safety-related switch-off thresholds The basic check is to perform a plausibility test between the two measuring channels A and B of the DCS31B option to compare the current position and velocity values with the configurable thresholds. The "incremental" switch-off threshold is the deviation in position permitted between the two recording channels A and B in the unit of velocity. The "velocity" switch-off threshold is the deviation in velocity permitted between the two recording channels A and B. Diagnostic functions are provided in the SCOPE dialog box of the configuration tool to determine the optimum parameter values. Manual MOVIDRIVE MDX61B DCS31B Option 25
Installation 4 Connecting position and velocity sensors Conversion example The ramp times of the MOVIDRIVE B inverter are based on a setpoint step change of Δn = 3000 1/min. The acceleration value a is calculated using the following formula: a = v t a = 3000 1 Ramp time [ /min] [ min] 60 Example: In MOVITOOLS, P137 Emergency ramp is set to 2 seconds. [ ] [ ] 3000 1/min 2 a = = 90000 [ 1/min ] 2 min 60 Conversion to 1/s 2 : 59723AEN 59725AXX 2 2 90000 [ 1/min ] 2 a = 90000 [ 1/min ] = = 25 [ 1/ s ] 60 [ s] 60 [ s] 59726AXX The values entered in the MOVISAFE CONFIG program are based on the travel type. This means that the motor revolutions still have to be converted to the travel type. Rotary system: Calculation of the velocity: v = i gear unit v i Motor add. gear 11464AXX 59728AEN v Motor i Gear unit i Additional gear = Motor velocity [1/min] = Gear unit ratio = Gear ratio of the additional gear 26 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting position and velocity sensors 4 Calculation of the acceleration: a = i gear unit a i Motor add. gear 59729AEN a Motor i Gear unit i Add. gear = Motor acceleration = Gear unit ratio = Gear ratio of the additional gear Linear system: Calculation of the velocity: 11465AXX v = i gear unit v i Motor add. gear D π drive wheel 59731AEN v v Motor i Gear unit i Add. gear D Drive wheel = Velocity [m/min] = Motor velocity [1/min] = Gear unit ratio = Gear ratio of the additional gear = Drive wheel diameter [m] Calculation of the acceleration a = i gear unit a x i Motor add. gear xd drive wheel x π 59729AEN a = Acceleration [m/min 2 ] a Motor = Motor acceleration [1/min 2 ] i Gear unit = Gear unit ratio i Add. gear = Gear ratio of the additional gear D Drive wheel = Drive wheel diameter [m] Manual MOVIDRIVE MDX61B DCS31B Option 27
Installation 4 Connecting position and velocity sensors In many cases, the data in millimeters or minutes can exceed the input s value range. In this case, you must scale the values from millimeters to meters (for linear systems) or from minutes to seconds (for rotary systems). Velocity: v [ mm/ s] v [ m/ s] = 1000 v [ U/min] v [ U/ s] = 60 59734AXX Acceleration: 2 2 a[ mm/ s ] a[ m/ s ] = 1000 2 2 2 au [ /min ] au [ /min ] au [ / s] = = 60 60 3600 59735AXX Encoder wiring diagrams NOTES For connection of an encoder to both a MOVIDRIVE B and the DCS31B option, you can order a prefabricated cable from SEW-EURODRIVE under the part number 1810 053 8. The prefabricated cable allows you to split the encoder signals and to connect the encoder to the options DCS31B and DEH11B. The following encoder types can be connected: Incremental encoder Sin/cos encoder Hiperface encoder (only the sin/cos tracks are evaluated) Connecting an absolute encoder DCS31B X84/X85 max. 100 m 9 6 5 1 CLK+ 3 CLK- 8 DATA+ 1 DATA- 6 DC 0 V DC 24 V 5 9 60551AXX In this type of connection, the pulse signals run from the DCS31B option to the absolute encoder and the data runs from the encoder to the DCS31B option. 28 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Connecting position and velocity sensors 4 Connecting an incremental encoder DCS31B X84/X85 max. 100 m 9 6 5 1 B B A A 2 7 1 6 DC 0 V DC 24 V 5 9 Figure 7: Connecting an incremental encoder 60552AXX Connecting a sin/cos encoder DCS31B X84/X85 max. 100 m 9 6 5 1 COS+ 2 COS- 7 SIN+ 1 SIN- 6 DC 0 V DC 24 V 5 9 Figure 8: Connecting a sin/cos encoder 60553AXX Manual MOVIDRIVE MDX61B DCS31B Option 29
Installation 4 Connecting position and velocity sensors One-encoder concept For applications in category 3 it is possible to use only one encoder. In this case, the signal outputs of the encoder are split between X15 of the DEH11B option and X85 of the DCS31B option ( following figure). The internal encoder simulation via backplane bus can be used as encoder 1. Hiperface cos+ 3 RD 1 9 8 cossin+ 4 BU 2 10 12 7 5 YE sin- 6 GN 3 11 6 DATA- 7 VT 4 5 DATA+ 8 BK TF/TH/KTY+ 9 BN TF/TH/KTY- 10 WH 11 GYPK U S 12 RDBU PK GY max. 100 m PE DEH11B, X15: 1 9 2 10 12 4 14 6 8 15 15 9 8 1 PE PE NOTES 59388AXX Limitations apply to planned encoder systems for applications with one encoder system in sin/cos signal form in category 3. The errors listed below are detected in the external encoder system and in the wiring by using internal diagnostic measures. Mechanical faults such as shaft breakage and slip are not detected and have to be ruled out by appropriate measures in the system design. Faults within the encoder (electrical and mechanical) have to be considered individually depending on manufacturer and type and examined with respect to ruling out faults. The design of the mechanical system and of the encoder must be subjected to a failure mode and effect analysis based on the system. The operating system of the DCS31B option detects the following faults of the external encoder system. Short circuits between the safety-related signal lines Interruptions in the safety-related signal lines "Stuck at 0" or "1" on one or all safety-relevant signal lines Rectangular oscillation caused by in-phase signals PE 1 2 3 4 5 6 7 8 9 DCS 31B X85 9 6 5 1 30 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Wiring of binary outputs 4 If the used encoder is not listed, you have to take a closer look at possible faults of the used encoder and qualify them within the context of an FMEA. 4.8 Wiring of binary outputs The DCS31B option has a total of 6 binary outputs, which can be used individually or combined in groups. Binary output Category (EN 954-1) Comment DO0_P and DO0_M 4 Complete shutdown channel of category 4 DO0_P DO0_M Not safe Only functional DO1_P and DO1_M 4 Complete shutdown channel of category 4 DO1_P DO1_M Not safe Only functional DO2_P and DO2_M 4 Complete shutdown channel of category 4 The binary outputs are subjected to a plausibility test in all operating states. When switched on, the binary outputs are tested for correct functioning with a cyclical test pulse. The binary outputs are switched to their inverse value for the duration of the test (< 100 µs), i.e. a P binary output is switched briefly to DC 0V potential, and an M binary output is switched briefly to DC 24 V potential. The binary output test function is performed for group and individual control. Binary output Output voltage Output current DO0_P DO0_M 0.1 A DO1_P DO1_M DO2_P DO2_M DC 24 V 1.5 A NOTES The total current load of the DCS31B option may not exceed 2 A. The output power of the binary outputs DO0/DO1 depends on the output power of the binary output DO2 and the clock outputs P1 and P2. Cross and short circuits in the external wiring of the binary outputs are not detected. For safe outputs, the faults cross circuit and short circuit have to be prevented according to EN ISO 13849-2 table D.4 Manual MOVIDRIVE MDX61B DCS31B Option 31
Installation 4 Wiring of binary outputs Using the binary outputs DO2_P and DO2_M The binary outputs DO2_P and DO2_M can be used for control of the safe stop function (X17) of MOVIDRIVE B. X83 1 DO2_P 2 DO2_M MOVIDRIVE MDX61B X17 4 3 2 1 SVI24 SOV24 VO24 DGND 59293AXX Single-pole switching P binary output without check You can use external contactors to connect multi-phase applications or in applications with an increased current consumption. Note that with single-pole connection without an external check, welding of one or more external contacts will not be detected by the DCS31B option. The following sample circuit is not suitable for safety applications. X82 DO0_P 1 DO0_M 2 DO1_P 3 DO1_M 4 X83 DO2_P DO2_M 1 2 DC 24 V DC 0 V Figure 9: Single-pole switching P binary output Not suitable for safety applications! 59268AXX 32 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Wiring of binary outputs 4 Single-pole switching M binary output without check Similar to the previous wiring example, the following sample circuit shows a single-pole M binary output without check. The following sample circuit is not suitable for safety applications. X82 DO0_P 1 DO0_M 2 DO1_P 3 DO1_M 4 X83 DO2_P DO2_M 1 2 DC 24 V DC 0 V Figure 10: Single-pole switching M binary output Not suitable for safety applications! 59267AXX NOTE Single-pole connections with monitoring of the external safety contact are permitted for use in safety applications up to category 2. Up to category 2, the status of the signal contact can be displayed and evaluated via binary outputs DO1 / DO2 or via the fieldbus interface. Manual MOVIDRIVE MDX61B DCS31B Option 33
Installation 4 Wiring of binary outputs Dual-channel switching binary output DO0 with external monitoring The dual-channel wiring can also be implemented with a check. The prerequisite for this solution is a switching element with checked forced contacts and test contact (NC contact). The monitoring contact is fed via clock output P1 and read via any input. The EMU1 (Emergency Monitoring Unit 1) must be configured correctly for this solution to function properly. X82 DO0_P 1 DO0_M 2 DO1_P 3 DO1_M 4 X83 DO2_P DO2_M 1 2 X81 P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 Figure 11: Dual-channel switching binary output with external contact monitoring 59280AXX NOTE Dual-channel connections of a relay with monitoring of the external safety contact are permitted for use in safety applications up to category 2! Up to category 2, the status of the signal contact can be displayed and evaluated via an additional auxiliary output, e.g. DO0_M. 34 Manual MOVIDRIVE MDX61B DCS31B Option
Installation Wiring of binary outputs 4 Dual-channel switching binary output DO0 with external monitoring For safety applications in category 3 and 4, two complementary binary outputs are connected as a group to control two external power contactors. DO0_P 1 X82 DO0_M 2 3 4 X83 DO2_P DO2_M 1 2 X81 P1 DI1 DI2 DI3 DI4 P2 DI5 DI6 DI7 DI8 1 2 3 4 5 6 7 8 9 10 Figure 12: Dual-channel switching binary output DO0 with external monitoring 59278AXX NOTE Take into account the maximum output current of the binary outputs and the maximum current consumption of the contactors. Manual MOVIDRIVE MDX61B DCS31B Option 35
I Startup 5 General startup instructions 0 5 Startup 5.1 General startup instructions Prerequisites The following prerequisites must be fulfilled to ensure successful startup The system must be configured correctly The installation of the MOVISAFE CONFIG configuration software. The software is available on the MOVISAFE software ROM, edition 02/2007, item number 1156 6604. MOVITOOLS version 4.50 or higher Firmware status 0824 854 0.18 or higher of the MOVIDRIVE MDX61B For detailed project planning information and a description of the parameters, refer to the online helps in the MOVISAFE CONFIG and in the MOVITOOLS operating software. Prerequisites for operating the MOVISAFE CONFIG configuration software: MOVISAFE CONFIG must be activated with a USB dongle (part number 1058 5834) Operating system: Microsoft Windows 2000 or XP Hard disk storage: Approximately 100 MB RAM: min. 256 MB, recommended 512 MB or more Required hardware components: Interface adapter type UWS21A (RS232 RS485) or interface adapter USB11A (USB RS485). For more information on the hardware components, refer to the MOVIDRIVE MDX60B/61B catalog. Startup steps Make sure that the installation of the DCS31B option the cabling the terminal assignment and the safety cut-outs have been configured correctly and are suited to the application. Prevent unintentional start up of the motor by implementing the following measures: Implement additional safety features for certain applications to prevent possible injuries to people and damage to machinery. Switch on the mains voltage and, if necessary, the DC 24 V supply voltage. Startup the drive with MOVIDRIVE MDX61B as described in the "MOVIDRIVE MDX60B/61B" operating instructions. Configure and program the DCS31B option according to your application. There is no need to activate the factory settings. If you have activated the factory settings, the terminal assignment and the parameter of the MOVIDRIVE MDX61B are reset to the basic setting. Use the parameters P555/P556 to set the error and alarm response of the DCS31B option to "NO RESPONSE" or to "DISPLAY FAULT" ( Sec. 5.2 "Parameter descriptions"). The fault response will also be triggered in the CONTROLLER INHIBIT inverter status. Perform a validation ( Sec. 6 "Validation"). Create a validation report ( Sec. 5.4 "Validation report"). 36 Manual MOVIDRIVE MDX61B DCS31B Option
Startup Parameter descriptions I 0 5 5.2 Parameter descriptions The parameter group P55x DCS safety monitor includes display and setting values that are specific to the DCS31B option. The factory setting is indicated by underline. P550 status DCS safety monitor Display value that cannot be changed. The parameter P550 displays the current status of the DCS31B option. RUN: Normal operation. STOP: The operation of the DCS31B option was stopped via the programming interface. ALARM: The DCS31B option has issued an alarm. ERROR: The DCS31B option has issued an error. You have the following options to read the corresponding error or alarm message from the fault memory of the DCS31B option: via the X87 service interface with the DBG60B keypad with the MOVISAFE CONFIG configuration software, if P555/P556 is set to "NO RESPONSE". P551 binary inputs DCS DI1... DI8 Display value that cannot be changed. The parameter P551 displays the current status of the binary inputs of the DCS31B option in the order DI1... DI8. P552 binary outputs DCS DO0_P... DO2_M Display value that cannot be changed. The parameter P552 displays the current status of the binary outputs of the DCS31B option in the following order: DO0_P DO0_M DO1_P DO1_M DO2_P DO2_M P553 DCS series number Display value that cannot be changed. The parameter P553 displays the series number of the DCS31B option. The series number displayed must be identical with the series number on the nameplate of DCS31B, which is attached to the MOVIDRIVE MDX61B. You have to enter the series number in the validation report ( Sec. "Validation"). Manual MOVIDRIVE MDX61B DCS31B Option 37
I Startup 5 Parameter descriptions 0 P554 CRC DCS Display value that cannot be changed. The parameter CRC DCS displays the CRC (cyclic redundancy check) of the program stored on the DCS31B option. You have to enter the CRC in the validation report ( Sec. "Validation"). P555 DCS error response / P556 DCS alarm response Factory setting: IMM. STOP /FAULT If the DCS31B option issues a fault (P555) or an alarm (P556), the inverter performs the set response. The following responses can be programmed: Response NO RESPONSE DISPLAY FAULT Description No fault is displayed and no fault response is triggered. The fault which is signaled is completely ignored. The fault is displayed (in 7-segment display and SHELL), the fault output is set (if programmed). The unit has no other fault responses. The fault can be reset (terminal, RS485, fieldbus, auto-reset). P557 DCS actual position source Setting range: Motor encoder (X15) / ext. encoder (X14) / absolute encoder If the option "Encoder inverter" is set as encoder 1 in the MOVISAFE CONFIG configuration software, the setting in P557 determines which encoder signal is evaluated by the DCS31B option. 38 Manual MOVIDRIVE MDX61B DCS31B Option
Startup Switch-on sequence I 0 5 5.3 Switch-on sequence After each restart of the DCS31B option, the following operating states are performed and displayed at the front status LEDs in case of fault-free operation. DCS31B A/F WD B A Status LED LED A/F: Alarm / fault LED WD: Watchdog LED B: System B LED A: System A 60577AXX Operating state LED display Mode Description 1 LEDs "A" and "B" flash in sync (changes every 1.2 s) LED "WD" off LED "A/F" off 3 LEDs "A" and "B" flash in sync (changing every 0.8 s) LED "WD" off LED "A/F" off STARTUP The processor systems are synchronized and the configuration/firmware data is checked. 2 SENDCONFIG Configuration/firmware data is distributed and checked again. An internal check is performed for the configuration data. 4 LEDs "A" and "B" flash in sync (changing every 0.4 s) LED "WD" on LED "A/F" off STARTUP BUS RUN If applicable. Watchdog is active, which means that all outputs can be switched. NOTE In operating states 1, 2 and 3, the outputs are switched off automatically by the firmware. In the "RUN" mode (operating state "4"), the outputs are controlled by the implemented PLC program. Manual MOVIDRIVE MDX61B DCS31B Option 39
I Startup 5 Validation report 0 5.4 Validation report To make sure that the implemented safety functions function correctly, the user must check and document the parameters and connections after startup and configuration. This is supported by the MOVISAFE CONFIG configuration software. You can call up the validation report directly from the programming interface under the menu item [File] / [Configuration report]. You can use the first page of the validation report to enter generation information on the system (type system, customer, supplier, setup operator, etc.). You can use the second page to enter more detailed information on the system / machine. This data is for information only, but the content and scope must be checked with the approval authorities / inspector. The last page of the report contains an itemization on the safety check. You must make the following entries here: Serial number (identical to the serial number on the nameplate) Correspondence between the serial number read off and the serial number on the nameplate of the DCS31B option Identity of the subassembly Here, the inspector of the safety subassembly confirms that the CRC displayed in the programming interface is identical to the one in the DCS31B option. This CRC signature comprises a five-digit number that is displayed in the connection dialog box of the configuration tool in the diagnostic system information section. In this case, the DCS31B option must have an active connection. Once all header data has been entered, you can generate the validation report by pressing the "Save" button. The configuration tool creates a text file (.TXT) with the file name of the parameter/parameter dataset. The text file includes the following information: The 3 pages of the header data listed above Encoder configuration Parameters of the monitoring functions Monitoring functions not required are also listed. These functions must also be checked! NOTES The correct program data and parameter data must be loaded to create the validation report. All listed parameters and program instructions must be validated at the system / machine and confirmed by a signature in the validation report. The inspector must validate all the configured data again in a printout of the validation report. All limit values set for the monitoring functions must be tested. The printed out AWL code must be validated. 40 Manual MOVIDRIVE MDX61B DCS31B Option
Validation Procedure 6 6 Validation 6.1 Procedure The concept for the DCS31B option is based on the following prerequisites: Parameter and PLC data stored in the DCS31B option flash memory cannot change automatically. Online tests and corresponding signatures make sure that this is the case by implementing basic measures on the subassembly. However, the configured parameters cannot be evaluated by the subassembly. This affects parameters for the sensors, thresholds and limit values. The user must confirm that the data in the test protocol matches the parameters in the subassembly. The user must validate and protocol the parameter values for the travel type, sensors and monitoring functions individually by performing a function test. In addition, the user must validate and protocol the connection of each programmed PLC function by inspecting the code. The MOVISAFE CONFIG configuration software generate a suitable output form and stores it in a text file. The program enters the following information in the text file: Manufacturer: SEW-EURODRIVE GmbH & Co KG Type: DCS31B Version of the hardware and activated functions You must enter the following data in the text file: Serial number (identical to the serial number on the nameplate) Correspondence between the serial number read off and the serial number on the nameplate of the unit. The text file can then be printed out. Any other entries must be made manually: Date the configuration dataset was created CRC signature from the dataset Manual MOVIDRIVE MDX61B DCS31B Option 41
Maintenance 7 Maintenance during operation 7 Maintenance 7.1 Maintenance during operation The DCS31B option is fitted with a battery for saving data. The battery can only be replaced (every 10 years) by SEW-EURODRIVE. 7.2 Changing / handling changes on the unit Hardware changes If changes to the DCS31B option are necessary, they can only be performed by SEW-EURODRIVE. Firmware changes Only SEW-EURODRIVE is authorized to make changes to the firmware. Repair Only SEW-EURODRIVE is authorized to repair the DCS31B option. Warranty NOTE The safety certification and any right to claim under warranty become void if the user manipulates the unit internally (e.g. replacing components, welding parts). 7.3 Disposal Dispose of materials separately in accordance with the current regulations in force, for example: Electronics scrap (circuit boards) Plastics Sheet metal Copper 42 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Meaning of the status LEDs kva i P f n Hz 8 8 Local Diagnostics 8.1 Meaning of the status LEDs DCS31B A/F WD B A Status LED LED A/F: Alarm / fault LED WD: Watchdog LED B: System B LED A: System A 60577AXX Status display The status LEDs display the status of the DCS31B option. Operating state LED display Mode Description 1 LEDs "A" and "B" flash in sync (changing every 1.2 s) LED "WD" off LED "A/F" off STARTUP The processor systems are synchronized and the configuration/firmware data is checked. 2 SENDCONFIG Configuration/firmware data is distributed and checked again. An internal check is performed for the configuration data. 3 LEDs "A" and "B" flash in sync (changing every 0.8 s) LED "WD" off LED "A/F" off 4 LEDs "A" and "B" flash in sync (changing every 0.4 s) LED "WD" on LED "A/F" off 5 LEDs "A" and "B" flash in sync (changing every 2 s) LED "WD" off LED "A/F" off 6 LEDs "A" and "B" flash in sync (changing every 1.6 s) LED "WD" on LED "A/F" flashing 7 LEDs "A" and "B" flash in sync (changing every 0.4 s) LED "WD" off LED "A/F" on STARTUP BUS RUN STOP ALARM Fault If applicable. Watchdog is active, which means that all outputs can be switched. In STOP mode, parameter and program data can be uploaded into the DCS31B. ALARM can be reset via the PLC functionality. Fault can only be reset via ON/OFF of the DCS31B option. NOTES In operating states 1, 2 and 3, the outputs are switched off automatically by the firmware. In the operating status "RUN" (display "4"), the outputs are controlled by the implemented PLC program. In the operating statuses 6 and 7, all outputs are deactivated. When the DCS31B option is restarted, the outputs are enabled and switched according to the used logic in the "RUN" operating status (display "4"). If the reason for the alarm is still present (e.g. faulty encoder signals), an alarm is triggered that deactivates the outputs. Manual MOVIDRIVE MDX61B DCS31B Option 43
n kva 8 f Local Diagnostics i Error and alarm classes P Hz 8.2 Error and alarm classes The DCS31B option makes a general distinction between fatal errors and alarm messages. Type of error Description Impact on the system Reset condition Fatal error Alarm Fatal error or activation of an internal safety function. Due to reasons of safety, a cyclical program run is no longer possible. Functional error caused by an external process. The monitoring function triggers an ALARM, but the subassembly remains in standby mode. All outputs are switched off Switch the DCS31B option off and on again Set parameters for binary input (DI6) Reset element NOTE You have the following options to read the corresponding error or alarm message from the fault memory of the DCS31B option: via the X87 service interface with the DBG60B keypad with the MOVISAFE CONFIG configuration software, if P555/P556 is set to "NO RESPONSE". 8.3 Error messages Fatal error code Error 108, subcode 001 Error message Error during transfer of configuration data to the monitoring unit. Interruption in connection during program download. Remedy Send the configuration files again. Fatal error code Error 108, subcode 002 Error message Configuration data for software version of the subassembly is invalid. Subassembly configured with incorrect software version of the programming interface. Remedy Configure subassembly with permitted version of the programming interface and then switch subassembly off and on again. Fatal error code Error 108, subcode 003 Error message Unit was programmed with incorrect programming interface. Program or configuration data was loaded into the unit using an incorrect programming interface. Remedy Check the version of the subassembly. Configure again with a valid programming interface. Then switch unit off and on again. 44 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Error messages kva i P f n Hz 8 Fatal error code Error 108, subcode 004/005 Error message Defective reference voltage. Supply voltage of the subassembly is defective. Faulty component in the subassembly Remedy Check supply voltage Switch unit off and on again. Fatal error code Error 108, subcode 006/007 Error message Defective system voltage. Supply voltage of the subassembly is defective. Faulty component in the subassembly Remedy Check supply voltage Switch unit off and on again. Fatal error code Error 108, subcode 008/009 Error message Defective test voltage. Supply voltage of the subassembly is defective. Faulty component in the subassembly Remedy Check supply voltage Switch unit off and on again. Fatal error code Error 108, subcode 010 Error message Defective DC 24 V voltage supply Supply voltage of the subassembly is defective. Faulty component in the subassembly Remedy Check supply voltage Switch unit off and on again. Fatal error code Error 108, subcode 011 Error message The unit s ambient temperature is not in the defined range. Temperature at the place of operation is not in the permitted range. Remedy Check the ambient temperature. Fatal error code Error 108, subcode 012 Error message Plausibility check for position changeover. For the position changeover, ZSC, JSS or DMC is permanently activated. Remedy Check ZSC activation Check JSS activation Check DMC activation (only for monitoring via position) Fatal error code Error 108, subcode 013 Error message Faulty switching of the LOSIDE driver DO2_P/DO2_M. Short circuit of the output. Remedy Check wiring of the output. Manual MOVIDRIVE MDX61B DCS31B Option 45
n kva 8 f Local Diagnostics i Error messages P Hz Fatal error code Error 108, subcode 014 Error message Faulty switching of the HISIDE driver DO2_P/DO2_M. Short circuit of the output. Remedy Check wiring of the output. Fatal error code Error 108, subcode 015 Error message Faulty switching of the LOSIDE driver DO0_M. Short circuit of the output. Remedy Check wiring of the output. Fatal error code Error 108, subcode 016 Error message Faulty switching of the HISIDE driver DO0_P. Short circuit of the output. Remedy Check wiring of the output. Fatal error code Error 108, subcode 017 Error message Faulty switching of the LOSIDE driver DO01_M. Short circuit of the output. Remedy Check wiring of the output. Fatal error code Error 108, subcode 018 Error message Faulty switching of the HISIDE driver DO1_P. Short circuit of the output. Remedy Check wiring of the output. NOTE If other error messages other than those described here appear, proceed as follows: Under what circumstances did the error occur? Save the current configuration set Take a note of the error code Contact the service team of SEW-EURODRIVE 46 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Alarm messages kva i P f n Hz 8 8.4 Alarm messages Alarm code Error 109, subcode 001 Alarm message Communication error CAN interface inverter. The DCS31B option does not receive any valid data from the inverter. Remedy Check hardware connection to the inverter Check version of the inverter Alarm code Error 109, subcode 002/003 Alarm message Plausibility error in binary input at cycle P1. There is no pulse1 voltage at binary input DI1. Remedy Configure binary input DI1 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 004/005 Alarm message Plausibility error in binary input at cycle P2. There is no pulse1 voltage at binary input DI2. Remedy Configure binary input DI2 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 006/007 Alarm message Pulse 1 plausibility error at binary input DI03. There is no pulse 1 voltage at binary input DI3. Remedy Configure binary input DI3 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 008/009 Alarm message Pulse 1 plausibility error at binary input DI4. There is no pulse1 voltage at binary input DI4. Remedy Configure binary input DI4 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 010/011 Alarm message Pulse 1 plausibility error at binary input DI5. There is no pulse 1 voltage at binary input DI5. Remedy Configure binary input DI5 in accordance with the project planning and wiring diagram Check wiring Manual MOVIDRIVE MDX61B DCS31B Option 47
n kva 8 f Local Diagnostics i Alarm messages P Hz Alarm code Error 109, subcode 012/013 Alarm message Pulse 1 plausibility error at binary input DI6. There is no pulse 1 voltage at binary input DI6. Remedy Configure binary input DI6 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 014/015 Alarm message Pulse 1 plausibility error at binary input DI7. There is no pulse 1 voltage at binary input DI7. Remedy Configure binary input DI7 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 016/017 Alarm message Pulse 1 plausibility error at binary input DI8. There is no pulse 1 voltage at binary input DI8. Remedy Configure binary input DI8 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 018/019 Alarm message Pulse 2 plausibility error at input DI1. There is no pulse 2 voltage at binary input DI1. Remedy Configure binary input DI1 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 020/021 Alarm message Pulse 2 plausibility error at binary input DI2. There is no pulse 2 voltage at binary input DI2. Remedy Configure binary input DI2 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 022/023 Alarm message Pulse 2 plausibility error at binary input DI3. There is no pulse 2 voltage at binary input DI3. Remedy Configure binary input DI3 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 024/025 Alarm message Pulse 2 plausibility error at binary input DI4. There is no pulse 2 voltage at binary input DI4. Remedy Configure binary input DI4 in accordance with the project planning and wiring diagram Check wiring 48 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Alarm messages kva i P f n Hz 8 Alarm code Error 109, subcode 026/027 Alarm message Pulse 2 plausibility error at binary input DI5. There is no pulse 2 voltage at binary input DI5. Remedy Configure binary input DI5 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 028/029 Alarm message Pulse 2 plausibility error at binary input DI6. There is no pulse 2 voltage at binary input DI6. Remedy Configure binary input DI6 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 030/031 Alarm message Pulse 2 plausibility error at binary input DI7. There is no pulse 2 voltage at binary input DI7. Remedy Configure binary input DI7 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 032/033 Alarm message Pulse 2 plausibility error at binary input DI8. There is no pulse 2 voltage at binary input DI8. Remedy Configure binary input DI8 in accordance with the project planning and wiring diagram Check wiring Alarm code Error 109, subcode 034/035 Alarm message Plausibility error in the speed recording. The difference between the two velocity sensors is higher than the configured speed cut-off threshold. Remedy Check track again with the data set in the configuration of the encoders Check the velocity sensor Use the SCOPE function to set speed signals so they are congruent Alarm code Error 109, subcode 036/037 Alarm message Plausibility error for position recording. The difference between the two position signals is higher than the configured value. Remedy Check track with the configured data of the encoder setting Check the position signal Are all signal connected correctly to the 9-pin encoder connector? Check the encoder connector is connected properly. Is the jumper between pin 1 and pin 2 on the 9-pin encoder connector closed (SSI absolute encoder)? Use the SCOPE function to set position signals so they are congruent Manual MOVIDRIVE MDX61B DCS31B Option 49
n kva 8 f Local Diagnostics i Alarm messages P Hz Alarm code Error 109, subcode 038/039 Alarm message Plausibility error - incorrect position range. The current position is outside of the configured range. Remedy Check track with configured data of the encoder setting Check position signal, correct offset if necessary Read off the position using the SCOPE function and set in ratio to the configured values Alarm code Error 109, subcode 040/041 Alarm message Plausibility error - incorrect speed. The current speed is outside of the configured maximum speed. Remedy The drive moves outside of the permitted and configured speed range Check the configuration (maximum speed) Analyze the speed development using the SCOPE function Alarm code Error 109, subcode 042/043 Alarm message Configuration error: Acceleration. Current acceleration is outside of the configured acceleration range. Remedy Check the encoder type and configuration (SSI / incremental) Checking the encoder connection / wiring Check the polarity of the encoder data Check the functions of the encoder Alarm code Error 109, subcode 044/045 Alarm message Plausibility error in encoder interface (A3401 = encoder 1 and A3402 = encoder 2). The encoder interface does not match the configured data. Remedy Check the encoder type and configuration (SSI / incremental) Checking the encoder connection / wiring Check the polarity of the encoder data Check the functions of the encoder Alarm code Error 109, subcode 046/047 Alarm message Faulty encoder voltage supply (A3401 = encoder 1 and A3402 = encoder 2). Encoder supply voltage is outside of the defined range (min. DC 20 V / max. DC 29 V). Remedy Overload in the supply voltage of the encoder; internal fuse has triggered Check supply voltage of the DCS31B option Alarm code Error 109, subcode 048/049 Alarm message Error in reference voltage. Reference voltage input of the encoder system is outside of the defined range. Remedy Check the reference voltage input of the encoder system 50 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Alarm messages kva i P f n Hz 8 Alarm code Error 109, subcode 050/051 Alarm message Voltage difference of RS485 driver 1 (error INC_B or SSI_CLK) is faulty. No encoder connection, incorrect encoder type. Remedy Check encoder connection Alarm code Error 109, subcode 052/053 Alarm message Voltage difference of RS485 driver 2 (error INC_B or SSI_CLK) is faulty. No encoder connection, incorrect encoder type. Remedy Check encoder connection Alarm code Error 109, subcode 054/055 Alarm message Difference in incremental counter. No encoder connection, incorrect encoder type. Remedy Check encoder connection Alarm code Error 109, subcode 056/057 Alarm message Plausibility error in encoder interface (A3401 = encoder 1 and A3402 = encoder 2). The encoder interface does not match the configured data. Remedy Check the encoder type and configuration (SSI / incremental) Checking the encoder connection / wiring Check the polarity of the encoder data Check the functions of the encoder Alarm code Error 109, subcode 058/059 Alarm message Plausibility error in the sin/cos encoder connection. Incorrect encoder type is connected. Remedy Check encoder connection Check encoder connection (jumper between pin 1 and pin 2) Alarm code Error 109, subcode 060/061 Alarm message Plausibility error - incremental encoder connection. Incorrect encoder type is connected. Remedy Check encoder connection Check encoder connection (jumper between pin 1 and pin 2) Alarm code Error 109, subcode 062/063 Alarm message Plausibility error - incremental encoder connection. Phase error in the incremental or sin/cos encoder. Remedy Check encoder connection Replace defective encoder Manual MOVIDRIVE MDX61B DCS31B Option 51
n kva 8 f Local Diagnostics i Alarm messages P Hz Alarm code Error 109, subcode 064/065 Alarm message Plausibility error - SSI encoder connection. Connected encoder type does not match the configuration. Remedy Check encoder connection Check connected encoder Alarm code Error 109, subcode 066/067 Alarm message Plausibility error - SSI-Listener encoder connection. Connected encoder type does not match the configuration. Remedy Check encoder connection Check connected encoder Alarm code Error 109, subcode 068 Alarm message Faulty switching of the LOSIDE driver DO2_M. DC 0 V short circuit at the output. Remedy Check wiring of the output. Alarm code Error 109, subcode 069 Alarm message Faulty switching of the HISIDE driver DO2_P. DC 0 V short circuit at the output. Remedy Check wiring of the output. Alarm code Error 109, subcode 070 Alarm message Faulty switching of the LOSIDE driver DO0_M. DC 0 V short circuit at the output. Remedy Check wiring of the output. Alarm code Error 109, subcode 071 Alarm message Faulty switching of the HISIDE driver DO0_P. DC 0 V short circuit at the output. Remedy Check wiring of the output. Alarm code Error 109, subcode 072 Alarm message Faulty switching of the LOSIDE driver DO1_M. DC 0 V short circuit at the output. Remedy Check wiring of the output. Alarm code Error 109, subcode 073 Alarm message Faulty switching of the HISIDE driver DO1_P. DC 0 V short circuit at the output. Remedy Check wiring of the output. 52 Manual MOVIDRIVE MDX61B DCS31B Option
Local Diagnostics Alarm messages kva i P f n Hz 8 Alarm code Error 109, subcode 074 Alarm message Undervoltage test WD for LOSIDE driver. DC 0 V short circuit at one of the DC 0 V outputs. Remedy Check wiring of the outputs. Alarm code Error 109, subcode 075 Alarm message Undervoltage test WD for HISIDE driver. DC -24 V short circuit at one of the DC -24 V outputs. Remedy Check wiring of the outputs. Alarm code Error 109, subcode 076/077 Alarm message CW and CCW monitoring (in the DMC module) activated simultaneously. Multiple activation. Remedy Only one enable may be activated in the programming. Alarm code Error 109, subcode 078/079 Alarm message CW and CCW monitoring range of the OLC activated simultaneously. Multiple activation. Remedy Only one direction of rotation can be activated in the DMC module. Alarm code Error 109, subcode 080/081 Alarm message CW and CCW monitoring range of the OLC activated simultaneously. Multiple activation. Remedy Only one direction of rotation can be activated in the DMC module. Alarm code Error 109, subcode 082/083 Alarm message Timeout error MET. Input element with time monitoring is faulty. Remedy Check the wiring of the input element Input element faulty Alarm code Error 109, subcode 084/085 Alarm message Timeout error MEZ. Two-hand operation with time monitoring is faulty. Remedy Check the wiring of the input element Input element faulty Manual MOVIDRIVE MDX61B DCS31B Option 53
n kva 9 f Technical Data i Plug connectors P Hz 9 Technical Data 9.1 Plug connectors Connector designation: X80 Type: Phoenix terminal, 2-pin Manufacturer: Phoenix Contact Order designation: 1803 578 PIN Signal description Specification 1 DC +24 V DC 24 V supply voltage DC 20 V... DC 29 V 2 0V24 0 V reference potential Connector designation: X81 Type: Phoenix terminal, 10-pin Manufacturer: Phoenix Contact Order designation: 1803 659 PIN Signal description Specification 1 Pulse 1 Clock signal 1 for safe inputs DC 24 V, clocked 2 DI1 Input 1 3 DI2 Input 2 4 DI3 Input 3 DC 20 V to DC 29 V 5 DI4 Input 1 6 Pulse 2 Clock signal 2 for safe inputs DC 24 V, clocked 7 DI5 Input 5 8 DI6 Input 6 9 DI7 Input 7 10 DI8 Input 8 DC 20 V to DC 29 V Connector designation: X82 Type: Phoenix terminal Manufacturer: Phoenix Contact Order designation: 1803 594 PIN Assignment Assignment Assignment Signal description 1 DO0_P HISIDE - output 0 2 DO0_M LOSIDE - output 0 3 DO1_P HISIDE - output 1 4 DO1_M LOSIDE - output 1 Specification DC 24 V, 0.1 A 54 Manual MOVIDRIVE MDX61B DCS31B Option
Technical Data Plug connectors kva i P f n Hz 9 Connector designation: X83 Type: Phoenix terminal, 2-pin Manufacturer: Phoenix Contact Order designation: 1803 578 PIN Signal description 1 DO2_P HISIDE output 2 DO2_M LOSIDE output Specification DC 24 V, 1.5 A Connector designation: X84/X85 Type: Sub-D socket Manufacturer: diverse A B C A 6 B 7 n.c. 8 VCC + 9 1 2 3 4 5 Assignment A 1 sin+ sinn.c. 8 Clk- 6 Datan.c. B 2 cos+ cos- 7 n.c. 3 n.c. n.c. 4 n.c. VCC+ 9 VCC + GND 5 GND 6 7 8 9 1 2 3 4 5 Data+ n.c. Clk+ n.c. GND 59397AXX Figure 13: Pin assignment for incremental encoder (A) / sin/cos (B) / absolute encoder (C) Pin assignment (depending on the technology): PIN Incremental (A) sin / cos (B) SSI binary (C) SSI Gray (C) 1 A Sin + Data+ Data+ 2 B Cos+ Unassigned Unassigned 3 Unassigned Unassigned CLK+ CLK+ 4 Unassigned Unassigned Unassigned Unassigned 5 A GND GND GND 6 A Sin Data Data 7 B Cos Unassigned Unassigned 8 Unassigned Unassigned CLK CLK 9 24V 24V 24V 24V Manual MOVIDRIVE MDX61B DCS31B Option 55
kva 9 f Technical Data Response times of DCS31B option i n P Hz 9.2 Response times of DCS31B option The following tables lists the response times of the DCS31B option. The cycle time of the system forms the basis for calculating response times. The cycle time (T_cycle) of the DCS31B option is 25 ms. The specified response times correspond to the maximum run time for the specific application within the DCS31B option. Depending on the application, additional, application-specific response times for the sensors and actuators have to be added to the total run time. Function Reading in of a digital NC contact and further processing by internal PLC Reading in of a digital NO contact and further processing by internal PLC Response of an activated monitoring function including PLC processing for position and velocity processing Response of an activated monitoring function including PLC processing for acceleration processing Response of a monitoring function activated by an external input including PLC processing using a NC contact. Response of a monitoring function activated by an external input including PLC processing using a NO contact. Response time [ms] Explanation 58 The DCS31B option detects an NC contact within one cycle. Another cycle is needed for further processing, including the switching of an output. 75 For a NO contact to be recognized as active ("1"), an active signal level must be present at the input for an entire clock cycle of the DCS31B option. In the worst case scenario, this results in a scan over two cycles to provide the required information for internal processing. As another cycle is needed for processing the input signal, this results in a total signal run time of three cycles. Note: Try to avoid using NO contacts in safety circuits! 50 For a monitoring function that has been activated via ENABLE, the DCS31B option needs one cycle to calculate the current speed value. In the next cycle, after the monitoring function has been calculated, the information is further processed and output by the PLC. That is, once the programmed logic has been performed, this can lead, e.g. to the switching of an output. 75 For a monitoring function that has been activated via ENABLE, the DCS31B option needs two cycles to calculate the current acceleration value. In the next cycle, after the monitoring function has been calculated, the information is further processed and output by the PLC. That is, once the programmed logic has been performed, this can lead, e.g. to the switching of an output. 83 The input signal processing lasts one scan cycle. An additional cycle is needed to set the ENABLE input for the required monitoring function. In the next cycle, the monitoring function and behavior of the result is calculated and, if necessary, the output is activated. 100 In the worst case scenario, two cycles are needed to process the digital input signal. An additional cycle is needed to set the ENABLE input for the required monitoring function. In the next cycle, the monitoring function is calculated, the result processed and, if necessary, the output is activated. 56 Manual MOVIDRIVE MDX61B DCS31B Option
Appendix Description of the input elements 10 10 Appendix 10.1 Description of the input elements General information The individual switches of the following input elements can be assigned to the digital outputs DI1 to DI8 as required. Operating mode selection switch Switch type Comment Classification in EN 954-1 2 positions Operating mode selection switch Category 4 SIL3 3 positions Operating mode selection switch, monitored Category 4 SIL3 Rating EN IEC 61508 NOTE When changing the position of the operating mode selection switch, use the Safe-PLC program that is to be created to ensure that the outputs of the DCS31B option are deactivated (EN 60204). Light curtain Switch type Comment Classification in EN 954-1 2 NC contacts Light curtain for increased demands Category 4 SIL3 2 NC contacts for time Light curtain, monitored Category 4 SIL3 monitoring 1 NO + 1 NC contact Light curtain for increased demands Category 4 SIL3 1 NO + 1 NC contact, timemonitored Light curtain, monitored Category 4 SIL3 Rating EN IEC 61508 Emergency stop Switch type Comment Classification in EN 954-1 1 NC contacts Emergency stop, simple Category 3 SIL2 2 NC contacts Emergency stop for increased Category 4 SIL3 demands 2 NC contacts for time monitoring Emergency stop, monitored Category 4 SIL3 Rating EN IEC 61508 Start / reset Switch type Comment Classification in EN 954-1 1 NO contacts Alarm reset, simple 1) - - 1 NO contacts Logic reset, simple Category 3 SIL2 1 NO contacts Start monitoring, simple (special function) - - Rating EN IEC 61508 1) The Alarm/Reset is subject to edge control and can always be operated with a DC 24 V voltage. Manual MOVIDRIVE MDX61B DCS31B Option 57
Appendix 10 Description of the input elements Sensor Switch type Comment Classification in EN 954-1 1 NC contacts Sensor input, simple Category 3 SIL2 1 NO contacts Sensor input, simple Category 3 SIL2 2 NC contacts Sensor input, increased demands Category 4 SIL3 2 NC contacts for time Sensor input, monitored Category 4 SIL3 monitoring 1 NO + 1 NC contact Sensor input, increased demands Category 4 SIL3 1 NO + 1 NC contact, timemonitored Sensor input, monitored Category 4 SIL3 Rating EN IEC 61508 Door monitoring Switch type Comment Classification in EN 954-1 2 NC contacts Door monitoring, increased demands Category 4 SIL3 2 NC contacts for time Door monitoring, monitored Category 4 SIL3 monitoring 1 NO + 1 NC contact Door monitoring, increased demands Category 4 SIL3 1 NO + 1 NC contact, timemonitored Door monitoring, monitored Category 4 SIL3 2 NO + 2 NC contact Door monitoring, increased demands Category 4 SIL3 2 NO + 2 NC contact, timemonitored Door monitoring, monitored Category 4 SIL3 3 NC contacts Door monitoring, increased demands Category 4 SIL3 3 NC contacts, time-monitored Door monitoring, monitored Category 4 SIL3 Rating EN IEC 61508 Confirmation button Switch type Comment Classification in EN 954-1 1 NC contacts Confirmation button, simple Category 3 SIL2 1 NO contacts Confirmation button, simple Category 3 SIL2 2 NC contacts Confirmation button, increased Category 4 SIL3 demands 2 NC contacts for time monitoring Confirmation button, monitored Category 4 SIL3 Rating EN IEC 61508 58 Manual MOVIDRIVE MDX61B DCS31B Option
Appendix List of encoders recommended by SEW-EURODRIVE 10 10.2 List of encoders recommended by SEW-EURODRIVE Incremental encoders Type designation Voltage supply Output signal EH1R, ES1R, ES2R, EV1R DC 24 V In accordance with RS422 (1024 increments/revolution) Sin/cos encoders Type designation Voltage supply Output signal ES1S, ES2S, EH1S, EV1S DC 24 V AC 1 V ss sin/cos (1024 increments/revolution) Hiperface encoders (sin/cos tracks) With Hiperface encoders, only the sin/cos tracks are evaluated by the MOVISAFE. The voltage supply for Hiperface encoders is provided via the DEH11B option card of MOVIDRIVE B. Type designation Voltage supply Output signal ES1H, AS1H ES3H, ES4H, AS3H, AS4H EV1H, AV1H DC 12 V AC 1 V ss sin/cos (1024 increments/revolution) Positive connection Hiperface encoder (sin/cos tracks) With positive connection Hiperface AF6H encoders, only the sin/cos tracks are evaluated by the MOVISAFE. The voltage supply for positive connection Hiperface encoders is provided via the DEH11B option card of MOVIDRIVE B. Type designation Voltage supply Output signal AF6H DC 12 V AC 1 V ss sin/cos (1024 increments/revolution) Absolute encoders (combi encoders) Type designation Voltage supply Output signal AV1Y DC 24 V AC 1 V ss sin/cos (512 increments/revolution) 4096 4096 increments SSI-Gray Absolute encoders Type designation Voltage supply Output signal CE58M (T&R) SSI Gray (4096 4096 increments) DC 24 V DME5000 (Sick-Stegmann) SSI Gray (10000 increments/m) Manual MOVIDRIVE MDX61B DCS31B Option 59
11 Index 11 Index A Alarm messages...47 C Confirmation button...58 Connecting binary inputs DI1 to DI8 Dual-channel sensor, checked...22 Dual-channel sensor, unchecked...20 Single-channel sensor, checked...21 Single-channel sensor, unchecked...19 Using clock outputs P1 and P2...18 Connecting position and velocity sensors...23 Before you begin...23 Combining different encoder types...24 Configuring the travel type...24 Connecting a sin/cos encoder...29 Connecting an absolute encoder...28 Connecting an incremental encoder...29 One-encoder concept...30 D DCS31B Terminal description...15 DCS31B unit design...12 E Encoder list (recommended by SEW-EURODRIVE)...59 Absolute encoders...59 Absolute encoders (combi encoders)...59 Hiperface encoders...59 Incremental encoders...59 Positive connection Hiperface encoders...59 Sin/cos encoders...59 Encoder wiring diagrams...28 Error and alarm classes...44 Error messages...44 I Input elements Confirmation button...58 Description...57 Door monitoring...58 Emergency stop...57 Light curtain...57 Operating mode selection switch...57 Sensor...58 Start / reset...57 Installation Configuring the measuring types...24 Connecting binary inputs DI1 to DI8...17 Connecting position and velocity sensors...23 External DC 24 V voltage supply...17 General installation information...13 Measures to ensure electromagnetic compatibility...16 Terminal description of DCS31B option... 15 Wiring of binary outputs... 31 Installation notes Combining different encoder types... 24 Installation of the DCS31B option card... 13 L Local diagnostics... 43 Meaning of the status LEDs... 43 Status display... 43 M Maintenance... 42 Changing / handling changes on the unit... 42 Disposal... 42 Maintenance during operation... 42 Meaning of the status LEDs... 43 Measures to ensure electromagnetic compatibility... 16 N Nameplate... 11 O Other applicable documents... 8 P Parameter descriptions... 37 Plug connectors... 54 S Safety Notes... 6 Safety notes Designated use... 7 Electrical connection... 7 General... 6 Installation... 7 Operation... 8 Target group... 6 Terminology... 8 Transportation, putting into storage... 7 Startup... 36 Prerequisites... 36 Startup steps... 36 Switch-on sequence... 39 Validation report... 40 Status display... 43 Switch-on sequence... 39 T Technical Data Plug connector... 54 Response times of DCS31B option... 56 Terminal description of DCS31B... 15 Terminology... 8 TÜV certificate... 9 60 Manual MOVIDRIVE MDX61B DCS31B Option
Index 11 U Unit characteristics of DCS31B...10 V Validation...41 Validation report...40 W Wiring of binary outputs...31 Dual-channel switching binary output DO0 with external monitoring... 34, 35 Wiring the binary outputs Single-pole switching M binary output without check...33 Single-pole switching P binary output without check...32 Manual MOVIDRIVE MDX61B DCS31B Option 61
Address List Address List Germany Headquarters Production Competence Center Bruchsal Central North East South SEW-EURODRIVE GmbH & Co KG Ernst-Blickle-Straße 42 D-76646 Bruchsal P.O. Box Postfach 3023 D-76642 Bruchsal SEW-EURODRIVE GmbH & Co KG Ernst-Blickle-Straße 1 D-76676 Graben-Neudorf SEW-EURODRIVE GmbH & Co KG Alte Ricklinger Straße 40-42 D-30823 Garbsen (near Hannover) SEW-EURODRIVE GmbH & Co KG Dänkritzer Weg 1 D-08393 Meerane (near Zwickau) SEW-EURODRIVE GmbH & Co KG Domagkstraße 5 D-85551 Kirchheim (near München) West SEW-EURODRIVE GmbH & Co KG Siemensstraße 1 D-40764 Langenfeld (near Düsseldorf) Electronics SEW-EURODRIVE GmbH & Co KG Ernst-Blickle-Straße 42 D-76646 Bruchsal Drive Hotline / 24 Hour Additional addresses for service in Germany provided on request! Tel. +49 7251 75-0 Fax +49 7251 75-1970 http://www.sew-eurodrive.de sew@sew-eurodrive.de Tel. +49 7251 75-1710 Fax +49 7251 75-1711 sc-mitte@sew-eurodrive.de Tel. +49 5137 8798-30 Fax +49 5137 8798-55 sc-nord@sew-eurodrive.de Tel. +49 3764 7606-0 Fax +49 3764 7606-30 sc-ost@sew-eurodrive.de Tel. +49 89 909552-10 Fax +49 89 909552-50 sc-sued@sew-eurodrive.de Tel. +49 2173 8507-30 Fax +49 2173 8507-55 sc-west@sew-eurodrive.de Tel. +49 7251 75-1780 Fax +49 7251 75-1769 sc-elektronik@sew-eurodrive.de +49 180 5 SEWHELP +49 180 5 7394357 France Production Haguenau SEW-USOCOME 48-54, route de Soufflenheim B. P. 20185 F-67506 Haguenau Cedex Production Forbach SEW-EUROCOME Zone Industrielle Technopôle Forbach Sud B. P. 30269 F-57604 Forbach Cedex Bordeaux Lyon Paris SEW-USOCOME Parc d'activités de Magellan 62, avenue de Magellan - B. P. 182 F-33607 Pessac Cedex SEW-USOCOME Parc d'affaires Roosevelt Rue Jacques Tati F-69120 Vaulx en Velin SEW-USOCOME Zone industrielle 2, rue Denis Papin F-77390 Verneuil I'Etang Additional addresses for service in France provided on request! Algeria Alger Réducom 16, rue des Frères Zaghnoun Bellevue El-Harrach 16200 Alger Tel. +33 3 88 73 67 00 Fax +33 3 88 73 66 00 http://www.usocome.com sew@usocome.com Tel. +33 3 87 29 38 00 Tel. +33 5 57 26 39 00 Fax +33 5 57 26 39 09 Tel. +33 4 72 15 37 00 Fax +33 4 72 15 37 15 Tel. +33 1 64 42 40 80 Fax +33 1 64 42 40 88 Tel. +213 21 8222-84 Fax +213 21 8222-84 Argentina Buenos Aires SEW EURODRIVE ARGENTINA S.A. Centro Industrial Garin, Lote 35 Ruta Panamericana Km 37,5 1619 Garin Tel. +54 3327 4572-84 Fax +54 3327 4572-21 sewar@sew-eurodrive.com.ar 62
Address List Australia Melbourne SEW-EURODRIVE PTY. LTD. 27 Beverage Drive Tullamarine, Victoria 3043 Tel. +61 3 9933-1000 Fax +61 3 9933-1003 http://www.sew-eurodrive.com.au enquires@sew-eurodrive.com.au Sydney SEW-EURODRIVE PTY. LTD. 9, Sleigh Place, Wetherill Park New South Wales, 2164 Tel. +61 2 9725-9900 Fax +61 2 9725-9905 enquires@sew-eurodrive.com.au Townsville SEW-EURODRIVE PTY. LTD. 12 Leyland Street Garbutt, QLD 4814 Tel. +61 7 4779 4333 Fax +61 7 4779 5333 enquires@sew-eurodrive.com.au Austria Wien SEW-EURODRIVE Ges.m.b.H. Richard-Strauss-Strasse 24 A-1230 Wien Tel. +43 1 617 55 00-0 Fax +43 1 617 55 00-30 http://sew-eurodrive.at sew@sew-eurodrive.at Belgium Brüssel SEW Caron-Vector S.A. Avenue Eiffel 5 B-1300 Wavre Tel. +32 10 231-311 Fax +32 10 231-336 http://www.sew-eurodrive.be info@caron-vector.be Brazil Production Sao Paulo SEW-EURODRIVE Brasil Ltda. Avenida Amâncio Gaiolli, 50 Caixa Postal: 201-07111-970 Guarulhos/SP - Cep.: 07251-250 Additional addresses for service in Brazil provided on request! Tel. +55 11 6489-9133 Fax +55 11 6480-3328 http://www.sew.com.br sew@sew.com.br Bulgaria Sofia BEVER-DRIVE GmbH Bogdanovetz Str.1 BG-1606 Sofia Cameroon Douala Electro-s Rue Drouot Akwa B.P. 2024 Douala Tel. +359 2 9151160 Fax +359 2 9151166 bever@fastbg.net Tel. +237 4322-99 Fax +237 4277-03 Canada Toronto Vancouver SEW-EURODRIVE CO. OF CANADA LTD. 210 Walker Drive Bramalea, Ontario L6T3W1 SEW-EURODRIVE CO. OF CANADA LTD. 7188 Honeyman Street Delta. B.C. V4G 1 E2 Montreal SEW-EURODRIVE CO. OF CANADA LTD. 2555 Rue Leger LaSalle, Quebec H8N 2V9 Additional addresses for service in Canada provided on request! Tel. +1 905 791-1553 Fax +1 905 791-2999 http://www.sew-eurodrive.ca l.reynolds@sew-eurodrive.ca Tel. +1 604 946-5535 Fax +1 604 946-2513 b.wake@sew-eurodrive.ca Tel. +1 514 367-1124 Fax +1 514 367-3677 a.peluso@sew-eurodrive.ca Chile Santiago de Chile SEW-EURODRIVE CHILE LTDA. Las Encinas 1295 Parque Industrial Valle Grande LAMPA RCH-Santiago de Chile P.O. Box Casilla 23 Correo Quilicura - Santiago - Chile Tel. +56 2 75770-00 Fax +56 2 75770-01 http://www.sew-eurodrive.cl ventas@sew-eurodrive.cl 63
Address List China Production Tianjin Suzhou SEW-EURODRIVE (Tianjin) Co., Ltd. No. 46, 7th Avenue, TEDA Tianjin 300457 SEW-EURODRIVE (Suzhou) Co., Ltd. 333, Suhong Middle Road Suzhou Industrial Park Jiangsu Province, 215021 P. R. China Additional addresses for service in China provided on request! Tel. +86 22 25322612 Fax +86 22 25322611 gm-tianjin@sew-eurodrive.cn http://www.sew-eurodrive.com.cn Tel. +86 512 62581781 Fax +86 512 62581783 suzhou@sew.com.cn Colombia Bogotá SEW-EURODRIVE COLOMBIA LTDA. Calle 22 No. 132-60 Bodega 6, Manzana B Santafé de Bogotá Tel. +57 1 54750-50 Fax +57 1 54750-44 http://www.sew-eurodrive.com.co sewcol@sew-eurodrive.com.co Croatia Zagreb KOMPEKS d. o. o. PIT Erdödy 4 II HR 10 000 Zagreb Tel. +385 1 4613-158 Fax +385 1 4613-158 kompeks@net.hr Czech Republic Praha SEW-EURODRIVE CZ S.R.O. Business Centrum Praha Lužná 591 CZ-16000 Praha 6 - Vokovice Tel. +420 220121234 Fax +420 220121237 http://www.sew-eurodrive.cz sew@sew-eurodrive.cz Denmark Kopenhagen SEW-EURODRIVEA/S Geminivej 28-30 DK-2670 Greve Tel. +45 43 9585-00 Fax +45 43 9585-09 http://www.sew-eurodrive.dk sew@sew-eurodrive.dk Estonia Tallin ALAS-KUUL AS Reti tee 4 EE-75301 Peetri küla, Rae vald, Harjumaa Tel. +372 6593230 Fax +372 6593231 veiko.soots@alas-kuul.ee Finland Lahti SEW-EURODRIVE OY Vesimäentie 4 FIN-15860 Hollola 2 Tel. +358 201 589-300 Fax +358 3 780-6211 sew@sew.fi http://www.sew-eurodrive.fi Gabon Libreville Electro-s B.P. 1889 Libreville Tel. +241 7340-11 Fax +241 7340-12 Great Britain Normanton SEW-EURODRIVE Ltd. Beckbridge Industrial Estate P.O. Box No.1 GB-Normanton, West- Yorkshire WF6 1QR Tel. +44 1924 893-855 Fax +44 1924 893-702 http://www.sew-eurodrive.co.uk info@sew-eurodrive.co.uk Greece Athen Christ. Boznos & Son S.A. 12, Mavromichali Street P.O. Box 80136, GR-18545 Piraeus Tel. +30 2 1042 251-34 Fax +30 2 1042 251-59 http://www.boznos.gr info@boznos.gr 64
Address List Hong Kong Hong Kong SEW-EURODRIVE LTD. Unit No. 801-806, 8th Floor Hong Leong Industrial Complex No. 4, Wang Kwong Road Kowloon, Hong Kong Tel. +852 2 7960477 + 79604654 Fax +852 2 7959129 contact@sew-eurodrive.hk Hungary Budapest SEW-EURODRIVE Kft. H-1037 Budapest Kunigunda u. 18 Tel. +36 1 437 06-58 Fax +36 1 437 06-50 office@sew-eurodrive.hu India Baroda SEW-EURODRIVE India Pvt. Ltd. Plot No. 4, Gidc Por Ramangamdi Baroda - 391 243 Gujarat Technical Offices Bangalore SEW-EURODRIVE India Private Limited 308, Prestige Centre Point 7, Edward Road Bangalore Tel. +91 265 2831086 Fax +91 265 2831087 http://www.seweurodriveindia.com mdoffice@seweurodriveindia.com Tel. +91 80 22266565 Fax +91 80 22266569 salesbang@seweurodriveinindia.com Ireland Dublin Alperton Engineering Ltd. 48 Moyle Road Dublin Industrial Estate Glasnevin, Dublin 11 Tel. +353 1 830-6277 Fax +353 1 830-6458 info@alperton.ie Israel Tel-Aviv Liraz Handasa Ltd. Ahofer Str 34B / 228 58858 Holon Tel. +972 3 5599511 Fax +972 3 5599512 office@liraz-handasa.co.il Italy Milano SEW-EURODRIVE di R. Blickle & Co.s.a.s. Via Bernini,14 I-20020 Solaro (Milano) Tel. +39 02 96 9801 Fax +39 02 96 799781 http://www.sew-eurodrive.it sewit@sew-eurodrive.it Ivory Coast Abidjan SICA Ste industrielle et commerciale pour l'afrique 165, Bld de Marseille B.P. 2323, Abidjan 08 Tel. +225 2579-44 Fax +225 2584-36 Japan Toyoda-cho SEW-EURODRIVE JAPAN CO., LTD 250-1, Shimoman-no, Iwata Shizuoka 438-0818 Tel. +81 538 373811 Fax +81 538 373814 http://www.sew-eurodrive.co.jp sewjapan@sew-eurodrive.co.jp Korea Ansan-City SEW-EURODRIVE KOREA CO., LTD. B 601-4, Banweol Industrial Estate Unit 1048-4, Shingil-Dong Ansan 425-120 Tel. +82 31 492-8051 Fax +82 31 492-8056 http://www.sew-korea.co.kr master@sew-korea.co.kr Latvia Riga SIA Alas-Kuul Katlakalna 11C LV-1073 Riga Tel. +371 7139253 Fax +371 7139386 http://www.alas-kuul.com info@alas-kuul.com 65
Address List Lebanon Beirut Gabriel Acar & Fils sarl B. P. 80484 Bourj Hammoud, Beirut Lithuania Alytus UAB Irseva Naujoji 19 LT-62175 Alytus Tel. +961 1 4947-86 +961 1 4982-72 +961 3 2745-39 Fax +961 1 4949-71 gacar@beirut.com Tel. +370 315 79204 Fax +370 315 56175 info@irseva.lt http://www.sew-eurodrive.lt Luxembourg Brüssel CARON-VECTOR S.A. Avenue Eiffel 5 B-1300 Wavre Tel. +32 10 231-311 Fax +32 10 231-336 http://www.sew-eurodrive.lu info@caron-vector.be Malaysia Johore SEW-EURODRIVE SDN BHD No. 95, Jalan Seroja 39, Taman Johor Jaya 81000 Johor Bahru, Johor West Malaysia Tel. +60 7 3549409 Fax +60 7 3541404 sales@sew-eurodrive.com.my Mexico Queretaro SEW-EURODRIVE MEXIKO SA DE CV SEM-981118-M93 Tequisquiapan No. 102 Parque Industrial Queretaro C.P. 76220 Queretaro, Mexico Tel. +52 442 1030-300 Fax +52 442 1030-301 http://www.sew-eurodrive.com.mx scmexico@seweurodrive.com.mx Morocco Casablanca Afit 5, rue Emir Abdelkader MA 20300 Casablanca Tel. +212 22618372 Fax +212 22618351 ali.alami@premium.net.ma Netherlands Rotterdam VECTOR Aandrijftechniek B.V. Industrieweg 175 NL-3044 AS Rotterdam Postbus 10085 NL-3004 AB Rotterdam Tel. +31 10 4463-700 Fax +31 10 4155-552 http://www.vector.nu info@vector.nu New Zealand Auckland SEW-EURODRIVE NEW ZEALAND LTD. P.O. Box 58-428 82 Greenmount drive East Tamaki Auckland Tel. +64 9 2745627 Fax +64 9 2740165 http://www.sew-eurodrive.co.nz sales@sew-eurodrive.co.nz Christchurch SEW-EURODRIVE NEW ZEALAND LTD. 10 Settlers Crescent, Ferrymead Christchurch Tel. +64 3 384-6251 Fax +64 3 384-6455 sales@sew-eurodrive.co.nz Norway Moss SEW-EURODRIVE A/S Solgaard skog 71 N-1599 Moss Tel. +47 69 241-020 Fax +47 69 241-040 http://www.sew-eurodrive.no sew@sew-eurodrive.no Peru Lima SEW DEL PERU MOTORES REDUCTORES S.A.C. Los Calderos, 120-124 Urbanizacion Industrial Vulcano, ATE, Lima Tel. +51 1 3495280 Fax +51 1 3493002 http://www.sew-eurodrive.com.pe sewperu@sew-eurodrive.com.pe 66
Address List Poland Lodz SEW-EURODRIVE Polska Sp.z.o.o. ul. Techniczna 5 PL-92-518 Łódź Tel. +48 42 67710-90 Fax +48 42 67710-99 http://www.sew-eurodrive.pl sew@sew-eurodrive.pl Portugal Coimbra SEW-EURODRIVE, LDA. Apartado 15 P-3050-901 Mealhada Tel. +351 231 20 9670 Fax +351 231 20 3685 http://www.sew-eurodrive.pt infosew@sew-eurodrive.pt Romania Bucureşti Sialco Trading SRL str. Madrid nr.4 011785 Bucuresti Tel. +40 21 230-1328 Fax +40 21 230-7170 sialco@sialco.ro Russia St. Petersburg ZAO SEW-EURODRIVE P.O. Box 36 195220 St. Petersburg Russia Tel. +7 812 3332522 +7 812 5357142 Fax +7 812 3332523 http://www.sew-eurodrive.ru sew@sew-eurodrive.ru Senegal Dakar SENEMECA Mécanique Générale Km 8, Route de Rufisque B.P. 3251, Dakar Serbia and Montenegro Beograd DIPAR d.o.o. Ustanicka 128a PC Košum, IV floor SCG-11000 Beograd Tel. +221 849 47-70 Fax +221 849 47-71 senemeca@sentoo.sn Tel. +381 11 347 3244 / +381 11 288 0393 Fax +381 11 347 1337 dipar@yubc.net Singapore Singapore SEW-EURODRIVE PTE. LTD. No 9, Tuas Drive 2 Jurong Industrial Estate Singapore 638644 Tel. +65 68621701 Fax +65 68612827 http://www.sew-eurodrive.com.sg sewsingapore@sew-eurodrive.com Slovakia Bratislava SEW-Eurodrive SK s.r.o. Rybničná 40 SK-83554 Bratislava Žilina SEW-Eurodrive SK s.r.o. ul. Vojtecha Spanyola 33 SK-010 01 Zilina Banská Bystrica SEW-Eurodrive SK s.r.o. Rudlovská cesta 85 SK-97411 Banská Bystrica Tel. +421 2 49595201 Fax +421 2 49595200 sew@sew-eurodrive.sk Tel. +421 41 700 2513 Fax +421 41 700 2514 sew@sew-eurodrive.sk Tel. +421 48 414 6564 Fax +421 48 414 6566 sew@sew-eurodrive.sk Slovenia Celje Pakman - Pogonska Tehnika d.o.o. UI. XIV. divizije 14 SLO - 3000 Celje Tel. +386 3 490 83-20 Fax +386 3 490 83-21 pakman@siol.net South Africa Johannesburg SEW-EURODRIVE (PROPRIETARY) LIMITED Eurodrive House Cnr. Adcock Ingram and Aerodrome Roads Aeroton Ext. 2 Johannesburg 2013 P.O.Box 90004 Bertsham 2013 Tel. +27 11 248-7000 Fax +27 11 494-3104 http://www.sew.co.za dross@sew.co.za 67
Address List South Africa Capetown SEW-EURODRIVE (PROPRIETARY) LIMITED Rainbow Park Cnr. Racecourse & Omuramba Road Montague Gardens Cape Town P.O.Box 36556 Chempet 7442 Cape Town Tel. +27 21 552-9820 Fax +27 21 552-9830 Telex 576 062 dswanepoel@sew.co.za Durban SEW-EURODRIVE (PROPRIETARY) LIMITED 2 Monaceo Place Pinetown Durban P.O. Box 10433, Ashwood 3605 Tel. +27 31 700-3451 Fax +27 31 700-3847 dtait@sew.co.za Spain Bilbao SEW-EURODRIVE ESPAÑA, S.L. Parque Tecnológico, Edificio, 302 E-48170 Zamudio (Vizcaya) Tel. +34 94 43184-70 Fax +34 94 43184-71 http://www.sew-eurodrive.es sew.spain@sew-eurodrive.es Sweden Jönköping SEW-EURODRIVE AB Gnejsvägen 6-8 S-55303 Jönköping Box 3100 S-55003 Jönköping Tel. +46 36 3442-00 Fax +46 36 3442-80 http://www.sew-eurodrive.se info@sew-eurodrive.se Switzerland Basel Alfred lmhof A.G. Jurastrasse 10 CH-4142 Münchenstein bei Basel Tel. +41 61 417 1717 Fax +41 61 417 1700 http://www.imhof-sew.ch info@imhof-sew.ch Thailand Chonburi SEW-EURODRIVE (Thailand) Ltd. 700/456, Moo.7, Donhuaroh Muang Chonburi 20000 Tel. +66 38 454281 Fax +66 38 454288 sewthailand@sew-eurodrive.com Tunisia Tunis T. M.S. Technic Marketing 5, Rue El Houdaibiah 1000 Tunis Tel. +216 71 4340-64 + 71 4320-29 Fax +216 71 4329-76 tms@tms.com.tn Turkey Istanbul SEW-EURODRIVE Hareket Sistemleri San. ve Tic. Ltd. Sti. Bagdat Cad. Koruma Cikmazi No. 3 TR-34846 Maltepe ISTANBUL Tel. +90 216 4419163 / 164 3838014/15 Fax +90 216 3055867 http://www.sew-eurodrive.com.tr sew@sew-eurodrive.com.tr Ukraine Dnepropetrovsk SEW-EURODRIVE Str. Rabochaja 23-B, Office 409 49008 Dnepropetrovsk Kiev SEW-EURODRIVE GmbH S. Oleynika str. 21 02068 Kiev Tel. +380 56 370 3211 Fax +380 56 372 2078 http://www.sew-eurodrive.ua sew@sew-eurodrive.ua Tel. +380 44 503 95 77 Fax +380 44 503 95 78 kso@sew-eurodrive.ua USA Production Greenville SEW-EURODRIVE INC. 1295 Old Spartanburg Highway P.O. Box 518 Lyman, S.C. 29365 Tel. +1 864 439-7537 Fax +1 864 439-7830 Fax Manuf. +1 864 439-9948 Fax Ass. +1 864 439-0566 Telex 805 550 http://www.seweurodrive.com cslyman@seweurodrive.com 68
Address List USA San Francisco Philadelphia/PA Dayton SEW-EURODRIVE INC. 30599 San Antonio St. Hayward, California 94544-7101 SEW-EURODRIVE INC. Pureland Ind. Complex 2107 High Hill Road, P.O. Box 481 Bridgeport, New Jersey 08014 SEW-EURODRIVE INC. 2001 West Main Street Troy, Ohio 45373 Dallas SEW-EURODRIVE INC. 3950 Platinum Way Dallas, Texas 75237 Additional addresses for service in the USA provided on request! Tel. +1 510 487-3560 Fax +1 510 487-6381 cshayward@seweurodrive.com Tel. +1 856 467-2277 Fax +1 856 845-3179 csbridgeport@seweurodrive.com Tel. +1 937 335-0036 Fax +1 937 440-3799 cstroy@seweurodrive.com Tel. +1 214 330-4824 Fax +1 214 330-4724 csdallas@seweurodrive.com Venezuela Valencia SEW-EURODRIVE Venezuela S.A. Av. Norte Sur No. 3, Galpon 84-319 Zona Industrial Municipal Norte Valencia, Estado Carabobo Tel. +58 241 832-9804 Fax +58 241 838-6275 http://www.sew-eurodrive.com.ve sewventas@cantv.net sewfinanzas@cantv.net 69
SEW-EURODRIVE Driving the world
Gearmotors \ Industrial Gear Units \ Drive Electronics \ Drive Automation \ s How we re driving the world With people who think fast and develop the future with you. With a worldwide service network that is always close at hand. With drives and controls that automatically improve your productivity. With comprehensive knowledge in virtually every branch of industry today. With uncompromising quality that reduces the cost and complexity of daily operations. SEW-EURODRIVE Driving the world With a global presence that offers responsive and reliable solutions. Anywhere. With innovative technology that solves tomorrow s problems today. With online information and software updates, via the Internet, available around the clock. SEW-EURODRIVE GmbH & Co KG P.O. Box 3023 D-76642 Bruchsal / Germany Phone +49 7251 75-0 Fax +49 7251 75-1970 sew@sew-eurodrive.com www.sew-eurodrive.com