Building Re-Tuning Training Guide: AHU Heating and Cooling Control



Similar documents
newsletter engineers energy-saving strategies for Water-Source Heat Pump Systems volume 36 2 providing insights for today s hvac system designer


HVAC Systems: Overview

Venice Library Humidity Study. for Williams Building Diagnostics, LLC th Street West Bradenton, FL Report April 13, 2015

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) March

Example Retrocommissioning Measure: Opening Throttled Discharge Valves

Automated Commissioning for Energy (ACE) Platform for Large Retail Property. Overview

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Guide Specification SECTION COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Using Time-of-Day Scheduling To Save Energy

Molds and mildew are fungi that grow

How Ground/Water Source Heat Pumps Work

Ener.co & Viridian Energy & Env. Using Data Loggers to Improve Chilled Water Plant Efficiency. Randy Mead, C.E.M, CMVP

CGC s Hybrid System Loop Control

HVAC Processes. Lecture 7

ENHANCED LABORATORY HVAC SYSTEM

1932 Lexington Houston, Texas (713) Recommendations for installation of cooling systems

ENERGY EFFICIENCY ENERGY EFFICIENCY: Saving Dollars While Clearing the Air

for K-12 School Buildings

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, November 2015

Energy Saving Tips. Adjust set point temperature up a few degrees... Window contact. Occupancy sensor. A Programmable Thermostat

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

Rev. No. 0 January 5, 2009

Lesson 36 Selection Of Air Conditioning Systems

Hospital Application Guide. Cost-effective climate control for hospitals

Modeling and Simulation of HVAC Faulty Operations and Performance Degradation due to Maintenance Issues

Analysis of data centre cooling energy efficiency

CHAPTER 8 HVAC (Heating, Ventilation, and Air-Conditioning)

Energy Saving Fact Sheet Air Conditioning

Air Conditioning Clinic

Chilled Water HVAC Systems

Design Guide. Retrofitting Options For HVAC Systems In Live Performance Venues

Home inspectors are not mold inspectors, however they do inspect for defects that

USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book

The District Energy Manager and Classroom Heating

air conditioners how to choose a cooling system

Variable Air Volume - VAV

Failure code manual. content

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

For installation guide see reverse of book

HEATING, VENTILATION & AIR CONDITIONING

The main steam enters the building in the basement mechanical room; this is where the condensate line also leaves the building.

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

How To Control Humidity With A Humidifier

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Bring the fresh in. Dedicated Outside Air Systems

Self-Correcting HVAC Controls Project Final Report

Sustainable Preservation Practices for Managing Storage Environments Webinar: April 3, 2013

Engineers Newsletter. Understanding Single-Zone VAV Systems. providing insights for today s hvac system designer. volume 42 2

CONTROL STRATEGIES FOR HVAC SYSTEMS

Design Options for HVAC Distribution Systems

3/29/2012 INTRODUCTION HVAC BASICS

for Plans Examiners and Building Inspectors

Eurovent Certification for Air Handling Units : Five Energy Efficiency classes to make the right choice

Knowledge for optimal efficiency

14. Troubleshooting Guide

PERCENT OUTDOOR AIR (%OA) CALCULATION AND ITS USE

Thermostatic Wiring Principles by Bob Scaringe Ph.D., P.E.

By Tom Brooke PE, CEM

Tech Byte 27: Small Computer Room and IT Closet Cooling

Energy Efficiency Tips for Businesses

Cornell University Chilled Water Best Management Practices Program

May 26, 2013 Grand Hyatt Tampa Bay Installs Innovative HVAC System Using Heat Pipe Technology Case Study

The Chilled Water and Hot Water Building Deferential Pressure Setpoint Calculation Chilled Water and Hot Water Pump Speed Control

06150 PORVOO, FINLAND Pelican eco ED(D), Pelican eco EDE(D), Pelican eco EDW(D), Pelican eco EDX(D)

Engineering White Paper UTILIZING ECONOMIZERS EFFECTIVELY IN THE DATA CENTER

COMPETENCY ANALYSIS PROFILE Refrigeration and Air Conditioning Systems Mechanic - Branch 1 313A

Programmable Thermostat MODEL XXX With Dehumidify XXX With Out Dehumidify

Dealer Sales & Service Guide

Whole House Dehumidification for Occupant Comfort and Energy Savings

Commissioning - Construction Documents (Page 1 of 6)

REMOTE CONTROL MANUAL

How air conditioning works

GREEN BAY AREA PUBLIC SCHOOL DISTRICT Board Policy Manual ENERGY MANAGEMENT

Ductless Heat Pumps. Gary Nordeen January

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Case Study. Redmond Middle School: Advanced Analytics to Detect Energy Waste in HVAC System

Energy Efficient Homes: Air Conditioning 1

Federation of European Heating, Ventilation and Air-conditioning Associations

CASE STUDY: NEW NCAA DIV. I COLLEGE BASKETBALL ARENA

Environmental Data Center Management and Monitoring

The natural ombination

The natural ombination

Design Options For HVAC Distribution System

How To Get A Passive House

Home Screen...4. Quick Start Guide...5. MyAir Standalone Zone Controls only...5. MyAir Zone Controls With Integrated Unit On/Off Control...

CONCEPTUALIZATION OF UTILIZING WATER SOURCE HEAT PUMPS WITH COOL STORAGE ROOFS

Condensing Boiler Efficiency

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

How To Design A Building In New Delhi

How to Save Over 60% on Cooling Energy Needed by a Data Center? The Roadmap from Traditional to Optimized Cooling

Glossary of HVAC Terms

ENERGY EFFICIENT HVAC DESIGN FOR WARM-HUMID CLIMATE CLIMATE

COMPARATIVE LIFE-CYCLE ANALYSIS OF ENERGY-EFFICIENCY MEASURES AT TVA S CHATTANOOGA OFFICE COMPLEX: PHASE II RESULTS & FINAL DESIGN

We have been working in an ideal climate for thirty years.

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

Transcription:

Building Re-Tuning Training Guide: AHU Heating and Cooling Control Summary The purpose of the air-handling unit (AHU) heating and cooling control guide is to show, through examples of good and bad operations, how AHU heating and cooling can be efficiently controlled. AHU heating and cooling coils are generally located in the discharge-air stream, immediately downstream of the mixing plenum and filters, to provide heating or cooling. On some AHUs, the cooling coil will also be used to de-humidify the air stream. This may require the heating coil to be located downstream of the cooling coil for climates where de-humidification is required. It is also possible that a secondary heating coil in the AHU is located in the downstream side of the supply fan or cooling coil. The purpose of this secondary heating coil is to add additional heat to the air stream in cold climate zones, or climate zones where dehumidification is required. By monitoring the outdoor-air temperature and heating- and cooling-coil-valve signals over time, the building operator can identify times when the AHU is simultaneously heating and cooling the discharge-air stream, and make adjustments to AHU operation. If the outdoor-air temperature heating lockout set point is lower than the outdoorair cooling lockout set point, this may be indicative of a leaking heating and/or cooling-coil valve. Inefficient operation of heating and cooling coils, such as leaky valves, incorrect outdoor-air temperature lockout set points for heating and cooling, poor heating and cooling control such as hunting and overheating and overcooling, and simultaneous heating and cooling, if not corrected, in all likelihood will lead to increased fan, heating and cooling energy consumption. Data needed to verify AHU heating and cooling control To analyze and detect deficiencies in AHU heating and cooling control, for single-duct variableair-volume (SDVAV) AHU(s), the following parameters must be monitored using the trending capabilities of the building automation system (BAS): Outdoor-air temperature (OAT) Cooling-coil-valve signal (CCV) Heating-coil-valve signal (HCV) 1

The recommended frequency of data collection is between 5 and 30 minutes. When analyzing heating and cooling control of the AHU, the trends to look for include: Are outdoor-air temperature lockout set points for heating and cooling reasonable, do they overlap? Is there simultaneous heating and cooling occurring? Are outdoor-air temperature lockout set points for heating and cooling reasonable, do they overlap? Outdoor-air temperature lockout set points for heating and cooling are critical to prevent additional energy consumption that otherwise is not needed. The balance point of the building, i.e., when the building needs neither heating nor cooling, is critical when setting these lockout set points. In general, the heating should be locked out above 50 o F or the lowest outdoor-air temperature that the building can maintain the discharge-air without requiring heat 1. Cooling should be locked out below 55 o F or the highest outdoor-air temperature that the building can maintain the discharge-air without requiring cooling. These set points should be checked to ensure that they are not backwards, i.e., the cooling lockout is lower than the heating lockout. There should be no overlap between these set points at any time. The goal is to lockout cooling during the winter season, and heating during the summer season. Suggested Actions Check the building automation system s (BAS) control logic for accuracy of heating and cooling lockout set points. Make sure that these lockout set points do not overlap. If the outdoor-air temperature heating lockout set point is lower than the outdoor-air cooling lockout set point, check the heating and cooling-coil valves for leaks. Is there simultaneous heating and cooling occurring? The goal is to avoid simultaneous heating and cooling from occurring in the AHU. Some simultaneous heating and cooling can be unavoidable in climate zones where dehumidification is required. The goal is to minimize the amount of heating and cooling occurring simultaneously, and to lock out heating or cooling coils whenever possible. Figure 1 below is a guideline for AHU heating- and cooling-coil-valve signals relative to one another. 1 For some buildings (museums or library) where the AHU provides dehumidification, heating may be required at higher outdoor temperatures. 2

Figure 1: AHU heating and cooling valve positions. The data in Figure 1 shows that the heating has been locked out (the hot-water valve is always at 0% while the chilled-water valve modulates). This would correspond to summertime operation, in which the outdoor-air temperature is always greater than 50 o F. When monitoring simultaneous heating and cooling, analyze the heating-coil valve, cooling-coil valve, and outdoor-air temperature versus time charts. Figure 2 below shows this chart for a 2- day period in November. As you can see, the outdoor-air temperature never gets above 30 o F, yet the cooling-coil valve is always 75% open. The heating coil appears to be 50% open during occupied hours, and then shuts off during the unoccupied periods. The amount of heating required to meet the discharge-air temperature set point would decrease if the cooling coil was locked when the outdoor-air temperatures are low. This is an example of bad operation. Figure 3 shows an example of good operation, where the same 2-day period in November shows the cooling-coil valve locked out. As a result, the heating-coil valve position has dropped from roughly 50% in Figure 2 to 25% in Figure 3 during occupied hours. 3

Figure 2: Simultaneous heating and cooling during the winter season. Figure 3: Cooling-coil valve locked out during winter season. 4

Figure 4 shows another example of good operation. The outdoor-air temperature varies between 50 and 60 o F during this 2-day span in November. The heating-coil valve never opens, and the cooling-coil valve modulates during occupied hours to maintain the discharge-air temperature set point. Figure 4: Heating-coil valve closed during AHU cooling mode. Suggested Actions If the plot of the cooling-coil valve, heating-coil valve, and outdoor-air temperature versus time shows simultaneous heating and cooling, check to make sure the coils are clean and that the valves are not leaking. To check the cooling coil for leaks, touch the cooling coil where it penetrates the AHU. If the pipe is colder than room temperature, then this indicates that the valve is leaking (perform the same check on the heating coil). Additionally, If condensate is observed on uninsulated lines or exposed coil sections during times when mechanical cooling is not being called for by the control system or during times when the outdoor-air conditions should be adequate for economizing, then leaking cooling-coil valves should be suspected. 5