HVAC System Selection Criteria. RTSPco Technical department M.dadkhah

Similar documents
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

Chapter 3.4: HVAC & Refrigeration System

Creating Efficient HVAC Systems

Commissioning - Construction Documents (Page 1 of 6)

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

HVAC Systems: Overview

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

Building Energy Systems. - HVAC: Heating, Distribution -

Presentation Outline. Common Terms / Concepts HVAC Building Blocks. Links. Plant Level Building Blocks. Air Distribution Building Blocks

Drives and motors. A guide to using variable-speed drives and motors in retail environments

Selection Tips For Air-Conditioning Cooling Systems

3/29/2012 INTRODUCTION HVAC BASICS

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

HEATING, VENTILATION & AIR CONDITIONING

Federal Wage System Job Grading Standards for Air Conditioning Equipment Operating, Table of Contents

Lesson 36 Selection Of Air Conditioning Systems

Air Conditioning Clinic

SPECIAL ISSUE: NATIONAL SCIENCE FOUNDATION WORKSHOP

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Life Cycle Costing Analysis of Water-cooled Chillers. Chillventa Nuremburg, Germany

HEAT RECOVERY FROM CHILLED WATER SYSTEMS. Applications for Heat Reclaim Chillers

Maximize energy savings Increase life of cooling equipment More reliable for extreme cold weather conditions There are disadvantages

Classification and Qualification STANDARDS

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

ASTACEA4 Inspect complex/central air conditioning systems

HVAC Processes. Lecture 7

HOW TO CONDUCT ENERGY SAVINGS ANALYSIS IN A FACILITY VALUE ENGINEERING STUDY

Optimization of Water - Cooled Chiller Cooling Tower Combinations

Comparing Energy Savings of Different VAV Systems

How To Design A Building In New Delhi

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

POLK STATE COLLEGE CHILLER PLANT EVALUATION WINTER HAVEN, FLORIDA APRIL 2, C arastro & A ssociates, C&A# 5747

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Why and How we Use Capacity Control

Large Energy Savings Per Installation VFDs for Large Chillers

HOT & COLD. Basic Thermodynamics and Large Building Heating and Cooling

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Knowledge for optimal efficiency

DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER

CHILLER PLANT CONTROL MULTIPLE CHILLER CONTROLS

HVAC For Schools How to purchase an HVAC system that meets your school s unique requirements and stays within your budget

Digital Realty Data Center Solutions Digital Chicago Datacampus Franklin Park, Illinois Owner: Digital Realty Trust Engineer of Record: ESD Architect

See any red flags? Let s take a look at the problems that occurred on the job and how to avoid making the same mistakes.

Defining Quality. Building Comfort. Precision. Air Conditioning

NEW JERSEY CENTER OF EXCELLENCE

Printing and Publishing Energy Savings Guide

Guidelines for energy efficient heating, ventilation and air conditioning (HVAC) systems

Heating, Ventilation & Air Conditioning Equipment

APPLICATION GUIDE. Comparison of Latent Cooling Performance of Various HVAC systems in a Classroom Application

The Different Types of Air Conditioning Equipment for IT Environments

Tim Sisson - Trane HVAC OVERVIEW

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

Element D Services Heating, Ventilating, and Air Conditioning

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

LG Electronics AE Company, Commercial Air Conditioning

Crowne Plaza Copenhagen Towers The world s greenest hotel

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Nominal Life Expectancy for Building Components

Energy Efficiency. Energy Efficient Home Cooling:

How and Why Mission- Critical Cooling Systems Differ From Common Air Conditioners

ABSTRACT DCMCCT PROJECT OVERVIEW

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

Characteristics of Evaporators

Energy Efficiency in Industrial HVAC Systems

Data Center. Ultra-Efficient chilled water system optimization. White paper. File No: Date: december 03, 2015 Supersedes: new Date: new

BUILDING PERFORMANCE METRICS

White Paper #10. Energy Efficiency in Computer Data Centers

Topics for Today. Order of Magnitude Mechanical Estimating. Order of Magnitude Estimate Goal. Project Delivery Methods. Questions for Client

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

GEOTHERMAL HEATING AND COOLING INTRODUCTION

21.1 Functions, Basic Configuration, and Interfaces

Facilities Maintenance Standards rev

HVACPowDen.xls An Easy-to-Use Tool for Recognizing Energy Efficient Buildings and HVAC Systems

HEATING OF DOMESTIC OUTDOOR SWIMMING POOLS

Carnegie Mellon University School of Architecture, Department of Mechanical Engineering Center for Building Performance and Diagnostics

Heat Recovery In Retail Refrigeration

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Heating, ventilation and air conditioning equipment. A guide to equipment eligible for Enhanced Capital Allowances

GLOBACON 05 HVAC Systems for Cogen

ALBUQUERQUE PUBLIC SCHOOLS Facility Design & Construction / Maintenance & Operations

KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005

Glossary of Heating, Ventilation and Air Conditioning Terms

ALONE. small scale solar cooling device Project No TREN FP7EN Project No TREN/FP7EN/ ALONE. small scale solar cooling device

ABSTRACT. aspects of potential waste heat recovery systems and the economics of installing them at selected survey factories.

Performing Arts Research/Lab Campus Life Athletics Student Housing Academics Campus Infrastructure Food Services

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Glossary of HVAC Terms

Ductless Heat Pumps. Gary Nordeen January

Drives and motors. A guide to using variable speed drives and motors in data centres Meeting your Carbon Reduction Commitment (CRC)

AIR CONDITIONING - ENERGY CONSUMPTION AND ENVIRONMENTAL QUALITY

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS

Integrated Solar Radiant Systems

THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power

Transcription:

HVAC System Selection Criteria RTSPco Technical department M.dadkhah

An HVAC system maintains desired environmental conditions in a space. In almost every application, many options are available to the design engineer to satisfy a client s building program and design intent. In the analysis, selection, and combination of these options, the design engineer should consider the criteria defined here, as well as project-specific parameters to achieve the functional requirements associated with the project design intent. The design engineer should consider sustainability as it pertains to responsible energy and environmental design, as well as constructability of the design. HVAC systems are categorized by the method used to produce, deliver, and control heating, ventilating, and air conditioning in the conditioned area. This paper addresses procedures for selecting the appropriate system for a given application while taking into account pertinent issues associated with designing, building, commissioning, operating, and maintaining the system. It also describes and defines the design concepts and characteristics of basic HVAC systems. This paper is intended as a guide for the design engineer, builder, facility manager, and student needing to know or reference the analysis and selection process that leads to recommending the optimum system for the job. SELECTING A SYSTEM The design engineer is responsible for considering various systems and recommending one or two systems that will meet the project goals and perform as desired. It is imperative that the design engineer and owner collaborate to identify and prioritize criteria associated with the design goal. In addition, if the project has preconstruction services, the designer and operator should consult with the construction manager to take advantage of the constructability and consider value-engineered options. Occupant comfort, process heating, and cooling or ventilation criteria may be considered, including the following: Temperature Humidity Air motion Air purity or quality Air changes per hour Air and/or water velocity requirements Local climate Space pressure requirements Capacity requirements, from a load calculation analysis Redundancy Spatial requirements Security concerns First cost Operating cost, including energy and power costs Maintenance cost Reliability Flexibility Life-cycle analysis Sustainability of design Acoustics and vibration Mold and mildew prevention Because these factors are interrelated, the owner, design engineer, and operator must consider how these criteria affect each other. The relative importance of factors such as these varies with different owners, and often changes from one project to another for the same owner. For example, typical owner concerns include first cost compared to operating cost, extent and frequency of maintenance and whether that maintenance requires entering the occupied space, expected frequency of system failure, effect of failure, and time required to correct the failure. Each concern has a different priority, depending on the owner s goals. Additional Goals In addition to the primary goal of providing the desired environment, the design engineer should be aware of and account for other goals the owner may require. These goals may include the following: Supporting a process, such as operation of computer equipment Promoting a germ-free environment Increasing sales Increasing net rental income Increasing property salability The owner can only make appropriate value judgments if the design engineer provides complete information on the advantages and disadvantages of each option. Just as the owner does not usually know the relative advantages and disadvantages of different HVAC systems, the design engineer rarely knows all the owner s financial and functional goals. Hence, the owner must be involved in system selection in the conceptual phase of the job. The same can be said for operator participation so that the final design is sustainable.

Figure 1 process flow diagram System Constraints Once the goal criteria and additional goal options are listed, many constraints must be determined and documented. These constraints may include the following: Performance limitations (e.g., temperature, humidity, space pressure) Available capacity Available space Available utility source Available infrastructure Building architecture The design engineer should closely coordinate the system constraints with the rest of the design team, as well as the owner, to overcome design obstacles associated with the HVAC systems under consideration for the project. Constructability Constraints The design engineer should take into account HVAC system issues before the project reaches the construction document phase. Some of these constraints may significantly affect the success of the design and cannot be overlooked in the design phase. Some issues and concerns associated with constructability are Existing conditions Maintaining existing building occupancy and operation Construction budget Construction schedule Ability to phase HVAC system installation Equipment availability (i.e., delivery lead times) Few projects allow detailed quantitative evaluation of all alternatives. Common sense, historical data, and subjective experience can be used to narrow choices to one or two potential systems. By establishing the capacity requirement, equipment size can be determined, and the choice may be narrowed to those systems that work well on projects within a size range. Loads vary over time based on occupied and unoccupied periods, and changes in weather, type of occupancy, activities, internal loads, and solar exposure. Each space with a different use and/or exposure may require a different control zone to maintain space comfort. Some areas with special requirements (e.g., ventilation requirements) may need individual systems. The extent of zoning, degree of control required in each zone, and space required for individual zones also narrow system choices. No matter how efficiently a particular system operates or how economical it is to install, it can only be considered if it (1) maintains the desired building space environment within an acceptable tolerance under all conditions and occupant activities and (2) physically fits into, on, or adjacent to the building without being objectionable. Cooling and humidity control are often the basis of sizing HVAC components and subsystems, but the system may also be determined based on ventilation criteria. For example, if large quantities of outside air are required for ventilation or to replace air exhausted from the building, only systems that transport large air volumes need to be considered. Effective heat delivery to an area may be equally important in selection. A distribution system that

offers high efficiency and comfort for cooling may be a poor choice for heating. The cooling, humidity, and/or heat delivery performance compromises may be small for one application in one climate, but may be unacceptable in another that has more stringent requirements. HVAC systems and associated distribution systems often occupy a significant amount of space. Major components may also require special support from the structure. The size and appearance of terminal devices (e.g., grilles, registers, diffusers, fan-coil units, radiant panels) affect architectural design because they are visible in the occupied space. Construction budget constraints can also influence the choice of HVAC systems. Based on historical data, some systems may not be economically feasible for an owner s building program. In addition, annual maintenance and operating budget (utilities, labor, and materials) should be an integral part of any system analysis and selection process. This is particularly important for building owners who will retain the building for a substantial number of years. Value-engineered solutions can offer (1) costdriven performance, which may provide for a better solution for lower first cost; (2) a more sustainable solution over the life of the equipment; or (3) best value based on a reasonable return on investment. Sustainable energy consumption can be compromised and long-term project success can be lost if building operators are not trained to efficiently and effectively operate and maintain the building systems. For projects in which the design engineer used some form of energy software simulation, these data should be passed on to the building owner so that goals and expectations can be measured and benchmarked against actual system performance. HVAC design is not complete without continuous system performance years after the system selection and analysis has been completed and the systems installed and turned over to the building owner. Comparing the criteria, other factors and constraints, and their relative importance usually identifies one or two systems that best satisfy project goals. In making choices, notes should be kept on all systems considered and the reasons for eliminating those that are unacceptable. Each selection may require combining a primary system with a secondary (or distribution) system. The primary system converts energy from fuel or electricity into a heating and/or cooling medium. The secondary system delivers heating, ventilation, and/or cooling to the occupied space. The systems are independent to a great extent, so several secondary systems may work with a particular primary system. In some cases, however, only one secondary system may be suitable for a particular primary system. Once subjective analysis has identified one or two HVAC systems (sometimes only one choice remains), detailed quantitative evaluations must be made. All systems considered should provide satisfactory performance to meet the owner s essential goals. The design engineer should provide the owner with specific data on each system to make an informed choice. Selection Report As the last step, the design engineer should prepare a summary report that addresses the following: The goal Criteria for selection Important factors, including advantages and disadvantages Other goals Security concerns Basis of design HVAC system analysis and selection matrix System narratives Budget costs Recommendation A brief outline of each of the final selections should be provided. In addition, HVAC systems deemed inappropriate should be noted as having been considered but not found applicable to meet the owner s primary HVAC goal. The report should include an HVAC system selection matrix that identifies the one or two suggested HVAC system selections (primary and secondary, when applicable), system constraints, and other constraints. In completing this matrix assessment, the design engineer should have the owner s input to the analysis. This input can also be applied as weighted multipliers, because not all criteria carry the same weighted value. Many grading methods are available to complete an analytical matrix analysis. Probably the simplest is to rate each item excellent, very good, good, fair, or poor. A numerical rating system such as 0 to 10, with 10 equal to excellent and 0 equal to poor or not applicable, can provide a quantitative result. The HVAC system with the highest numerical value then becomes the recommended HVAC system to accomplish the goal. The system selection report should include a summary followed by a more detailed account of

the HVAC system analysis and system selection. This summary should highlight key points and findings that led to the recommendation(s). The analysis should refer to the system selection matrix (such as in Table 1) and the reasons for scoring. With each HVAC system considered, the design engineer should note the criteria associated with each selection. Issues such as close temperature and humidity control may eliminate some HVAC systems from consideration. System constraints, noted with each analysis, should continue to eliminate potential HVAC systems. Advantages and disadvantages of each system should be noted with the scoring from the HVAC system selection matrix. This process should reduce HVAC selection to one or two optimum choices to present to the owner. Examples of similar installations for other owners should be included with this report to support the final recommendation. Identifying a third party for an endorsement allows the owner to inquire about the success of other HVAC installations. HVAC SYSTEMS AND EQUIPMENT The majority of buildings built, expanded, and /or renovated may be ideally suited for decentralized HVAC systems, with equipment located in, throughout, adjacent to, or on top of the building. The alternative is primary equipment located in a Table 1 Sample HVAC System Analysis and Selection Matrix (0 to 10 Score) central plant (either inside or outside the building) and distributing air and/or water for HVAC needs from this plant. Decentralized System Characteristics Temperature, Humidity, and Space Pressure Requirements. A decentralized system may be able to fulfill any or all of these design parameters. Capacity Requirements. A decentralized system usually requires each piece of equipment to be sized for zone peak capacity, unless the systems are variable-volume. Depending on equipment type and location, decentralized systems do not benefit as much from equipment sizing diversity as centralized systems do. Redundancy. A decentralized system may not have the benefit of back-up or standby equipment. This limitation may need review. Facility Management. A decentralized system can allow the building manager to maximize performance using good business/ facility management techniques in operating and maintaining the HVAC equipment and systems. Spatial Requirements. A decentralized system may or may not require equipment rooms. Because of space restrictions imposed on the design engineer or architect, equipment may be located on the roof and/or the ground adjacent to the Goal: Furnish and install an HVAC system that provides moderate space temperature control with minimum humidity control at an operating budget of 70,000 Btu/h per square foot per year Categorizes System #1 System #2 System #3 Remarks 1. Criteria for selection: 78 F space temperature with ±3 F control during occupied, with 40% Rh and ±5% Rh control during cooling 68 F space temperature with ±2 F, with 20% Rh and ±5% Rh control during heating season. First cost Equipment life cycle 2. Important Factors: First-class office space stature Individual tenant utility metering 3. Other Goals: Engineered smoke control system ASHRAE Standard 62.1 ventilation rates Direct digital control building automation 4. System Constraints: No equipment on first floor No equipment on ground adjacent to building 5. Other Constraints: No perimeter finned-tube radiation or other type of in-room equipment TOTAL SCORE

building. Depending on system components, additional space may be required in the building for chillers and boilers. Likewise, a decentralized system may or may not require duct and pipe shafts throughout the building. First Cost. A decentralized system probably has the best first cost benefit. This feature can be enhanced by phasing in the purchase of decentralized equipment as needed (i.e., buying equipment as the building is being leased/occupied). Operating Cost. A decentralized system can save operating cost by strategically starting and stopping multiple pieces of equipment. When comparing energy consumption based on peak energy draw, decentralized equipment may not be as attractive as larger, more energy-efficient centralized equipment. Maintenance Cost. A decentralized system can save maintenance cost when equipment is conveniently located and equipment size and associated components (e.g., filters) are standardized. When equipment is located outdoors, maintenance may be difficult during bad weather. Reliability. A decentralized system usually has reliable equipment, although the estimated equipment service life may be less than that of centralized equipment. Decentralized system equipment may require maintenance in the occupied space, however. Flexibility. A decentralized system may be very flexible because it may be placed in numerous locations. Level of Control. Decentralized systems often use direct refrigerant expansion (DX) for cooling, and on/off or staged heat. This step control results in greater variation in space temperature and humidity, where close control is not desired or necessary. As a caution, oversizing DX or stepped cooling can allow high indoor humidity levels and mold or mildew problems. Sound and Vibration. Decentralized systems often locate noisy machinery close to building occupants, although equipment noise may be less than that produced by large central systems. Constructability. Decentralized systems frequently consist of multiple and similar-in-size equipment that makes standardization a construction feature, as well as purchasing units in large quantities. Centralized System Characteristics Temperature, Humidity, and Space Pressure Requirements. A central system may be able to fulfill any or all of these design parameters. Capacity Requirements. A central system usually allows the design engineer to consider HVAC diversity factors that reduce installed equipment capacity. As a result, this offers some attractive first-cost and operating-cost benefits. Redundancy. A central system can accommodate standby equipment that decentralized configurations may have trouble accommodating. Facility Management. A central system usually allows the building manager to maximize performance using good business/ facility management techniques in operating and maintaining the HVAC equipment and systems. Spatial Requirements. The equipment room for a central system is normally located outside the conditioned area: in a basement, penthouse, service area, or adjacent to or remote from the building. A disadvantage with this approach may be the additional cost to furnish and install secondary equipment for the air and/or water distribution. A second consideration is the access and physical constraints throughout the building to furnish and install this secondary distribution network of ducts and/or pipes and for equipment replacement. First Cost. Even with HVAC diversity, a central system may not be less costly than decentralized HVAC systems. Historically, central system equipment has a longer equipment service life to compensate for this shortcoming. Thus, a lifecycle cost analysis is very important when evaluating central versus decentralized systems. Operating Cost. A central system usually has the advantage of larger, more energy-efficient primary equipment compared to decentralized system equipment. In addition, with multiple pieces of HVAC equipment, a central system allows strategic planning and management of the HVAC systems through staging equipment based on HVAC demands. Maintenance Cost. The equipment room for a central system provides the benefit of maintaining HVAC equipment away from occupants in an appropriate service work environment. Access to occupant workspace is not required, thus eliminating disruption to the space environment, product, or process. Because of the typically larger capacity of central equipment, there are usually fewer pieces of HVAC equipment to service.

Reliability. Centralized system equipment generally has a longer service life. Flexibility. Flexibility can be a benefit when selecting equipment that provides an alternative or back-up source of HVAC. Level of Control. Centralized systems generally use chilled water for cooling, and steam or hydronic heat. This usually allows for close control of space temperature and humidity where desired or necessary. Sound and Vibration. Centralized systems often locate noisy machinery sufficiently remote from building occupants or noisesensitive processes. Constructability. Centralized systems usually require more coordinated installation than decentralized systems. However, consolidation of the primary equipment in a central location also has benefits. Among the largest centralized systems are HVAC plants serving groups of large buildings. These plants improve diversity and generally operate more efficiently, with lower maintenance costs, than individual central plants. Economic considerations of larger centralized systems require extensive analysis. The utility analysis may consider multiple fuels and may also include gas and steam turbine-driven equipment. Multiple types of primary equipment using multiple fuels and types of HVAC-generating equipment (e.g., centrifugal and absorption chillers) may be combined in one plant. Systems and Equipment Selection Selection of HVAC equipment and systems depends on whether the facility is new or existing, and whether it is to be totally or partially renovated. For major renovations or new construction, new HVAC systems and equipment should be installed. When applicable, the remaining useful life of existing equipment and distribution systems should be considered. Case Study: In this paper we want to investigate the centralized commercial building. SELECTION The largest factor that determines total liquid chiller owning cost is the cooling load size; therefore, the total required chiller capacity should be calculated accurately. The practice of adding 10 to 20% to load estimates is unnecessary because of the availability of accurate load estimating methods, and it proportionately increases costs of equipment purchase, installation, and the poor efficiency resulting from wasted power. Oversized equipment can also cause operational difficulties such as frequent on/off cycling or surging of centrifugal machines at low loads. The penalty for a small underestimation of cooling load, however, is not serious. On the few design-load days of the year, increased chilled-liquid temperature is often acceptable. However, for some industrial or commercial loads, a safety factor can be added to the load estimate. Total owning cost is comprised of the following: Equipment price. Each machine type and/or manufacturer s model should include all necessary auxiliaries such as starters and vibration mounts. If these are not included, their price should be added to the base price. Associated equipment, such as condenser water pump, tower, and piping, should be included. Installation cost. Factory-packaged machines are both less expensive to install and usually considerably more compact, thus saving space. The cost of field assembly must also be evaluated. Energy cost. Using an estimated load schedule and part-load power consumption curves furnished by the manufacturer, a year s energy cost should be calculated. Water cost. With water-cooled towers, the cost of acquisition, water treatment, tower blowdown, and overflow water should be included. Maintenance cost. Each bidder may be asked to quote on a maintenance contract on a competitive basis. Insurance and taxes. For packaged chillers that include heat recovery, system cost and performance should be compared in addition to equipment costs. For example, the heat recovery chiller installed cost should be compared with the installed cost of a chiller plus a separate heating system. The following factors should also be considered: (1) energy costs, (2) maintenance requirements, (3) life expectancy of equipment, (4) standby arrangement, (5) relationship of heating to cooling loads, (6) effect of package selection on sizing, and (7) type of peripheral equipment. Capital cost shall include all cost elements associated with the HVAC systems and their infrastructure, not just the cost of the particular item of plant. E.g. water-cooled plant options shall include the associated cost of providing the cooling tower/dry cooler enclosure, piers, additional structural supports, water supply, water treatment equipment, initial licensing costs etc.

Capital cost shall be cost-effective when compared to operation and maintenance costs. METHOD OF SELECTION Ratings Two types of ratings are published. The first, for a packaged liquid chiller, lists values of capacity and power consumption for many combinations of leaving condenser water and chilled-water temperatures (ambient dry-bulb temperatures for air-cooled models). The second type of rating shows capacity and power consumption for different condensing and chilled-water temperatures. This type of rating allows selection with a remote condenser that can be evaporative, water-, or air-cooled. Sometimes the required rate of heat rejection is also listed to aid in selecting a separate condenser. Power Consumption With all liquid-chilling systems, power consumption increases as condensing temperature rises. Therefore, the smallest package, with the lowest ratio of input to cooling capacity, can be used when condenser water temperature is low, the remote air-cooled condenser is relatively large, or when leaving chilled-water temperature is high. The cost of the total system, however, may not be low when liquid chiller cost is minimized. Increases in cooling tower or fan-coil cost will reduce or offset the benefits of reduced compression ratio. Lifecycle costs (initial cost plus operating expenses) should be evaluated. Fouling A fouling allowance of 0.00025 ft 2 F h/btu is included in manufacturers ratings in accordance with ARI Standard 550/590. However, fouling factors greater than 0.00025 should be considered in the selection if water conditions are not ideal. Primary Refrigeration Equipment Central cooling plant refrigeration equipment falls into two major categories: (1) vapor-compression refrigeration cycle (compressorized) chillers, and (2) absorption-cycle chillers. In some cases, the chiller plant may be a combination of these machines, all installed in the same plant. Cooling towers, air-cooled condensers, evaporative condensers, or some combination are also needed to reject heat from this equipment. Mechanical chillers could be centrifugal, screw, or reciprocating, and could driven by electric motors, steam turbines, or engines. These chillers can use CFCs, HCFCs, or ammonia as a refrigerant and can cool the inlet air to 42 F (or below, if desired) without the risk of forming ice crystals. Installed cost of motor-driven mechanical chillers is lower than that for any other chiller. Compressors may be purchased as part of a refrigeration chiller that also includes the drive, evaporator, condenser, and necessary safety and operating controls. Reciprocating and helical rotary compressor units can be field-assembled and include air- or water-cooled (evaporative) condensers arranged for remote installation. Centrifugal compressors are usually included in packaged chillers, although they can be very large and sometimes require field erection. These types of chillers also require remote air- or water-cooled ancillary equipment. Ancillary Refrigeration Equipment Ancillary equipment for central cooling plants consists primarily of heat-rejection equipment (aircooled condensers, evaporative condensers, and cooling towers), pumps (primary, secondary, and tertiary), and heat exchangers (water-to water), as well as water pumps and possibly heat exchanger(s). Air-cooled condensers pass outside air over a dry coil to condense the refrigerant. These results in a higher condensing temperature and thus a larger power input at peak condition (although peak time may be relatively short over 24 h). Air-cooled condensers are popular in small reciprocating, scroll and helical rotary compressor units because of their low maintenance requirements. Evaporative condensers pass outside air over coils sprayed with water, thus taking advantage of adiabatic saturation to lower the condensing temperature. As with cooling towers, freeze prevention and close control of water treatment are required for successful operation. The lower power consumption of the refrigeration system and much smaller footprint of the evaporative condenser are gained at the expense of the cost of water and water treatment used and increased maintenance cost. Cooling towers provide the same means of heat rejection as evaporative condensers but pass outside air through an open condenser return water spray to achieve similar adiabatic cooling performance. Either natural or mechanical-draft cooling towers or spray ponds can be used; the mechanical-draft tower (forced-draft, induceddraft, or ejector) can be most easily designed for most conditions because it does not depend on wind. Cooling tower types and sizes range from packaged units to field-erected towers with multiple cells in unlimited sizes. Location of heat

rejection equipment should consider issues such as reinfection or short-circuiting of discharge heat rejection air because of location in a confined area, tower plume, and the effect of drift on adjacent roadways, buildings, and parking lots. Makeup water subtraction meters should be evaluated for both evaporative condensers and cooling towers by the design engineer or owner. In many areas, sewage costs are part of the overall water bill, and most domestic water supplied to a typical facility goes into the sewage system. However, evaporated condenser water is not drained to sewer, and if a utility grade meter is used, potential savings in plant operating costs can be made available to the owner. Metering should be evaluated with chilled-water plants, especially those in operation year-round. Consult with the water supplier to identify compliance requirements. Consider piping cooling tower water blowdown and drainage (e.g., to remove dissolved solids or allow maintenance when installing subtraction meters) to the storm drainage system, but note that the environmental effects of the water chemistry must be evaluated. Where chemical treatment conditions do not meet environmental outfall requirements, drainage to the sanitary system may still be required unless prefiltration can be incorporated. Water pumps move both chilled and condenser water to and from the refrigeration equipment and associated ancillary equipment. Source The source is the point where heat is added to (heating) or removed from (cooling) the system. Ideally, the amount of energy entering or leaving the source equals the amount entering or leaving through the load. Under steady-state conditions, the load energy and source energy are equal and opposite. Also, when properly measured or calculated, temperature differentials and flow rates across the source and loads are all equal. Following equations express the source capacities as well as the load capacities. Any device that can be used to heat or cool water under controlled conditions can be used as a source device. The most common source devices for heating and cooling systems are the following: Cooling source devices Electric compression chiller Thermal absorption chiller Heat pump evaporator Air-to-water heat exchanger Water-to-water heat exchanger The two primary considerations in selecting a source device are the design capacity and the partload capability, sometimes called the turndown ratio. The turndown ratio, expressed in percent of design capacity, is The reciprocal of the turndown ratio is sometimes used (for example, a turndown ratio of 25% may also be expressed as a turndown ratio of 4). The turndown ratio has a significant effect on system performance; lack of consideration of the source system s part-load capability has been responsible for many systems that either do not function properly or do so at the expense of excess energy consumption. The turndown ratio has a significant effect on the ultimate equipment and/or system design selection. Note that the turndown ratio for a source is different from that specified for a control valve. Turndown for a valve is comparable to valve rangeability. Whereas rangeability is the relationship of the maximum controllable flow to the minimum controllable flow based on testing, turndown is the relationship of the valve s normal maximum flow to minimum controllable flow.. 3 Primary/Secondary Pumping Chilled-Water System Where: = heat transfer rate to or from water, Btu/h = density of water, lb/ft 3 = specific heat of water, Btu/lb F t = water temperature increase or decrease across unit, F = water flow rate, gpm For standard conditions in which the density is 62.4 lb/ft3 and the specific heat is 1 Btu/lb F, following Equation becomes