A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks



Similar documents
7. Reactive energy compensation

The design and performance of Static Var Compensators for particle accelerators

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Phase Balancing of Unbalanced Distribution Network through Hybrid Greedy-Fuzzy Algorithm

EMTP STUDIES PERFORMED TO INSERT LONG AC CABLES IN THE FRENCH GRID

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

OPTIMAL DISPATCH OF POWER GENERATION SOFTWARE PACKAGE USING MATLAB

Optimal Feeder Reconfiguration with Distributed Generation in Three-Phase Distribution System by Fuzzy Multiobjective and Tabu Search

Modeling Simulation Technology Research for Distribution Network Planning *

Voltage regulation in distribution systems - Tap changer and Wind Power

Reduction of Power Losses Using Phase Load Balancing Method in Power Networks

Voltage Stability Improvement using Static Var Compensator in Power Systems

Power Factor The Basics

SURVEY OF HARMONIC DISTORTION IN LV AND MV NETWORKS: RESULTS AND CORRECTIVE STRATEGIES

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

2012 San Francisco Colloquium

SCADA Controlled Multi-Step Automatic Controlled Capacitor Banks & Filter Banks

Three phase circuits

Pierre Archambault, PEng. VP Engineering Power Survey International Inc. 16 September 2009

IMPROVED NETWORK PARAMETER ERROR IDENTIFICATION USING MULTIPLE MEASUREMENT SCANS

2Azerbaijan Shahid Madani University. This paper is extracted from the M.Sc. Thesis

Power Quality Analysis and Evaluation at Water Pumping Station Supplied by Medium Voltage

Simulation of Cable Overloading Problem on a University Distribution System

Kinetic energy recovery on railway systems with feedback to the grid

Impact of electric vehicles on the IEEE 34 node distribution infrastructure

NEURO-FUZZY BASED POWER QUALITY IMPROVEMENTS IN A THREE PHASE FOUR WIRE DISTRIBUTION SYSTEM USING DSTATCOM

VOLTAGE CONTROL IN DISTRIBUTION SYSTEMS AS A LIMITATION OF THE HOSTING CAPACITY FOR DISTRIBUTED ENERGY RESOURCES

COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS

Analysis of the Effect of Tap Changing Transformer on Performance of SVC

Typical Data Requirements Data Required for Power System Evaluation

Measurement, Modeling and Simulation of Capacitor Bank Switching Transients

Radial Distribution Test Feeders

Contouring and Advanced Visualization

HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM

Lecture Notes ELE A6

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Conservation Voltage Reduction (CVR)

C4-106 POWER QUALITY MONITORING OF ELECTRIFIED RAILWAY SYSTEM IN MALAYSIA LEONG WHYE HIN* MOHD HALMI MAD DIAH AMINUDDIN MUSA TNB TNB.

Impact of Distributed Generation on Voltage Profile in Deregulated Distribution System

Optimal Branch Exchange for Feeder Reconfiguration in Distribution Networks

Application of GA for Optimal Location of FACTS Devices for Steady State Voltage Stability Enhancement of Power System

Chapter L Power factor correction and harmonic filtering

Modeling of electric railway vehicle for harmonic analysis of traction power-supply system using spline interpolation in frequency domain

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

Phase Balancing of Distribution Systems Using a Heuristic Search Approach

Chapter 24. Three-Phase Voltage Generation

Knowing the FACTS. FACTS that enhance power quality in rail feeder systems

A COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM

Dynamic Security Assessment in the Future Grid. Vijay Vittal Ira A. Fulton Chair Professor Arizona State University

Control of Distributed Generation Units in Stand-Alone Industrial Networks

Calculation of Voltage Sag Indices for Distribution Networks

Chapter 9 Balanced Faults

Chapter 1. Network Structures

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

(2) Words and expressions used and not defined in these regulations but defined in the Act shall have the meaning assigned to them in the Act.

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

11. MEASUREMENT OF POWER CONSUMPTION OF THE NONBALANCED THREE-PHASE LOAD

FACT SHEET. BSES, Delhi - Distribution Network. Power Systems Consultancy from ABB

SOFTWARE FOR THE OPTIMAL ALLOCATION OF EV CHARGERS INTO THE POWER DISTRIBUTION GRID

ENGINEERING REPORT. XYZ Corporation 100 Anyplace Drive Chicago, Illinois 60613

System configuration of v-f control with solar PV generator operating at MPPT with a battery storage System

Interfacing Renewable Energy Sources to the AC Grid by a CMLI with Voltage Regulation under Low THD

Control Strategy for Three Phase Shunt Active Power Filter with Minimum Current Measurements

Neutral to Earth Voltage Reduction Methods in Three-Phase Four Wire Distribution Systems

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Data center power dynamics within the settings of regional power grid

LV4MV: A CONCEPT FOR OPTIMAL POWER FLOW MANAGEMENT IN DISTRIBUTION GRIDS, USING DER FLEXIBILITY

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Power Quality Standards for Electric Service

A Reactive Tabu Search for Service Restoration in Electric Power Distribution Systems

Engineering innovation

Load Tap Changing Control

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

Product Data Bulletin

STATCOM Application at VELCO Essex Substation

Experimental Verification of Advanced Voltage Control for Penetration of PV in Distribution System with IT Sectionalizing Switches

Distribution Inside Large Buildings

General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

Simulation and Analysis of Parameter Identification Techniques for Induction Motor Drive

STATEMENT OF CHARGING METHODOLOGY FOR USE OF ELECTRICITY NORTH WEST LIMITED S ELECTRICITY DISTRIBUTION NETWORK

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Scholars Research Library

Improvement of Power Factor for Industrial Plant with Automatic Capacitor Bank

How To Improve Power Quality

6545(Print), ISSN (Online) Volume 4, Issue 2, March April (2013), IAEME & TECHNOLOGY (IJEET)

Bill is the author of 15 papers and lectures on transmission lines and other power system topics.

F.C. Chan General Manager, CLP Engineering Ltd., Hong Kong SAR, China

Modeling and Analysis of DC Link Bus Capacitor and Inductor Heating Effect on AC Drives (Part I)

Study to Determine the Limit of Integrating Intermittent Renewable (wind and solar) Resources onto Pakistan's National Grid

On-site Measurement of Load and No-load Losses of GSU Transformer

A Changing Map. Four Decades of Service Restoration at Alabama Power. By G. Larry Clark

Transcription:

A Fuzzy Based Solution for Improving Power Quality in Electric Railway Networks Mohammad Ali Sandidzadeh School of Railway Engineering, Iran University of Science & Technology, Tehran, Iran Tel: 98-21-7749-1030 E-mail: sandidzadeh@iust.ac.ir Saleh Akbari School of Railway Engineering, Iran University of Science & Technology, Tehran, Iran E-mail: Sakbari118@gmail.com Received: October 13, 2011 Accepted: October 19, 2011 Published: Feburary 1, 2012 doi:10.5539/mas.v6n2p22 URL: http://dx.doi.org/10.5539/mas.v6n2p22 Abstract There are many fundamental differences between electric traction networks and other industrial supply networks in terms of dynamic behavior and static characteristics. For example, the time variation of a load causes voltage variations in a supply network, which results in variations of power flow in the supply network. Today, reactive power compensators are the most practical solutions for keeping voltage levels in normal boundaries. In this paper, with the aim of fuzzy logic, a method for compensating reactive power losses in electrical traction networks is proposed. The proposed method has many advantages such as decreasing the reactive power compensation costs, determining the optimum switching step of capacitor banks and deducing the losses in electric traction networks. Keywords: Reactive Power, Electric Traction Networks, Railway Electrification, Fuzzy Logic 1. Introduction Reactive power creates numerous problems in electric railway supply networks. Because of the particular characteristics of electric traction loads, the problems have higher intensity in railway supply networks than other types of electric supply networks. Reactive power can be compensated by implementation of active or static methods. Nowadays a common method, in most electric substations, is to use shunt capacitors (Chin H. C., & Lin Wh. M., 1994; Baghzouz Y., & Ertem S., 1995). The advantages and disadvantages of this method are explained in Table 1. Allocation of these shunt capacitors in the network shall be according to the power network topology. Electric railway networks has individual characteristic such as time variant and location variant trains' power demand. So, this paper proposed improving power quality based on optimization of capacitor allocation in electric railway power supply network. In next sections, this solution is expressed. 2. Calculation of the Capacitor Power for Power Factor Correction In three phase circuits, the power factor correction capacitor is installed as shown in Figure 1. The capacitor power can be calculated from equation (1) (Chin Hong-Chan, & Lin Whei-min, 1996). Q C o C P tan tan (1) L In Figure1, phases a and b are the supplying overhead lines in both sides and C 1 and C 2 are the shunt capacitors. In a traction substation, the power factor is obtained from WP Cos 2 2 (2) WP WQ Where W P is the measured active power (kwh) and W Q is the measured reactive power (kvarh) (Baghzouz Y., & Ertem S., 1990). In the electric railway supply circuit, by considering the circuit, the capacitor power can be calculated from 22 ISSN 1913-1844 E-ISSN 1913-1852

1 QC = PL (tano tanc ) (3) 1 PO Where P o is the circuit no-load probability. Generally, implantation of capacitors in three phases (between the lag, lead or no-load phases) is not necessary. Capacitors are usually installed in circuits in the following ways (Shirmohamadi D., et al., 1988): I. If I lead >> I lagging capacitor in lag and lead phases II. If I lead << I lagging capacitor in no-load and lag phases III. If I lead = I lagging capacitor in the lag phase In case II, it is also possible to install the capacitor in the lead phases; however, this would be harmful to the network power factor. 3. Cost Equation After calculating the loss and considering the required capacitor for reactive power compensations, the cost value (Chin Hong-Chan, & Lin Whei-min, 1994) can be acquired from k f = KpPLoss KjQj (4) j1 where K P is the cost of the reactive losses, P loss is the total losses of the overhead network in each step of capacitor allocation, J (=1,2,,K) is the selected bus for capacitor installation, Kj is the minimum cost of possible circumstance coefficients plus the installation and maintenance, and Q j is the total power of the existing capacitors. 4. Problems Constraints Each optimization problem usually includes constraints. The operational constraint is the voltage amplitude in traction substations, which must be kept in the permitted limits of v min vi v max (5) where V i is the voltage of substation i, and V max and V min are the maximum and minimum permitted voltages, respectively. 5. Determining the Required Capacitor Power via Fuzzy Logic Various capacitor allocation methods are implemented for minimization of the reactive power losses. One of the implemented methods is based on Fuzzy logic that can assign sensitive points for capacitor installation. A Fuzzy-logic based solution benefits from high accuracy, response rate and μp (Chin Hong-Chan, & Lin Whei-min, 1996). In this research, the active power losses are used as the static input data to the fuzzy sensitive system of voltage in the electric train location (or bus). It should be noted that the minimum membership functions of the reactive power and bus voltage sensitiveness have assigned the required capacitor power in each operation period. Thus any increase in the losses results in an increase in the value of the membership function. Also, any decrease in the losses results in a decrease in the value of the membership function. One of the useful equations for demonstration of the function is where w is the weight coefficient obtained from wp ( Li) p( Loss (6) i) e P w P( Li) P t (7) where P(L i ) is the active power losses in the train to the substation circuit, P t is the total active power of other trains and Ρ Loss is the sum of the active power losses. In order to find a solution for the bus voltage sensitiveness problem, in case of large voltage deviations, a low membership function is taken into account. Thus, the relative membership function can be expressed as Published by Canadian Center of Science and Education 23

2 v( i) 1 w v( i) e v max v min (8) where v(i) is the voltage of bus i, V max is the maximum voltage limit, V min is the minimum voltage limit and w is the weight coefficient acquired from equation 7. Generally for calculating the required capacitor power, both the bus voltage sensitiveness (as in Figure 2) and the active losses (as in Figure 3) factors should be considered. Therefore it becomes necessary to define a decision function that contains μs. For finding the candidate locations for capacitor installation, both the active losses and the voltage sensitiveness factor are vital. Thus, considering the mentioned factors, a comprehensive decision function can be defined as µ s (i)= min{µ v (i),µ p (i)} i=1, 2,,m (9) The minimum point of the membership function is selected as the candidate location for capacitor installation. The low value of μ s indicates that the point of the overhead network has a very high sensitiveness to voltage deviations and power losses. 6. Explanation of the Fuzzy-based Procedure Figure 4 explains the Flowchart of the Optimum Capacitor Allocation Procedure in the Electric Railway Overhead Network. The main steps of this procedure are (Ng H. N., et.al, 2000): i. Calculating the network load flow, determining voltages and losses of the buses, and calculating μ p and μ v. ii. Distinguishing the candidate point (i.e. bus M) by considering the minimum decision function. iii. Determining the capacitor power, which satisfies both the voltage and the cost constraints, after performing the capacitor installation steps in bus M and running the load flow. If any capacitor power value does not satisfy voltage constraints of a selected bus, the bus should be eliminated from the list of candidate buses. iv. After eliminating bus M from the decision function and setting the calculated capacitor on it, the load flow is run and a new decision function is formed without considering bus M. v. Distinguishing the new candidate bus from the new decision function, then jumping to step iii. vi. The flowchart should be taken into account until it satisfies the voltage constraints. Also decreasing the cost value in an instant step from proceeding is lower than the defined minimum value for all buses. One of the advantages of the demonstrated flowchart is that it considers the voltage constraints, while minimizing the active losses and therefore the corresponding cost function. In addition, the introduced procedure is capable of solving minimization of active losses problem (i.e. minimization of the cost function). The procedure can also determine the location and rate of the required capacitor for installation in the overhead network, provided that the bus voltages are in the permitted limits. 7. Simulation Results and Comparisons 7.1 The Required Information A radial supply feeder is considered and presented in Figure 5. The feeder has 9 load buses (an electric train per block), a nominal voltage of 25 kv and a rated power of 15 MVA. The loads and the feeder data of the assumed overhead network are shown in Tables 2 and 3. Other data presented are: V min =0.9 p.u., V max =1.1 p.u. and kp =168 $/kw. In Table 2, the maximum capacitor power should not exceed the total reactive power (i.e. 4186 VAR). Therefore, regarding the existing capacitor and the minimum cost conditions (including the maintenance, installation and purchase costs), the capacitor step value and the corresponding cost coefficients can be acquired from Table 4. The network load flow results before compensation via the presented procedure are shown in Table 5. It is clear from Table 6 that the costs and total losses in the presented procedure have more appropriate values than the referenced value in (Chin H. C., & Lin Wh. M., 1994). 24 ISSN 1913-1844 E-ISSN 1913-1852

8. Flowchart Implementation Results According to Table 7, the probable rates of the capacitors are obtained by considering the corresponding cost coefficients in every step of the calculations. The voltage magnitudes for each selected item are shown in Table 8. 9. Conclusion An appropriate method for determining the capacitors rates in each step, by considering the voltage magnitude constraints and the cost of losses, was proposed. In the proposed method, by setting the capacitor conditions in each period of operation and considering the absorbed power from each substation and the number of trains in each line, it became possible to ensure the improvement of the power quality index of the electric railway networks. In addition, the proposed Fuzzy-based solution had many advantages such as optimization of the compensation steps and reduction of the compensation costs. Acknowledgement The authors would like to thank Mr. H Zafari for his assistance to improve the contents of this paper. References Baghzouz, Y., Ertem, S. (1990). Shunt Capacitor Sizing for Radial Distribution Feeders with Disturbed Substation Voltages. IEEE Trans. on Power Delivery, 5(2), 650-657. http://dx.doi.org/10.1109/61.53067 Chin, H. C., Lin, W. M. (1994). Capacitor Placements for Distribution Systems with Fuzzy Algorithm. Theme frontiers of computer technology. TECON94, IEEE Region 10's, Ninth annual international conference, Proceedings of Aug., pp. 22-26. Ng, H. N., et al. (2000). Capacitor Allocation by Approximate Reasoning: Fuzzy Capacitor Placement. IEEE Trans. on Power Delivery, 15(1), 393-398. http://dx.doi.org/10.1109/61.847279 Ng, H. N., Salama, M. M. A., Chikhani, A. Y. (1996). Capacitor Placement in Distribution System Using Fuzzy Technique. IEEE electrical and computer conference, 2, 26-29. Shirmohamadi, D., et al. (1988). A Compensation-based Power Flow Method for Weakly Meshed Distribution and Transmission Networks. IEEE Trans. on Power Systems, 3(2), 753-762. http://dx.doi.org/10.1109/59.192932 Table 1. Advantages and disadvantages of compensating the reactive power via shunt capacitors Disadvantages -Insufficient life cycle -Instability during faulty conditions -Increased switching over voltages -Accretion in shunt resonance occurrence probability Advantages -Improvements of network utilization coefficient -Deduction of losses -Power supply quality improvement -Deduction of negative sequence component -Improvement of Total Harmonic Distortion (THD) factor -Simple installation Table 2. Load data of assumed overhead network Number of P (KW) Q (KVar) Bus 1 460 1840 2 340 980 3 446 1790 4 1840 1598 5 600 1610 6 110 780 7 60 1150 8 130 980 9 200 1640 Published by Canadian Center of Science and Education 25

Table 3. Feeder data of assumed overhead network Primary Bus Final Bus (i) (i+1) R(Ω) X(Ω) 0 1 0.1233 0.4127 1 2 0.014 0.6051 2 3 0.7463 1.205 3 4 0.6984 0.6084 4 5 1.9831 1.7276 5 6 1.905 0.7886 6 7 2.0552 1.164 7 8 4.7953 2.716 8 9 5.3434 3.0264 Table 4. Variable choices of capacitor rates and corresponding cost coefficients J Q K i ($/kvar) J Q K i ($/kvar) 1 150 0.5 15 2250 0.197 2 300 0.5 16 2400 0.17 3 450 0.253 17 2550 0.189 4 600 0.22 18 2700 0.187 5 750 0.276 19 2850 0.183 6 900 0.183 20 3000 0.18 7 1050 0.228 21 3150 0.195 8 1200 0.17 22 3300 0.174 9 1350 0.207 23 3450 0.188 10 1500 0.201 24 3600 0.17 11 1650 0.193 25 3750 0.183 12 1800 0.187 26 3900 0.182 13 1950 0.211 27 4050 0.179 14 2100 0.176 --- --- --- Table 5. Bus voltage results Voltage J Q (the defined method in this paper) 1 0.993 0.9929 2 0.987 0.9874 3 0.963 0.967 4 0.984 0.9482 5 0.917 0.9175 6 0.907 0.908 7 0.889 0.8892 8 0.859 0.8593 9 0.838 0.8382 26 ISSN 1913-1844 E-ISSN 1913-1852

Table 6. The results of comparing the presented procedure with reference value Reference (Chin H. C., 1994) Defined method in this paper 119,736 119007.4 707 701.66 9 5 4 9 8 5 4 3 Total losses($/kvar) Total losses(kw) Compensated buses 900 2500 2100 900 300 1800 450 2400 Q c (kvar) Table 7. Variable choices of capacitor rates and the corresponding cost coefficients J Q Kj($/kvar) 1 150 0.5 2 300 0.5 3 450 0.253 4 600 0.22 5 750 0.276 6 900 0.183 7 1050 0.228 8 1200 0.170 9 1350 0.207 Table 8. The voltages of the bus after capacitor placement Scenario Voltage 1 0.993 2 0.9874 3 0.967 4 0.948 5 0.917 6 0.908 7 0.889 8 0.859 9 0.834 Published by Canadian Center of Science and Education 27

I l a I ab b I r C 1 C 2 I C1 c Figure 1. Power factor correction in a three-phase circuit by using shunt capacitors I C2 Figure 2. Voltage sensitivity membership function(μv) Figure 3. Loss membership function(μp) 28 ISSN 1913-1844 E-ISSN 1913-1852

Figure 4. Flowchart of the optimum capacitor allocation procedure in the electric railway overhead network Figure 5. Single line diagram of radial feeder of the assumed overhead network Published by Canadian Center of Science and Education 29