Leading Techniques for Energy Savings in Colleges and Universities



Similar documents
Leading Techniques for Energy Savings in Commercial Office Buildings

Leading Techniques for Energy Savings in Commercial Office Buildings

Leading Techniques for Energy Savings in Healthcare Facilities

Leading Techniques for Energy Savings in Healthcare Facilities

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Using Time-of-Day Scheduling To Save Energy

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Commissioning - Construction Documents (Page 1 of 6)

Example Retrocommissioning Measure: Opening Throttled Discharge Valves


CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Sample - Existing Building Commissioning Plan

Bring the fresh in. Dedicated Outside Air Systems

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Lesson 36 Selection Of Air Conditioning Systems

HVAC Processes. Lecture 7

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Trinchero Family Estates Building: Operation User s Guide

Variable Air Volume - VAV

Rev. No. 0 January 5, 2009

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

HEATING, VENTILATION & AIR CONDITIONING

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Energy-Saving Systems For Small Buildings

Sample Company SECTION GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Subtropical Cities September Design for Energy Efficiency in Commercial Buildings in Queensland

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Meet the New Standard. in Building Management Solutions for Commercial Buildings

Building Energy Management: Using Data as a Tool

HVAC System Optimization

SAM HOUSTON STATE UNIVERSITY

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Case Study -Sandy Grove Middle School First Net Positive Energy P3 School In North Carolina

HVAC Systems: Overview

Tim Sisson - Trane HVAC OVERVIEW

Xcel Business Customers: Program and Rebate Summary

Enclosed Football Stadium Design History and Lessons Learned

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

Reducing the Impact of Energy Costs on Business

Energy Design Resources Commissioning Plan Outline Template

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

Building Management Systems

KNX for building and room automation simple and efficient

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

ENERGY AUDITS AND RETRO- COMMISSIONING Local Law 87

Statement of Work. 3.0 Details of Service Pre Start-up Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

TOWER RENEWAL CASE STUDY

FAQ' s. Frequently Asked Questions. A1 Control Units. Pge 1 of 7 PUMPKIN HOOK ROAD PO BOX OGD VAN HORNESVILLE NY USA

The Business Case Annual fuel cost savings of 26% worth more than 28,000 Annual fuel savings of 1.3million kwh Annual CO2 savings of over 245 tonnes

Impact of Control System Technologies on Industrial Energy Savings

Seven Steps to Maximizing Central Plant Efficiency

Greenhouse Gas Implications of HVAC Upgrades in Multi-Unit Residential Buildings

Printing and Publishing Energy Savings Guide

Fundamentals of HVAC Control Systems

Components HVAC General Standards HVAC Guidelines HVAC System Selection Life Cycle Cost Analysis

Ventilation Retrofit Opportunities for Packaged HVAC

Building Analytics Improve the efficiency, occupant comfort, and financial well-being of your building.

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

Smart Ideas for Your Business. Energy Saving Opportunities for Hospitals

CONTROL STRATEGIES FOR HVAC SYSTEMS

Datacenter Efficiency Program

SIMULATION OF RADIANT COOLING PERFORMANCE WITH

Heating & Cooling Efficiency

Building Energy Systems. - HVAC: Heating, Distribution -

Smart Energy Consumption and the Smart Grid

Designer. of control solutions NA O7.124A

1. Summary. electric grid, strengthen saving programs sponsored by utilities. The project

Affordable Building Automation System Enabled by the Internet of Things (IoT)

Continuous Energy Management at UC San Diego. Anna Levitt, P.E. Assistant Energy Manager June 13, 2013

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Ammonia Detection System Codes and Design Specifications

Methods for Effective Room Air Distribution. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

It s all open from here.

AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries

Heating / Ventilation / Air Conditioning Room Climate Control with ABB i-bus KNX

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

ENERGY CONSERVATION GUIDELINES

Reducing the Impact of Energy Costs on Business

CATALYST Frequently Asked Questions

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

More efficiency in schools with HVAC, lighting and security

The THERMOSTAT THE EVOLUTION OF CAPABILITIES INTO A PLATFORM FOR ENERGY MANAGEMENT

Overview. PG&E and Energy Efficiency. CA Energy Efficiency Regulatory & Policy Roadmap. Financing Options for Efficiency & Demand Response

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

Combining Cold Aisle Containment with Intelligent Control to Optimize Data Center Cooling Efficiency

Transcription:

Leading Techniques for Energy Savings in Colleges and Universities Learn how building automation products and services can reduce energy costs at colleges and universities. This paper outlines proven techniques, effective in achieving energy conservation results with an attractive return on investment. January 2007 / White Paper Make the most of your energy

Summary I. Executive Overview...3 II. Energy Facts at Colleges and Universities Today...4 Energy Conservation Contributes to both Operating Income and Higher Education...4 Adding Energy Meaning to the Term College Town...5 III. Unique Control Considerations of Colleges and Universities...6 Housing and the Campus Central Loop...6 Daylighting...6 Submetering Campus Buildings...6 Acoustics and the Classroom...6 IV. The Role of Building Automation Standards...7 BAS Integration...7 BAS Interoperability...7 V. Moving Beyond Basic Energy Controls...8 Best Practice Control Strategies...8 Fundamental Control Applications...8 Advanced Control Applications...9 Integrated Controls Applications...10 VI. Energy Services...12 The Complete Building Envelope...12 Types of Energy Services...12 VII. Examples of TAC Customer Solutions...13 University of New Hampshire...13 Chippewa Valley Technical College, Wisconsin...13 VIII. Conclusion...14

I. Executive Summary At colleges and universities, energy consumption has a large impact on both financial and environmental interests. New construction, aging infrastructure, financial constraints, increasing energy costs, and environmental responsibility are motivating institutions to re-evaluate their energy demand and related conservation programs. In a time of growing concern about increasing tuition costs and greater competition for qualified students, institutions must take every measure possible to reduce this large line-item in the budget. This paper is intended to raise awareness of the many areas of potential savings that relate to energy consumption at colleges and universities. Costeffective recommendations and best practices will be outlined, demonstrating how management can take action to address energy inefficiencies and implement new initiatives in their energy programs. The reader will also learn some of the often overlooked techniques that comprehensively address energy conservation and increased building operating efficiency. Finally, this paper will discuss several examples where TAC has effectively applied building automation products and related services to provide optimal facility operations at the lowest possible energy costs. Leading Techniques for Energy Savings in Colleges and Universities 3

II. Energy Facts at Colleges and Universities Today The U.S. Energy Information Administration s (EIA) Annual Energy Outlook for 2006 shows that energy costs rose 31 percent from 2003 to 2005. Using another source to corroborate the EIA figures, The Producer Price Index for Fuels, Related Products, and Power clearly illustrates the trend for increasing prices. And high energy prices are forecast to continue due to limited supply and refining capacity, a tense global political climate, and brisk worldwide demand for fossil fuel. Looking at the academic community, the U.S. Department of Energy (DOE) estimates that at least 25% of the $6 billion colleges and universities spend annually on energy could be saved through better energy management. Research from the DOE s Building Technologies Program indicates that more efficient lighting and control, including the use of effective daylighting strategies, can save up to 30% on electrical demand. It is clear, then, that colleges and universities can do more to reduce energy expenses. And institutions should not only be motivated by budget, but also by the desire to be seen as an energy leader in the community, and environmentally responsible both inside and outside the campus community. Energy Conservation contributes to both operating income and higher education Energy efficient campus buildings not only save money, but are also comfortable and have an abundance of natural light. These features contribute to a more effective learning environment. Research has shown that students with the most daylighting in their classrooms performed 20% Leading Techniques for Energy Savings in Colleges and Universities 4

better in mathematics and 26% better in reading comprehension than those with the least amount of daylighting 1. Moreover, a high quality classroom environment also captures the interest of students and parents alike as they make their college selections from a competitive field. The goals achieved through energy conservation also promote awareness of the environment and our limited natural resources; important topics to evangelize in a university setting. The institution then has the potential to become a laboratory for students to study engineering and environmental principles 3. This fosters a sense of leadership in the student body that helps contribute to lower energy demand and environmental responsibility. Students can monitor energy technologies in use, conduct campus building energy audits, and increase energy visibility in the student community. Adding energy meaning to the term college town Perhaps no other type of business under one management has as diverse a facility infrastructure as that of colleges and universities. To serve populations of students that can reach 30,000 or more, institutions run self-sufficient little towns inand-of-themselves. A campus has office buildings, restaurants, retail shops, multi-family dwellings, sports facilities, entertainment complexes, and Research by the EPA shows that facilities that implement energy conservation measures outperform their competitors by as much as 10 percent in net operating income 2. classrooms. Research universities and specialty schools can have museums, medical centers, agricultural centers, high security biomedical laboratories, and many other buildings with very unique characteristics and varied energy needs. With such diversity of use, operations and maintenance staff responsible for campus facilities must consider not just energy management factors that exist today, but those that may exist in the future as the campus grows. Hence, a building automation system (BAS) needs to have maximum flexibility to adapt to the changing needs of a growing and evolving institution. Section IV gives examples of specific energy conservation measures and automation methods that can be implemented by the institution s energy service provider. Techniques that progress from fundamental control to more advanced and integrated applications are outlined for the reader. 1 Hershong Mahone Group, Daylighting in Schools: An Investigation into the Relationship Between Daylighting and Human Performance, 1999 2 EPA Study, Boosting Your Bottom Line through Improved Energy Use, June 2005 3 Supported by the U.S. Department of Energy, Rebuild America Program, www.rebuild.gov Leading Techniques for Energy Savings in Colleges and Universities 5

III. Unique Control Considerations of Colleges and Universities Due to the wide variety of building uses on campuses, energy demand changes from building to building. In residential housing for example, students usually have some degree of manual control and occupant override of HVAC and lighting. In a classroom building, the campus facilities staff will likely schedule the HVAC systems and dictate room temperature setpoints with little or no occupant override capability. Even tighter controls may be specified for laboratories, where strict control of airflow, humidity, and temperature may be required. So what is special about conserving energy at colleges and universities? And what control applications can be implemented that result in multiple benefits uniquely suited to the campus setting? Housing and the campus central loop Where the campus has a central chilled water and/ or hot water distribution, new student housing may be connected to the campus central plant for space heating, space cooling, and domestic hot water. This makes campus housing somewhat unique from other multi-family dwellings, which are unlikely to use chilled and hot water for heating and cooling. The interconnection between the campus chilled and hot water loops and the student housing project is a key area where a BAS can help conserve energy 4. Daylighting When properly designed and effectively integrated with the electric lighting system, daylighting can offer significant energy savings by offsetting a portion of the electric lighting load. Related benefits include a reduction in cooling required, higher student learning retention, and improved comfort. Strategies to get the most of daylighting include light shelves, skylights, clerestory windows, and related controls that optimize daylight using occupancy and photocell sensors. Submetering campus buildings Decisions about improving energy systems in buildings rest, in part, on detailed knowledge of current energy use. That, in turn, depends upon the metering of all energy sources such as electricity, natural gas, steam, and chilled water. Metering of individual buildings on college campuses is not traditionally practiced, but this is changing as energy costs increase dramatically. Submetering helps allocate costs appropriately by department, encourages conservation, produces more accurate energy reports and profiles, and assists in decision-making about energy upgrades and conservation investments 5. Acoustics and the classroom The impact mechanical system noise has on learning is often considered in design, but seldom given attention after construction is complete. Proper HVAC and lighting maintenance includes control of fan speed, air flow and velocity, and appropriately sized variable air volume (VAV) units. These are important factors to create and sustain the proper learning environment for both students and faculty. Specific energy saving techniques that relate to these topics are discussed in Section V. 4 CTG Energetics, Inc., Lessons Learned from Commissioning LEED-Certified Campus Housing, April 2006 5 EPA Study, Sub-Metering Energy Use in Colleges and Universities: Incentives and Challenges, April 2002 Leading Techniques for Energy Savings in Colleges and Universities 6

IV. The Role of Building Automation Standards Most facility managers and staff engineers are familiar with open systems standards such as LON, BACnet, XML, TCP/IP, and others that are part of the building automation world. These standards are needed because the product interoperability they represent enables customers to obtain competitive bids from several vendors when construction or renovation projects are in the design phase. After installation and commissioning, these standards then permit flexibility in software programming and alarm notification, often using a single front-end workstation with graphical views of the buildings being managed. Two aspects of these standards are often confused, but equally important to understand: BAS integration and BAS interoperability. Knowing the difference between the two will help the college or university make the best selection of a new or upgraded BAS, thereby providing the greatest opportunities to effectively implement energy conservation measures today and tomorrow. BAS integration When controls from multiple vendors communicate through an intermediary gateway or protocol translation device, or have hard wired connections, we call this BAS integration. While this is effective in enabling shared data and control between vendors, the wiring, gateway device or translation software does not guarantee future integration when other controls are added to the building or campus. BAS integration establishes a static, onetime link between systems that may need to be upgraded when control changes are required. Open Systems Standards in Building Automation BAS interoperability When controls from multiple vendors communicate over a common field-bus network using a common protocol (LON or BACnet), we call this BAS interoperability. This not only enables shared data and controls between vendors, but also the assurance that baseline characteristics of the standards are being followed for backward compatibility. Gateway devices and protocol translators are not necessary because the controls themselves comply with the established industry standards. Devices that comply with LON are certified LonMark compatible. Devices that comply with BACnet are certified by the BACnet Testing Laboratory (BTL), and are also known as native BACnet. Choosing to standardize on a single protocol such as LON or BACnet positions the college or university to leverage the best choices of control hardware and software, so future construction projects are designed for the greatest control over energy consumption 6. 6 LonMark is a registered trademark of LonMark International. BACnet is a registered trademark of the American Society of Heating Refrigeration and Air Conditioning Engineers (ASHRAE). Leading Techniques for Energy Savings in Colleges and Universities 7

V. Moving Beyond Basic Energy Management Regardless of the choice between an open or proprietary system, many institutions have some kind of BAS in place for the entire inventory of buildings on campus. It is inexpensive to implement basic controls. However, while initial costs are lowest, the ability to more aggressively manage energy is compromised by these lowcost, fixed-function solutions. This means there is limited or no capacity to do more with the system. Hence, when energy costs rise, there is no easy or cost-effective way to respond because all of the systems energy saving features are already being applied. Additional costs must then be incurred to implement control strategies that could have been designed from the start in a more scalable BAS. So what kind of control is necessary for optimal energy performance and reasonable return-oninvestment? The answer depends on how a given building is currently used, and the desired costsavings timeframe. In the campus environment, climate control needs can change from building to building, or even room to room depending on the type of facility. Today s BASs can be expanded to control every piece of equipment in the building, including pumps, fans, valves, dampers, compressors, lighting, and more. Integrated control applications (not to be confused with the protocol discussion of While the initial costs of basic or proprietary controls may be lowest, the institution s ability to more aggressively manage energy is compromised by these low-cost, fixed-function solutions. BAS integration above) can link disparate functions such as card access to lighting and climate control in any number of divided zones of a building. If a new application of control is necessary, choosing a good BAS results in a flexible and scalable system that protects the institution s initial investment in controls. This makes it possible for the system to be expanded in the future should the need arise. Where existing controls are already in place, management should evaluate whether software can be modified or upgraded to achieve the desired results. Best practice control strategies If a BAS is either being considered or already in place, the options for taking greater control of energy demand increase dramatically. Well designed building automation can save 5% to 20% annually 7 in energy costs; more if advanced and integrated control techniques are applied throughout the facility. The following are a few best practice control strategies commonly implemented by BASs and proven financially justifiable by facility managers. Fundamental Control Applications This is the starting point for the facility manager that wants to move beyond programmable thermostats or sensor-activated lighting control. Techniques for fundamental control include: Zone Scheduling Permits defined sections of a building to have HVAC and lighting reduced or shut down on a schedule. Zone scheduling means that a whole building does not need to run at a 100% comfort setting if on only a few occupants are in a given area. 7 Portland Energy Conservation, Inc. (PECI) study for the U.S. Department of Energy, Fifteen O&M Best Practices for Energy- Efficient Buildings, September 1999. Leading Techniques for Energy Savings in Colleges and Universities 8

Night/Unoccupied Setback Changes the comfort settings (setpoints) of HVAC so that space temperature decreases in winter and increases in summer, thereby reducing demand for heating and cooling during unoccupied hours. This feature can also be done using a programmable thermostat, but with only a few schedules and no flexibility to more aggressively change setback temperatures. After-Hours Override Allows temporary changes to comfort settings after-hours. This eliminates the need to modify schedules, which can sometimes become permanent by accident. This also avoids having the entire building run in occupied mode to meet the needs of a small group. Occupancy Sensors Detect motion or infrared signatures in the space, and trigger lights or HVAC accordingly. The BAS also enables scheduled overrides or triggers based on card access to an area of the building. Holiday Scheduling A calendar defines HVAC and lighting control for classrooms, theatres, lecture halls or labs for an entire calendar year, saving staff time implementing special schedules and ensuring holiday weekdays do not run in occupied mode. Advanced Control Applications In most cases, the same BAS put in place for fundamental controls is also capable of more advanced control applications, often with only software changes. Techniques for advanced control include: Follow Sunrise & Sunset Permits lighting schedules (such as parking lots, signs, and outdoor access lighting) to vary throughout the year as the length of daylight changes. This prevents lights from being on during the daytime. Fundamental Fundamental Control Control Applications Applications This This is is the the starting starting point point for for the the facility facility manager manager that that wants want sensor-activated sensor-activated lighting lighting control. control. Techniques Techniques for for fundamen fundamen The BAS automatically computes sunrise and Best Best Practices Practices -- Fundamental Fundamental sunset based on the latitude and longitude of the building s location. Daylight Harvesting 8 In zones of the building near exterior walls and windows, lighting can be dimmed or shut off based on specified minimum lighting levels detected by photocells. Controlled use of motorized shades can also optimize the availability of natural light without compromising energy efficiency. See also pages 5 and 6 on how daylighting benefits learning. Advanced Control Applications Optimum Start Starts HVAC equipment only as early as required to bring the building setpoints to comfort levels for occupancy. Control routines take into account outside air temperature and inside Zone Zone Scheduling Scheduling and and lighting lighting reduced reduce that that a a whole whole buildin buildi on on only only a a few few occup occu Night/Unoccupied of of HVAC HVAC so so that that spa summer, summer, thereby thereby rer unoccupied unoccupied hours. hours. T thermostat, thermostat, but but with aggressively aggressively change After-Hours Overr after-hours. This This eli e sometimes become become entire entire building building run runi Occupancy Senso Senso and and trigger trigger lights lights or o overrides or or trigger Holiday Schedulin classrooms, theatre saving staff staff time time im im weekdays do do not not rur In In most cases, the the same BAS put put in in place for for fundamental applications, often with only software changes. Techniques Best Practices -- Advanced 8 According to the California Institute for Energy Efficiency and the U.S. Department of Energy, 77,000,000 MWh of electricity are consumed in the United States each year for lighting buildings perimeter zones where daylight is already present. Best Practices Fundamental Follow Sunrise & lots, signs, and and outd the the length of of daylig the the daytime. The The BA B on on the the latitude and and Best Practices Advanced Daylight Harvestin windows, lighting cac lighting levels detec can also optimize tht energy efficiency. S learning. Optimum Start S bring the the building ses routines take into a temperatures when down cycles. Optim startup. Leading Techniques for Energy Savings in Colleges and Universities 9 8 According to to the California Institute for for Energy Efficiency and

classrooms, theatr saving staff time im White Paper weekdays do not r Advanced Control Applications In most cases, the same BAS put in place for fundamenta applications, often with only software changes. Technique space temperatures when initiating classroom or lecture hall warm-up or cool-down cycles. Optimum start takes the guess-work out of scheduled startup. Optimum Stop Determines the earliest possible time to initiate setback temperatures before unoccupied periods while still maintaining occupant comfort. Also known as coasting. Space temperature drifts gradually beyond comfort levels in anticipation of the unoccupied period. Ventilation On Demand CO 2 levels in the occupied space are used as an indicator of the number of occupants in a larger room, such as a theatre or lecture hall. Calculations are then performed that relate the CO 2 level to the fresh air intake damper, indicating when more outdoor air is needed. CO 2 levels also assist heating and cooling anticipation in thermostatic control to optimize comfort and air circulation. Variable Air Volume (VAV) Supply Air Temperature Reset The supply air temperature (SAT) of variable volume air handlers can be reset upwards when full cooling is not required. The SAT setpoint is increased on cooler days based upon the actual building load. Then when terminal boxes reach 100% open, the SAT is decreased. This minimizes the need for mechanical cooling, optimizes the use of economizers, and improves occupant comfort by reducing drafts due to the movement of excessively cold air. Demand Limiting or Load Shedding Monitors electric meters and current draw on high-demand equipment, then relaxes setpoints to immediately reduce demand. This technique can, for example, prevent a chiller from further loading, but can also globally change setpoints throughout the building to shed electric load to avoid peak utility charges. Non-critical equipment and lighting loads can also be shut off. Chiller Optimization The chilled water loop temperature Best can Practices be raised as - the Advanced cooling requirements for the building are reduced, increasing chiller efficiency. A technique known as load reset raises the chilled water temperature setpoint until one of the chilled water valves is 100% open. Cooling Tower Optimization The condenser water supply to the chiller can be decreased to a minimum setpoint, as defined by the manufacturer. already present. Then an optimal water supply setpoint can be calculated using a combination of the outside air wet-bulb temperature and the cooling tower approach temperature. The reduced water temperature improves the chiller s partial load efficiency and also optimizes the cooling tower s operation. LEADING TECHNIQUES FOR ENERGY SAVINGS IN COLLEG Hot Water Reset Hot water system temperatures can be reset based on outside air temperature, decreasing heat losses in supply piping. This not only saves energy, but also makes the occupied space more comfortable because it reduces localized heating caused by excessively hot pipes. Integrated Control Applications The concept of integrated control is an extension of fundamental and advanced control, but with links to more diverse parts of campus facilities. Integrated control provides a high level of Follow Sunrise & lots, signs, and ou the length of daylig the daytime. The B on the latitude and Best Practices Advanced (cont.) Daylight Harvest windows, lighting c lighting levels dete can also optimize t energy efficiency. learning. Optimum Start bring the building routines take into temperatures whe down cycles. Optim startup. 8 According to the California Institute for Energy Efficiency an electricity are consumed in the United States each year for lig Leading Techniques for Energy Savings in Colleges and Universities 10

Integrated Control Applications The concept of integrated control is an extension of fundam diverse parts of campus facilities. Integrated control provid the flexibility to expand control, at least cost, for future en potential business benefits, plus the flexibility to expand control, at least cost, for future energy savings objectives. Variable Frequency Drives (VFDs) VFDs optimize the power consumed by HVAC fans, speeding up or slowing down the fan based on climate demands of the space under control. Using VFDs, a 20% reduction in fan speed (and air flow) results in a 49% decrease in electrical consumption. Integrated control of VFDs can also be part of a load shedding strategy. Multiple Use Card Access Cards used by students or faculty permit access to specific authorized areas. When integrated with the BAS, cards can also be used to trigger lighting and climate control. This is especially useful to save energy in areas that have unpredictable occupancy periods. The same cards can be used for cost accounting at the cafeteria, gymnasium, laundry facilities, or other fee-for-service locations. Reporting The BAS produces weekly, monthly, or annual trends in energy consumption. These can include custom reports that verify bill-back or sub-metering charges by department or building. Proper reporting provides early warning when energy efficiency begins to drift. Many options for reporting are available using BAS data. Smart Circuit Breakers The BAS runs software that can switch on and off electrical circuit breakers (known as smart breakers ). This enables integrated control of lighting and electrical consumption, which reduces the need for a separate lighting control system installation, training, and maintenance. Third-party Equipment Systems such as HVAC equipment, Best Practices fire detection - Integrated systems, alarm systems, smoke evacuation systems, and elevators are integrated into a single BAS. This type of integration brings total control of the facility to a single graphical interface. Central Monitoring and Control Maintenance staff or the energy manager can monitor and control the whole building from a single console, either on-site or remotely over the Internet. Alarms defined by the user can appear at the console, or be sent to an email address or cell phone. These are examples of best practices in control operations, though not an exhaustive list. There are many techniques that apply to the specific equipment at colleges and universities in a designto-suit offer. No matter what level of automation or control is present, the facility director should be inquiring with their supplier about whether any of these techniques can be achieved with modifications to an installed BAS. Variable Frequenc consumed by HVAC climate demands o reduction in fan sp electrical consumpt load shedding strat Multiple Use Card access to specific a can also be used to useful to save ener The same cards ca gymnasium, laundr Reporting The BA energy consumptio back or sub-meteri provides early warn options for reportin Smart Circuit Brea off electrical circuit integrated control o the need for a sepa maintenance. Third-party Equipm detection systems, elevators are integ total control of the Central Monitoring manager can moni console, either onthe user can appea phone. These are examples of best practices in control operations techniques that apply to the specific equipment at colleges what level of automation or control is present, the facility whether any of these techniques can be achieved with mod Leading Techniques for Energy Savings in Colleges and Universities 11

Outsourced remote monitoring and reporting Evaluations of infrastructure that relate to energy White Paper VI. Energy Services Types of energy services We have discussed the unique facets of energy use at college campuses. And we have outlined Experience tells us that early identification of best practice techniques that apply a BAS toward excessive energy expenses can often be corrected solving the costs related to energy demand. This for very little cost with regular service to controller section now discusses energy services, and how software, schedules, and economizer operation, ongoing review of energy practices can ensure and by practicing simple and inexpensive energy management objectives are continuously maintenance procedures. Ignoring, or not even being met. seeing spikes in energy costs can consume many times what the remedy would have cost The complete had it been implemented in a timely manner. building envelope Energy services that look at the complete building envelope include: Unless a BAS is maintained and upgraded regularly, it is likely there are energy inefficiencies. Outsourced remote monitoring and reporting Buildings are known to drift out of control over Outsourced operations & maintenance, time due to reconfiguration, changes in use, including controls staffing changes, and relaxed operations and Alarm notification and mechanical service maintenance (O&M) practices. response Building automation system fine-tuning Energy conservation measures should not be VI. looked Energy at individually Services Periodic energy audits and reports of without considering how they recommendations interact and impact other planned steps toward We have discussed the unique facets of energy use at college Evaluations campuses. of infrastructure And we have that relate outlined to energy best practice energy efficiency. So an important aspect of energy techniques that apply a BAS toward solving the costs related consumption, to energy such demand. as roofing, This glass, section airlocks, now discusses conservation is to manage demand with control energy services, and how ongoing review of energy practices insulation, can ensure etc. energy management objectives are systems combined with energy services that continuously being met. Assistance finding government rebates apply to the complete building envelope, including and financing the windows, walls, foundation, basement slab, THE COMPLETE BUILDING ENVELOPE Comprehensive energy efficiency programs, ceiling, roof, and insulation. Looking at the building Unless a BAS is maintained and upgraded regularly, it is such likely as there TAC EnergyEdge are energy inefficiencies. Buildings are envelope broadens energy management beyond known to drift out of control over time due to reconfiguration, changes in use, staffing changes, and relaxed just smart BAS techniques. It considers noncontrol facets of the building that can affect energy operations and maintenance (O&M) practices. Once initial steps are taken to maximize energy efficiency, periodic reviews ensure building demand. Energy services, usually part of an energy Energy conservation measures should not be looked at configuration, individually equipment, without considering controls, or how other they interact and program, are designed to maintain optimum impact other planned steps toward energy efficiency. systems So an important have not been aspect altered of energy by users conservation or is to energy efficiency after initial efforts to establish manage demand with control systems combined with maintenance energy services staff. Energy that apply efficiency to the drift complete can building energy conservation are put in place. envelope, including the windows, walls, foundation, basement defeat the slab, best intended ceiling, roof, energy and program. insulation. A trained Looking at the and building qualified envelope energy broadens specialist understands energy management the beyond complete just smart building BAS techniques. envelope. Expert It considers services, non-control combined facets of with the building effective knowledge that can affect of controls energy demand. helps Energy colleges services, and universities usually part maximize of an energy savings, program, are not designed just once, to maintain but on an annual optimum basis. energy efficiency after initial efforts to establish energy conservation are put in place. TYPES OF ENERGY SERVICES Experience tells us that early identification of excessive energy expenses can often be corrected for very little cost with regular service to controller software, schedules, and economizer operation, and by practicing simple and inexpensive maintenance procedures. Ignoring, or not even seeing spikes in energy costs can consume many times what the remedy would have cost had it been implemented in a timely manner. Energy services that look at the complete building envelope include: Leading Techniques for Energy Savings in Colleges and Universities 12

VII. Examples of TAC Customer Solutions University of New Hampshire University of New Hampshire (UNH) is a nationally recognized energy leader, receiving awards from the U.S. Department of Energy (DOE) for being in the top 5% of energy-efficient research universities in the country. UNH chose TAC for its flexible software that allows additional control sequences to be implemented as required. Solution TAC partner BASiX has installed and serviced more than 1,000 controllers at UNH s 40 buildings since 1981. The TAC system controls the central steam and hot water plant, indoor lighting, and the unique needs of diverse types of buildings on campus. A high-rise building required extra heat in specific zones when windy conditions prevailed. An anemometer that detects wind velocity now helps control building setpoints. In a laboratory, high fume hood air velocity was placing increased demand on heating and cooling. VAV air supply was then set to match that of the fume hoods, minimizing energy consumption while maintaining student safety. The DOE award was also influenced by the skills of UNH s technical staff, which continually monitor the TAC system and make software changes as needed to sustain energy conservation. Gains UNH saves more than $4 million in energy costs each year using a well-designed control strategy, and attention to ongoing efficiency. Energy use at the university is only 181 kbtu per square foot, compared to a regional average of 250 kbtu/sf. Chippewa Valley Technical College Chippewa Valley Technical College (CVTC) enrolls 4,000 students on 5 campus locations in Wisconsin. CVTC selected TAC for energy management to maximize their flexibility to control individual classrooms and integrate card access control. Solution The TAC system controls heating, ventilation, and air conditioning on all 5 campuses, and uses a central monitoring workstation on the Eau Claire campus. CVTC employs techniques such as optimum start, load shedding, outdoor air damper control, outdoor lighting control, and access control that triggers HVAC zones. One technique that schedules VAV boxes and air handlers individually permits the college to set comfort levels in classrooms based on occupancy and teaching schedules. Gains CVTC has the lowest energy use of all the state s 16 technical colleges, yielding a net savings of $400,000 per year. CVTC was also able to increase comfort levels in classrooms to 72-73 degrees from 70 degrees and still reduce energy expenses. In some buildings, return-on-investment was achieved in 3.5 months. Leading Techniques for Energy Savings in Colleges and Universities 13

VIII. Conclusion An effective building control system is not a commodity, nor is it a cost. A well engineered and maintained building automation system can provide a return on investment over many years. Ensure that the automation system you install or modify is fully programmable to take advantage of the control strategies outlined in this paper. Make sure the energy conservation measures you put in place today are sustained over time. The best way to do this is to use energy services from a provider that understands the complete building envelope and the interrelated aspects of the building that affect energy demand. Finally, require your solution provider reduce your building s energy costs immediately, provide a sensible return-on-investment timeframe, and convey confidence that they are proposing products or services that are necessary and effective to achieve your energy savings goals. Leading Techniques for Energy Savings in Colleges and Universities 14

Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice. On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric, however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate corporate brand changes. 2007-2009 Schneider Electric. All rights reserved. WP-COLLEGEENERGY-A4.BU.N.EN.1.2007.0.00.CC January 2007 sm