FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80



Similar documents
Boiler efficiency for community heating in SAP

M&V of Hot Water Boiler Plant. Boban Ratkovich, P. Eng, CEM, BESA, LEED AP President CES Engineering Ltd

ME Heat Transfer Laboratory. Experiment No. 7 ANALYSIS OF ENHANCED CONCENTRIC TUBE AND SHELL AND TUBE HEAT EXCHANGERS

ECOplus Solar Cylinder

Continuous flow direct water heating for potable hot water

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Session 2: Hot Water Supply

Temperature Calibration; Depths of Immersion

GAS HEATING IN COMMERCIAL PREMISES

Is an air source heat pump the right choice for my home? Important information and key things to consider before installing an air source heat pump

Electric Flow Boiler

Stove-boiler for solid fuels KW Directions for use and assembling

HEAVY DUTY STORAGE GAS

Heat. Investigating the function of the expansion valve of the heat pump. LD Physics Leaflets P Thermodynamic cycle Heat pump

Mixing Warm and Cold Water

Visage. Digital. Digital diverter. Installation guide. Visage Digital diverter installation instructions Page 1

STOVE-BOILER FOR SOLID FUELS Directions for use and assembling

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

How to calibrate an RTD or Platinum Resistance Thermometer (PRT)

Making heating systems efficient and cost-effective: boilers, heating controls & more

COMMERCIAL REPORT / STOCK CONDITION SURVEY. Sydenham Hill Estate Sydenham Hill London SE 23

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

Daikin Altherma hybrid heat pump. The natural combination

IFC 070 Technical Datasheet

Measurement of Domestic Hot Water Consumption in Dwellings

Case Studies: Infrared Heating in Industrial Applications

Condensing Boilers. High Efficiency. Proven Reliability, American-Made Home Heating Comfort. ANYWHERE UNMATCHED

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

DETERMINATION OF THE HEAT STORAGE CAPACITY OF PCM AND PCM-OBJECTS AS A FUNCTION OF TEMPERATURE. E. Günther, S. Hiebler, H. Mehling

OPTIONS. for. Replacing Boiler Plant. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

Sizing and Selection of Hot Water Generating Plant. Presentation by: Rob Larner & David Dutch

COUNCIL DIRECTIVE 92/42/EEC of 21 May 1992 on efficiency requirements for new hot-water boilers fired with liquid or gaseous fuels

Energy Efficiency E-module - Guidance. Efficient Operation of Low Temperature Hot Water Boilers in the Public Sector

Hot water supply, distribution and use

1 DESCRIPTION OF THE APPLIANCE

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

Energy Saving Fact Sheet Boilers

building engineering services association specification for: Domestic Heating

AMTRON E-30 Compact heat and cooling meter

EcoDesign & Labelling Directive (ErP)

Performance ratio. Contents. Quality factor for the PV plant

Cooking at the Speed of light!

Performance of the Boiler and To Improving the Boiler Efficiency Using Cfd Modeling

Evaluation copy. Build a Temperature Sensor. Project PROJECT DESIGN REQUIREMENTS

Printing and Publishing Energy Savings Guide

Propane-Fueled Microturbine: Case Study

Non-Domestic Building Services Compliance Guide

Common Boiler Excess Air Trends and Strategies to Optimize Efficiency


For installation guide see reverse of book

RESPONSE TIME INDEX OF SPRINKLERS

Daikin Altherma. hybrid heat pump. The natural combination

Safety Storage Cabinets

Series GM. Peerless Boilers. Residential/Commercial Gas Boilers

PSAC/SAIT Well Testing Training Program Learning Outcomes/Objectives Level B

WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS

SIRIUX. SINGLE AND DOUBLE HIGH EFFICIENCY CIRCULATORS Heating Air-conditioning OPERATING LIMITS APPLICATIONS. 28 m 3 /h* Heads up to: Flows up to:

What is Energy? Session 1

Best Practice Guide BPGCS007

T0118 T2118 T3118. Instruction Manual

ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user

IDEAL AND NON-IDEAL GASES

American Society of Agricultural and Biological Engineers

Operating instructions

NIBE INSTALLER GUIDE TO ErP, SIMPLE AS 1 2 3

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2014/07) en

Absorption. LG HVAC Solution.

Ampere's Law. Introduction. times the current enclosed in that loop: Ampere's Law states that the line integral of B and dl over a closed path is 0

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

BIOPOWER 5 CEX. 1 Wärtsilä 10 January 2012 Presentation name / Author

Solid Oxide Fuel Cell Gas Turbine Hybrid Power Plant. M. Henke, C. Willich, M. Steilen, J. Kallo, K. A. Friedrich

Module 5: Combustion Technology. Lecture 34: Calculation of calorific value of fuels

Floor Heating Warehouse.co.uk

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

T U R B I N E G A S M E T E R

High-efficient gas boiler CompactGas

The natural ombination

EVALUATION OF GEOTHERMAL ENERGY AS HEAT SOURCE OF DISTRICT HEATING SYSTEMS IN TIANJIN, CHINA

User's Instructions. Alpha HE CB25/33 and HE SY25

جامعة البلقاء التطبيقية

Water Volume Calculation in Hydronic Heating & Cooling Systems

GUIDE TO AIR SOURCE HEAT PUMPS. Consumer, Specifier, Installer and Merchant guide to Air to water heat pump technology

OZW30. Central Unit SYNERGYR

BIOHOUSING Seminar Success stories of biomass heating in small scale

Technical Specification. Generating Set with Waukesha engine burning natural gas

Automatic Fire Sprinkler Submittal Requirements

High efficiency, cast-iron gas boiler

PART 11: START-UP PROCEDURES FOR THE INSTALLER

BoilerMate SP. benchmark. user instructions A - C L A S S

Plumbing, Heating & Gas Industry Course Information

THERMOSTATIC ACTUATORS WITH LIQUID-FILLED SENSITIVE ELEMENTS AND TEMPERATURE LOCKING

PRO-CLEAN. Technical Description. Specifications. Space-saving design with minimum heat loss (melamine resin insulation)

AVL FUEL MASS FLOW METER & FUEL TEMPERATURE CONTROL

Heating Controller. Building Technologies HVAC Products

Temperature Scales. The metric system that we are now using includes a unit that is specific for the representation of measured temperatures.

Oil, Gas and Dual Fuel Burners

Performance Evaluation of a Heat Pump System for Simultaneous Heating and Cooling

Centrifugal Fans and Pumps are sized to meet the maximum

Drayton Digistat +2RF/+3RF

Transcription:

FIELD TESTS OF FUEL EFFICIENCY MAGNETS J A CRABB JULY 1997 SWEEG REPORT 80

List of symbols T f average temperature at the flow header, C T r average temperature at the return header, C f average water flow rate through the boiler, l s -1 Q g total calorific value of gas used over a period t of intermittent firing, MJ q g average rate of gas consumption (MJs -1 ) over a period t of intermittent firing Q max total calorific value of gas used over a period t of continuous firing, MJ q max average rate of gas consumption (MJs -1 ) over a period t of continuous firing Q h total useful heat output over a period t, MJ L average boiler load factor; total firing time/ total plant running time or Qg/Qmax q s rate of total boiler losses during stand-by as ratio of q max e b full-load boiler efficiency e u seasonal boiler efficiency

Background A previous paper (1 ) reported measurements made on a range of devices purporting to reduce boiler fuel consumption. The majority of these were electronic devices which exercised control over boiler switching and replaced normal thermostatic boiler control. Amongst the devices tested, however, was a system comprising permanent magnets which were attached to the fuel line. The magnets were claimed to improve boiler efficiency by "ionising" the fuel and improving combustion efficiency. Field experiments were conducted to test the effect of all these devices on boiler efficiency. This was felt to be the key issue since, if the devices reduced fuel consumption only at the expense of heat input to the building, this effect could be achieved by simple manipulation of existing controls. If the devices offered any added value, they needed to demonstrate an ability to reduce fuel consumption whilst maintaining heat output. With the exception of one of the electronic devices, which achieved some improvement in boiler efficiency by running the system at very low temperatures, none of the devices had any discernible effect on efficiency. Following the publication of these results, representations were received from the manufacturer and distributor of the magnets tested. It was claimed that this device had not been subject to a fair test on two counts. Firstly it was claimed that two magnets rather than one should have been used on the size of fuel pipe at that site. Secondly it was asserted that insufficient time (the experiment was conducted over two weeks) had been allowed for the effect of the magnets to be seen. A considerable "settling in" period was normally required. Following negotiations it was agreed to re-test the magnets with the cooperation and assistance of the distributor and the manufacturer. A site was identified (described below) and visited by the distributor and the managing director of the manufacturing company. The boiler installation was inspected and approved as were the details of the experimental procedure. The main feature insisted upon was that the magnets would be allowed to operate for a period of four weeks following a period during which measurements would be made to establish the normal boiler characteristics. It was agreed that the magnets would be fitted by the distributor. The distributor was invited to attend all site visits by the experimenters and offered access to all data collected. Experiment The experiment was conducted at a light industrial building on an industrial estate in Cornwall. The chosen boiler was a wall mounted Gloworm Spacesaver 40BR MkII gas-fired unit rated at 11.72 kw output and 15.03 kw input. It provided heating to adjoining office space under simple time-clock control. Hot water from the boiler circulated through a number of steel radiators fitted with thermostatic radiator valves. Gas was supplied to the boiler via a 15mm copper pipe. The aim of the experiment was to measure the heat output to the circulating water and the simultaneous gas consumption. Heat output was determined by measuring the water flow and return temperatures, T f and T r, along with the rate of water flow, f.

Gas consumption was measured directly using a suitable dedicated gas meter on the boiler supply line. When averaged over a suitable period, these data allow the mean efficiency of the boiler to be deduced. Control over the operation of the system was exercised by the boiler thermostat and the thermostatic radiator valves as normal. The load on the system would be very variable and the efficiency figures obtained would therefore relate to boiler operation under part load. It is shown in the next section how the effects of variation in load factor can be largely eliminated and boiler full load efficiency, e b, deduced from these measurements. Instrumentation installed for the purpose of these measurements comprised a Kent MK20M hot water meter to measure water flow from the boiler, platinum resistance thermometers to measure flow, return, flue gas and ambient external air temperature and a UGI gas meter to measure fuel supply to the boiler. A schematic of the experimental installation is shown in figure 1. Figure 1 Schematic of the system monitored. Points labelled T indicate the location of Platinum resistance elements used to measure flow and return temperatures The gas and water meters were fitted with pulse heads to allow the flows to be monitored automatically. Daily average calorific values of the gas supplied were obtained from Transco and the information used to convert gas volumes to heat energy content. The platinum resistance elements measuring boiler flow and return temperatures were tightly attached to the pipework with nylon cable ties. A heat conducting compound

was used to ensure good thermal contact and an insulating sleeve of 25mm neoprene was wrapped around the sensors to insulate them from the effect of ambient air temperature. A further ceramic coated platinum resistance element was inserted into the outlet of the balanced flue to measure flue gas temperature. External air temperature was measured with a platinum resistance thermometer mounted on an external north facing wall. The resistance thermometers and the outputs from the two flow meters were connected to a Datataker 100L electronic data logger. This unit provides automatic conversion of resistance thermometer voltages to degrees centigrade. The logger was programmed to record the averages of repeated 20 second samples of temperature every 15 minutes. Pulses from the flow meters were totalled over the same interval. The complete temperature measurement system, including the logger, junction box and all cabling exactly as installed, was calibrated by immersing the sensors simultaneously in a water bath at various temperatures. Regression fits to the data obtained from this calibration were used to correct the measured values of boiler flow and return temperature for differences between the two sensors employed. Calibration data are shown in Figure A1 in the appendix. Measurement history Measurements originally commenced on 10th February 1997 but difficulty was experienced with the hot water meter which was not suitable for use at the temperatures experienced. This was replaced with the type indicated above and measurements recommenced on 25th February 1997. Data were collected on the performance of the boilers prior to the installation of the magnets. The magnets were installed by the distributor on 13th March 1997. Data were then collected for a period of twenty nine days with the magnets in place. On 10th April 1997 the magnets were removed and logging continued for a further thirty three days without the magnets. The experiment terminated on the 13th May 1997. Theory Boiler efficiency calculated as a simple ratio of heat output to gas input over a given period includes the effect of periods of non-firing as the boiler cycles off under thermostatic control. During these periods heat is lost from the boiler fabric which has to be made up during the next firing cycle. Thus efficiency calculated in this way, socalled seasonal efficiency, varies according to the load on the boiler and the consequent variability in the length of the non-firing periods. During the course of these experiments, which were conducted towards the end of the heating season, a steady reduction in seasonal efficiency was recorded. Theory developed elsewhere ( 1), and similarly in (2-6), relates seasonal efficiency to full load efficiency and load factor according to: e = e - ( 1 L - 1) q...1 u b s Thus, for the combustion over a period t of a quantity of gas with calorific value Qg, the predicted heat output is

Qh = eu Qg... 2 substituting for e u yields, Qh = eqg b - ( 1L - 1) qs Qg...3 and since L = Q Q g max Q = Q ( e + q ) Qmax qs...4 h g b s It is also instructive to substitute Q equation 3, giving Qh = Qg eb - qs qmax ( 1- L) t...5 g = L t q for the last occurrence of Q g in From which it may be seen that the useful heat obtained from a boiler operating at part load is the calorific value of the gas consumed multiplied by the boiler full-load efficiency, less the calorific value of the gas consumed in meeting stand-by losses during periods of non-firing. The reduction in seasonal efficiency at low load factor, L, clearly arises from the increased proportion of total gas consumption accounted for by that required to meet standing losses at low total heat output. max Results Figures 2 and 3 show heat produced, Q h, and gas consumed, Q g, corresponding to the boiler operating without and with the magnets respectively. The quantities plotted are the daily averages of the heat and gas energy values over all fifteen minute intervals for which the boiler flow temperature, T f, exceeded 40 C. This selection was made specifically to exclude extended periods when the boilers were not operating, e.g. at night and over weekends. This also ensured that results were only analysed within the calibrated range of the sensors monitoring boiler flow and return temperatures. Figure 4 shows the two data sets plotted on the same graph. Equation 3 allows the full load efficiency, e b, to be deduced from daily average measurements of Q h and Q g. Load factor was deduced by comparing the recorded daily gas consumption with that which would have been consumed had the boiler been firing continuously at the manufacturer s declared rated input. The boiler standing loss rate, q s, was ascribed a value of 0.05 of full rated input in line with data reported in the literature (1,2 and 7). Figure 5 shows the average deduced values of full load efficiency for each of the four measurement periods. Experiments 1 and 4 correspond to the periods when the magnets were not fitted, and 2 and 3 to those when they were. The standard deviations on each mean value are indicated in the form of error bars. The first impression is that the magnets have made no difference to boiler efficiency and this impression is confirmed by appropriate statistical analysis.

The mean value of boiler full load efficiency for all data without the magnets is: 0.675 with a standard deviation of 0.0246. For the data corresponding to the magnets fitted the mean value is 0.691 with a standard deviation of 0.0281. To assess the significance of these results we note that the standard deviation of the difference between two quantities a and b with standard deviations s a and s b is s = ( 2 ab s + 2 - a s ) b and the value of the Student's t = ( a- b) s ab - We take as the null hypothesis that the application of the magnets has not improved the full load efficiency of the boiler, i.e.; h 0 : (e b magnets - e b nomagnets) =0, and the alternative, h 1 : (e b magnets > e b nomagnets) Calculation the value of t gives t = ( 0. 691-0. 675) ( 0. 0281 2 + 0. 0246 2 ) t = 0.43 Reference to standard statistical tables reveals that the value of t required for rejection of the no effect hypotheses would be 2.08 at the 95% confidence level. Thus the value of t obtained does not allow rejection of the null hypothesis. The alternative hypothesis, that the magnets have improved full-load efficiency, is therefore rejected. Discussion In these experiments the magnets failed to show any improvement in boiler efficiency within the limits of probability stated above. This confirms the results obtained earlier (1). Since these magnets were installed by the distributor and since the design of the experiment conformed to the requirements of the distributor and the manufacturer it may be concluded that they represent a fair test. The distributor attended site on two occasions during the experiment. No representations were made concerning any experimental deficiencies and no comments have been received since communicating the results of the tests directly to the distributor. It may be concluded that this device did not exercise any beneficial effect on the operation of a gas fired boiler.

3.5 3.0 daily average heat output, MJ 2.5 2.0 1.5 1.0 0.5 0.0 0 1 2 3 4 5 6 daily average gas input, MJ Figure 2 Daily average heat output vs. gas input (for all fifteen minute periods when T f exceeded 40 C) for the boiler operating without magnets 3.0 2.5 average heat output, MJ 2.0 1.5 1.0 0.5 0.0 0 1 2 3 4 5 6 average gas input, MJ Figure 3 Daily average heat output vs. gas input (for all fifteen minute periods when T f exceeded 40 C) for the boiler operating with magnets.

3.0 2.5 average heat output, MJ 2.0 1.5 1.0 0.5 0.0 0.0 0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5 5.0 5.5 6.0 average gas input, MJ Figure 4 Combined plot of figures 2 and 3. Data relating to boiler running with magnets are shown as open circles. 1.0 Experiments 1 and 4 = no magnets Experiments 2 and 3 = magnets fitted Boiler full-load efficiency, e b 0.8 0.6 0.4 0.2 0.0 0 1 2 3 4 Experiment number Figure 5 Mean values of deduced boiler full-load efficiency, standard deviations show as vertical bars.

References 1 Crabb J A Field Testing of Boiler Economy Devices Building Serv. Eng. Res. Technol. 17(2) 55-64 (1996) 2 Peat B J, The Control of Multi-boiler Installations in Schools. BSRIA Report 1 on Contract 3239. March 1982. 3 Holmes M, Part Load Efficiency of Gas and Oil-fired Boilers. BSRIA Technical Note 1/76. 4 Don W A, The Efficiency of Domestic Oil-burning Boilers at Reduced Loading. Energy World. Jan 1976.pp 6-10 5 Don W A, Factors Affecting the Part-load Efficiency of Boilers. Energy World. Oct 1977. pp 2-5 6 Meijnen A J, Development of a Computer Model for the Selection of Boiler Plants from the Viewpoint of a Low Energy Consumption. Report of the Commission of European Communities. EUR 9917 EN. 1985 7 Osborn P D, Handbook of Energy Data and Calculations. Butterworths 1985 pp 184-192

Appendix 100 Sensor calibration sensor 1 = sensor 2 *1.009-0.435 90 temperature, sensor 1 80 70 60 50 40 30 30 40 50 60 70 80 90 temperature, sensor 2 Figure A1 Calibration curve derived from water bath tests on the two sensors used to monitor boiler flow and return temperatures.