Testing Rules for Thermal Conductivity October 2015



Similar documents
Scheme rules for thermal insulation products for building equipment and industrial installations - VDI certification scheme

Fire 2This Technical Bulletin has been commissioned by the UK SIP Association in

The University of Birmingham (Live System)

STEEL BUILDINGS IN EUROPE. Single-Storey Steel Buildings Part 8: Building Envelope

Quality Regulations for Profiles

RPV - RP - RA air handling units

Prefabricated building PVC vertical sliding window

SANDWICH PANEL FILLING MATERIALS

Master Panel 1000 R5 Roof

Linear thermal transmittance of the assembly of the glazing and the frame in windows

Master Panel 1000 W Wall

DECLARATION OF PERFORMANCE

ETAG 016 SELF-SUPPORTING COMPOSITE LIGHTWEIGHT PANELS. (Part one : G E N E R A L)

ModuSec. Secure and efficient IT room solutions Composite Panel Systems Compared. Panel Systems are not all the same!

03/05/14 REVISOR RSI/JC RD3945

EN Insulating glass units, intended to be used in buildings and construction works

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver

Module 7. CE marking of Vehicle Restraint Systems EN Göran Fredriksson, SSBA

The Danish Enterprise and Construction Authority to inspect CE marking of windows and pedestrian doors

FACTORS AFFECTING ENERGY CONSUMPTION OF BUILDINGS

research highlight Highly Energy Efficient Building Envelope Retrofits for Houses

Colorcoat Technical Paper Fire performance of pre-finished steel cladding systems

Module 3.7. Thermal bridging

Composite Panel Firewall Systems

Thermal Performance of Steel Beam Junctions using Different Connection Methods

Your essential guide to CE Marking

European Organisation for Technical Approvals

Check-list for auditors. Audit visit at candidate registered laboratories

Energy Company Obligation (ECO): Technical Monitoring Questions

Test Report No. C908LPEN

Insulated Roof & Wall Panels. Product Data Sheet. Trapezoidal Insulated Roof Panels KS1000 RW

Section 2.4. Built-up Metal Roofs. Rail and bracket system. Standing seam system. Bu02. Product: Earthwool FactoryClad range Bu01

Garage Sectional Doors

HFM Heat Flow Meter Thermal Conductivity Analyzer

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5

BuildDesk U 3.4. Manual

GUIDANCE SHEET FOR CONSERVATORIES, SUNROOMS AND EXTENSIONS TO DWELLINGS.

FIREPROOF Panels Trimoterm

ProRox Slabs (formerly known as RW slabs)

FIRE BEHAVIOR CERTIFICATION OF THERMAL INSULATION MATERIALS

PROPOSED SPECIFICATION FOR ALUCOBOND PLUS Aluminium Composite Panel Cladding System Fixed Watertight Cassette Panel System - 4mm thick

Annex to Accreditation Certificate D ZE according to DIN EN ISO/IEC 17065:2013

Hoesch Matrix System individuell. ThyssenKrupp Steel Europe Thinking the future of steel

Test Report No. C926LPEN

Loss Prevention Standard

FIRE PERFORMANCE OF STRUCTURAL INSULATED PANEL SYSTEMS

Dow Corning PROPRIETARY. Dow Corning. A Thermal Modelling Comparison of Typical Curtain Wall Systems


Improving thermal insulation of concrete sandwich panel buildings

Dubai Municipality Standard DMS 1: Part 5: 2004

High performance thermal insulation materials

European Technical Approval ETA 13/0282

) and air spaces (R a

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

Insulation R-Value Comparisons

European Technical Approval ETA 13/0384

HEAT TRANSFER ANALYSIS OF COLD STORAGE

8 EXTRA LIGHT GRC SANDWICH ELEMENTS FOR ROOFING IN INDUSTRIAL BUILDINGS

AMF Line; wall absorbers Wall mounted acoustic designs PERFORMANCE CEILINGS. M ore s c op e f or i n n ovat i on MADE IN GERMANY

Signs of insulation problems In the winter. In the summer. conditioning system

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

THERMAL INSULATION MATERIALS TEST METHOD SELECTION LIST

FACADE DESIGN & EXECUTION

Structural Insulated Panels: Design and Application

ORAY PREFABRICATED GSM SHELTER CONTAINERS TECHNICAL SPECIFICATIONS

ETAG 004 EXTERNAL THERMAL INSULATION COMPOSITE SYSTEMS WITH RENDERING

Introduction. Facade Fire Test on PUR External Thermal Insulation Composite System (ETICS)

Test Report No. C1319LPEN

Building Envelope Design by Roxul (BEDR ) FireWall and Roxul Plus MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

WORKING DOCUMENT FOR SCC CONSULTATION CONSTRUCT09/874 EUROPEAN COMMISSION ENTERPRISE AND INDUSTRY DIRECTORATE-GENERAL

Guidance from the Group of Notified Bodies for the Construction Products Directive 89/106/EEC. GNB-CPD position paper from SG17 - EN :2009

Building Envelope Design using ROXUL. FIREWALL and ROXUL PLUS MB. Fire Rated Board Insulation for Pre-Engineered Metal Buildings

Rockwool Cladding Roll

Assessment Report Construction Product Regulation* * CPR - REGULATION (EU) No 305/2011

B. ASTM C 533 Calcium Silicate Block and Pipe Thermal Insulation. C. ASTM C 547 Mineral Fiber Preformed Insulation

ROCKWOOL Rigid, Semi-rigid and Flexible Slabs are high quality resin bonded slabs that can be used for thermal, acoustic and fire insulation.

REACTION TO FIRE CLASSIFICATION REPORT No. RA ACCORDING TO THE EUROPEAN STANDARD NF EN A1:2013

APIB Test Specification No. 09 WATERPROOFING MEMBRANES SWISS HAIL IMPACT PROTECTION REGISTER HSR / 07-15en Version 1.

General Properties of Polyurethane Insulation. Chris Ungermand Huntsman Nordic IDA Fyn seminar Odense

Glass partitions SFB 3074

DOCUMENT CAESAS/1: SCHEME DESCRIPTION AND BENEFITS

STANDARD SPECIFICATION. for. Plumbing, Heating, Hot Water, Cold Water & Electrical work. Sussex Lodge London W2 & 16 Stanhope Terrace London W2

Mineral fibreglass insulation

European technical approval

Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA / Israel. J. Magner Dipl.-Ing. N. Machill.

EN Insulating glass units, intended to be used in buildings and construction works

Sealfire W1000 Compound. (2 references for the same product) Fire Stopping and Sealing Product: Penetration Seals

ENERGY AUDIT. Project : Industrial building United Arab Emirates (Case study) Contact person (DERBIGUM):

Eurooppalainen tekninen hyväksyntä ETA - 13/0613 European Technical Approval

INSULATION FOR PRE-ENGINEERED METAL BUILDINGS. ROXUL SAFE 55 & 65 and ROXUL PLUS MB. Insulation for Pre-Engineered Metal Buildings

Part A: Fluid properties

ETAG 022. GUIDELINE FOR EUROPEAN TECHNICAL APPROVAL of Watertight covering kits for wet room floors and or walls

European Technical Approval ETA 12/0419

Long-Term Hygrothermal Performance of Green Roofs

Transcription:

Testing Rules for Thermal Conductivity October 2015

Testing Rules for Thermal Conductivity (October 2015) 1 Normative references (to be inserted as additional chapter in the Testing Rules for Panels) 1. EN 14509 Self-supporting double skin metal faced insulating panels - Factory made products Specifications 2. EN 13172 Thermal insulating products. Evaluation of conformity 3. EN ISO 10456 Building materials and products. Hygrothermal properties - Tabulated design values and procedures for determining declared and design thermal values (replacing EN 12524) 4. Product standards for core materials: EN 13162 Thermal insulation products for buildings Factory made mineral wool (MW) products Specification EN 13163 Thermal insulation products for buildings Factory made expanded polystyrene (EPS) products Specification EN 13164 Thermal insulation products for buildings Factory made extruded polystyrene foam (XPS) products Specification EN 13165 Thermal insulation products for buildings Factory made rigid polyurethane foam (PU) products Specification 5. EN ISO 10211 Thermal bridges in building construction Heat flows and surface temperatures Part 1: Detailed calculations (ISO 10211) 6. ISO 9001 Quality management systems Requirements For all standards mentioned, the last version published in the Official Journal of the European Union (OJEU) is the basis of these Testing Rules.

Testing Rules for Thermal Conductivity (October 2015) 2 Determination of the thermal conductivity based on EN 14509, 5.2.2 and A.10 The declared thermal conductivity shall be determined in accordance with the procedures described in the appropriate product standard for the core material in the direction used for insulation in the sandwich panel. For preformed CE-marked mineral wool core materials, the values and the results from the manufacturer of the core material can be used without any further testing, if the manufacturer has a quality system that respects the requirements of EN 13172, the CE markings provide the λ values for the orientation used in the panel manufacturing process and these core material performances are controlled under responsibility of a third party, in AVCP system 1+ (EPAQ system A of PPA-Europe). For other materials than core materials (e.g. metal sheets), tabulated values in accordance with EN 10456 shall be used. The declared thermal conductivity (λ Declared) and the design value of the thermal conductivity (λ Design) shall be determined. In case of aged values, λ Declared is equal to λ Design (if not stated otherwise). Afterwards, the thermal transmittance value (UdS) for the panel system excluding the transversal joints, but taking into account the effects of the longitudinal joints, shall be calculated according to EN 14509. Above note that λ Design is a national choice. General procedure (process chart) Determination of thermal conductivity Manufacturer: testing 4 samples of different batches Basic testing / ITT Accepted notified (test) laboratory 1) : testing 4 samples of the same batches as the manufacturer Manufacturer: additional testing of minimum 6 samples from other batches Independent Expert has to compare the test results and then to make the statistical evaluation considering the ITT values from manufacturer and accepted notified (test) laboratory 1) λ Declared 1) Accepted by PPA-Europe for thermal conductivity testing. As there are no notified bodies for thermal characteristics in case of EN 14509, the tests can be performed by notified bodies for testing the thermal conductivity of PU according to EN 13165, of MW according to EN 13162, of EPS according to EN 13163 or of XPS according to EN 13164, from the list of third parties accepted by PPA-Europe for thermal conductivity testing.

Testing Rules for Thermal Conductivity (October 2015) 3 The declared thermal conductivity (λ Declared) shall be determined in accordance with the procedures described in the appropriate product standard for the core material. A. Test procedure for panels with PU core: The method according to Fixed increment procedure shall be used (for core material with CO2 as propellant, additional requirements have to be respected). 1. Basic Testing / ITT: a. Initial λ-test: 4 samples 20 mm thick or a variety of different thicknesses by agreement with the accepted notified (test) laboratory, cut out of the center of panels from different productions and thicknesses, without cover sheets, have to be tested in the same time by the manufacturer and by an accepted notified (test) laboratory from the list of third parties accepted by PPA-Europe for thermal conductivity testing. The manufacturer has to manage the coordination of the parallel testing. b. Normality-test: the same 4 samples have to be tested by an accepted notified (test) laboratory, after aging 21 days at 70 C. 2. Additional Testing: The manufacturer has to perform 6 more λ-tests on different batches. 3. Comparing of the test results by an Independent Expert: a. The difference between the λ-values of the manufacturer and the accepted notified (test) laboratory shall be within the tolerances given in Table 1. b. If the difference of all 4 single λ-values after aging 21 days at 70 C is lower than 6mW/(m*K), the fixed increment can be used. Evaluation of the test results by an Independent Expert: Number of tests: a. Fixed increment procedure: λ ini + fixed increment b. Statistical evaluation delivers λ 90/90 c. Rounding rules λ Declared 4 samples of different batches have to be tested by the manufacturer. Simultaneously another 4 samples of the same 4 batches have to be tested by a European accepted notified (test) laboratory from the list of third parties accepted by PPA-Europe for thermal conductivity testing. The manufacturer has to test another 6 samples from different batches to complete the 10 results for the ITT test. The Independent Expert has to control that the results of the manufacturer and the results of the accepted notified (test) laboratory are equal. Otherwise, the reason for the different results has to be eliminated and the tests may have to be repeated. The EPAQ Independent Expert has also to control

Testing Rules for Thermal Conductivity (October 2015) 4 if the test results of the normality test fulfill the requirements for the normality test. Following, the Independent Expert has to determine the declared thermal conductivity (λ Declared) and the design value (λ Design). These values have to be used by the Independent Expert to calculate the U-values (Uds) for the Certification Document and the threshold values for the FPC. Further running production: The manufacturer has to collect and document all results from his FPC (minimum once a month with possibility to test more). The single test results with the fixed increment have to be below the declared value. Furthermore, the results have to be added in the statistical evaluation to control that the newly calculated values of the thermal conductivity (λ Declared_new) and the design value (λ Design_new) are below or equal to the values of the initial type testing that are used for declaration on the CE-mark and for calculating the U-values (Uds). During each external third party control according to the Quality Regulations, a panel has to be taken out of the production and the thermal conductivity has to be tested in the laboratory of third party accepted by PPA-Europe. The single test results with the fixed increment have to be below or equal to the declared value, otherwise, the reason for the deviation has to be cleared and the tests have to be repeated or the declared values have to be changed. Furthermore the results have to be added in the statistical evaluation to control that the newly calculated values of the thermal conductivity (λ Declared_new) and the design value (λ Design_new) are below or equal to the values of the initial type testing that are used for declaration on the CE-mark and for calculating the U-values (Uds). If the test results of the manufacturer and/or the accepted notified (test) laboratory show permanent deviation from the declared thermal conductivity, the declared and design values as well as the U-values (Uds) have to be adjusted in the Certification Document by an Independent Expert. B. Test procedure for panels with MINERAL WOOL or EPS core: 1. Basic Testing / ITT: Initial λ-test: 4 samples 50 mm thick or thicker (20 mm thick in case 50 mm is not applicable for the manufacturer), cut out of the center of panels from different productions and thicknesses, without cover sheets or lamellas taken out before bonding with the steel sheets, have to be tested in the same time by the manufacturer and by an accepted notified (test) laboratory from the list of third parties accepted by PPA-Europe for thermal conductivity testing. The manufacturer has to manage the coordination of the parallel testing. Samples from MW slabs must be cut in such way so that they correspond to lamellas; the cutting direction (line direction or transversal direction) has to be noticed, because thermal conductivity is different.

Testing Rules for Thermal Conductivity (October 2015) 5 2. Additional Testing: The manufacturer has to perform 6 more λ-tests on different batches. 3. Comparing of the test results by an Independent Expert: The difference between the λ-values of the manufacturer and the accepted notified (test) laboratory shall be within the tolerances given in Table 1. Evaluation of the test results by an Independent Expert: Number of tests: a. Statistical evaluation delivers λ 90/90 b. Rounding rules λ Declared 4 samples of different batches have to be tested by the manufacturer. Simultaneously another 4 samples of the same 4 batches have to be tested by a European accepted notified (test) laboratory from the list of third parties accepted by PPA-Europe for thermal conductivity testing. The manufacturer has to test another 6 samples from different batches to complete the 10 results for the ITT test. The Independent Expert has to control that the results of the manufacturer and the results of the accepted notified (test) laboratory are equal. Otherwise, the reason for the different results has to be eliminated and the tests may have to be repeated. Following, the Independent Expert has to determine the declared thermal conductivity (λ Declared) and the design value (λ Design). These values have to be used by the Independent Expert to calculate the U-values (Uds) for the Certification Document and the threshold values for the FPC. In case the tests for thermal conductivity are performed by the manufacturer of the mineral wool, the manufacturer of the mineral wool has to be involved in the basic tests and has to test also 4 samples of the same batch as the accepted notified (test) laboratory and as or instead of the manufacturer of the panel. The manufacturer of the mineral wool has to follow the regulation of the EN 13172. Further running production: The manufacturer has to collect and document all results from his FPC (minimum once a month with possibility to test more). The single test results have to be below the declared value. Furthermore, the results have to be added in the statistical evaluation to control that the newly calculated values of the thermal conductivity (λ Declared_new) and the design value (λ Design_new) are below or equal to the values of the initial type testing that are used for declaration on the CE-mark and for calculating the U-values (Uds). Otherwise, the reason for the deviation has to be cleared and the tests have to be repeated or the declared values have to be changed. During each external third party control according to the Quality Regulations, a panel has to be taken out of the production and the thermal conductivity has to be tested in the laboratory of a third party accepted by PPA-Europe. The single test results have to be

Testing Rules for Thermal Conductivity (October 2015) 6 below the declared value. Furthermore, the results have to be added in the statistical evaluation to control that the newly calculated values of the thermal conductivity (λ Declared_new) and the design value (λ Design_new) are below or equal to the values of the initial type testing that are used for declaration on the CE-mark and for calculating the U-values (Uds). If the test results of the manufacturer and/or the accepted notified (test) laboratory show permanent deviation from the declared thermal conductivity, the declared and design values as well as the U-values (Uds) have to be adjusted in the Certification Document by an Independent Expert. Core material Mineral Wool PUR / PIR Others Type of production continuous continuous discontinuous discontinuous Single- / Meanλ-values Maximum deviation allowed (%) s 7,5 m 5 s 5 m 3 s 7,5 m 5 s 5 m 3 Table 1. Maximum deviation allowed between λ-values obtained by manufacturer and by the accepted notified (test) laboratory