Fire Alarm Call Points, Hazardous Location BG and PB Description: These manual fire alarm call points have been designed for use in hazardous locations and harsh environmental conditions. The GRP enclosures are suitable for use offshore or onshore, where light weight combined with a high level of corrosion resistance is required. Features: ATEX approved UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups A-D Class II, Div 2, Groups F & G Class I, Zones 1 & 2, AExd IIC T4 Ordinary locations: Audible-Signal Device CSA Certified NEMA 4x &6, IP66 and IP67 Certified temperature 13 F to +131 F ( 25 C to +55 C) Corrosion resistant GRP Plastic break glass element available Retained stainless steel cover screws Optional lift flap Key operated test facility on BG Architects and Engineers Specifications Fire alarm call points and push buttons for hazardous locations and harsh environments shall be UL Listed for Class I, Division2, Groups A,B,C&D, and Class I, Zone 1&2 applications. They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -13 F to +131 F (-25 C to +55 C). Actuation of the call point or push button shall require the opening of a flap and depression of an actuator. An actuated unit shall remain latched until reset. A reset operation shall only take place through the use of a key. ATEX GOST
Specification Certification: Voltage: Up to 240V. Certified temp: Configuration Options: UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups A-D. Class II, Div 2, Groups F & G. Class I Zones 1 & 2, AExd IIC T4. Listing No: E186629 Ordinary locations: Audible-Signal Device. Listing No. S8117. CSA Certified to C22.2 (PB only), Nos. 0-M, 0.4M, 14-M, 25,30-M, 94, 142-M 1987, 157M 1987, 157-92, Enclosure Type 4, 4A, Class 1, Groups A-D, Cert. No. 79120. ATEX Approved: EN50014, EN50018, EN50019, EN50028. Cert. No. BAS02ATEX2105X (BG & PB), EExed II C T6 (switch only), EExedm IIC T4 (other versions). Zones 1 and 2. BGUL: 13 F to +131 F ( 25 C to + 55 C); PBUL: 13 F t+131 F ( 25 C to +55 C). PB (CSA): -58 F to +104 F (- 50 C to +40 C). Ingress Protection: NEMA 4x & 6, IP66 & 67. Terminals: 6 x 14 AWG standard (BGUL), 7 or 9 x 14 AWG standard. Switch Rating (1 or 2 changeover switches fitted): Max Rating 240VAC, 3A. Cable Entries: Weight: Material: Model Certification Entries Labels Switches Features Terminals Finish Finish: Resistors: Up to 4 entries 1 2 NPT. 2.6 lb/1.2kg (Varies with model & entries). Glass reinforced polyester. Red epoxy painted finish as standard or to Customer s specification. Various configurations available on versions up to 24V, 470R minimum. LED Indication: A high intensity red LED can be fitted as an optional extra to indicate operation on versions up to 24V. Labelling: BG Glass label reads either (1) Fire Break glass press here. (2) Break glass press here. (3) Worded to Client s requirements. PB & BG Duty label worded to Client s requirements. Riveted on. PB & BG Tag label worded to Client s requirements. Screwed on. Model BG PB Entries Certification CSA Exi (PBI only) UL Class I, Div. 2 UL - Ordinary locations Standard Models 1 /2" NPT *C *Prefix entry size (see diagram above) with entry position code e.g. 1A, 2A. IC UL UW Labels None 0 Glass label (1) reqd. 1 Glass label (2) reqd. 2 Glass label (3) reqd. 3 Duty label reqd. 4 Tag label reqd. 5 Specify wording on 3, 4 or 5 as required. Series Model Number Order Decription Switches PB PBUL4C6C4DSN7R 109210-001 Push button, Fire label, Red finish Features Single changeover *S Double changeover *D *Prefix with voltage A for A.C. D for D.C. except for BGI. None N LED A Lift Flap (BG only) B Resistor Series *C Resistor EOL *D Break glass P *Specify values Finish Red (Standard) R Natural Black N Blue B Yellow Y Grey G Yellow/Black Stripes X Other specify S Terminals *BGUL only *6 x 14 AWG (standard) 6 7 x 14 AWG (standard) 7 9 x 14 AWG (optional) 9 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA BG and PB 08/06
Strobe/Sounder Combination Units, Heavy Duty Industrial and Marine, Weatherproof Description: This range of audio/visual combination units may be assembled from a range of strobes and horns. Mounted on a sturdy, drilled, painted, stainless steel plate, the units are pre-wired as standard such that a single input operates both the sounder and strobe simultaneously. Units are available for use in potentially explosive atmospheres and dedicated units are now available for use in industrial and marine environments. Example of installed combination unit Features*: Zones 1, 2 and safe area use ATEX approved Ex II 2GD UL listed Class I, Div. 1 & 2, Groups C & D IP66 and 67 Certified temperature 67 F to +158 F ( 55 C to +70 C) Corrosion free GRP strobe/sounder Strobe available as xenon, filament, fluorescent or LED Xenon: up to 21J Filament: up to 100W Fluorescent: up to 39W LED: up to 192cd Sounder: up to 115dBA output at 1 metre All stainless steel (316), epoxy painted back plate *Model dependent. XB11/DB3 Example shown is for illustration only. Other combinations are available. Architects and Engineers Specifications Horn/Strobe Combination units Horns and strobes for hazardous locations and harsh environments shall be factory assembled in combination on a stainless steel mounting plate and shall be factory wired for simultaneous operation of the horn and strobe from a single input. Speaker/Strobe Combination units Speakers and strobes for hazardous locations and harsh environments shall be factory assembled in combination on a stainless steel mounting plate with separate inputs provided for the speaker and the strobe. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Configuration Options: 1. XB11/DB3 or XB11/DB4 Explosionproof Xenon 5J; Sounder up to 115dB(A), all GRP corrosion free products. Certification: ATEX: Ex II 2GD, EExdIIBT5. UL: Class I, Div. 2, Groups C & D. Voltage: 24V d.c.,110v a.c., 240V a.c. Strobe: Standard: XB11 (Xenon 5J). Option: Filament (10W). Fluorescent ( 10W). Sounder: Standard: DB3 (long flare) 115dBA at 1 metre. Option: DB3 (short flare) 108dBA at 1 metre. Dimensions (mm): 420 (height) x 220 (width) x 337 (depth). Options: Refer to data sheet. Specify when ordering. Ordering information Specify options 1 to 4 Product 1. Certification 2. Voltage 3. Lens color 4. Finish XB11+DB3 + ATEX UL + see above + Red Amber + Natural Black Red or XB11+DB4 2. SM87HXB/DB1 Explosionproof Xenon 5J; Sounder up to 110dB(A), LM25 or stainless steel construction, red finish. Certification: ATEX: Ex II 2G, EExdIIBT4(T3). UL: Class I, Div. 1, Groups C & D. Voltage: 24V d.c.,110v a.c., 240V a.c. Strobe: Standard: SM87 (Xenon 5J). Option: Filament (10W). Fluorescent ( 10W). LED ( 192cd) Sounder: Standard: DB1 HP 110dB(A) at 1 metre. Option: DB1 P 106dB(A) at 1 metre. Dimensions (mm): 351 (height) x 228 (width) x 205 (depth). Options: Refer to data sheet. Specify when ordering. Note: Example only actual arrangement may vary (contact sales office) Ordering information Specify options 1 to 5 Product 1. Body Material 2. Certification 3. Voltage 4. Lens color 5. Finish SM87HXB+DB1HP + LM25 stainless steel + ATEX UL + see above + Red Amber + specify Ordering information Specify options 1 to 5 Product 1. Body Material 2. Certification 3. Voltage 4. Lens color 5. Finish SM87HXB+DB3 + LM25 stainless steel + ATEX UL + see above + Red Amber + specify 3. XB13/DB12 or XB13/DB15 Heavy Duty Industrial & Marine Xenon 10J; Sounder DB12 (DB15) up to 110dB(A) (117 db(a)) Applications: Voltage: Strobe: Sounder: Harsh Industrial & Marine Environments. 12V, 24V d.c., 110V, 240V a.c. Standard: XB13 (Xenon 10J). Standard: DB12 110dB(A) at 1 metre. Standard: DB15 115dB(A) at 1 metre. Dimensions (mm): 300 (height) x 195 (width) x 220 (depth). Ordering information Specify options 1 to 3 Product 1. Voltage 2. Lens color 3. Finish XB13/DB12 + see above + Red Amber + Natural Red Standard Models Series Model Number Order Decription XB11/DB3 XB11DB3UL24CR 109209-002 Multitone/Strobe, Clear lens, Red finish XB11/DB4 XB11DB4UL25CR 109209-001 Speaker/Strobe, Clear lens, Red finish XB11/DB3 XB11DB3UL24RR 109209-003 Multitone/Strobe, Red lens, Red finish XB11/DB4 XB11DB4UL25RR 109209-004 Speaker/Strobe, Red lens, Red finish Other combinations of strobes and sounders are available please contact sales office for detailed specifications. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA Combo Units 08/06
Horn - 103dB, Explosion Proof, High Output DB1 Description: This range of light weight, flameproof horns has been designed with a high weatherproof rating to cope with the harsh environmental conditions found offshore and onshore in the oil, gas and petrochemical industries. New electronic circuitry allows the DB1P and DB1HP to be switched between two selectable tones by either reversing the supply polarity, or connecting a second voltage supply. The higher output are particularly suitable for noisy environments. Features*: UL Listed Class I, Div 1. Groups C & D Class I, Zone 1 and Zone 2 use ATEX approved NEMA 4x, IP66 Certified temperature 13 F to +158 F ( 25 C to +70 C) NFPA 72 compliant 4 wire diode monitored connection for operation in supervisory mode Up to 103 dba output @ 10 feet Marine grade alloy Up to 27 output tones, user selectable 12V, 24V & 48 VDC, 110 VAC Tones can be selected remotely Any two tones may be switched via the external voltage supply *Depends on version Architects and Engineers Specifications Explosion-proof horns shall be UL Listed for Class I, Division 1, Groups C&D, and Class I, Zone 1 hazardous locations. The horns shall be constructed of marine grade alloy with an epoxy paint finish and shall meet NEMA 4x and IP 66 environmental requirements over a temperature range of -13 F to 158 F (-25 C to 70 C) in hazardous and harsh environments. The horns shall have 27 user selectable output tones. Multiple horns shall be able to operate in synchronization. Rated current draw at 24 vdc shall not exceed 250 ma for rated sound output of 93 dba at 10 feet or 700 ma for rated sound output of 100 dba at 10 feet. The horns shall be capable of direct surface mounting. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
NOTE:- DB1H(P) DIMENSIONS IN BRACKETS Specification Certification: UL Listing: Class I, Div 1, Groups C & D. Listing No. E187688. ATEX approved: EExd, IIB T3 Cert No. Baseeta 02ETEX0207 for DB(1P) Cert No. Baseeta 02ETEX0209 for DBH(P) Material: Finish: Max Sound Levels: Weight: LM25 corrosion resistant alloy or ANC4B stainless steel with stainless steel cover screws. ABS flare. Epoxy paint finish as standard or to customer's specification. DB1(P)=93±3dB(A) (86±3dB(A) for 12V DB1). DB1H(P)=100 ± 3dB(A) @ 10 feet Note: Sound level is dependent upon the tone selection. DB1P 7.7lb./3.5 Kg approx. DB1HP 12.3lb./5.6 Kg approx. Certified Temperature: 13 F to +158 F ( 25 C to +70 C) Ingress Protection: NEMA 4x, IP66. Tone Selection: 27 User Selectable Tones 1 Alt Tones 800/970 Hz at 1/4 sec. 15 554 Hz for 0.1S/440 Hz for 0.1S 2 Sweeping 800/970 Hz at 7 Hz 16 Int 660 Hz 150 ms on 150 ms off 3 Sweeping 800/970 Hz at 1 Hz 17 Int 660 Hz 1.8 sec. on 1.8 sec. off 4 Continuous at 2850 Hz 18 Int 660 Hz 6.5 sec. on 13 sec. off 5 Sweeping 2400-2850 Hz at 7 Hz 19 Continuous 660 Hz 6 Sweeping 2400-2850 Hz at 1 Hz 20 Alt 554/440 Hz at 1 Hz 7 Slow Whoop 21 Int 660 Hz at 7/8 Hz 8 Sweep 1200-500 Hz at 1 Hz 22 Int 2850 Hz 150 ms on 100 ms off 9 Alt Tones 2400/2850 Hz at 2 Hz 23 Sweep 800-970 Hz at 50 Hz 10 Int Tones of 970 Hz at 1 Hz 24 Sweep 2400-2850 Hz at 50 Hz 11 Alt Tones 800/970 Hz at 7/8 Hz 25 3x970 Hz pulses 0.5 off, 1.5 off 12 Int Tone at 2850 Hz at 1 Hz 26 3x2850z pulses 0.5 on/0.5 off, 1.5 off. 13 970 Hz at 1/4 sec. on 1 sec. off 27 Int 3100 Hz 0.3 sec. on 0.7 sec. off 14 Continuous at 970 Hz Current Consumption: DB1(P) DB1H(P) 12V 125mA 900mA 24V 250mA 700mA 48V 250mA 110V 60mA 200mA Labels: Entries: Terminals: Duty and tag labels optional. Up to 3 x 1/2" or 3/4" NPT Suitable to accept up to 12AWG conductor size Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Single Stage - 4 wire diode monitored connection - on board diode allows unit to be operated in supervisory mode when monitoring line in reverse polarity Two Stage - Switchable unit available in DC versions only either by: (i) Reversing the polarity of the supply, or, (ii) By a 3 wire common +ve system, switching between the -ve lines Unit Type Voltage Cable Entries Duty Labels Tag Label Features Finish DB1P ULA DB1HP ULA Voltage 12V d.c. 012 24V d.c. 024 48V d.c. DB1(P) only 048 110V a.c. 110 240V a.c. 240 Entries 1 /2" NPT C 3 /4" NPT D LHS 1 RHS 2 Bottom 3 *Prefix position with entry size code e.g. C1C3 = 20mm left and bottom entries. Standard Models Series Model Number Order Decription DB1 DB1PULA024D1D2NNNR 109205-001 Multitone, 93dBA, 24 VDC, Red finish DB1 DB1HPULA024D1D2NNNR 109205-002 Multitone, 100dBA, 24 VDC, Red finish Duty Labels None Required* *(Please specify) Tag N D None Required *Please specify Label N T Finish Red Grey Special Features Not required Yes* *Please specify R G S N Y 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA DB1 08/06
Horns - Up to 108dB(A), Hazardous Location, Weatherproof DB3 Range Sounder/Strobe Combination Unit Description: This range of light weight all GRP, explosionprrof horns is intended for use in potentially explosive atmospheres and has been designed with high ingress protection to cope with the harsh environmental conditions found offshore and onshore in the oil, gas and petrochemical industries. The flamepaths, flare and the body, are manufactured completely from a UV stable glass reinforced polyester. Stainless steel screws and sinter are incorporated thus ensuring a corrosion free product. A tapered flamepath is used to overcome the problems of assembly of parallel spigot flamepaths. An optional Exe terminal chamber is available. Features*: UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups A, B, C & D Class II, Div 2, Groups F & G Class I, Zones 1 & 2, AExd IIC T4 Ordinary locations: Audible-Signal Device ATEX approved NEMA 4x &6, IP66 and IP67 Certified temperature 67 F to +158 F ( 25 C to +70 C) All GRP corrosion free flamepaths Up to 108dBA output at 10 feet Integral volume control 27 tones, user selectable Two tones may be switched via the external voltage supply Horn/Strobe Combination Unit available *Depends on version Architects and Engineers Specifications Horns for hazardous locations and harsh environments shall be UL and cul listed for Class I, Division 2, Groups A,B,C&D, and Class I, Zones 1&2, AExd IIC T4 applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67 F to +158 F (-55 C to +70 C). The horns shall have 27 user selectable output tones. Multiple horns shall be able to operate in synchronization. Rated current draw at 24 vdc shall not exceed 380 ma for rated sound output of 105 dba at 10 feet. The horns shall include an integral volume control and a stainless steel mounting bracket with ratchet facility to direct sound output. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Terminals: Mounting: Labels: Cable Entries: Tone Selection: Horn/Strobe Unit: Two Stage Unit DB3P: D.C. A.C. 4 x 14 AWG, 6 x 14 AWG Stainless steel bracket with ratchet facility. Duty and tag labels optional. Up to 2 x 1 /2" NPT UL. 27 user selectable tones. The DB3 may be combined with a strobe to create a combined audio/visual alarm. Switchable between two tones: (i) Reversing the polarity of the supply, or (ii) by a 3 wire common +ve system, switching between the two ve lines. (iii) Closing/opening connection between 2 terminals e.g. by using a volt free relay contact at the panel. 2 tones must be specified at time of order. 3/4 Tone Unit: Remote 3 or 4 tone available contact sales office for details. Specification Certification: Material: Finish: UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups A, B, C & D Class II, Div 2, Groups F & G. Class I Zones 1 & 2, AExd IIC T4. UL Listing No: E203310. Ordinary locations: Audible-Signal Device. Listing No. S8116. ATEX Approved: CENELEC EN50014, 18, 19 Cert. No. BAS00ATEX2097X, EExd IIC. Cert. No. BAS00ATEX2098X, EExde IIC. Zones 1 and 2. Body & horn in anti-static, UV stable, glass reinforced polyester. Swivel bracket & captive cover screws in stainless steel. Body and horn, natural black or epoxy paint coated to client s color requirements Sound Output: DB3 105 ± 3dB(A) at 10 feet (tone dependent) Volume Control: *Nominal Output (dba) Input Current (ma) 83 50 95 100 98 150 101 200 102 250 104 300 105 350 *Output measured with 24V input voltage. Tone set to 970Hz continuous. Weight: Certified Temperature: Ingress Protection: Voltage: Current Consumption: 13.2lb./6.0kg approx. 67 F to +158 F ( 55 C to +70 C) NEMA 4x & 6, IP66 and IP67 Up to 48V d.c. Up to 254V a.c. V 12VDC 24VDC 48VDC 110VAC 120VAC 220VAC 230VAC 240VAC 254VAC I 760mA 380mA 190mA 135mA 124mA 68mA 65mA 62mA 59mA Configuration Options: The following code is designed to help in selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Other Unit Type Certification Voltage Labels Entries Options Finish Certified Plugs Type DB3 DB3P Standard Models Series Model Number Order Decription DB3 DB3 Details Standard unit Two stage Type UL Listed UL (Ordinary Locations) UL UW Voltage 12V - 48V d.c. 048 110V a.c. 110 120V a.c. 120 220V a.c. 220 230V a.c. 230 240V a.c. 240 254V a.c. 254 DB3UL048N2CNRZ 109207-001 Multitone, 108 dba, 24 VDC, Red finish, plugs DB3UL110N2CNRZ 109207-006 Multitone, 108 dba, 110 VAC, Red finish, plugs Label Duty D* Tag T* None N *Please specify wording Entries Features 1 x 1 /2" NPT 1C 2 x 1 /2" NPT 2C Colour None N End of line resistor E* *State value. Natural Black N Red R Special S* *Please specify Certified Plugs Plugs *Z *must always be indicated with a Z. If no plugs are required omit the "Z" from the order code 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA DB3 02/07
Speakers - Up to 25 Watts, Hazardous Location, Weatherproof DB4 Range 15W/20W/25W (Long Flare) 8W (Short Flare) Description: This range of loudspeakers, intended for use in potentially explosive gas and dust atmospheres, has a power rating of up to 25 watts and is suitable for use in all gas groups including hydrogen. The flamepaths, flare and the body, are manufactured completely from a UV stable glass reinforced polyester. Stainless steel screws and sinter are incorporated thus ensuring a corrosion free product. A tapered flamepath is used to overcome the problems of assembly of parallel spigot flamepaths. This product does not include a blocking capacitor. Contact Cooper Wheelock Technical Support for models with a blocking capacitor*. *Coming Soon Features*: UL listed for USA and Canada: Class I, Div 2, Groups A-D. Class I, Zones 1, AExd IIC, T4 Class II, Div 2, Groups F & G ATEX approved NEMA 4x & 6, IP66 and IP67 Certified temperature 67 F to +158 F (-55 C to +70 C) GRP corrosion-free flamepaths 109dBA at 25 watts at 10 feet 8, 15 and 25 watt versions Power tappings, via integral transformer Ratcheted swivel bracket Stainless steel sinter Stainless steel mounting bracket Tapered flamepath *Depends on version Architects and Engineers Specifications Speakers for hazardous locations and harsh environments shall be UL and cul listed for Class I, Division 2, Groups A,B,C&D, and Class I, Zones 1, AExd IIC T4 applications. They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67 F to +158 F (-55 C to +70 C). The speakers shall be rated for 70 vrms input with power taps for 1,2,4,6,12.5 or 25 watt operation. Rated sound output shall be up to 109 dba at 10 feet and rated frequency response shall be 400Hz to 8kHz. The speakers shall include a stainless steel mounting bracket with ratchet facility to direct sound output. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Polar plot (1W/1m) for 25 watt version. Specification Rated Power: Certification: Material: Finish: Output: Weight: Certified Temperature: Ingress Protection: Frequency Range: Voice Coil Impedence: Transformer: 8, 15 or 25 watts RMS continuous (at 77 F). UL listed for USA and Canada: Class I, Div 2, Groups A-D Class I, Zones 1, AExd IIC T4. Class II, Div 2, Groups F & G ATEX approved: EN50014, 18, 19. No. BAS00ATEX2097X. EExd 11C T41/T5 Cert. No. BAS00ATEX2098X. EExd 11C T41/T5 Zones 1 not for use in atmospheres containing carbon disulphide Body & horn in anti-static, UV stable, glass reinforced polyester. Swivel bracket in stainless steel. Captive cover screws in stainless steel. Body and horn, natural black or epoxy paint coated to client s color requirements. 97 dba at 1 Watt at 10 feet 109 dba at 25 Watts at 10 feet Measured in accordance with IEC 268. 11lb./5.0kg approx. 67 F to +158 F (55 C to +70 C) NEMA 4x & 6, IP66 & IP67. 400Hz to 8kHz. 8 ohms. Used to vary the rated power by selecting different tappings (see table below). Transformer Power Tappings 25W 15W 8W 1:2 25.0* 15.0* 8.0* 2:3 12.5* 7.5* 4.0* 3:4 6.0 5.0 2.0 1:3 4.0 4.0 1.5 2:4 2.0* 2.0* 0.7* Transformer Tappings 1:4 1.0 0.8 0.4 Transformer Options: i) Standard Tapping: (4 x 2) terminal tap change (8 terminals). ii) Optional Tapping: 4 terminal tap change with 2 terminals (5 & 6), directly connected to driver (8 ohms). Other tappings & driver impedances available on request. Terminals: Mounting: Labels: Cable Entries: 8 x 14AWG Bracket with ratchet facility. Duty and tag labels optional. 2 x 1 /2" NPT. *Include blocking capacitor for DC supervision of field wiring Polar plot and frequency response curves for other speakers are available upon request. Configuration Options: Max. Rated Power Certification Transformer Labels Entries Color DB4 UL Power 8 watt 8 15 watt 15 25 watt 25 Standard Models Type UL listed UL Series Model Number Order Decription DB4 DB4 Transformer Yes X* None N *Std 100V Other values available, specify voltage. DB425ULXN2CR 109208-001 Speaker, 25 Watt, Transformer, Red Finish DB415ULXN2CR 109208-002 Speaker, 15 Watt, Transformer, Red Finish Label Duty D* Tag T* None N *Please specify wording Color Natural Black N Red R Special S* *Please specify Entries 1 x ½" NPT 1C 2 x ½" NPT 2C To specify certified plug, suffix appropriate code with 'P'. e.g. 2CP is 2 x 1/2" NPT entries with one certified plug 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA DB4 04/07
Series MAX Strobes: Amber, Blue, Clear, Red Description: The AC-MAX and AC-MAXS models are for 120 VAC applications. The DC-MAX and DC-MAXS models are for DC applications, with a DC voltage range of 10.5 VDC to 31.0 VDC. MAXS versions offer two steady lights in addition to the strobe light. SERIES MAX STROBE High Intensity, weather-resistant visible warning signal, designed for stationary or mobile applications. Available in AC or DC voltage and with steady light option. Features for all Models: Approvals include: UL Standard 1638 Listed for indoor or outdoor use AC-MAX and AC-MAXS mdels are for 120 VAC applications Powerful double flash light burst 60 double flashes per minute Available lens colors per SAE specifications: Amber, Blue, Clear, Red Durable, high impact Lexan construction Mounting options: 1/2 inch pipe, surface mount, flange mount, standard 4-inch square electrical box or Wheelock WBB Weather Resistant Backbox (order code 2959) Overall height: 5 inches Diameter: 6.2 inches Weight: 2 lbs. Applications for Series MAX Strobes: Hazard warning/alerting Industrial visual signaling Strobe beacons for vehicles or equipment Process control area notification Access gate/loading dock identification Features for Steady Light Models: Two 7 watt incandescent lamps Independent wiring for electrical hook-up Applications for Strobe & Steady Light Models: Location of specific equipment Eye wash station/emergency medical kit location Emergency phone location Warning lights Security alert indication NOTE: The Series MAX Strobes are not designed to operate on a synchronized NAC Circuit. U L S5391
Architects and Engineers Specifications Industrial Strobes shall be Wheelock Series MAX Strobes; AC-MAX, AC-MAXS, DC-MAX, DC-MAXS. Wheelock Series MAX Strobes; AC-MAX, AC-MAXS, DC-MAX, DC-MAXS shall be UL Standard 1638 Listed. Series MAX AC shall have a rated operating voltage of 120 VAC Series MAX DC shall have a rated operating voltage range of 10.5-31.0 VDC Series MAX AC and DC shall have a strobe with flash energy of 7.5 joules and flash rate of 60 double flashes per minute. Series MAX MAXS AC and DC shall have the addition of two 7 watt incandesent lamps for steady light applications. Steady light lamps shall be 7C7 type for Series MAX AC-MAXS models and 2470X type for Series MAX DC-MAXS models. Lens colors; amber, blue, clear and red shall conform to SAE J578D specifications. Base and lens shall be constructed of high strength, high temperature G.E. Lexan. Operating temperature range for all models shall be; -31 F to + 151 F (-35 C to + 66 C). Dimensions shall be Height; 5, Diameter; 6.2. Weight shall be 2 lbs. Specifications and Ordering Information Model Number Order Lens Color Voltage Product Description Effective Candela (cd) AC-MAX-A 8120 Amber 120 VAC Double Flash MAX Strobe 80 AC-MAX-B 8121 Blue 120 VAC Double Flash MAX Strobe 12 AC-MAX-C 8122 Clear 120 VAC Double Flash MAX Strobe 100 AC-MAX-R 8124 Red 120 VAC Double Flash MAX Strobe 20 AC-MAXS-A 8125 Amber 120 VAC Double Flash MAX Strobe w/ two 7 watt steady light lamps 80 AC-MAXS-B 8126 Blue 120 VAC Double Flash MAX Strobe w/ two 7 watt steady light lamps 12 AC-MAXS-C 8127 Clear 120 VAC Double Flash MAX Strobe w/ two 7 watt steady light lamps 100 AC-MAXS-R 8129 Red 120 VAC Double Flash MAX Strobe w/ two 7 watt steady light lamps 20 DC-MAX-A 8130 Amber 10.5-31.0 VDC Double Flash MAX Strobe 80 DC-MAX-B 8131 Blue 10.5-31.0 VDC Double Flash MAX Strobe 12 DC-MAX-C 8132 Clear 10.5-31.0 VDC Double Flash MAX Strobe 100 DC-MAX-R 8134 Red 10.5-31.0 VDC Double Flash MAX Strobe 20 DC-MAXS-A 8135 Amber 10.5-31.0 VDC Double Flash MAX Strobe w/ two 7 watt steady light lamps 80 DC-MAXS-B 8136 Blue 10.5-31.0 VDC Double Flash MAX Strobe w/ two 7 watt steady light lamps 12 DC-MAXS-C 8137 Clear 10.5-31.0 VDC Double Flash MAX Strobe w/ two 7 watt steady light lamps 100 DC-MAXS-R 8139 Red 10.5-31.0 VDC Double Flash MAX Strobe w/ two 7 watt steady light lamps 20 Model AC-MAX and AC-MAXS AC-MAX and DC-MAXS Current Draw 0.20 @ 120 VAC 1227 ma @ 10.5 VDC 1010 ma @ 12 VDC 470 ma @ 24 VDC 344 ma @ 31 VDC Steady Light Lamps Current Draw DC Inrush Current Draw: 12V 5A Max 24V 10A Max 31V 12A Max Note: Series MAX Strobes are not intended for use in wash down areas. AC-MAXS Models DC-MAXS Models 120 ma 665 ma NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA I1008 Max 06/06
EMNA Emergency Mass Notification Appliance EMNA Description: The Emergency Mass Notification Appliance (EMNA) is a combination appliance consisting of 1 E70 or ET70 Multicandela Wall Speaker Strobe, 1 RSSP Colored Lens Strobe Plate (Amber, Blue, Green or Red) and 1 ISP-2 and/or SPL-2 backbox. The E70 Low Profile Speaker Strobes are designed for high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. The Series ET70 Speaker Strobes provide high audio output, clear audibility, dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 8 watts. The strobe portion of the Series E70 and ET70 Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or Wheelock s PS- 12/24-8CP and PS-12/24-8MP Power Supplies with Wheelock Patented Sync Protocol. The Series RSSP Strobe Plates are a cost effective way to retrofit colored lens strobe appliances to speakers and easily mounts to standard 4 backboxes or for surface mount use with Wheelock s SBL2 surface backbox. The strobes are available in amber, blue, green and red. The strobes operate from 16 to 33 vdc (using filtered or FWR voltage). Intensity options for amber, blue and green lens strobes include multi-candela models with four field-selectable settings or 110 candela models. Red lens strobes are available in 75 or 110 candela models and are Listed under UL Standard 1638. Applications for EMNA: Mass Notification Systems Hazard warning/alerting Security alert indication Personnel alerting (Pictures includes: RSSPA-24MCC-NW, E70-24MCW-FW and backboxes SBL-2 and ISP-2) Features: (E70 and ET70) Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information Compliant with UFC-04-021, ADA, OSHA L1910.165 Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or Wheelock PS-12/24-8CP and PS-12/24-8MP Power Supply with built-in sync protocol High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ (RSSP Colored Lens Strobe Plates) Approvals include: UL Standard 1638 Choice of four strobe lens colors with wide range of intensity options Wide operating voltage range Strobes can be synchronized with Wheelock s SM or DSM sync modules or POWERPATH power supplies Combination speaker/strobes available for voice messages with visual alerting Mount to standard electrical boxes High quality designs from the leader in fire notification alarms
SPECIFICATIONS AND ORDERING INFORMATION Model Number Order Lens Color Strobe Candela Mounting Options Strobe Voltage Strobe Current (RMS) note 1 note 2 16 vdc 24 vdc Agency Approvals RSSPA-24MCC-NW 3308 AMBER MCC wall or ceiling 24 vdc note 3 none RSSPB-24MCC-NW 3306 BLUE MCC wall or ceiling 24 vdc note 3 none RSSPG-24MCC-NW 3307 GREEN MCC wall or ceiling 24 vdc note 3 none RSSPR-24110-NW 3309 RED 110 wall or ceiling 24 vdc 0.420 0.37 UL, CSFM, MEA, BFP E70-24MCW-FW 9023 CLEAR MCW wall 24 vdc note 4 UL, CSFM, MEA, BFP ET70-24MCW-FW 9021 CLEAR MCW wall 24 vdc note 4 ISP2-W 3195 N/A N/A N/A N/A N/A N/A N/A SBL2-W 6989 N/A N/A N/A N/A N/A N/A N/A Note 1. Candela is measured on axis per UL 1638. Models with MCC strobes have 4 field selectable candela settings. MCC settings are rated for clear lens - derate approximately 25% for amber, 55% for green and 70% for blue Note 2. All strobes operate from 16 to 33 volts at 1 flash/second using filtered or full-wave-rectified DC voltage (See Installation Instructions) Note 3. Strobe Current for MCC Strobes: MCC setting 15 30 75 95 current @ 16 vdc 0.065 0.105 0.189 0.249 current @ 24 vdc 0.045 0.070 0.119 0.159 Note 4. Strobe Current for MCW Strobes: MCW setting 15 30 75 110 current @ 16 vdc 0.062 0.102 0.192 0.265 current @ 24 vdc 0.041 0.065 0.116 0.155 Military and Government Systems offered by Wheelock Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications. Operational and Storage Specifications: Temperature Range: 32 F - 120 F (0-49 C) Humidity Range: 0-85% Non-Condensing SPECIAL ORDER Wheelock systems meet all requirements of the Unified Facilities Criteria (UFC) 4-021-01, 18 December 2002 UFC Performance Criteria for Mass Notification System for the Interior of Structures Personnel Alert Systems (PAS) Provide force protection and early warning in emergency situations including: Bomb Threat, Terrorist Attack, Security Breach, Chemical Release, Natural Disaster and OEM Wheelock Wireless Platform for Base Wide (exterior) and Building Facility (interior) Systems Mass Notification Systems (MNS) Secure Systems for SCIF room applications Contact your Wheelock representative for additional information regarding base or facility site visits and equipment recommendations. For additional specifications, refer to the following data sheets: S0310 Series ET Speaker Strobes S1610 Series E Speaker Strobes S9020 Series RSS Colored Lens Strobes S7000 Mounting Accessories Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA M1000 EMNA 06/06
Series STH-15S Supervised Horn Loudspeaker STH-15S (Gray) STH-15SR (Red) SHMP-R Adapter Plate Description The Wheelock Series STH-15S supervised horn loudspeakers are equipped with a compression driver providing up to 15 watts RMS power handling capability, superior intelligibility and dispersion to achieve maximum sound projection and penetration. Weather-resistant metal construction and reentrant acoustic path assure protection against water, humidity, vermin and corrosion. The mounting bracket allows directional sound dispersion via vertical and horizontal positioning. Provisions are also included for surface or strap mounting to pillars and I-beams. All models include a built-in 25/70/100 V transformer featuring a screwdriver adjustable, 7-position watt/impedance selection switch. Wiring terminals are protected with a vandal-resistant adapter cover for control equipment utilizing cable or conduit. A built-in, 5 mfd capacitor is provided on both models for line supervision. All models meet or exceed the UL Listed standards for audible signal appliances and are capable of operating within an ambient temperature range of 66 C (150 F) to -35 C (-30 F). Models comply with UL Standard 1480 Speakers for Fire Protective Signaling Systems and California State Fire Marshal (Title 19). Features Approvals include: UL Standard 1480 (Speakers for Fire Protective Signaling Systems), California State Fire Marshal (CSFM) Title 19 Meets or exceeds UL Listed standards for audible signal appliances 15-Watt High Efficiency Compression Driver Weather-resistant, vandal-resistant aluminum construction assures protection against water, humidity, vermin, and corrosion Reentrant acoustic path 25/70/100 V transformer featuring a screwdriver adjustable, 7- position watt/impedance selection switch 5 mfd Capacitor for Line Supervision STH-15S Gray baked epoxy finish STH-15SR Red baked epoxy finish Simplified, universal-mounting bracket adjustable in horizontal and vertical planes with banding slots for beam or pillar mounting Installation terminals and power selector are recessed mounted, and protected by the metal interface adapter, or clear plastic shield Applications The Wheelock Series STH-15S supervised horn loudspeakers are surface-mounting, high-efficiency units for life safety and communication system applications. When used with compatible control equipment, they provide high-intelligibility voice reproduction and signal transmission for indoor or outdoor emergency alarm and protective signaling. Specifications and Ordering Information Model Number Order Product Description Weight STH-15S 7937 9 Dia. Supervised, Weatherproof, 15 Watt Horn, Loudspeaker with Transformer, Aluminum, Gray 4.5 lbs. (2.0 kgs.) STH-15SR 7938 9 Dia. Supervised, Weatherproof, 15 Watt Horn, Loudspeaker with Transformer, Aluminum, Red 4.5 lbs. (2.0 kgs.) SHMP-R 8154 STH- RSSP-KIT 6096 UL Listed Adapter Plate, Designed to mount the STH-15SR Horn Speaker (7938) to a Series RSSP Strobe Mounting Plate. For Surface Mount Applications, the SBL-2 (6988) Surface mount backbox is required. Weatherproof 15 watt supervised 25/70 horn loudspeaker and 15/30/75/110cd strobe with mounting plate, adjustable mounting base for horn and backbox. Red color. U L S2652 151-92-E 7320-0785:144
Architects and Engineers Specifications The supervised horn loudspeaker shall be a STH-15S/STH-15SR or approved equal. The horn shall be weather resistant and constructed of heavy gauge, treated aluminum. The horn shall be able to operate within any ambient temperature environment ranging from 66 degrees C (150 F) to -35 degrees C (-30 F). The horn shall be a double reentrant type with a 15 watt RMS audio power rated compression driver producing a UL rated 102 db measured at 15 watts at 10 feet. The horn shall have an impedance selection via a 7 position switch of 5000, 2500, 1300, 666, 333, 89 & 45. Power taps shall be available at 2.0, 4.0, 7.5 & 15 watts for the 100 volt line,.9, 1.8, 3.8, 7.5 & 15 watts for the 70 volt line and.48,.94, 1.8, 7.5 & 15 watts for the 25 volt line. Each power tap shall have a 3dB incremental rating. The frequency response range shall be 400-4000 Hz. The horn shall have a dispersion of 70 degrees. The horn assembly shall be furnished with a mounting bracket that allows adjustment on either a vertical or horizontal plane with a single locking pin and include provisions for mounting, banding or strapping. Wiring terminals shall be fully enclosed and a vandal-resistant adapter cover shall provide connection protection for cable or conduit. The horn shall be 7.875 W x 8.75 H x 9.313 D (200 x 222 x 237 mm). The horn shall be finished in gray (STH-15S) or red (STH-15SR) baked epoxy. WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR AP- PLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. STH-15S & STH-15SR Power Switch Selections Setting Impedance (Ohms) Watts 70.7 Volts 25 Volts 100 Volts db @ 10 Feet Watts db @ 10 Feet Watts db @ 10 Feet 1 5,000 0.9W 90 Not Used Not Used 2.0W 93 2 2,500 1.8W 93 Not Used Not Used 4.0W 96 3 1,300 3.8W 96 0.48W 87 7.5W 99 4 666 7.5W 99 0.94W 90 15.0W 102 5 333 15.0W 102 1.8W 93 Not Used Not Used 6 89 Not Used Not Used 7.5W 99 Not Used Not Used 7 45 Not Used Not Used 15.0W 102 Not Used Not Used Specifications (UL RATING) POWER RATING: 15 Watt Continuous FREQUENCY RESPONSE: 400-4,000 Hz SENSITIVITY: 102 db @ 15 Watts @ 10 SPECIFICATIONS GENERAL DISPERSION ANGLE: 70 Degrees (-6 db @ 2,000 Hz Octave Band) Anechoic Measurements: 15 watt tap @ 10 feet -3 Tone Slow Whoop Siren 107.2 dba 108.5 dba 107.8 dba NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0100 STH 11/06
Series CVX/CSX Explosion -Proof Bells Description: Wheelock s Series CVX/CSX Explosion-Proof Bells have earned the reputation for rugged, reliable performance over years of service in hazardous environments. These bells are Listed for service in Division One applications which means that they are designed to operate safely in atomospheres that actually contain the explosive elements in free form (in contrast to Division Two environments, wherein the explosive elements are stored and protected). Features: Approvals include: UL Standard, New York (MEA) and California State Fire Marshal (CSFM) Rugged cast mechanism enclosure Available in single stroke and vibrating models Available in 24 VDC and 115 VAC versions High sound output with large 10 bell shell Outdoor models include protective hood and guard CLASS GROUP CONTENTS OF HAZRDOUS ATMOSPHERE I B Hydrogen or Gases & Vapors of equivalent hazard such as Manufactured Gas I C Ethyl & Ether Vapors I D Gasoline, Petroleum, Naphtha, Alcohol, Acetone, Benzene, Lacquer Solvent, Vapors, Natural Gas II F Carbon Black, Coal, Coke Dust II G Flour, Starch, Grain Dusts Vibrating Listed for Hazardous Atmospheres Specification and Ordering Information: Indoor Model Number Order Outdoor Model Number Order Shell Size Input Volt. Input Current dba @ 10 Ft. Mounting CVX10-115-R* 3742 CVXG10-115-R* 4930 10 115VAC.220 90 Note 1 CVX10-115-S* 0132 CVXG10-115-S* 0134 10 115VAC.220 90 Note 1 Single Stroke Indoor Model Number Order Outdoor Model Number Order CSX10-115-R* 4715 CSXG10-115-R* 4929 Shell Size Input Volt. Input Current 115VAC 0.125 CSX10-115-S* 0166 CSXG10-115-S* 0167 10 115VAC 0.125 CSX10-24-R 3582 CSXG10-24-R 3402 24VDC 0.500 CSX10-24-S 0164 CSXG10-24-S 0196 24VDC 0.500 dba @ 10 Ft. Mounting 87 Note 1 E5946 S5391 151-92-E 7125-0785:142 NOTES: 1. All models Include integral cast backbox for surface mounting with 1 /2 threaded conduit entrances on top and bottom of housing. 2. Wheelock also offers a line of explosion-proof relays. Consult Customer Service for information.
ARCHITECTS AND ENGINEERS SPECIFICATIONS The alarm bells shall be Wheelock Series CVX/CSX explosion-proof bells or approved equals. They shall be UL Listed for Hazardous Atomospheres, and suitable for use in Division One applications: Class One, groups B, C and D; and Class Two, groups F and G. Specific models shall be designed for either single stroke or vibrating mode, and operation for either 24 VDC or 115 VAC. Sound output at 10 feet shall be 87 dba for single stroke versions and 90 dba for the vibrating version. All versions shall be polarized for DC supervision. Operating current shall be as follows:.220 amperes for 115 VAC vibrating,.125 amperes for 115 VAC single stroke;.500 amperes for 24 VDC single stroke. Outdoor versions shall incorporate a cast protective hood and guard over the bottom half of the bell shell. Dimensions for the indoor versions shall be 10 and one-eighth inches wide, 11 inches high and 6 and one-half inches deep. Outdoor versions shall measure 11 and one-half inches wide, 11 and one-half inches high, and 7 and one-half inches deep. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0200 CVX/CSX 05/06
Series ET Speakers and Speaker Strobes SERIES ET70 Description The Wheelock high performance Series ET Speakers and Series ET Speaker Strobes provide high audio output, clear audibility, dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 8 watts. They are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired. The low profile design incorporates a speaker mounting plate for faster and easier installation. Each model has a built-in level adjustment feature and an aesthetic two (2) screw grille cover. The Series ET Speaker Strobe models incorporate Low Current draw Series RSS Strobes. Strobe options for wall mount models include 1575 cd or Wheelock s patented MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock s patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The strobe portion of all Series ET Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM sync modules or the Wheelock PS-24-8MC Power Supplies with patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. Series ET70 and ET90 Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring. Color options for Series ET speakers and speaker strobes are red, white, or nickel plated. SERIES ET90 Features Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshall (CSFM), Factory Mutual (FM), and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/UFC/ANSI compliant Meets OSHA 29 Part 1910.165 Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi-Candela models) or 1575cd (Single Candela model) Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (multi-candela models) Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Synchronize with sync modules or power supplies with built-in sync protocol Field selectable taps for 25 or 70 VRMS operation from 1/8 watt to 8 watts High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 S2652 151-92-E 7125-0785:152 (ET70/90 MC) 7125-0785:146 (ET70WP)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: UL Max Current* ET70/ET90 Speaker Strobes ET70 Strobe current - Wall Mount ET90 Strobe current - Ceiling Mount 241575W 24MCW 24MCWH 24MCC 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 16-33 VDC 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: ET70/ET90 UL Reverberant dba @ 10 Feet** watts 1/8 1/4 1/2 1 2 4 8 ET Speaker 75.0 78.0 81.0 84.0 87.0 90.0 93.0 ET Speaker Strobe 75.0 78.0 81.0 84.0 87.0 90.0 93.0 **dba ratings are based on UL testing under UL Standard 1480 *UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # SERIES ET SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) FROM PRECEDING APPLIANCE OR VOICE EVACUATION PANEL FACP + FROM PRECEDING STROBE, SYNC MODULE, POWER SUPPLY OR FACP - + - + - STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN + - + STROBE DSM SYNC +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + - + OUT 2 SPEAKER TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR SERIES ET SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A - + - ET ET ET ET ET ET SERIES ET SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P F A C P Strobe NAC Cir. Strobe NAC Cir. Strobe NAC Cir. DSM #1 Sync + - DSM #2 Sync + - DSM #3 Sync + - DSM Interconnecting wiring shown. Maximum of twenty (20) Series PS-12/24-8MP ET ET ET SERIES ET SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP ET ET ET ET ET ET Note: Figure shows interconnection to strobe through sync module. Speaker portion requires 2 separate conductors to FACP. RSS RSS RSS EOLR For wiring information on the PS-24-8MC Power Supply, please refer to Data Sheet #8900. Specifications and Ordering Information Model Order Wall Mount Ceiling Non- Mount Sync Strobe Sync w/ SM, DSM or PS-12/24-8CP/MP Strobe Candela # Model Color RED # Model Color White # Model Color Nickel Mounting Options Agency Approvals UL MEA CSFM FM BFP ET70-24MCW-FR 9020 X - X X 15/30/75/110 X - L,O,P,Q,U,Y X X X X X ET70-24MCW-FW 9021 X - X X 15/30/75/110 - X L,O,P,Q,U,Y X X X X X ET70-24MCW-FN 3091 X - X X 15/30/75/110 * - X L,O,P,Q,U,Y X X X X X ET70-241575W-FR 7848 X - X X 15 (75 on Axis) X - L,O,P,Q,U,Y X X X X X ET70-241575W-FW 7853 X - X X 15 (75 on Axis) - X - L,O,P,Q,U,Y X X X X X ET70-241575W-FN 3092 X - X X 15 (75 on Axis) - - X L,O,P,Q,U,Y X X X X X ET70-24MCWH-FR 3472 X - X X 135/185 X - - L,O,P,Q,U,Y X X X X * ET70-24MCWH-FW 3475 X - X X 135/185 - X - L,O,P,Q,U,Y X X X X * ET70-24MCWH-FN 0061 X - X X 135/185 - - X L,O,P,Q,U,Y X X X X * ET70WP-2475-FR 9077 X - X X 180 X - - M (Outdoor) X X X * * ET90-24MCC-FW 3164 - X X X 15/30/75/95 - X - L,Q,U,V,Y X X X X * ET90-24MCC-FR 3163 - X X X 15/30/75/95 X - - L,Q,U,V,Y X X X X * ET90-24MCC-FN 3186 - X X X 15/30/75/95 - - X L,Q,U,V,Y X X X X * ET90-24MCCH-FW 3473 - X X X 115/177 - X - L,Q,U,V,Y X X X X * ET90-24MCCH-FR 0139 - X X X 115/177 X - - L,Q,U,V,Y X X X X * ET90-24MCCH-FN 0062 - X X X 115/177 - - X L,Q,U,V,Y X X X X * ET70-R 7840 X X - - - X - - L,O,P,Q,U,Y X X X X X ET70-W 7844 X X - - - - X - L,O,P,Q,U,Y X X X X X ET70-N 3097 X X - - - - - X L,O,P,Q,U,Y X X X X X ET90-R 7842 X X - - - X - - L,Q,U,V,Y X X X X X ET90-W 7846 X X - - - - X - L,Q,U,V,Y X X X X X ET90-N 3098 X X - - - - - X L,Q,U,V,Y X X X X X # Models are available in either Red or White. Call Customer Service for Order & Delivery. *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The speaker appliances shall be Wheelock Series ET Speakers and speaker strobe appliances shall be Wheelock Series ET Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Signaling Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 8 watts. All models shall have listed sound output of up to 93 db at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobe shall be of low current design. Where, Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95 cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 strobe shall be specified when 15 candela UL Standard 1971 listing with 75 candela onaxis is required (e.g. ADA compliance). When synchronization is required, the strobe portion of the appliance shall be compatible with the Wheelock SM, DSM sync modules or Wheelock PS-24-8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor surface or flush mounting. The speaker and speaker strobe shall incorporate a speaker mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. The finish of the Series ET speakers and speaker strobes shall be white, red or nickel plate. All speakers and speaker strobes shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0310 ET 03/07
FIRE ALARM SYSTEMS INC. Helping People Take Action SM Description Wheelock s Series ET provides a full range of rugged, high performance speakers and speaker strobe combinations specifically designed to meet the critical needs of the life safety industry for voice and tone signaling. Available in compact, aesthetically pleasing package styles, each ET model covers both 25 or 70 volt audio systems. Their high-efficiency design provides improved evacuation signal, such as the slow whoop and code-3. The Series ET provides unequaled performance and installation flexibility at the job site, while minimizing confusion about mounting and performance capabilities. SERIES ET SPEAKERS & SPEAKER STROBES Series ET-1010 Vandal Resistant Series ET Speaker Strobes use an Xenon flashtube with solid state circuitry enclose din a rugged Lexan lens to provide maximum reliability for effective visible signaling. All Series ET models have IN and OUT wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each terminal. Strobe inputs are polarized and audio inputs include a 10 uf blocking capacitor for compatibility with standard reverse polarity DC supervision of NAC circuits. Features Approvals include: CAN/ULC-S541-99 for speaker appliances and CAN/ULC-S526-02 for visual appliances High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ Field selectable taps for 25 VRMS operation from 1/8 watt to 2 watts Field selectable taps for 70 VRMS operation from 1/8 watt to 8 watts. Series ET Speaker Strobes models available with 15 candela strobes featuring low current draw and low temperature compensation to reduce power consumption and wiring costs All audio and strobe inputs are compatible with standard reverse polarity type supervisions of circuit wiring by an alarm panel Four attractive package styles for flush, semi-flush or surface mounting to low cost electrical backboxes Choice of vandal resistant die cast grilles (ET-1010/1080) or general purpose sheet metal grilles (ET-1070/1090) Sealed back speaker construction for extra protection and improved audibility Sealed back speaker construction for extra protections and improved audibility Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires Series ET-1070 + LS Series ET-1080 + LS Vandal Resistant w/stobe Series ET-1090 +LS Copyright 2005 Wheelock Inc. All rights reserved. 48
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. CAUTION: Always operate audio amplifiers and speakers within their specified ratings. Excessive input may distort sound quality and may damage audio equipment. Do not exceed +30% of speaker rated voltage per CS 243. Improper input voltage can damage speaker. If distortion is heard, check for clipping of the audio signal with an oscilloscope and reduce the amplifier level or gain level to eliminate any clipping. Specifications Model Number Speaker db @ 10 Feet** Strobe Voltage (Rated Watts) ( VDC) Strobe Candela 1/8 1/ 4 1/ 2 1 2 4 * 8* NOM ET-1010 78 81 84 87 90 93 96 - - ET-1070 78 81 84 87 90 93 96 - - ET-1080 78 81 84 87 90 93 96 - - ET-1090 78 81 84 87 90 93 96 - - ET-1070-LS-24 78 81 84 87 90 93 96 24 15 ET-1080-LS-24 78 81 84 87 90 93 96 24 15 ET-1090-LS-24 78 81 84 87 90 93 96 24 15 Notes: 1. Frequency range of speakers is 400-4000 Hz. 2. A 10 uf blocking capacitor for DC Supervisoin of audio lines by the FACP is factory wired in series with the speaker input. 3. dba is rated per UL 1480. *4 and 8 watt taps not available for 25 VRMS applications. Voltage Rated Average Current LS Rated Peak Current LS Rated Inrush Current LS 24 VDC. 080. 190.250 24 VFWR. 081. 216.380 Note: All VFWR voltages in table are measured with DC volt meter. Multiply VFWR voltage by 1.11 to convert to VRMS. WARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT THESE STROBES FUNCTION EVEN AT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOM- MENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS. The UL Listed Rated Input Voltage uses either filtered (DC) or unfiltered full-wave-rectified (FWR) voltage. Check the minimum and maximum output of the power supply and stand by battery and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage to the strobes. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. ET-1010 Speakers are Listed for indoor/outdoor use with a temperature range of -35 C to 66 C (-31 F to 150 F) and maximum humidity of 95% RH. All other ET Speakers and Speaker Strobes are Listed for indoor use with a temperature range of 0 C to 49 C (32 F to 120 F) and maximum humidity of 85%RH. WARNING: USE STROBES ONLY ON NAC CIRCUITES WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBES ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF, AS THE STROBE MAY NOT FLASH. Series ET Speakers ET Speaker Strobes Model Number Order Strobe Candela dba @ 10 Feet Strobe Average Current @ 24 VDC Mounting Options ET-1010-R-ULC 4066-78-96 - E,K,N,R, S ET-1010-W-ULC 4188-78-96 - E,K,N,R, S ET-1070-R-ULC 4243-78-96 - E,L,O,P,Q, V ET-1080-R-ULC 4337-78-96 - E,L,O,P, Q ET-1080-W-ULC 3231-78-96 - E,L,O,P, Q ET-1090-W-ULC 4231-78-96 - E,N,O,Q, V ET-1070-LS-24-VFR-ULC 6144 15 78-96. 074 E,L,O,P,Q, V ET-1070-LS-24-VFW-ULC 8081 15 78-96. 074 E,L,O,P,Q, V ET-1080-LS-24-VFR-ULC 6145 15 78-96. 074 E,L,O,P, Q ET-1080-LS-24-VUR-ULC 8165 15 78-96. 074 E,L,O,P, Q ET-1090-LS-24-CFR-ULC 9031 15 78-96. 074 E,N,O,Q, V ET-1090-LS-24-CFW-ULC 6146 15 78-96. 074 E,N,O,Q, V Notes: 1. Models code suffix V= vertical lens; C= ceiling lens; F= fire lettering; R= red plate; W= white plate. 2. Approval codes: ULC= Underwriter Laboratories of Canada. 49
WARNING: CONTACT WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS AND GENERAL INFORMATION SHEET ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING THESE PRODUCTS, INCLUDING: TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALL APPLIANCES ON THOSE NAC CIRCUITS. THE TIME DURATION OF THE MAXIMUM STROE INRUSH OR PEAK CURRENT IS 2 MILLISECONDS FOR LS MODELS. INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. Application Notes: CAUTION: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4 conduit fittings are used. 1. Mounting hardware for each mounting option is supplied. 2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit should enter through the backbox, not the extension ring. Note not all Canadian Extension Rings fit Series E. Call factory for assistance. 3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the signaling device. 4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 5. Do not pass additional wires (used for other than the signaling device) through the backbox. Such additional wires could result in insufficient wiring space for the signaling appliance. Wiring Diagrams # SPEAKER AND STROBE OPERATE INDEPENDENTLY FROM PRECEDING APPLIANCE OR VOICE EVACUATION PANEL FROM PRECEDING STROBE, SYNC MODULE, POWER SUPPLY OR FACP + - + - + - + - + - STROBE SPEAKER + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR CEILING FLUSH MOUNTING Circular Backbox for 4 Speaker available in Canada only Series ET-1090 By Others (BO) 50
ARCHITECTS AND ENGINEERS SPECIFICATIONS The speaker appliance shall be a Wheelock Series ET speaker and speaker strobe appliance or equivalent. The speaker and strobes shall be ULC Listed under CAN/ULC-S541-99 and CAN/ULC-S526-02 for Fire Protective Service. All speakers shall be either 25 or 70 VRMS inputs with field selectable power taps. Strobes shall use filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination speaker strobe appliances signals shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobe shall meet ULC and produce a flash rate of one (1) flash per second minimum over the Listed input voltage range. The strobe intensity shall be rated per ULC for 15 candela. The combination speaker strobe appliances shall be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The appliance shall be finished in a textured red or white color. Wheelock products must be used within their published specification and must be properly specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instruction at the time of installation and at least twice a year or more often and in accordance with local, state, and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL & ULC), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to all appendices and amendments an the requirements of local authority having jurisdiction (AHJ). Due to continuous development of our products, specifications and offering are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Distributed By: National Sales Office ASSEMBLED IN THE USA 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com 51 273 Branchport Avenue Long Branch, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 S0310C 02/05
Series RSS and RSSP Strobes and Strobe Plates Series RSS Series RSS Series RSSWP RSS Round Description The Wheelock patented Series RSS Strobe Appliances and Series RSSP Strobe Plates have lower current draw while maintaining outstanding performance, reliability and cost effectiveness. These versatile appliances will satisfy virtually all requirements for indoor, wall or ceiling mount applications. Strobe options for wall mount models include 1575 or the Wheelock Patented MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models include the patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. All models may be synchronized using the Wheelock SM, DSM Sync Modules or the PS-24-8MC Power Supplies with the Wheelock Patented Sync Protocol. Synchronized strobes can eliminate possible restrictions on the number of strobes in the field of view. Wheelock s synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy as well as meeting the requirements of NFPA 72. The Wheelock Series RSS Strobes employ a Patented Integral Strobe Mounting Plate that can be mounted to a single gang, double gang, 4 square, 100mm European backboxes or the SHBB surface backbox. If the flush backbox has side or top space between it and the finished wall, the NATP (Notification Appliance Trimplate) may be used. It provides an additional.65 of trim for the Appliance. An attractive cover plate is provided for a clean, finished appearance on all models. The Series RSSP Multi-Candela Strobe Plates are a cost effective way to retrofit required wall strobe appliances to bells, horns, chimes, multitones or speakers and easily mounts to standard 4 backboxes or for surface mount use with the Wheelock SBL2 surface backbox. Features Approvals include: UL Standard 1971, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/UFC/ANSI compliant. Meets OSHA 29 Part 1910.165 Wall mount Multi-Candela models are available with Field Selectable Candela Settings of 15/30/ 75/110cd or 135/185cd. Single Candela models are available in 1575cd Ceiling mount Multi-Candela models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd. (Round or Square) Strobes produce 1 flash per second over the regulated voltage range 12 and 24 VDC models with wide UL Regulated Voltage using filtered (DC) or unfiltered VRMS input voltage Synchronize using the Wheelock sync modules or power supplies with built-in sync protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wire For Weatherproof Series RSS See Datatsheet S9004 U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7125-0785:141 7300-0785:154
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Average RMS Current* RSS/RSSP 24VDC Models RSS/RSSP - Wall Mount RSS - Ceiling Mount 241575W 24MCW 24MCWH 24MCC 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 RSS/RSSP 24VDC Models RSS/RSSP Wall Mount 121575W 12 vdc 0.152 UL max* 0.255 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Table 2: Audibles/Speakers for RSSP Strobe Plate Product Multitone Appliances Horns AMT, MT AH, NH, HS Series Wiring Diagrams # SERIES RSS/RSSP APPLIANCE Motor Bells Speakers Chimes MB-G6/G10 ET-1010/1080, E70, ET70 CH70 FROM + PRECEDING - APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - + - TO NEXT APPLIANCE OR EOLR SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A NAC CIRCUIT FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + OUT 2 RSS RSS RSS RSS RSS RSS SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 F A C P Strobe NAC Cir. Strobe NAC Cir. Sync + - DSM #2 Sync + - RSS Strobe NAC Cir. Sync + - RSS DSM #3 RSS RSS RSS RSS DSM Interconnecting wiring shown. Maximum of twenty (20)
STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE IN UNISON FROM + + PRECEDING - - APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - STROBE + - AUDIBLE TO NEXT APPLIANCE OR EOLR SERIES RSS/RSSP APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS B NAC CIRCUIT F A C P Strobe NAC Circuit SM + STROBE - STROBE + Audible EOLR - Audible RSS RSS STROBE/PLATE ASSEMBLY AUDIBLE & VISIBLE APPLIANCE OPERATE INDEPENDENTLY FROM PRECEDING APPLIANCE OR FACP + FROM PRECEDING STROBE, SYNC MODULE, POWER SUPPLY OR FACP - + - + - + - + STROBE - APPLIANCE + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84515 for PS- 12/24-8CP and P84333 for PS-12/24-8MP. SERIES RSS/RSSP APPLIANCES SYNCHRONIZED WITH PS-12/24-8CP or PS-12/24-8MP F A C P Series PS-12/24-8MP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP AS AS AS RSS RSS RSS EOLR Specifications and Ordering Information Model Order Wall Mount Ceiling Mount Non- Sync Strobe Candela 24 VDC 12 Color VDC RED Square Color WHITE Mounting Options*** or Round Agency Approvals UL MEA CSFM FM BFP RSS-24MCW-FR 940 X - X 15/30/75/110 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-24MCW-FW 9401 X - X 15/30/75/110 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-241575W-FR 7471 X - X 15 (75 on Axis) X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-241575W-FW 7788 X - X 15 (75 on Axis) X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-121575W-FR 7476 X - X 15 (75 on Axis) - X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-121575W-FW 7468 X - X 15 (75 on Axis) - X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X X RSS-24MCC-FW 3158 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS-24MCC-FR 3157 - X X 15/30/75/95 X - X - B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS-24MCCR-FW 3160 - X X 15/30/75/95 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X * RSS-24MCCH-FW 3461 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSS-24MCCHR-FW 3463 - X X 115/177 X - - X B,D,E,F,G,H,J,N,O,R,X Round X X X X * RSS-24MCWH-FR 3465 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSWP-2475W-FR** 9013 X - X 180@ 77 F 75@ -31 F X X X - B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSWP-2475W-FW** 3034 X - X 180@ 77 F 75@ -31 F X X - X B,D,E,F,G,H,J,N,O,R,X Square X X X X * RSSP-121575W-FR 7798 X - X 15 (75 on Axis) - X X - D,E,Z Square X X X X X RSSP-24MCW-FR 9402 X - X 15/30/75/110 X - X - D,E,Z Square X X X X X RSSP-241575W-FR 7793 X - X 15 (75 on Axis) - - X - D,E,Z Square X X X X X RSSP-24MCWH-FR 9482 X X 135/185 X X B,D,E,F,G,H,J,N,O,R,X Square X X X * * All models sync with Wheelock SM, DSM or PS-12/24-8CP or PS-12/24-8MP. # Models are available in either Red or White. Call Customer Service for Order & Delivery. **For Weatherproof Series RSS Strobe specifications see data sheet S9004. ***Refer to data sheet S7000 for mounting options. *PENDING
Architects and Engineers Specifications The visual notification appliances shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). When Strobe Plates are to be installed, they shall be the Wheelock Series RSSP Strobe Plate and shall have the same electronic circuitry as the Wheelock Series RSS. The Series RSS Strobe shall be of low current design. Where Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock s SM, DSM Sync Modules or the Wheelock PS-24-8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. The Series RSS Strobe Appliances shall incorporate a Patented, Integral Strobe Mounting Plate that shall allow mounting to singlegang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. An attaching cover plate shall be provided to give the Appliance and attractive appearance. The Appliance shall not have any mounting holes or screw heads visible when the installation is completed. The Series RSSP Multi-Candela or single candela Strobe Plate shall mount to either a standard 4 inch square backbox for flush mounting, or the Wheelock SBL2 backbox for surface mounting. All notification appliances shall be backward compatible. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0410 RSS/RSSP 06/06
Series 31T AC Horns Description The Wheelock Series 31T-115 VAC Horns are high performance horns. They are ideal alarm signals for life safety applications where high sound output, low current draw and dependable operation are of critical concern. The 31T AC Horn offers rugged, vandal resistant construction with die case metal housings for the horn mechanism. All models include screw terminal inputs for in-out field wiring. Features Approvals include: UL Standard 464, New York (MEA), California State Fire Marshal (CSFM) and ULC Resonant grille design for high sound output with low current draw Each 31T is fully factory assembled to save installation time Screw terminal inputs for fast and secure in-out field wiring Indoor or outdoor mounting options for semi-flush, or surface mounting Attractive red textured finish enhances appearance and durability Vandal Resistant Specifications and Ordering Information Model Number Order Input Voltage Rated Current Rated dba @ 10 Feet Mounting Options 31T-115-R 2805 115 VAC 0.160 95 31T-115-S 0521 115 VAC 0.160 95 D,E,J,K,N,O,R 1. Typical dba at 10 feet is measured in an anechoic chamber with nominal voltage. 2. Refer to Data Sheet #S7000 for mounting options. 3. Refer to the most current Installation Instructions P10010 and General Information P82380 sheets on these products. E5946 151-92-E 7135-0785:007
Architects and Engineers Specifications The AC horns shall be Wheelock Series 31T-115, or approved equal. Models shall be UL 464 Listed for Fire Protective Service and shall include a die cast metal housing to protect the horn mechanism. Sound output shall be 95 dba minimum at 10 feet. Mounting options shall include surface mounting in indoor or outdoor applications and semiflush in indoor applications. All models shall have screw terminal inputs for in-out field wiring. The finish shall be textured enamel. Wiring AC HORN GND FROM PRECEDING APPLIANCE OR FACP NEXT HORN NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0500 31T 06/06
Series E50 Speaker and Speaker Strobes SERIES E50 Speaker Strobe SERIES E50 Speaker Description The Wheelock Series E50 Speakers and Speaker Strobes feature high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. They are designed to provide a sleek, aesthetic appearance for emergency voice/alarm communications systems. All Series E50 models mount to standard 4 x 2-1/8 electrical boxes (with no extension ring required) and incorporate a speaker mounting plate for faster installation. The grille cover snaps on so no mounting screws are visible. Attractive surface boxes are also available for surface installations. The Series E50 Speaker Strobe models use Wheelock low current draw Series RSS strobes for wall mounted applications. Strobe options include patented MCW multi-candela strobes with field selectable candela settings of 15/30/75/110 cd or high intensity MCWH strobes with field selectable 135/185 candela. Models with 1575 candela (75 cd on axis) are also offered. Series E50 Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired. The strobe portion of all Series E Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or the Wheelock s PS-24-8MC Power Supply with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA and NFPA regulations concerning photosensitive epilepsy. Series E50 Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances). All inputs employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring and are compatible with FACP line supervision. Color options for the Series E50 Speakers and Speaker Strobes are red or off-white. Features Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model in Specifications and Ordering Information ADA/NFPA/ANSI compliant Complies with OSHA 29 Part 1910.165 Wall mount speaker strobe models with field selectable candela settings of 15/30/75/110cd or 135/185cd (Multi-Candela models), or 1575cd (Single Candela model) Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ 24 VDC strobes produce 1 flash per second with wide UL Regulated Voltage of 16 to 33 volts using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or Wheelock PS-12/24-8CP and PS-12/24-8MP Power Supply with built-in sync protocol Mount to 4 square x 2-1/8 deep backbox with no extension ring required Snap on grille cover with no visible mounting screws Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7125-0785:165 7320-0785:166
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Average RMS Current E50 Speaker Strobes E50 Strobe Current - Wall Mount 241575W 24MCW 24MCWH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 24 vdc 0.060 0.041 0.063 0.109 0.140 0.195 0.270 UL max* 0.090 0.060 0.092 0.165 0.220 0.300 0.420 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For unfiltered FWR ratings, see installation instructions. Table 2: E50 UL Reverberant dba @ 10 Feet** watts 1/8 1/4 1/2 1 2 E50 Speaker 77 79.5 82.5 85 88 E50 Speaker Strobe 77 79.5 82.5 85 88 **dba ratings are based on UL testing under UL Standard 1480
Wiring Diagrams # SERIES E50 SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) FROM PRECEDING APPLIANCE OR VOICE EVACUATION PANEL + FROM PRECEDING STROBE, SYNC MODULE, POWER SUPPLY OR FACP - + - + - + - + STROBE SPEAKER TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR SERIES E50 SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + OUT 2 - + - E50 E50 E50 E50 E50 E50 SERIES E50 SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P F A C P Strobe NAC Cir. DSM #1 DSM #2 Strobe NAC Cir. Sync + - DSM #3 Strobe NAC Cir. Sync + - Sync + - E50 E50 E50 Series PS-12/24-8MP or PS-12/24-8CP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP or PS-12/24-8CP E50 E50 E50 DSM Interconnecting wiring shown. Maximum of twenty (20) SERIES E50 SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP E50 Note: Figure shows interconnection to strobe through sync module. Speaker portion requires 2 separate conductors to communications system. RSS RSS RSS EOLR Specifications and Ordering Information Model Order Wall Ceiling Mount Mount Strobe Candela Grill Color Flush Mount Bacbox Surface Mount Backbox Mounting Options Agency Approvals UL MEA CSFM FM BFP E50-R 0222 X X - Red 4 x 4 x 2-1/8 E50SB-R E,O,P,Q,R,U,Y,AA X * X X * E50-W 0223 X X - White 4 x 4 x 2-1/8 E50SB-W E,O,P,Q,R,U,Y,AA X * X X * E50-241575W-FR 0224 X - 15 (75 on Axis) Red 4 x 4 x 2-1/8 E50SSB-R E,Q,U,BB X * X X * E50-241575W-FW 0225 X - 15 (75 on Axis) White 4 x 4 x 2-1/8 E50-SSB-W E,Q,U,BB X * X X * E50-24MCW-FR 0226 X - 15/30/75/110 Red 4 x 4 x 2-1/8 E50SSB-R E,Q,U,BB X * X X * E50-24MCW-FW 0227 X - 15/30/75/110 White 4 x 4 x 2-1/8 E50-SSB-W E,Q,U,BB X * X X * E50-24MCWH-FR 0228 X - 135/185 Red 4 x 4 x 2-1/8 E50SSB-R E,Q,U,BB X * X X * E50-24MCWH-FW 0229 X - 135/185 White 4 x 4 x 2-1/8 E50-SSB-W E,Q,U,BB X * X X * *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E50 Speakers and the speaker strobe appliances shall be Wheelock Series E50 Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 89 dba at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall be of low current design. Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mounting. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required. When synchronization is required, the strobe portion of the appliance shall be compatible with the Wheelock s SM, DSM sync modules or Wheelock PS-24-8MC Power Supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor flush mounting to 4 x 2-1/8 electrical boxes without need for an extension ring or surface mounting to Wheelock s E50SB or E50SSB surface boxes. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap-on grille cover. The finish of the Series E50 speakers and speakers strobes shall be white or red. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0510 E50 06/06
Series 43T AC Bells 10-INCH BELLS 6-INCH BELLS Description The Wheelock Series 43T bells provide the durable operation and dependable performance required for life safety alarm systems. A complete range of vibrating models is offered in 6 and 10 sizes for 115 or 24-volt AC operation in indoor or outdoor installations. All models provide high sound output with low power consumption. All models are provided with screw terminal inputs for secure in-out field wiring. Specifications and Ordering Information Model Number Order Shell Size Input Voltage Input Current dba @ 10 Ft. 43T-G6-24-R 1627 6 24 VAC 0.410 86 43T-G6-24-S 1626 6 24 VAC 0.410 86 43T-G6-115-R 1631 6 115 VAC 0.085 86 43T-G6-115-S 1630 6 115 VAC 0.085 86 43T-G10-24-R 1647 10 24 VAC 0.410 88 43T-G10-24-S 3800 10 24 VAC 0.410 88 43T-G10-115-R 1651 10 115 VAC 0.085 88 43T-G10-115-S 3693 10 115 VAC 0.085 88 Features Approvals include: UL Standard 464, Factory Mutual (FM), California State Fire Marshal (CSFM), New York (MEA) and Chicago (BFP) Complies with OSHA 29,Part 1910.165 High sound output with low current draw 6 and 10 shell sizes in 115 or 24 AC models Integral RFI suppression minimizes induced noise on alarm lines Semi-flush mounting to standard 4 square backboxes or surface mounting to Wheelocks surface backboxes Polarized for supervision of alarm lines with screw terminal inputs for fast and secure in-out field wiring of #12 to #18 AWG wire Attractive textured finish to enhance appearance and durability For combined audible (bell) and visual signaling, convenient retrofit assemblies (Series RSSP) are available with Multi- Candela or single candela strobes (See Data Sheet S0410 or Wheelock Fire Products Catalog) Mounting Options * D,E,J,K,N,O,P,R,S * Refer to Data Sheet #S7000 for mounting options. 1. Typical dba at 10 feet is measured in an anechoic chamber. 2. All models are provided with in-out screw terminals. 3. Each bell mechanism is adjusted to operate only with the shell provided. Do not mix shells and mechanisms during installation. E5946 151-92-E 7135-0785:108
Architects and Engineers Specifications The alarm signals shall be Wheelock Series 43T Bells or approved equal. They shall be UL Listed for Fire Protective Service with models for vibrating operation and optional steel shells from 6 to 10 diameter. Sound output at 10 feet shall range up to 88 dba. The bells shall semi-flush mount to standard 4 square backboxes or surface mount to Wheelock indoor BB backbox or outdoor WBB backbox. All bell models shall be polarized for line supervision and shall have screw terminals for in-out field wiring. The finish on all models shall be textured enamel. Wiring (All Bell Models) + - GND FROM PRECEDING APPLIANCE OR FACP TO NEXT APPLIANCE OR EOLR Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE US- ING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARN- INGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0600 43T 06/06
Series CH Chimes and Chime Strobes SERIES CH70 CHIME STROBE SERIES CH90 CHIME STROBE SERIES CH90 CHIME SERIES CH70 CHIME Description The Wheelock Series CH Chimes and Chime Strobes minimize alarm system power supply requirements and wiring costs with a low current draw and a patented chime mounting plate for fast, easy installation. Each model has a built-in level adjustment feature and an aesthetic two (2) screw grille cover. These unique solid-state chime appliances provide field selectable single-stroke or vibrating operation with Anechoic sound levels adjustable up to 83 db and tone adjustable from 800 to 1200 Hz. Strobe options for wall mount models include 1575cd or Wheelock patented MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The strobe portion of all Series CH Chime Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with patented Sync Protocol. Wheelock s synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy as well as meeting the requirements of NFPA 72 and UFC. The Series CH Chime Strobes are UL Listed for indoor, wall or ceiling mount applications under Standard 1971 for Signaling Devices for the Hearing-Impaired and under Standard 464 for Private Mode Audible Signal Appliances. They are available in two attractive package styles for flush mounting to standard electrical boxes or convenient surface mounting. All models include IN/OUT wiring terminations that accept two #12 to #18 AWG wires at each terminal. Inputs are polarized for compatibility with industry standard reverse polarity supervision. Features Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), and California State Fire Marshal (CSFM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/UFC/ANSI compliant Complies with OSHA 29 Part 1910.165 Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi-Candela models) or 1575cd (single candela model) Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multi-candela models) Low current draw with temperature compensation to reduce power consumption and wiring costs Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or the Wheelock PS-24-8MC Power Supply with built-in sync protocol Adjustable Volume and Tone Control Single Stroke or Vibrating Operation Fast Installation with IN/OUT screw terminals using #12 to #18 AWG wires U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7125-0785:151 7135-0785:109 (Chime Only)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Average RMS Current CH70/ CH90 Chimes Chime current CH70 Strobe current - Wall Mount CH90 Strobe current - Ceiling Mount 241575W 24MCW 24MCWH 24MCC 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.022 0.060 0.041 0.063 0.109 0.140 0.195 0.270 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.022 0.090 0.060 0.092 0.165 0.220 0.300 0.420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: Chime dba ratings CH70/CH90 sound level Peak dba @ 10 ft. anechoic dba @ 10 ft reverberant Min Max 83 52 58 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Application 1. The chimes are factory set in single stroke (SS) mode. They can be changed to vibrating (VIB) mode with jumper on PC Board. SINGLE STROKE OPERATION: The minimum input pulse duration must be at least 160 ms on time and 160 ms off time. The chime will only operate once each time it is pulsed. This mode is recommended for coded systems. VIBRATING OPERATION: Continuous input voltage applied to the chime will activate the chime at one-second intervals. 2. The volume and tone controls have been adjusted at the factory to insure maximum dba output. However, once the mode is selected, the installer may want to fine-tune the signal to better suit the application. 3. Anechoic dba is measured in an anechoic chamber with peak meter response. Reverberant dba is rated per UL Standard 464. 4. Chime inrush current is 0.100 amps maximum with filtered DC input (0.140 amps with VRMS input voltage) with a time duration of 100 milliseconds.
Wiring Diagrams # SERIES CH CHIME & STROBE OPERATE INDEPEN- DANTLY (NON-SYNC OR SYNC) + FROM PRECEDING APPLIANCE, SYNC MODULE, - POWER SUPPLY OR FACP FROM PRECEDING APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - + - - + + COM STROBE (OPTIONAL) CHIME + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR SERIES CH CHIME STROBES SYNCHRONIZED W/ MULTIPLE DSM MODULES F A C P Strobe NAC Cir. Strobe NAC Cir. DSM #1 Sync + - DSM #2 Sync + - CH Strobe NAC Cir. Sync + - CH DSM #3 CH CH CH CH DSM Interconnecting wiring shown. Maximum of twenty (20) Note: Figure shows interconnection to strobe through sync module. Chime portion requires 2 separate conductors to FACP. SERIES CH CHIME STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A SERIES CH CHIME STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP Series PS-12/24-8MP F A C P OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" CH CH RSS RSS EOLR CH RSS Series PS-12/24-8MP For wiring information on the PS-24-8MC Power Supply, please refer to Data Sheet #8900. Specifications and Ordering Information Model Number Order Wall Ceiling Mount Mount Strobe Sync w/ SM, DSM or PS-24-8MC Strobe Candela Model 24 Color VDC RED Model Color White Mounting Options Agency Approvals UL MEA CSFM BFP CH70-24MCW-FR 9018 X X 15/30/75/110 X X - L,O,P,Q,R,U,Y X X X X CH70-24MCW-FW 9019 X - X 15/30/75/110 X - X L,O,P,Q,R,U,Y X X X X CH70-24MCWH-FR 9083 X - X 135/185 X X - L,O,P,Q,R,U,Y X X X * CH70-24MCWH-FW 9084 X - X 135/185 X - X L,O,P,Q,R,U,Y X X X * CH70-241575W-FR 7830 X - X 15 (75 on Axis) X X - L,O,P,Q,R,U,Y X X X X CH90-24MCC-FW 3168 - X X 15/30/75/95 X - X Q,U,V X X X * CH90-24MCCH-FW 3110 - X X 115/177 X - X Q,U,V X X X * CH70-24-R 7825 X X - - X X - L,O,P,Q,R,U,Y X X X X CH70-24-W 7827 X X - - X - X L,O,P,Q,R,U,Y X X X X CH90-24-W 7826 X X - - X - X Q,U,V X X X X Models are available in either Red or White. Call Customer Service for Order & Delivery. *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The chime appliances shall be Wheelock Series CH Chimes and the chime strobe appliances shall be Wheelock Series CH Chime Strobes or approved equals. The chime shall be UL Listed under Standard 464 for Audible Signal Appliances and chimes equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B and shall incorporate low temperature compensation to ensure the lowest possible current consumption. All chimes shall use solid state components and shall provide field selectable single stroke or vibrating operation with volume control and tone control. All models shall have a peak Anechoic sound output of 83 db at 10 feet and an adjustable frequency range of 800 to 1200 Hz. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobe shall be of low current design. Where Multi-Candela Chime Strobes are specified, the strobe intensity shall have a minimum of four (4) field selectable settings and shall be rated per UL Standard 1971 at: 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant and not accessible from the front of the appliance. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock SM, DSM sync modules or the Wheelock PS-24-8MC Power Supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The chime and the chime strobe appliances shall be designed for indoor surface or flush mounting. The chime and chime strobe shall incorporate a chime mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. All chime and chime strobe appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0710 CH 06/06
Series ET-1010 and ET80 Vandal Resistant Speakers and Speaker Strobes ET80 Description The Wheelock Series ET Vandal Resistant speakers and speaker strobes provide a full range of rugged, high performance combinations specifially designed to meet the critical needs of the life safety industry for voice and tone signaling. Available in compact, aesthetically pleasing package styles, each ET model covers both 25 and 70 volt audio systems, and has multiple wattage taps from 1 / 8 to 8 watts. Their high-efficiency design provides improved voice clarity and higher sound output for typical low frequency fire evacuation signal, such as the slow whoop and temporal code-3. Series ET80 Speaker Strobes are designed to meet the latest requirements of NFPA 72 (National Fire Alarm ), ANSI 117.1 (American National Standard of Accessible and Usable Buildings and Facilities) and UL Standard 1971 (Standard for Signaling Devices for the Hearing Impaired) and UL Standard 1480 (Speakers for Fire Protective Signaling Systems). Series ET80 Speaker Strobes are UL Listed for indoor use, wall mount, under Standards 1971 and 1480 for Speaker Appliances, and incorporate a Lexan lens to provide maximum reliability for effective visible signaling. Strobe options include Multi-candela MCW strobes with field selectable 15/30/75/110 or MCWH strobes with field selectable 135/185 candela. Single candela 1575 strobes (rated 15cd with 75 cd on axis) are also available. Series ET80 Speaker Strobes, when used with Wheelock SM/DSM Sync Modules or Wheelock Power Supplies produce synchronized strobe flashes for compliance with ADA guidelines concerning photosensitive epilepsy. ET-1010 Features Approvals Include: UL Standard 1480, UL Standard 1971, California State Fire Marshal (CSFM), New York City (MEA), Chicago (BFP), and FCC Part 15 Complies with OSHA 29, Part 1910.165 Designed to meet or exceed NFPA/ANSI Standards and ADA Accessibility Guidelines High efficiency speakers designed for maximum output at minimum wattage across 400 to 4000 Hz frequency range Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 8 watts in 3 db steps ET80 Speaker Strobe models available with Multi-candela strobes rated 15/30/75/110cd and 135/185cd or single candela strobes rated 15cd (with 75cd on axis) All strobe inputs are compatible with standard reverse polarity type supervision of circuit wiring by an alarm panel Attractive package styles for flush or surface mounting to standard low cost backboxes ET-1010 models UL Listed for outdoor use with Wheelock WBB outdoor backbox Vandal resistant die cast grilles ET-1080 Sealed back speaker construction for extra protection and improved audibility Fast installation with IN/OUT screw terminals using #12 to #18 AWG wring Compliance with RFI limits in FCC Part 15, Class B for compatibility with sensitive detection and communication circuits Audio inputs include a 10 uf blocking capacitor for compatibility with DC supervision of Speaker Notification Appliance Circuits S5391 151-92-E 7125-0785:152 (ET80) 7320-0785:105 (ET-1010)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Speaker dba at 10 Feet (ET-1010 ) Watts 1/8 1/4 1/2 1 2 4 8 dba 77 80 83 86 87 92 94 Notes 1. A 10 uf blocking capacitor for DC supervision of speaker NAC S by the Voice Evaucation System is factory wired in series with the speaker input. 2. dba is rated per UL Standard 1480. Speaker dba at 10 Feet (ET-1080 and ET80-24MCW) Watts 1/8 1/4 1/2 1 2 4 8 ET80 dba 78 81 84 87 90 92 94 ET-1080 dba 78 81 84 87 90 93 96 UL Max* Current Model Number ET80-241575 ET80-24MCW ET80-24MCWH candela 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 16-33 VDC 0.090 0.060 0.092 0.165 0.220 0.300 0.420 *UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams SERIES ET SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) FROM PRECEDING APPLIANCE OR VOICE EVACUATION PANEL + FROM PRECEDING STROBE, SYNC MODULE, POWER SUPPLY OR FACP - + - + - + - + STROBE SPEAKER TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR SERIES ET SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A DSM FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN SYNC +OUT 1 + IN 1 + IN 2 + - MINUS 1 + AUDIBLE - MINUS 2 + OUT 2 - + - ET ET ET ET ET ET SERIES ET SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P F A C P Strobe NAC Cir. Strobe NAC Cir. Strobe NAC Cir. DSM #1 Sync + - DSM #2 Sync + - DSM #3 Sync + - DSM Interconnecting wiring shown. Maximum of twenty (20) SERIES ET SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP or PS-12/24-8MP Series PS-12/24-8CP or PS-12/24-8MP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8CP or PS-12/24-8MP ET ET ET ET ET ET ET ET ET RSS RSS RSS EOLR For wiring information on the PS-24-8MC power supply, please refer to Data Sheet #S8900. For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supply refer to Installation Instructions P84662. Specification and Ordering Information Model Number Order Color Mounting Location Mounting Options # Candela Agency Approvals UL MEA CSFM FM BFP ET-1010-R 3135 red wall/ceiling K,N,O,R - X X X X X ET-1010-W 3137 white wall/ceiling K,N,O,R - X X X X X ET-1080-R 3141 red wall/ceiling O,P,Q,Y - X X X X X ET80-241575W-FR 3037 red wall O,P,Q,R,Y 15(75 on axis) X X * X * ET80-241575W-FW 3038 white wall O,P,Q,R,Y 15(75 on axis) X X * X * ET80-24MCW-FR 3476 red wall O,P,Q,R,Y 15/30/75/110 X X X X * ET80-24MCW-FW 3477 white wall O,P,Q,R,Y 15/30/75/110 X X X X * ET80-24MCWH-FR 3478 red wall O,P,Q,R,Y 135/185 X X X X * ET80-24MCWH-FW 3479 white wall O,P,Q,R,Y 135/185 X X X X * #Refer to Data Sheet S7000 for mounting options. *Approvals Pending
Architects and Engineers Specifications The speaker appliances shall be Wheelock Series ET-1010, ET-1080 or ET80 vandal resistant speakers and speaker strobes or equivalent. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Signaling Devices for the Hearing-Impaired ET-1010 models shall be Listed for outdoor use under UL Standard 1480. All speakers shall include both 25 and 70 volt VRMS inputs with field selectable power taps from 1/8 to 8 watts with listed sound output up to 96 db for speakers or speaker strobes. Strobes shall be listed for 16-33 VDC input using filtered power or unfiltered power. All models shall have provisions for standard NAC supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination speaker strobe appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobes shall meet UL Standard 1971 and produce a flash rate of one (1) flash per second minimum over the listed input voltage (16VDC-33VDC) range. Multi-candela strobe intensity shall be rated per UL Standard 1971 at 15/30/75/110cd 135/185cd. The 1575 candela strobes shall be specified when 15 candela UL Standard 1971 Listing with 75 candela intensity on-axis is required. All strobes versions shall incorporate circuitry for synchronized strobe flash and shall be designed for compatibility with Wheelock SM and DSM Sync Modules and PS-24-8MC power supply. All UL Standard 1971 Listed strobe appliances shall be verified to meet FCC Part 15, Class B. Strobe activation shall be via independent input from the speaker notification appliance circuit. The combination speaker strobe appliances may be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. All appliances shall be vandal resistant die cast metal finished in a textured red or white color. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S0800 ET Vand 04/07
Series S 8 Ceiling Speakers and Speaker Strobes SERIES S-24MCC Speaker Strobe SERIES S Speaker Description The Wheelock Series S Speakers and Speaker Strobes are designed for high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 8 watts. The Series S Speaker Strobe models incorporate the Low Current draw Series RSS Strobes. Strobe options for ceiling mount models include Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. Series 8 Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired. The strobe portion of all Series S Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or Wheelock PS-24-8MC Power Supplies with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. Series S Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring. The Series S, 8 Ceiling Speakers and Speaker Strobes are available in three configurations: S8-70/25 - Dual Voltage, multi-tap speaker S8-24MCC - Speaker strobe with field selectable settings of 15/30/75/95cd S8-24MCCH - Speaker strobe with field selectable candela settings of 115/117cd Features Approvals include: UL Standard 1971, UL Standard 1480, California State Fire Marshal (CSFM) and MEA (See approvals by model number under Specification and Ordering Information) ADA/NFPA/ANSI compliant Complies with OSHA 29 Part 1910.165 Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multicandela models) Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or Wheelock PS- 12/24-8CP and PS-12/24-8MP Power Supply with built-in sync protocol Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 8 watts High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires Frequency Response: 200Hz - 15kHz Magnet weight: 9.5 oz. Speaker impedance: 8 ohms 400Hz - 4kHz (UL) Round metal 12 grille, with white powder coated finish Compatible with DC circuit supervision Applications: Use with SP40/2 Multi-Function Audio Supervised System Provides for audio quality background music U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7320-0785:164
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Specification and Ordering Information Speaker Strobe Strobe Model Number Order Voltage (VRMS) dba @ 10 Feet (Rated Watts) 1 / 8 1 / 4 1 / 2 1 2 4 8 Regulated Voltage VDC/FWR Voltage Range VDC/RMS Candela S8-70/25 0052 25/70 75 78 81 84 87 90 93 - - - Average RMS Current 24MCC 24MCCH 15cd 30cd 75cd 95cd 115cd 177cd S8-24MCC 0054 25/70 75 78 81 84 87 90 93 24 16.0-33.0 15/30/75/95 24 VDC 0.045 0.070 0.119 0.159 0.195 0.270 S8-24MCCH 0056 25/70 75 78 81 84 87 90 93 24 16.0-33.0 115/177 UL Max* 0.065 0.105 0.189 0.249 0.300 0.420 CBB-8 3314 UL Listed Circular Backbox for 8 Speakers Approvals UL 1480 UL 1971 CSFM MEA S8-70/25 X N/A X X S8-24MCC X X X X S8-24MCCH X X X X CBB-8 X N/A Pending Pending * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes, the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Note: In order to maintain proper UL 1480 listing, the CBB-8 Speaker Back Box (available separately) or other UL approved back box must be installed.
Wiring Diagrams # SERIES S SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) + FROM PRECEDING APPLIANCE - OR VOICE EVACUATION PANEL FROM PRECEDING STROBE, SYNC- MODULE, POWER SUPPLY OR FACP + + - + - + - STROBE SPEAKER + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR SERIES S SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P Audible NAC Cir. Strobe NAC Cir. Audible NAC Cir. DSM #1 Sync + - DSM #2 Strobe NAC Cir. Sync + - Audible NAC Cir. DSM #3 Sync Strobe NAC Cir. + - DSM Interconnecting wiring shown. Maximum of twenty (20) S S S S S S Note: Figure shows interconnection to strobe through sync module. Speaker portion requires 2 separate conductors to FACP. SERIES S SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + OUT 2 S S S S S S SERIES S SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-24-8MC F A C P Series PS-12/24-8MP or PS-12/24-8CP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP S S S RSS RSS RSS EOLR # For details on using SM or DSM Sync Modules refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84662 for PS-24-8MC power supply.
Architects and Engineers Specifications Series S, 8 UL listed ceiling speakers and speaker strobes specifications: The series S8 eight-inch supervised UL Standard 1480 Listed Ceiling speaker shall be mounted to round metal 12 grille, with a white powder coated finish, designed for indoor use. The speaker shall have a dual voltage transformer (25/70V) with jumper selectable 1 /8, ¼, ½, 1, 2, 4, 8 wattage taps. The frequency response shall be 200Hz 15kHz, per UL Standard 1480 shall be 400Hz 4kHz. The sensitivity shall be 93 dba @ 10 feet with 8 watts of source power, 90 dba @ 10 feet with 4 watts of source power, 87 dba @ 10 feet with 2 watts of source power, 84 dba @ 10 feet with 1 watts of source power, 81 dba @ 10 feet with 1/2 watt of source power, 78 dba @ 10 feet with 1/4 watt of source power, 75 dba @ 10 feet with 1/8 watt of source power. The magnet weight shall be 9.5 ounces. The speaker impedance shall be 8 ohms. The Speaker Strobe versions shall be Wheelock Series RSS Strobe Appliances or approved equals. The Series RSS shall meet and be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. The strobe appliances shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). The Series RSS Strobe shall be of low current design. The strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/95cd or 115/177cd. When synchronization is required, the appliance shall be compatible with Wheelock s SM, DSM Sync Modules or Wheelock s PS-12/24-8CP and PS-12/24-8MP Power Supply with built-in Patented Wheelock Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The strobes shall be designed for indoor surface of flush mounting. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1100 S 8 06/06
Series MB Motor Bells RSSP REMOTE PLATE Description The Wheelock Series MB Motor Bells provide a better engineered motor bell for fire and life safety alarm systems. The Wheelock Series MB Bells include higher dba, low current draw, built-in trimplate for semi-flush mounting, low frequency aluminum shells, and low RFI noise. The motor for Series MB Bells is a durable, high torque permanent magnet motor selected for its high performance and long life. These DC vibrating Series MB Motor Bells are offered in 6 and 10 shell sizes in both 12 and 24 VDC models. Series RSSP Sync/Non-Sync retrofit plates are used in conjunction with the Series MB Motor Bell when combination appliances are required. The Series RSSP retrofit plates are available with either Multi-Candela or single candela strobes and easily mount to a 4 square or Wheelock SBL-2 backbox. All Series RSSP strobe appliances meet or exceed the requirements of NFPA 72 (National Fire Alarm ), ANSI 117.1 (American National Standard for Accessible and Usable Buildings and Facilities), ADA (Americans with Disabilities Act) and UL Standard 1971 (Signaling Devices for the Hearing Impaired). The Series RSSP retrofit plates may be synchronized when installed with the Wheelock Series SM, DSM, Sync Modules or the PS-24-8MC Power Supply with Wheelock patented sync protocol. Wheelock synchronized strobes offer an easy way to comply with ADA requirements concerning photo-sensitive epilepsy. Features Approvals include: UL Standard 464, Factory Mutual (FM), Califor nia State Fire Marshal (CSFM), New York (MEA) and Chicago (BFP) Meets OSHA 29 Part 1910.165 High sound output with low current draw Low frequency aluminum shells for better audibility through walls, doors and other structures 6 and 10 shell sizes in 12 or 24 VDC models Integral RFI suppression to minimize included noise on the NAC circuit Mounting options for surface, semi-flush, outdoor, and concealed conduit installation Built-in trimplate makes semi-flush mounting simpler and less expensive Screw terminals permit fast in-out field wiring of #12 to 18 AWG wire Polarized for DC supervision of NAC circuits Operates on filtered or unfiltered DC For combined audible (bell) and visual signaling, convenient retrofit plate assemblies are available with Multi-Candela or Single candela strobes (Refer to Fire Alarm Products Catalog for Series RSSP Sync/Non-Sync Strobes specifications and technical information) Ordering Information Model Number Order Shell Size Input Voltage (VDC) Average RMS Current UL Max* MB-G6-12-R 3942 6 12 0.060 0.090 MB-G6-12-S 4221 6 12 0.060 0.090 MB-G6-24-R 3941 6 24 0.030 0.040 MB-G6-24-S 4222 6 24 0.030 0.040 MB-G10-12-R 3944 10 12 0.060 0.090 MB-G10-12-S 4223 10 12 0.060 0.090 MB-G10-24-R 3943 10 24 0.030 0.040 MB-G10-24-S 4224 10 24 0.030 0.040 E5946 151-92-E 7135-0785:113 dba @ 10 Ft. Mounting Options 92 D,E,J,K,N,O,P,R,S NOTES: 1. Typical dba at 10 feet is measured in an anechoic chamber. 2. For bells all 12 VDC models are UL rated for 9.0 to 15.6 VDC and all 24 VDC models for 18.0 to 31.0 VDC. * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Architects and Engineers Specifications The alarm appliances shall be Wheelock Series MB vibrating Motor Bells or approved equal. They shall be UL Standard 464 Listed for Fire Protective Service. Shells shall be aluminum in 6 or 10 diameter. Sound output at 10 feet shall be 92 dba. The bells shall incorporate a permanent magnet motor and suppression circuitry to minimize RFI. They shall include a built-in trimplate for semi-flush mounting to a standard 4 square backbox, or surface mounting to Wheelock s indoor BB backbox or outdoor WBB backbox. For bell strobe applications, retrofit plates Wheelock Series RSSP with Multi-Candela or Single Candela strobes shall be used. All bell models shall be polarized for line supervision and shall have screw terminals for in-out field wiring of #12 to #18 AWG wire. Operating voltage shall be nominal 24 VDC or 12 VDC. Finish on all models shall be textured enamel. Model Number Order Nominal Voltage (VDC) Strobe Candela Average Current (AMPS) at listed VDC UL Max* **Mounting Options RSSP-24MCW-FR 9402 24 15/30/75/110.041/.063/.109/.140.060/.092/.165/.220 D,E,Z RSSP-241575W-FR 7793 24 15 (75 on-axis).060.090 D,E,Z RSSP-121575W-FR 7798 12 15 (75 on-axis).152.255 D,E,Z * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. Wiring Fig. 1 Bell Models FROM PRECEDING APPLIANCE OR FACP + - { } TO NEXT APPLIANCE OR END-OF-LINE RESISTOR (EOLR) Fig. 2 Retrofit Strobe Plate Models (RSSP) FROM PRECEDING APPLIANCE OR FACP FROM PRECEDING STROBE OR FACP AUDIBLE STROBE + - + - - - + + - - + + TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice In accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1500 MB 06/06
Series E70 Speakers and Speaker Strobes SERIES E70 STROBE SERIES E90 STROBE Description The Wheelock Series E Low Profile Speakers and Speaker Strobes are designed for high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. The low profile design incorporates a speaker mounting plate for faster and easier installation. Each model has a built-in level adjustment feature and an aesthetic two (2) screw grille cover. The Series E Speaker Strobe models incorporate the Low Current draw Series RSS Strobes. Strobe options for wall mount models include 1575 or Wheelock patented MCW multi-candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models are available in Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. Series E Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired. The strobe portion of all Series E Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or Wheelock PS-24-8MC power supply with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. Series E Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring. Color options for the Series E Speakers and Speaker Strobes are red, white and nickel plated. Features SERIES E90 SPEAKER Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/ANSI compliant Complies with OSHA 29 Part 1910.165 Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi- Candela models), or 1575cd (Single Candela model) Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multicandela models) Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage SERIES E70 SPEAKER using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or Wheelock PS-24-8MC Power Supply with built-in sync protocol Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires S5391 151-92-E 7125-0785:152 7320-0785:134 (Speaker)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: UL Max Current* E70/E90 Speaker Strobes E70 Strobe Current - Wall Mount E90 Strobe Current - Ceiling Mount 241575W 24MCW 24MCWH 24MCC 24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd 16-33 VDC 0.090 0.060 0.092 0.165 0.220 0.300.0420 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: E70/E90 UL Reverberant dba @ 10 Feet** watts 1/8 1/4 1/2 1 2 E Speaker 77 81 83 86 89 E Speaker Strobe 76 80 82 85 88 **dba ratings are based on testing under UL Standard 1480. * UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # SERIES E SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) FACP + FROM PRECEDING APPLIANCE - OR VOICE EVACUATION PANEL FROM PRECEDING STROBE, SYNC- MODULE, POWER SUPPLY OR FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN + - + - STROBE SERIES E SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A DSM SYNC +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + - + OUT 2 SPEAKER + - + + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR E E E E E E SERIES E SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P F A C P Audible NAC Cir. Strobe NAC Cir. Audible NAC Cir. DSM #1 Sync + - DSM #2 Strobe NAC Cir. Sync + - Audible NAC Cir. DSM #3 Sync Strobe NAC Cir. + - DSM Interconnecting wiring shown. Maximum of twenty (20) E E E SERIES E SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP Series PS-12/24-8MP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP E E E E E E Note: Figure shows interconnection to strobe through sync module. Speaker portion requires 2 separate conductors to FACP. RSS RSS RSS EOLR For wiring information on the PS-24-8MC power supply, please refer to Data Sheet #S8900. # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84662. Specifications and Ordering Information Model Order Wall Ceiling Mount Mount Strobe Sync w/ SM, DSM or PS-24-8MC Strobe Candela Model Color RED Model Color White Model Color Nickel Mounting Options Agency Approvals UL MEA CSFM FM BFP E70-24MCW-FR 9022 X - X 15/30/75/110 X - - L,O,P,Q,R,U,Y X X X X X E70-24MCW-FW 9023 X - X 15/30/75/110 - X - L,O,P,Q,R,U,Y X X X X X E70-24MCW-FN 3099 X - X 15/30/75/110 - - X Q,U X X X X X E70-241575W-FR 7871 X - X 15 (75 on Axis) X - - L,O,P,Q,R,U,Y X X X X X E70-241575W-FW 7876 X - X 15 (75 on Axis) - X - L,O,P,Q,R,U,Y X X X X X E70-241575W-FN 3100 X - X 15 (75 on Axis) - - X L,O,P,Q,R,U,Y X X X X X E70-R 7866 X X - - X - - Q,U X X X X X E70-W 7868 X X - - - X - Q,U X X X X X E70-N 3108 X X - - - - X Q,U X X X X X E70-24MCWH-FR 3470 X - X 135/185 X - - L,O,P,Q,R,U,Y X X X X * E70-24MCWH-FW 3474 X - X 135/185 - X - L,O,P,Q,R,U,Y X X X X * E70-24MCWH-FN 0059 X - X 135/185 - - X Q,U X X X X * E90-24MCC-FW 3166 - X X 15/30/75/95 - X - Q,U,V X X X X * E90-24MCC-FR 3165 - X X 15/30/75/95 X - - Q,U,V X X X X * E90-24MCC-FN 3185 - X X 15/30/75/95 - - X Q,U,V X X X X * E90-W 7869 X X - - - X - Q,U,V X X X X X E90-R 7867 X X - - X - - Q,U,V X X X X X E90-N 3109 X X - - - - X Q,U,V X X X X X E90-24MCCH-FW 3471 - X X 115/177 - X - Q,U,V X X X X * E90-24MCCH-FR 3481 - X X 115/177 X - - Q,U,V X X X X * E90-24MCCH-FN 0062 - X X 115/177 - - X Q,U,V X X X X * *PENDING
Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E Speakers and the speaker strobe appliances shall be Wheelock Series E Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 87 db at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobe shall be of low current design. Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110cd or 135/185cd for wall mount and 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock SM, DSM sync modules or Wheelock PS-24-8MC power supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a nonsynchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor surface or flush mounting. The speaker and speaker strobe shall incorporate a speaker mounting plate with a grille cover which is secured with two screws for a level, aesthetic finish and shall mount to standard electrical hardware requiring no additional trimplate or adapter. The finish of the Series E speakers and strobe speakers shall be white, red, or nickel plate. All speaker and speaker strobe appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1610 E70/E90 03/07
Series E60 Speakers and Speaker Strobes Speaker Strobe Speaker Description The NEW Wheelock Series E60 Ceiling Speakers and Speaker Strobes are designed for high efficiency sound output, with dual voltage (25/70 VRMS) capability and field selectable taps from 1/8 to 2 watts. These E60 Multi-Candela ceiling appliances are part of the new family of ceiling mount strobe appliances that will also be available on strobes, horns and horn/strobes. Optional Extender (E60 Ext) is for mounting to 4 backboxes with no extension ring. The Series E60 Speaker Strobe models incorporate the Low Current draw Series RSS Strobes. These ceiling mount round models are available in Wheelock patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. Series E60 Speakers and Speaker Strobes provide high audio output with clear audibility and are designed to meet the critical needs of the life safety industry for effective emergency voice communications, tone signaling and visible signaling to alert the hearing impaired. The low profile design incorporates a speaker mounting plate for faster and easier installation. Each model has a built-in level adjustment feature and snap-on cover with no visible mounting screws. The strobe portion of all Series E60 Speaker Strobes may be synchronized when used in conjunction with the Wheelock SM, DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with Patented Sync Protocol. Wheelock synchronized strobes offer an easy way to comply with ADA recommendations concerning photosensitive epilepsy. Series E60 Speaker Strobes are UL Listed for indoor use under Standard 1971 (Signaling Devices for the Hearing-Impaired) and Standard 1480 (Speaker Appliances), and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visual signaling. All inputs are supervised and employ IN/OUT wiring terminals for fast installation using #12 to #18 AWG wiring. Color options for the Series E60 Speakers and Speaker Strobes are red and white. Features Approvals include: UL Standard 1971, UL Standard 1480, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/ANSI compliant Complies with OSHA 29 Part 1910.165 Ceiling mount strobe models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (Multi-candela models) Strobes produce 1 flash per second over the regulated voltage range 24 VDC with wide UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Synchronize with Wheelock SM, DSM or Wheelock PS- 24-8MC Power Supply with built-in sync protocol Field selectable taps for 25 or 70 VRMS operation from 1/8 watt up to 2 watts High efficiency design for maximum output at minimum wattage across a frequency range of 400 to 4000 HZ Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires Optional Extender (E60 Ext) is for mounting to 4 backboxes with no extension ring. U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Average RMS Current E60 Speaker Strobes E60 Strobe Current - Ceiling Mount 24MCC 24MCCH 15cd 30cd 75cd 95cd 115cd 177cd 24 vdc 0.045 0.070 0.119 0.159 0.195 0.270 UL max* 0.065 0.105 0.189 0.249 0.300 0.420 Table 2: E60 UL Reverberant dba @ 10 Feet** watts 1/8 1/4 1/2 1 2 E Speaker 77 79.5 82.5 85 88 E Speaker Strobe 77 79.5 82.5 85 88 **dba ratings are based on testing under UL Standard 1480. * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # SERIES E60 SPEAKER & STROBE OPERATE INDEPENDENTLY (NON-SYNC OR SYNC) FACP + FROM PRECEDING APPLIANCE - OR VOICE EVACUATION PANEL FROM PRECEDING STROBE, SYNC- MODULE, POWER SUPPLY OR FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN + - + - STROBE SERIES E60 SPEAKER STROBE APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + OUT 2 SPEAKER + - + + - TO NEXT APPLIANCE OR EOLR TO NEXT STROBE OR EOLR E E E E E E SERIES E60 SPEAKER STROBES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 Note: Figure Audible NAC Cir. Strobe NAC Cir. Sync shows interconnection to strobe + E E - F Audible NAC Cir. DSM #2 through sync A Strobe NAC Cir. Sync module. Speaker + E E C - portion requires 2 Audible NAC Cir. DSM #3 separate conductors to FACP. P Sync Strobe NAC Cir. + E E - DSM Interconnecting wiring shown. Maximum of twenty (20) SERIES E60 SPEAKER STROBE APPLIANCES & RSS STROBES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP F A C P Series PS-12/24-8MP OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8MP E E E RSS RSS RSS EOLR For wiring information on the PS-24-8MC power supply, please refer to Data Sheet # S8900. # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84662. Specifications and Ordering Information Model Order Wall Ceiling Mount Mount Non- Sync Strobe Sync w/ SM, DSM or PS-12/24-8CP/MP Strobe Candela Model Color RED Model Color White Mounting Options Agency Approvals UL MEA FM BFP CSFM E60-R 3746 X - - - X - Q,U X X X * X E60-W 3745 X - - - - X Q,U X X X * X E60-24MCC-FR 3748 - X X X 15/30/75/95 X - Q,U,V X X X * X E60-24MCC-FW 3747 - X X X 15/30/75/95 - X Q,U,V X X X * X E60-24MCCH-FW 3749 - X X X 115/177 - X Q,U,V X X X * X E60-24MCCH-FR 3750 - X X X 115/177 X - Q,U,V X X X * X E60EXT-R** 3578 X X X * * E60EXT-W** 3757 X X X * * **E60 EXT is an attractive extender ring that mounts behind the speaker to permit mounting to a 4 square x 2 1/8 deep electrical box without need for an extension ring on the box. *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The speaker appliances shall be Wheelock Series E60 Speakers and the Speaker Strobe appliances shall be Wheelock Series E60 Speaker Strobes or approved equals. The speakers shall be UL Listed under Standard 1480 for Fire Protective Service and speakers equipped with strobes shall be listed under UL Standard 1971 for Emergency Devices for the Hearing-Impaired. In addition, the strobes shall be certified to meet the requirements of FCC Part 15, Class B. All speakers shall be designed for a field selectable input of either 25 or 70 VRMS, with selectable power taps from 1/8 watt to 2 watts. All models shall have listed sound output of up to 87 db at 10 feet and a listed frequency response of 400 to 4000 Hz. The speaker shall also incorporate a sealed back construction. All inputs shall employ terminals that accept #12 to #18 AWG wire sizes. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The strobe shall be of low current design. Where Multi-Candela Speaker Strobes are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 15/30/75/95cd or 115/177cd for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. When synchronization is required, the strobe portion of the appliance shall be compatible with Wheelock SM, DSM sync modules or the Wheelock PS-24-8MC Power Supply with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flash rate. The speaker and speaker strobe appliances shall be designed for indoor flush mounting. The speaker and speaker strobe shall incorporate a speaker mounting plate with a snap-on grille cover with no visible screws for a level, aesthetic finish and shall mount to standard electrical hardware. The finish of the Series E60 Speakers and Speaker Strobes shall be white or red. All speaker and speaker strobe appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1611 E60 08/06
Series MIZ Mini Horn Appliances SERIES MIZ Description: Wheelock Series MIZ piezoelectric Mini Horns are compact electronic alarm appliances that are listed under UL Standard 464 for Audible Appliances in Public Mode Fire Protection Systems. The Series MIZ-24S models provide a field selectable Continuous or 3 horn tone when connected directly to a fire alarm control panel. They can also provide a synchronized code 3 horn tone using the Wheelock SM, DSM Sync Modules or PS-24-8MC power supply. The series MIZ appliances are attractive, offer high sound output along with low current draw and are ideal for alarm signaling in individual rooms, apartments, hotels, motels and offices. Color choices of red or off-white will blend with any décor. Wiring Diagrams (for all models) Features: Approvals include: UL Standard 464, California State Fire Marshal (CSFM), New York City (MEA), Factory Mutual (FM), and Chicago (BFP) Field selectable settings for Temporal ( 3) or Continu ous Horn Synchronized code 3 horn when used with Wheelock Sync Module Designed to meet or exceed NFPA/ANSI standards Convenient mounting to any standard single-gang box Beauty plugs to cover mounting screws No additional trimplate required for flush mounting Fast installation with In/Out screw terminals using #12 to #18 AWG High sound output with low current draw Available in red or off-white color FROM PRECEDING APPLIANCE OR FACP + - + - + - TO NEXT APPLIANCE OR EOLR Applications: Individual Rooms Apartments Hotels Motels Offices Specifications and Ordering Information Model Order Description Mounting Options** Agency Approvals UL MEA CSFM FM BFP MIZ-24S-R 8485 24 Volt, Red B X X X X * MIZ-24S-W 8484 24 Volt, White B X X X X * *PENDING **Refer to Data Sheet S7000 for Mounting Options. U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS General Notes: Mini Horn models are Listed for indoor use with a temperature range of 32º F to 120º F (0º C to 49º C) and maximum humidity of 93% RH ±2%. Rated Input voltage (either filtered DC or unfiltered full-wave-rectified FWR): 16-33 VDC (for 24 VDC MIZ-24S models) S5391 151-92-E 7125-0785:161
Architects and Engineers Specifications The notification appliance shall be a Wheelock MIZ-24S audible appliance or approved equal. The Notification Appliance shall be electronic and shall have field selectable settings for Temporal ( 3) or continuous horn and support coded systems operation. The anechoic sound pressure measurement on Temporal ( 3) setting shall be 87 dba minimum at 24VDC. The anechoic sound pressure measurement on Continuous Horn setting shall be 87 dba minimum at 24 VDC. Operating voltages shall be 24 VDC using filtered power or unfiltered power supply (full-wave-rectified). All models shall have provision for standard reverse polarity type supervision and IN/OUT wiring using terminals that accept #12 to #18 AWG wiring. The appliances shall be mounted indoors and mount on standard single-gang electrical backboxes requiring no additional trimplates or adapters. Table 1: UL Listed Models and Ranges Model MIZ-24S Regulated UL Voltage Average RMS Current* (AMPS) Reverberant dba Per UL 464 @ 10 ft Anechoic dba @ 10 ft Continuous 3 Continuous 3 dba dba dba dba Mounting Options 24 VDC 0.025 83.2 78.8 87.9 87.9 B UL max* 0.026 85.8 81.3 90.6 89.7 B * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. WARNING: CONTACT WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS (P84408) AND GENERAL INFORMATION SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED VOLTAGE RANGE. FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1700 MIZ 06/06
Series SA-S Supervised Self-Amplified Speakers and Speaker Strobes Series SA-S70-24MCW-FR Series SA-S70-R Series SA-S90-24MCC-FR Description: The Series SA-S Supervised Self-Amplified Speakers and Speaker Strobes are designed to meet the critical needs for the life safety industry. These speakers and speaker strobes are a perfect fit for SCIF (Sensitive Compartmented Information Facilities) room applications. Features: Approvals Include: UL Standard 1480 (Speakers) and UL Standard 1971 and UL Standard 1480 (Speaker Strobes) Accepts audio input levels of 0.5 VRMS or 25 VRMS Power Input Voltage 16.0 to 33.0 VDC Wall or ceiling mount models Speaker strobes utilize Wheelock s synchronizable Multi- Candela Strobe 1 watt high efficiency speaker Frequency range of 400Hz to 4000Hz Mounts onto a 4 square deep backbox with an extension ring Power Input Voltage: Appliance Input Level: Appliance Input Impedence: 16.0-33.0 VDC, regulated 0.5 V RMS or 25 V RMS (Switch selectable) 0.5-V Setting: Greater than 400 Ohms, or equivalent to less than 1/1000 W (0.001 W or 1 mw) load 25-V Setting: Greater than 20 kohms, or equivalent to less than 1/32 W (.03125 W or 31.25 mw) load Sound Level Speaker Amplifier Current Draw: (Loudest) Level 6: < 120mA RMS Level 5: < 97mA RMS Level 4: < 80mA RMS Level 3: < 68mA RMS Level 2: < 60mA RMS (Lowest) Level 1: < 54mA RMS U L db Sound Output Sound Level SA-S90R SA-S90W SA-S70R SA-S70W SA-S90-24MCC-FR SA-S90-24MCC-FW SA-S70-24MCC-FR SA-S70-24MCC-FW 6 84 84 82 5 82 81 81 4 77 77 76 3 75 74 74 2 71 71 70 1 69 68 68 S5391
Specification and Ordering Information Model Number Order Wall Mount Ceiling Mount Strobe Candela Model Color Red Model Color White Mounting Options# Agency Approvals SA-S90-R 1000 - X - X - Q,U,V X SA-S90-W 1001 - X - - X Q,U,V X SA-S70-R 1002 X - - X - C,O,P,Q,R,U,Y X SA-S70-W 1003 X - - X C,O,P,Q,R,U,Y X SA-S90-24MCC-FR 1004 - X 15/30/75/95 X - Q,U,V X SA-S90-24MCC-FW 1005 - X 15/30/75/95 - X Q,U,V X SA-S70-24MCW-FR 1006 X - 15/30/75/110 X C,O,P,Q,R,U,Y X SA-S70-24MCW-FW 1007 X - 15/30/75/110 - X C,O,P,Q,R,U,Y X UL Average Strobe Current SA-S70-24MCW-FR and SA-S70-24MCW-FW UL Strobe Current Ratings Rated Average Current (RMS) Voltage 15cd 30cd 75cd 110cd 24.0 VDC 0.041 0.063 0.109 0.140 UL Max* 0.060 0.092 0.165 0.220 24.0 VRMS 0.079 0.114 0.179 0.235 UL Max* 0.102 0.155 0.253 0.347 SA-S90-24MCC-FR and SA-S90-24MCC-FW UL Strobe Current Ratings Rated Average Current (RMS) Voltage 15cd 30cd 75cd 95cd 24.0 VDC 0.045 0.070 0.119 0.159 UL Max* 0.065 0.105 0.189 0.249 24.0 VRMS 0.085 0.125 0.200 0.255 UL Max* 0.110 0.170 0.280 0.375 Architects and Engineers Specifications The Series SA-S Self-Amplified Speakers and Speaker Strobes shall be UL Listed under Standards UL 1480 (Standard for Speakers for Fire Alarm, Emergency, and Commercial and Professional Use). The Speaker Strobe models shall be UL Listed under Standards UL 1971 (Standard for Signaling Devices for the Hearing Impaired) and for indoor fire protection service. The Series SA-S Self-Amplified Speakers and Speaker Strobes shall provide a choice of 6 different sound output levels and operate with audio input levels of 0.5 V RMS and 25 V RMS, all by means of selectable switch settings. The Series SA-S Self-Amplified Speakers and Speaker Strobes shall incorporate a high efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and feature a sealed back construction for extra protection and improved audibility. Al The SA-S Series Multi-Candela Speaker Strobe models shall offer four selectable light output intensities in one unit and can provide a non synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM) or Wheelock s Power Supplies listed for synchronization. The ceiling mount Speaker Strobe models shall provide 15/30/75/95 candela options. The wall mount Speaker Strobe models shall provide 15/30/75/110 candela options. All strobe candela options shall be field selectable via a tamper resistant selector switch. The Strobe uses a Xenon flashtube with solid-state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling. The SA-S Series shall be listed for indoor use. Lexan is a registered trademark of General Electric Corporation. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S1800 SA 06/06
Series MT and MT Strobe Multitone Electronic Appliances SERIES MT STROBE MT4-115-WH SERIES MT-12/24 Description: The Wheelock Series MT and MT Strobe Multitone electronic appliances offer a choice of eight (8) nationally and internationally recognized alerting sounds: Horn, Bell, March Time Horn, - 3 Tone, -3 Horn, Slow Whoop, Siren or Hi/Lo Tone. The -3 Horn and tone patterns are engineered to comply with NFPA/ANSI Temporal Pattern specifications without requiring additional equipment. With MT and MT Strobe appliances, one alarm appliance meets most of your signaling needs. The MT strobes can be synchronized using the Wheelock SM, DSM Sync Modules or the PS-24-8MC Power Supply with the Wheelock patented Sync Protocol. The MT Strobes are designed for ADA applications while meeting or exceeding the latest requirements of NFPA 72, ANSI 117.1, UFC and UL Standard 1971 as well as meeting ADA requirements concerning photosensitive epilepsy. Each MT and MT Strobe appliance has two installer selective sound output levels: STANDARD dba and HIGH dba. Non-strobe versions provide selectable voltage capability in one unit, 12VDC or 24VDC. Strobe versions are specific for either 12VDC or 24VDC and all models may be used with filtered or unfiltered (full-waverectified) input voltages. Separate input terminals are available, shunt wires are provided to enable both tone and strobe to operate simultaneously from a single input. The Series MT Multitone Strobe appliances are UL Listed for indoor wall mount applications under Standard 1971 for Signaling Devices for the Hearing Impaired and under Standard 464 for Audible Signaling Appliances. Features: Approvals include: UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), New York City (MEA), Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information Designed to meet or exceed ADA/NFPA/UFC/ANSI Standards and Accessibility Guidelines Complies with OSHA 29, Part 1910.165 Series MT appliances have IN and OUT wiring terminations that accept two #12 to #18 American Wire Gauge (AWG) wires at each terminal. Inputs are polarized for compatibility with standard reverse polarity type supervision One alarm appliance with (8) eight selective signals to provide superior sound penetration for various ambient and wall conditions with two field selectable sound output levels -3 Horn and Tone meet ANSI/NFPA temporal pattern for standard emergency evacuation signaling Audible and strobe can operate from a single NAC circuit or from separate NAC circuits with any of the (8) eight audible sounds MT Strobe models are available with Wheelock patented MCW Multi-Candela strobes with field selectable c andela settings at 15/30/75/110cd or with single candela 1575cd strobes. The strobes can be synchronized using Wheelock sync modules or power supplies with built in Sync Protocol Selectable input voltage on non-strobe versions. Strobe versions are factory set for either 12 or 24VDC, with wide- Listed voltage range, filtered (DC) and FWR No additional trimplate required for flush mounting For Weatherproof MTWP See Data Sheet S9004 U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS E5946 151-92-E 7135-0785:118 (MT4) 7125-0785:155 (MT) 7125-0758:156 (MTWP)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range (16-33v for 24VDC units and 8-17.5v for 12VDC units). Regulated Voltage Range is the newest terminology used by UL to identify the listed voltage range. All candela ratings represent minimum effective Multitone Strobe intensity based on UL Standard 1971. MT Strobe models are UL Standard 1971 Listed for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% ±2%. The MT-12/24, MTWP and MT4 models and listed for outdoor use at -31 F to 150 F (-35 C to 66 C) and maximum humidity of 95% (See Data Sheet S9004 or Installation Instruction Sheet P84150 for more detail on MTWP). MTWP and MT4 strobes are listed under UL 1638. MT Audible is UL Standard 464 Listed. Alarm Tones TONE HORN BELL MARCH TIME HORN CODE-3 HORN CODE-3 TONE SLOW WHOOP SIREN HI/LO ALARM TONES PATTERN DESCRIPTION BROADBAND HORN (Continuous) 1560 Hz MODULATED (0.07 sec. ON/Repeat) HORN (0.25 sec. ON/0.25 sec. OFF/Repeat HORN (ANSI S3.41 Temporal Pattern) 500 Hz (ANSI S3.41 Temporal Pattern) 500-1200 Hz SWEEP (4.0 sec. ON/0.5 sec. OFF/Repeat) 600-1200 Hz SWEEP (1.0 sec. ON/Repeat) 1000/800 Hz (0.25 sec. ON/Alternate) Table 1: dba and Current Ratings for Multitone Audible Portion RMS Current (amps) dba @ 10ft (UL Reverberant) 24 VDC 12 VDC 120 VAC 24 VDC 12 VDC 120 VAC HI Output STD Output HI Output STD Output @ 24 VDC UL max* @ 24 VDC UL max* @ 24 VDC UL max* @ 24 VDC UL max* HI Output UL max* STD Output UL max* HI Output STD Output HI Output STD Output HI Output STD Output Horn 0.074 0.108 0.033 0.044 0.145 0.176 0.023 0.034 0.050 0.042 92 87 90 77 85 82 Bell 0.040 0.053 0.018 0.024 0.077 0.095 0.014 0.020 0.041 0.039 86 80 85 69 82 75 March Time Horn 0.067 0.104 0.033 0.038 0.109 0.142 0.023 0.034 0.050 0.040 89 84 89 74 85 79-3 Horn 0.069 0.091 0.026 0.035 0.100 0.142 0.023 0.034 0.050 0.042 88 83 88 73 82 75-3 Tone 0.061 0.075 0.026 0.035 0.088 0.105 0.015 0.021 0.042 0.040 85 80 84 70 79 75 Slow Whoop 0.069 0.098 0.028 0.037 0.100 0.142 0.025 0.035 0.050 0.042 90 89 89 75 85 82 Siren 0.080 0.104 0.027 0.036 0.122 0.152 0.021 0.030 0.045 0.041 89 84 89 75 85 82 HI/LO 0.044 0.057 0.020 0.026 0.089 0.114 0.018 0.026 0.042 0.039 86 81 86 71 82 79 Table 2: Strobe Current Ratings RMS Current (amps) Model MT-121575 MT-241575 MTWP-2475 MT-24MCW Candela 1575cd 1575cd 180cd 15cd 30cd 75cd 110cd @ 24VDC 0.152 0.060 0.094 0.041 0.063 0.109 0.140 UL max* 0.255 0.090 0.138 0.060 0.092 0.165 0.220 Note: If the strobe and audible operate on the same circuit, add the strobe current from Table 2 to the audible current from Table 1. * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams (for all models) MT SIGNAL AUDIBLE SIGNAL AND STROBE OPERATE INDEPENDENTLY AUDIBLE SIGNAL AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED. Specifications and Ordering Information Model Number Order Input Voltage Rated Candela Mounting Options*** Agency Approvals UL MEA CSFM FM BFP MT-12/24-R 5023 12/24 - D,E,F,L,M,O,P,R X X X X X MT-12/24-W 5024 12/24 - D,E,F,L,M,O,P,R X X X X X MT-241575W-FR # 8422 24 15 (75 on AXIS) D,E,F,L,M,O,P,R X X X X * MT-24MCW-FR 3301 24 15/30/75/110 D,E,F,L,M,O,P,R X * X * * MT-24MCW-FW 3303 24 15/30/75/110 D,E,F,L,M,O,P,R X * X * * MT-121575W-FR # 8421 12 15 (75 on AXIS) D,E,F,L,M,O,P,R X X X X * MT-121575W-NW 9747 12 15 (75 on AXIS) D,E,F,L,M,O,P,R X X X X * MTWP-2475W-FR** 8420 24 180 @ 77 F (25 C) M X X X X * MTWP-2475W-NW** 9744 24 180 @ 77 F (25 C) M X X X X * MT4-115-R 6223 120 VAC - D,E,J,K,N,O,R X X X X X MT4-115-S 6142 120 VAC - D,E,J,K,N,O,R X X X X X MT4-115-WH-VFR ## 6224 120 VAC 15 D,E,J,K,N,O,R X X X X X MT4-12/24-R 5308 12/24 - D,E,J,K,N,O,R X * * * * MT4-12/24-S 7997 12/24 - D,E,J,K,N,O,R X * * * * NOTE: **MTWP-2475W is Weatherproof and rated for 180 cd @ 77 F (25 C). See Data Sheet S9004 or Installation Instruction P84150. ***For additional information on mounting please refer to Data Sheet S7000. # 1575 strobes are UL Listed for 15cd with 75cd on AXIS. *Pending ## Series WH Strobe is listed for UL Standard 1638 only. See Instruction Sheet P83160. WARNING: CONTACT WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS P82467 MT-12/24, P84155 MT w/strobe P84150 MTWP WEATHERPROOF GENERAL INFORMATION SHEET (P82380) ON THESE PRODUCTS. THESE DOCUMENTS DO UNDERGO PERIODIC CHANGES. IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS. THESE MATERIALS CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING THESE PRODUCTS, INCLUDING: TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. FUSE RATINGS ON NOTIFICATION APPLIANCE CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON THOSE CIRCUITS. COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW. THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE RANGE. INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. USE STROBES ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS COULD RESULT IN IMPROPER INSTALLATION, APPLICATION, AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION,WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. CONDUCTOR SIZE (AWG), LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION PRIOR TO DESIGN AND INSTALLATION OF THESE PRODUCTS, PARTICULARLY IN RETROFIT INSTALLATIONS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ).
Architects and Engineers Specifications The notification appliance shall be a Wheelock Series MT audible/visual appliance or equivalent. Notification appliance shall be electronic and use solid state components. Electromechanical alternatives are not approved. Each electronic appliance shall provide eight (8) field selectable alarm tones. The tones shall consist of: HORN, BELL, MARCH TIME HORN, CODE-3 HORN, CODE-3 TONE, SLOW WHOOP, SIREN and HI/LO. Tone selection shall be by durable dip switch assembly and not clips or jumpers. The Multitone Audible appliance shall be UL Listed under Standard 464 for Audible Signal Appliances. The audible and the strobe shall be able to operate from a single NAC circuit while producing any of these tones. The appliance shall provide two output sound levels: STANDARD and HIGH dba. The HIGH dba setting shall provide a minimum 5 dba increase in sound output at nominal voltage. The HIGH anechoic dba measurement at 10 feet at the alarm HORN SETTING shall be 99 dba minimum. Operating voltages shall be either 12 VDC or 24 VDC using filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination audible/visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobe shall produce a flash rate of one (1) flash per second minimum over the voltage range. The MT strobe intensity shall be rated per UL and Listed under Standard 1971 for Signaling Devices for the Hearing Impaired for 1575cd multi-candela with field selectable 15/30/75/110 candela settings. The 1575 candela strobe shall be specified when 15 candela or with 75 candela intensity on-axis is required. Strobe Models shall incorporate circuitry for synchronized strobe flash and shall be designed for compatibility with Wheelock SM and/or DSM Sync Modules or Wheelock s Power Supplies with Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the module fails to operate (i.e., contacts remain closed), the strobes shall revert to a non-synchronized default flash rate. Strobe activation shall be via independent input or from the same input circuit as the audible. The combination audible/visual appliances shall be installed indoors and may be surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The aesthetic appearance shall not have any mounting holes or screw heads visible when the installation is completed. The appliance shall be finished in a textured red color. The Series MT-12/24, MTWP and MT4 appliances may be installed indoor or outdoor with the proper back box. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S2000 MT 06/06
Series NS Horn Strobes and Series NH Horns Series NS Series NH Description: The Series NS Horn Strobe Appliances are designed for indoor, wall and ceiling mount applications. The Series NH Horn and the horn portion of the Series NS include a selectable continuous horn tone or temporal pattern ( 3) with selectable dba settings of 90 or 95 dba. Strobe options include 1575cd or the Wheelock patented Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd for wall mount and 15/30/75/95cd and 115/177cd for ceiling mount. These versatile Horn Strobe Appliances can be synchronized using the Wheelock SM, DSM Sync Modules or the PS-24-8MC Power Supply with the Wheelock patented Sync Protocol. Additionally, the audible may be silenced while maintaining strobe activation. All models of the Series NS and NH are designed for maximum performance, reliability and cost-effectiveness while meeting or exceeding the latest requirements of NFPA 72/ANSI 117.1/UFC and UL Standards 1971 and 464 as well as meeting ADA requirements concerning photosensitive epilepsy. The Wheelock patented 2-Wire Series NS Horn Strobes and Series NH Horns offer more features with lower current draw than competitors. Features: Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM) and Chicago (BFP). See approvals by model number in Specifications and Ordering Information ADA/NFPA/UFC/ANSI compliant Complies with OSHA 29, Part 1910.165 Wall mount model Field Selectable Candela Setting 15/30/75/110cd (24 VDC Multi-Candela models) or 1575cd in 12 or 24 VDC Ceiling mount model Field Selectable Candela Setting 15/30/75/95cd and 115/177cd (24 VDC Multi-Candela models) Selectable Continuous Horn or Temporal ( 3) 2 Selectable dba settings of 90 and 95 dba in both tones Patented Universal Mounting Plate 12 and 24 VDC models with UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Wall and Ceiling Mount Ceiling models with same look as Wheelock round ceiling strobes and speakers NH horn is selectable 12 or 24 VDC in 1 appliance The strobes can be synchronized using the Wheelock sync modules or power supplies with built in Sync Protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires NS and NH Ceiling Mount Appliances will be available July 2006. U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS E5946 S5391 151-92-E 7125-0785:142
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Ratings Per UL Standard 1971 Model Input Voltage VDC Regulated Voltage Range VDC/FWR Strobe Candela (CD) NS-24MCW 24 16.0-33.0 15/30/75/110 NS-241575W 24 16.0-33.0 15 (75 on Axis) Table 2: dba Ratings for Series NS/NH Horn Description Continuous Horn Volume Reverberant dba Anechoic dba @ 10ft per UL 464 @ 10 ft 12 VDC 24 VDC 12 VDC 24 VDC High 83 87 89 95 Low 76 81 84 90 NS-121575W 12 8.0-17.5 15 (75 on Axis) NS-24MCC 24 16.0-33.0 15/30/75/95 NS-24MCCH 24 16.0-33.0 115/177 3 Horn High 79 82 89 95 Low 72 76 84 90 Table 3: UL Max Current* Series NS/NH 24 VDC Audible Wall Mount Strobe Models Ceiling Mount Strobe Models NH-12/24 NS-241575W NS-24MCW NS-24MCC NS-24MCCH @24VDC 15/75cd 15cd 30cd 75cd 110cd 15cd 30cd 75cd 95cd 115cd 177cd High (95) dba 24VDC 0.044 0.104 0.074 0.107 0.184 0.244 0.082 0.124 0.209 0.275 0.350 0.477 Low (90) dba 24VDC 0.018 0.096 0.066 0.101 0.177 0.232 0.071 0.114 0.201 0.261 0.306 0.429 Series NS/NH 12VDC Audible NH-12/24 @12V Wall Mount Aud/Strobe NS-121575W High (89) dba 12 VDC 0.021 0.220 Low (84) dba 12VDC 0.012 0.210 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # NS/NH APPLIANCE FROM + PRECEDING - APPLIANCE, SM/DSM, PS-12/24-8MP, PS-12/24-8CP OR FACP + - SIGNAL + - TO NEXT APPLIANCE OR EOLR NS AND NH APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS B NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE F A C P Strobe NAC Circuit Audible NAC Circuit SM + - STROBE STROBE + Audible EOLR - Audible NS NH NS AND NH APPLIANCES SYNCHRONIZED WITH DSM MODULE DUAL CLASS A NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE NOTE: NS/NH must be set on 3 horn tone to achieve synchronized temporal ( 3) tone. Refer to installation instruction (P83983, P83600 respectively). # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84515 for PS-12/24-8CP and P84333 for PS-12/24-8MP. SPECIFICATION & ORDERING INFORMATION Model Number Order Strobe Candela Sync w/ SM, DSM or PS-24-8MC 24 VDC 12 VDC Mounting Options# Agency Approvals UL MEA CSFM FM BFP NS-24MCW-FR 9404 15/30/75/110 X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS-24MCW-FW 9405 15/30/75/110 X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS-241575W-FR 7806 15 (75 on Axis) X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS-241575W-FW 7811 15 (75 on Axis) X X - B,D,E,F,G,H,J,N,O,R,X X X X X X NS-121575W-FR 7816 15 (75 on Axis) X -- X B,D,E,F,G,H,J,N,O,R,X X X X X X NS-121575W-FW 7818 15 (75 on Axis) X - X B,D,E,F,G,H,J,N,O,R,X X X X X X NH-12/24-R 7449 - X X X B,D,E,F,G,H,J,N,O,R,X X X X X X NH-12/24-W 7500 - X X X B,D,E,F,G,H,J,N,O,R,X X X X X X NS-24MCC-FR 3754 15/30/75/95 X X - E X * * * * NS-24MCC-FW 3753 15/30/75/95 X X - E X * * * * NS-24MCCH-FR 3756 115/177 X X - E X * * * * NS-24MCCH-FW 3755 115/177 X X - E X * * * * NH-12/24R-R 3752 - X - X B,D,E,F,G,H,J,N,O,R,X X * * * * NH-12/24R-W 3751 - X - X B,D,E,F,G,H,J,N,O,R,X X * * * * NS and NH Ceiling Mount Appliances will be available July 2006. *Pending Note: Models are available in Red or White. Contact Customer Service for Order and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
ARCHITECTS AND ENGINEERS SPECIFICATIONS The audible/visual notification appliances shall be Wheelock Series NS Horn Strobe appliances and Series NH Horn appliances or approved equals. The Series NS appliances shall meet and be listed for UL Standard 1971(Emergency Devices for the Hearing- Impaired for Indoor Fire Protection Service). The Series NH Horn shall be UL Listed under Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of two (2) field selectable settings for dba levels (90 and 95 dba) and shall have a choice of continuous or temporal ( 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series NS shall be of low current design. Where wall mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/110 candela. Where ceiling mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for 15/30/75/95 candela or 115/177 candela. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with the Wheelock SM, DSM Sync Modules or the Wheelock PS-24-8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flashrate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation. The Series NS Horn Strobes and NH horn shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a singlegang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S2100 NS/NH 05/06
Series HS Horn and Horn Strobe Appliances SERIES HS4 SERIES HS Description The Series HS4 Horn Strobe and HS Horn Appliances are an ideal choice for retrofit applications as well as new installations. They satisfy virtually all requirements for indoor, wall mount applications. The Series HS Horn and the horn portion of the Series HS4 include a selectable continuous horn tone or temporal pattern ( 3) with three selectable dba settings for each tone. Strobe options include 1575cd or the Wheelock patented MCW Multi-Candela strobe with field selectable candela settings of 15/30/75/110cd or the high intensity MCWH strobe with field selectable 135/185cd. The Series HS4 horn and strobe inputs are electrically isolated to allow for independent operation of the strobe circuit and the horn circuit. The horn and strobe may also be wired in parallel to operate on a single circuit. These versatile Horn and Horn Strobe Appliances may be synchronized using Wheelock SM, DSM Sync Modules or the PS-24-8MC Power Supplies with Wheelock patented Sync Protocol. All models are designed for maximum performance, reliability and cost-effectiveness while meeting or exceeding the latest requirements of NFPA 72/ANSI 117.1/UFC and UL Standards 1971 and 464 as well as meeting ADA requirements concerning photosensitive epilepsy. Features Approvals include: UL Standard 1971, UL Standard 464, New York City (MEA), California State Fire Marshal (CSFM) and Factory Mutual (FM) and Chicago (BFP) See approvals by model in Specifications and Ordering Information ADA/NFPA/UFC/ANSI compliant Complies with OSHA 29, Part 1910.165 Field Selectable Candela Settings: 15/30/75/110cd or 135/185cd (Multi-Candela models) or 1575cd (single candela model) Selectable Continuous Horn or Temporal ( 3) 3 Selectable dba settings of 90/95/99 dba in both tones 4-Wire Horn Strobe Appliance allows for separate operation of the horn and strobe circuits 24 VDC models with 16 to 33 VDC UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Wall mount flush to standard 4-inch square or double-gang boxes or surface mount to IOB backbox Synchronize with Wheelock Sync Modules or Power Supplies with built-in sync protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7125-0785:161
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Ratings Per UL Standard 1971 Model Number Input Voltage VDC Regulated Voltage Range VDC/FWR Strobe Candela (CD) HS4-24MCW 24 16.0-33.0 15/30/75/110 HS4-241575W 24 16.0-33.0 15 (75 on Axis) HS4-24MCWH 24 16.0-33.0 135/185 HS-24 24 16.0-33.0 - Table 2: dba Ratings for Horn Description Volume Reverberant dba @ 10ft per UL 464 Anechoic dba @ 10 ft 24VDC 24VDC Continuous Horn 3 Horn High 91 99 Med 88 95 Low 83 90 High 87 99 Med 84 95 Low 79 90 Table 3: Average RMS Current* Audible Current Strobe Current HS/HS4 Series HS and HS4 HS4-241575W HS4-24MCW HS4-24MCWH High (99) dba Med (95) dba Low (90) dba 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 24 vdc 0.098 0.052 0.024 0.060 0.041 0.063 0.109 0.140 0.195 0.270 UL max* 0.110 0.068 0.027 0.090 0.060 0.092 0.165 0.220 0.300 0.420 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # HS4 or HS APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS B NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE F A C P Strobe NAC Circuit Audible NAC Circuit SM + STROBE - STROBE Horn and Strobe wired in parallel + Audible EOLR - Audible HS4 HS4 HS4 (4WIRE) APPLIANCE INDEPENDENT OPERATION OF AUDIBLE SIGNAL AND STROBE FROM PRECEDING APPLIANCE, SYNC MODULE, POWER SUPPLY or FACP FROM PRECEDING APPLIANCE, SM/DSM, PS-12/24-8CP or MP POWER SUPPLY or FACP + - + - + - - + Horn and Strobe on separate circuits - + + - TO NEXT APPLIANCE OR EOLR TO NEXT APPLIANCE OR EOLR HS4 AND HS APPLIANCES SYNCHRONIZED WITH DSM MODULE DUAL CLASS A NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE HS4 OR HS APPLIANCES SYNCHRONIZED WITH DSM MODULE 2 CLASS B CIRCUITS Horn and Strobe wired in parallel Horn and Strobe on separate circuits Note: HS4 or HS must be set on 3 horn tone to achieve synchronized temporal ( 3) tone. Refer to installation instruction. Specifications and Ordering Information Model Number Order Strobe Candela Non- Sync Sync w/ SM, DSM or PS-12/24-8CP/MP 24 VDC 2 WIRE 4 WIRE Mounting Options** Agency Approvals UL MEA CSFM FM BFP HS4-24MCW-FR 3150 15/30/75/110 X X X X X D,E,F,L,M,O,P,R X X X X * HS4-24MCW-FW 3151 15/30/75/110 X X X X X D,E,F,L,M,O,P,R X X X X * HS4-241575W-FR 3176 HS4-121575W-FR 3177 15 (75 on Axis) 15 (75 on Axis) X X X X X D,E,F,L,M,O,P,R X X X X * X X X X X D,E,F,L,M,O,P,R X X X X * HS4-24MCWH-FR 3132 135/185 X X X X X D,E,F,L,M,O,P,R X X X * * HS4-24MCWH-FW 3148 135/185 X X X X X D,E,F,L,M,O,P,R X X X * * HS-24-R 3152 - X X X X D,E,F,L,M,O,P,R X X X X * HS-24-W 3153 - X X X X D,E,F,L,M,O,P,R X X X X * Models are available in either Red or White. Cal Customer Service for Order & Delivery. **Refer to Data Sheet S7000 for Mounting Options. *PENDING NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The audible/visual notification appliance shall be Wheelock Series HS4 Horn Strobe and HS Horn Appliances or approved equals. The Series HS4 and HS appliance shall meet ad be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired for Indoor Fire Protection Service) and Standard 464 (Fire Protective Signaling). The horn strobe shall be listed for indoor use and shall meet the requirement of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by the Fire Alarm Control Panel (FACP). The HS Horn and the audible portion of the HS4 appliance shall have a minimum of three (3) field selectable setting for dba levels and shall have a choice of continuous or temporal ( 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series HS4 shall be of low current design. Where wall mount, Multi-Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 for: 15/30/75/110cd or 135/185cd. The selector switch for selecting the candela setting shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required. When synchronization is required, the appliance shall be compatible with Wheelock s SM, DSM Sync Modules or Wheelock PS-24-8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobes shall revert to a non-synchronized flashrate. All notification appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S2400 HS 06/06
FIRE ALARM SYSTEMS INC. Helping People Take Action SM SERIES HS4 MULTI-CANDELA HORN STROBE APPLIANCE Description The Series HS4 Horn Strobe Appliances are an ideal choice for retrofit applications as well as new installations. They satisfy virtually all requirements for indoor, wall mount applications. Series HS4 includes a selectable continuous horn tone or temporal pattern ( 3) with three selectable dba settings for each tone. Strobe options include Wheelock s patented MCW Multi- Candela strobe with field selectable candela settings of 15/30/75/110cd. The Series HS4 horn and strobe inputs are electrically isolated to allow for independent operation of the strobe circuit and the horn circuit. The horn and strobe may also be wired in parallel to operate on a single circuit. These versatile Horn and Horn Strobe Appliances may be synchronized using Wheelock SM, DSM Sync Modules or the PS-12/24-8CP and PS-12/24-8MP Power Supplies with Wheelock s patented Sync Protocol. All models are designed for maximum performance, reliability and cost-effectiveness while meeting or exceeding the latest requirements of CAN/ULC-S526-02 for Visual Signaling Appliances and CAN/ULC-S525-99 for Audible Signaling Appliances. SERIES HS4 Multi-Candela Indicator (bottom of lens) Features Approvals include: CAN/ULC-S526-02 for Visual Signaling Appliances and CAN/ULC-S525-99 for Audible Signaling Appliances ADA/NFPA/ANSI compliant Field Selectable Candela Settings: 15/30/75/110cd Selectable Continuous Horn or Temporal ( 3) 3 Selectable dba settings of 90/95/99 dba in both tones 4-Wire Horn Strobe Appliance allows for separate operation of the horn and strobe circuits 24 VDC models with 16 to 33 VDC UL Regulated Voltage using filtered DC or unfiltered VRMS input voltage Wall mount flush to standard 4-inch square or double-gang boxes or surface mount to IOB backbox Synchronize with Wheelock Sync Modules or Power Supplies with built-in sync protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires Copyright 2005 Wheelock Inc. All rights reserved. 10
Series SM and DSM Sync Modules Series SM or DSM Description The Wheelock Series SM and DSM Sync Modules are utilized with the Series AS/AH, Series NS/NS4/NH, Series RSS, Series RSSP, Series SLM and selected strobe applications with other Wheelock combination appliances. When used with Series AS Audible Strobes and/or Series NS Horn Strobes, the SM and DSM Sync Modules provide independent operation of synchronized temporal pattern (code 3) horn and synchronized strobe flash, as well as the ability to silence the horn while maintaining the strobe flash. while using only a single pair of wires. The sync modules are available in two versions; the SM-12/24 for control of a Class B NAC circuit; and a dual output version, the DSM-12/24 for control of either a Class A or two (2) Class B NAC circuits. Features Approvals include: UL Standard 1971, ULC, New York City (MEA), California State Fire Marshal (CSFM) and Chicago (BFP) Uniquely designed to accept an independent strobe and audible input from the FACP and convert to a single output that connects to Wheelock s Series AS or Series NS family of audible strobes Series SM and DSM Sync Modules can also be used to synchronize Wheelock s Series RSS, RSSP and SLM Sync Strobes 3 ampere per circuit current handling at 12 or 24 VDC Low operating current draw Compatible with all standard fire alarm control panels Meets the NFPA-72 requirement for Temporal Pattern when used with the Series AS/AH and/or Series NS/NS4/NH 3 year warranty FIRE ALARM CONTROL PANEL (FACP) POWERPATHCP POWERPATHMP OR OTHER POWER BOOSTERS SM OR DSM AS/AH, NS, HS4/HS NH, RSS, RSSP, E w/stb, ET w/stb, CH w/stb APPLIANCES SM or DSM Connection Diagram with Power Booster U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS E5946 151-92-E 7300-0785:132
Table 1: Sync Module (SM) Current Requirements (AMPS) Table2: Sync Module (DSM) Current Requirements (AMPS) UL Voltage ULC Voltage Rated Average Current Rated Peak Current Rated Inrush Current UL Voltage ULC Voltage Rated Average Current Rated Peak Current Rated Inrush Current In1 Audible In1 Audible In1 Audible In1/In2 Audible In1/In2 Audible In1/In2 Audible 8.0 VDC 10.5 VDC 0.017 0.004 0.055 0.004 0.140 0.016 8.0 VDC 10.5 VDC 0.019 0.004 0.055 0.004 0.150 0.016 12.0 VDC 12.0 VDC 0.017 0.004 0.060 0.004 0.160 0.019 12.0 VDC 12.0 VDC 0.020 0.004 0.064 0.004 0.170 0.019 24.0 VDC 24.0 VDC 0.028 0.008 0.070 0.008 0.320 0.030 24.0 VDC 24.0 VDC 0.035 0.008 0.080 0.008 0.342 0.030 33.0 VDC 33.0 VDC 0.038 0.010 0.080 0.010 0.440 0.040 33.0 VDC 33.0 VDC 0.045 0.010 0.090 0.010 0.470 0.040 8.0 VRMS 8.0 VRMS 0.026 0.006 0.085 0.008 0.210 0.016 8.0 VRMS 8.0 VRMS 0.028 0.005 0.107 0.008 0.210 0.016 12.0 VRMS 12.0 VRMS 0.028 0.006 0.090 0.009 0.225 0.019 12.0 VRMS 12.0 VRMS 0.030 0.006 0.103 0.009 0.240 0.019 24.0 VRMS 24.0 VRMS 0.040 0.010 0.120 0.015 0.446 0.033 24.0 VRMS 24.0 VRMS 0.048 0.010 0.145 0.015 0.480 0.033 33.0 VRMS 31.0 VRMS 0.055 0.012 0.150 0.022 0.645 0.056 33.0 VRMS 31.0 VRMS 0.062 0.012 0.175 0.022 0.685 0.056 NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO A SM OR DSM DOES NOT EXCEED 3.0A OR EXCEED THE RATING OF THE FIRE ALARM CONTROL PANEL S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. When calculating the total current, use Tables 1& 2 to determine the highest value of Rated Average Current for the SM or DSM (across the listed voltage range), then add this value to the total current for any other appliances powered by the same source and include any required safety factors. Refer to Instruction Sheet for addtional information. WARNING: MAKE SURE THAT ALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. Table 3: Current Consumption of the SM and DSM Modules Outpurt Circuit Description of SM/DSM Module SM Module DSM Module Ref. Fig. Class B with Audible Silence (single circuit) Y 1 Class B with No Audible Silence (single circuit) Y 2 Class B with Audible Silence (dual circuit) Y 3 Class B with No Audible Silence (dual circuit) Y 4 Class A with Audible Silence (single circuit) Y 5 Class A with No Audible Silence (single circuit) Y 6 Note: SM Sync Modules are rated for 3.0 amperes at 12/24 VDC; DSM Dual Sync Modules are rated for 3.0 amperes per circuit. The maximum number of interconnected DSM modules is twenty (20). CAUTION: Use SM or DSM Sync Modules only on NAC circuits with continuously applied voltage. Do not use SM or DSM Sync Modules on coded or interrupted NAC circuits in which the applied voltage is cycled on and off. CAUTION: Power Boosters may be used in conjunction with the SM or DSM Sync Modules only in the order shown below. Only one SM or DSM Sync Module shall be allowed on a NAC circuit. Do not connect Power Booster to the NAC circuit after the one SM or DSM Sync Module. Exception: The Wheelock PS-24-8MC Power Booster can be connected either before or after the SM or DSM Sync Module. Refer to Power Booster instruction manual for proper application and installation.
FIG. 1 SINGLE CLASS B CIRCUIT WITH AUDIBLE SILENCE FEATURE FIG. 2 SINGLE CLASS B CIRCUIT WITH NO AUDIBLE SILENCE FEATURE FIG. 3 DUAL CLASS B CIRCUIT WITH AUDIBLE SILENCE FEATURE FIG. 4 DUAL CLASS B CIRCUIT WITH NO AUDIBLE SILENCE FEATURE FIG. 5 SINGLE CLASS A CIRCUIT WITH AUDIBLE SILENCE FEATURE FIG. 6 SINGLE CLASS A CIRCUIT WITHOUT AUDIBLE SILENCE FEATURE Notes 1. Non-Sync Appliances can be installed before or after a SM or DSM. If the Non-Sync appliance requires audible silence, four wire connection is necessary with the strobe circuit connected before the SM or DSM NAC circuit, and the audible leads connected to a silenceable NAC circuit from the FACP. 2. The audible appliance produces a momentary interruption (approximately 25ms) each time the strobes flash. 3. Circuit #2 may be omitted if only 1 circuit is required when using the DSM. 4. Non-Sync Audible Appliances can be installed on the audible NAC. Be aware of the current requirement for the SM or DSM module. See table 3. Specifications and Ordering Information Model Order Input Voltage VDC Average Current @ 12 or 24 VDC UL Max* Mounting Options** SM-12/24-R 6369 12 0.017 0.023 W 24 0.028 0.038 W DSM-12/24-R*** 6374 12 0.020 0.026 W 24 0.035 0.055 W R = Red * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions. ** Refer to Data sheet # S7000 for Mounting Options. *** The maximum number of interconnected DSM modules is twenty (20). *** The total distance from the first to the last DSM shall not exceed 1,000 feet of #18 AWG wire. Use only #18 AWG wire.
WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 8-33 VOLTS USING FILTERED DC OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). WARNING: CONTACT WHEELOCK FOR INSTALLATION INSTRUCTIONS (P83123-SM & P83177-DSM) AND GENERAL INFORMATION SHEET ON THESE PRODUCTS. These documents do undergo periodic changes. It is important that you have current information on these products. These materials contain important information that should be read prior to specifying or installing these products including: TOTAL CURRENT REQUIRED BY ALL APPLIANCES CONNECTED TO SYSTEM SECONDARY POWER SOURCES. FUSE RATINGS ON NAC CIRCUITS TO HANDLE MAXIMUM INRUSH OR PEAK CURRENTS FROM ALLAPPLIANCES ON THOSE NAC CIRCUITS. COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW. THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED IN PUT VOLTAGE RANGE. INSTALLATION IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES. USE STROBES ONLY ON NAC CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE. DO NOT USE STROBE ON CODED OR INTERRUPTED NAC CIRCUITS IN WHICH THE APPLIED VOLTAGE IS CYCLED ON AND OFF AS THE STROBE MAY NOT FLASH. Architects and Engineers Specifications The sync modules shall be Wheelock Series SM or DSM Sync Modules. Series SM or DSM Sync Modules shall be the master controllers for Wheelock Series AS/AH, NS/NS4/NH, RSS, RSSP and appliances where a synchronized audible/visual audible or visual only appliance is specified. All modules shall be UL listed under Standard 464. Series SM and DSM modules shall be designed to interface with Series AS Audible Strobe Appliances and NS Horn Strobe Appliances to produce a synchronized temporal ( 3) horn as well as synchronized strobe flash on a two-wire alarm circuit. Other synchronized products are the Wheelock Series RSS, RSSP, SLM visual only appliances and Series AH and NH Horn Appliances. SM Sync Module shall incorporate two input NAC circuits for power connection from the Fire Alarm Control Panel; one for the strobe NAC circuit and one for the audible NAC circuit. DSM modules shall provide an additional strobe circuit input/output for control of either two Class B NAC circuits or a single Class A NAC circuit. Upon activation of the audible silence function at the Fire Alarm Control Panel, the audible signal component of Series AS Audible Strobe and/or the Series NS Horn Stobe may be silenced while maintaining strobe activation. Series SM or DSM module shall be designed and available in two versions; the SM-12/24 for control of a single Class B NAC circuit and a dual output version, the DSM-12/24 for control of either Class A two (2) Class B NAC circuits. The DSM dual circuit version shall provide the additional capability of daisy-chaining, that is, the ability to interconnect multiple DSM s for synchronous horn and strobe operation on multiple NAC circuits. Interconnection capability shall be for a maximum of 40 NAC circuits. All modules shall operate on either 12 or 24 VDC. Rated average current requirement for the SM 12/24 shall be.017 amperes @ 12 VDC and.028 amperes @ 24 VDC. The DSM 12/24 shall be.020 amperes @ 12 VDC and.035 amperes @ 24 VDC. A single circuit SM Sync Module shall be capable of handing a 3 ampere load at 12 or 24 VDC and the dual circuit DSM Sync Module shall be capable of handling a load of 3 amperes per NAC circuit at 12 or 24 VDC. All versions shall be polarized for DC supervision and shall incorporate screw terminals for in/out field wiring of #18 to #12 AWG wire size. The SM and DSM Sync modules shall mount to a 4-11/16 x 2-1/8 deep backbox. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S3000 SM/DSM 06/06
Series AMT Multitone and AMT Multitone Strobe Appliances AMT-24MCW AMT-241575 AMT-12/24 Description: The Wheelock Series AMT Multiple Input Electronic Appliances provide the industry with a UL Standard 1971 and UL Standard 464 combination audible/visual device that simplifies installation and offers three (3) distinct prioritized audible signals from three isolated inputs. Priority (1) will override all other commands upon activation. The AMT offers a choice of eight (8) self-prioritized sound combinations for suppression releasing systems, combination security and emergency evacuation systems and high risk installations as well as many other applications. The AMT Strobes are designed for ADA applications while meeting or exceeding the latest requirements of NFPA 72 (the National Fire Alarm ), ANSI 117.1 (the American National Standard For Accessible and Usable Buildings and Facilities) and UL Standard 1971 (Standard for Signaling Devices for the Hearing Impaired). Each AMT Audible and AMT Strobe appliance has two user selective sound output levels: STANDARD dba and HIGH dba. The AMT Audible provides 12VDC or 24VDC operation, filtered or FWR. The AMT Strobe Electronic Appliances operate at 24VDC and may be used with filtered or unfiltered (full-wave-rectified) input voltages. Separate supervised sets of input terminals are available for each prioritized input. Jumper plugs are provided to enable both tone and strobe to operate simultaneously for all inputs. The AMT Multitone Strobe Appliances are UL Listed for indoor use, wall mount, under Standard 1971 for Signaling Devices for the Hearing Impaired and Standard 464 for Audible Signal Appliances, and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visible signaling. Features: Approvals include: UL Standard 1971 and UL Standard 464, FCC, ULC, Factory Mutual (FM), California State Fire Marshal (CSFM), New York City (MEA) and Chicago (BFP) See approvals by model in Specifications and Ordering Information Compliance with RFI limits in FCC Part 15, Class B for compatibility with sensitive detection and communication circuits Designed to meet or exceed NFPA/ANSI Standards and ADA Accessibility Guidelines. Meets OSHA 29 Parts 1910.165 Three separate prioritized inputs that will activate three isolated signals All inputs are supervised -3 Horn and Tone meet ANSI/NFPA/ISO temporal pattern Two power taps for high dba and standard dba @ 10 feet Low current draw with low temperature compensation to reduce power consumption and wiring costs AMT Strobe models are available with Wheelock patented MCW Multi-Candela strobes with field selectable candela settings at 15/30/75/110cd or with single candela 1575cd strobes AMT with strobe can be wired to flash independently or in unison with all audible signals The strobes can be synchronized using Wheelock sync modules or power supplies with built in Sync Protocol Selectable input voltage (12 or 24 VDC) for non-strobe applications Polarized inputs for compatibility with standard reverse polarity type supervision of circuit wiring by an alarm panel Low cost installation via standard electrical boxes. Attractive flush or surface mounting options No additional trimplate required for flush mounting. Fast installation with In/Out screw terminals using #12 to #18 AWG U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS S5391 151-92-E 7125-0785:160 7135-0785:127 (horn)
General: Wheelock s AMT Appliances are unique multitone alarm signals with separate input terminals for each sound. They are the ideal choice for suppression systems and emergency signaling systems where distinctive multiple alarm conditions are required. Eight groups of three self-prioritized sound outputs are provided with separate electrically isolated input terminals for each sound (see Table 1 and Table 5 for sound selections). Sound output can be field set to provide either HIGH (HI) dba or STANDARD (STD) dba sound output level. All AMT Multitone Strobe models are designed for use with either filtered or unfiltered Full-Wave-Rectified (FWR) input voltage. The AMT Multitone Strobe Appliances have separate input terminals for alarm tone activation and strobe activation. The strobes can be easily field programmed to operate independently or in unison with all of the audible alarms. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a fire Alarm Control Panel (F.A.C.P.). In the event that three simultaneous commands occur, priority one will activate. If priority 2 + priority 3 exist, priority 2 will activate. Table 1: dba Ratings for AMT Multitone Audible Signals Tone Tone Description dba @ 10ft (reverberant) dba @ 10ft. (anchoic) HI Output STD Output HI Output STD Output Horn Broadband Horn (continuous) 92 86 98 92 Bell 1500 Hz Modulated (0.07 Sec. On/Repeat) 84 78 91 86 March Time Horn Horn (0.25 Sec. ON/0.25 Sec. Off/Repeat) 88 82 98 92-3 Horn Horn (ANSI S3.41 Temporal Pattern) 88 81 98 92-3 Tone 500 Hz (ANSI S3.41 Temporal Pattern) 84 78 94 89 Slow Whoop 500-1200Hz Sweep (4.0 Sec. On/0.5 Sec OFF/Repeat) 88 83 98 93 Siren 600-1200 Hz Sweep (1.0 Sec. On/Repeat) 89 83 97 92 HI/LO 1000/800 Hx (0.25 Sec. On/Alternate) 86 81 92 87 Vibrating Chime 700 Hz (1.0 Sec. Decay, Repeat) 78 71 88 82 Table 2: RMS Current Ratings for AMT Multitone Audible Portion* RMS Current (amps) 24 vdc 12 vdc HI Output STD Output HI Output STD Output Tone @ 12 @ 24 VDC UL max* @ 24 VDC UL max* UL max* @ 12 VDC UL max* VDC Horn 0.085 0.108 0.034 0.043 0.100 0.210 0.020 0.058 Bell 0.042 0.057 0.020 0.026 0.031 0.117 0.010 0.031 March Time Horn 0.085 0.108 0.026 0.035 0.100 0.210 0.020 0.059-3 Horn 0.085 0.108 0.034 0.043 0.100 0.210 0.020 0.057-3 Tone 0.048 0.060 0.022 0.030 0.060 0.168 0.015 0.052 Slow Whoop 0.087 0.112 0.034 0.044 0.100 0.182 0.025 0.056 Siren 0.081 0.102 0.028 0.038 0.082 0.177 0.020 0.055 HI/LO 0.047 0.064 0.023 0.030 0.044 0.131 0.013 0.028 Vibrating Chime 0.032 0.041 0.015 0.020 0.027 0.090 0.010 0.028 Add strobe current from Table 3 (ordering information) to audible current from Table 2 to obtain total current for each unit, if the strobe and audible are wired to operate in unison on a single circuit. Refer to Installation Instruction Sheet (P84158) for peak and inrush current across the UL listed voltage range for both filtered and unfiltered full-wave-rectified voltage. The Series AMT Multitone Strobe Appliances are UL Listed under Standard 1971 for Emergency Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. They are listed for indoor only use with the backboxes specified in these instructions. AMT models without strobes are UL 464 Listed for indoor or outdoor use (see mounting options). Table 3: Strobe RMS Current Ratings RMS Current (amps) Model AMT-121575 AMT-24MCW Candela 1575cd 15cd 30cd 75cd 110cd @24VDC 0.064 0.041 0.063 0.109 0.140 UL max* 0.101 0.060 0.092 0.165 0.220 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Table 4: Specification and Ordering Information Model Number Order Input Voltage Candela Mounting Options** Agency Approvals UL MEA CSFM FM BFP AMT-12/24-R 5887 12/24 - D,E,F,L,M,N,O,P,R X X X X X AMT-12/24-W 5893 12/24 - D,E,F,L,M,N,O,P,R X X X X X AMT-241575W-FR 9463 24 15 (75 on axis) D,E,F,L,M,N,O,P,R X X X X * AMT-241575W-NW 3047 24 15 (75 on axis) D,E,F,L,M,N,O,P,R X X X X * AMT-241575W-FW 9466 24 15 (75 on axis) D,E,F,L,M,N,O,P,R X X X X * AMT-24MCW-FR 3300 24 15/30/75/110 D,E,F,L,M,N,O,P,R X * X * * AMT-24MCW-FW 3302 24 15/30/75/110 D,E,F,L,M,N,O,P,R X * X * * AMT-12/24-R-NYC 7920 12/24 - D,E,F,L,M,N,O,P,R X X AMT-241575W-FR-NYC 9465 24 15 (75 on axis) D,E,F,L,M,N,O,P,R X X * Pending ** Mounting Options: Refer to Data Sheet S7000 or current catalog for mounting options The UL Listed voltage range is 16-33 VDC for 24 VDC and 8-17.5 VDC for 12 VDC using either filtered (DC) or unfiltered full-waverectified (FWR) voltage. Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage to the notification appliance. AMT Multitone strobe models are Listed for indoor use with a temperature rate of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. REFER TO CURRENT INSTALLATION INSTRUCTION SHEET P84158. WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS DOES NOT EXCEED THEIR RATED CURRENT. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY. WARNING: MAKE SURE THAT ALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CURRENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE. WARNING: THE STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS (NON-CODED) APPLIED VOLTAGE. THE STROBES MAY NOT FLASH IF USED IN CODED SYSTEMS. AMT Multitone Strobe Appliances are field set for any one of eight groups of self-prioritized tones by setting a four position switch (SW1) as shown in Table 5. Use SW1 POS 2,3,4 to select the desired alarm tones.note: The prioritized tones contained in each group is factory pre-set which can not be changed. Table 5 Tones Switch Settings PRI 1 PRI 2 PRI 3 POS 2 POS 3 POS 4 Horn Bell Siren 1 1 1 3 Horn Siren Vibrating Chime 1 0 1 Slow Whoop March Time Horn HI/LO 0 0 1 March Time Horn HI/LO Vibrating Chime 1 1 0 3 Horn Bell Siren 0 1 1 Siren Horn Vibrating Chime 0 1 0 Bell March Time Horn Siren 1 0 0 3 Tone HI/LO Siren 0 0 0 Note: The -3 Horn and -3 Tone (set on HIGH dba) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation signaling. They should be used only for fire evacuation signaling and not for any other purpose. The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently. All other tones are recommended for use only on continuous (non-coded) systems.
Architects and Engineers Specifications When notification appliances are required for applications with more than one function, an appliance with multiple inputs and capable of being programmed shall be used. The notification appliance shall be capable of accepting three (3) individual DC signals and providing three (3) distinct audible signals. In the event the signals are simultaneous, the priority shall be as follows. Highest priority = PR1, Second priority = PR2 and the Third priority = PR3. With the addition of the Strobe, the appliance shall operate with an independent input DC voltage to the strobe terminals. When it is desired to operate the strobe with all of the audible signals, only a set of jumpers shall be required. The notification appliance shall be a Wheelock Series AMT audible/visual appliance or equivalent. Notification appliance shall be electronic and use solid state components. Electromechanical alternatives are not approved. Tone selection shall be by durable dip switch assembly and not clips or jumpers. The audible and the strobe shall be able to operate from a single NAC circuit while producing any of these tones. The appliances shall provide two output sound levels: STANDARD and HIGH dba. The HIGH anechoic dba measurement at 10 feet at the alarm HORN SETTING shall be 98 dba for AMT and 98 dba for AMT Strobes, at nominal voltage. Operating voltages shall be either 12VDC (Audible only) or 24VDC using filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination audible/visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobe shall meet UL 1971 and produce a flash rate of one (1) flash per second minimum over the Listed input voltage (16VDC-33VDC) range. The Series AMT-241575W shall be specified when 15 candela UL 1971 Listing with 75 candela intensity nearaxis is required. The AMT-24MCW shall be specified when field selectable 15/30/75/110 candela ratings are required. All UL Standard 1971 Listed strobe appliances shall be verified to meet FCC Part 15, Class B. Strobe activation shall be via independent input or from the same input circuit as the audible. The combination audible/visual appliances may be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The aesthetic appearance shall not have any mounting holes or screw heads visible when the installation is completed. The appliance shall be finished in a textured red color. The audible appliance may be installed indoor or outdoor with the proper backbox. Wiring Diagrams (for all models) Isolated inputs are provided for independent supervision and actuation of the three audible inputs. In case of simultaneous inputs, the three audible outputs are self-prioritized as follows: 1st priority = PRI 1; 2nd priority = PRI 2, 3rd priority = PRI 3. (See table 4 for tone selection). Leave any unused inputs disconnected. For applications not requiring supervision: connect all positive (+) terminals to the power source. The negative (-) terminal for each signal will actuate the device. Unsupervised System Common Negative PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) VVVVVVVV Supervised System PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - Unsupervised System Common Positive PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) COMMON NEGATIVE V V V V V COMMON NEGATIVE TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) V FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) COMMON POSITIVE V V V V COMMON POSITIVE TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) 1. AMT Multitone appliances have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and connect to screw terminals. 2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown on left. The polarity shown in the wiring diagrams is for operation of the appliance. The polarity is reversed by the F.A.C.P. during supervision. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S4000 AMT 06/06
Series AMT and AMT Strobe Multitone Electronic Appliances for New York City SERIES AMT STROBE SERIES AMT-12/24 Description: The Wheelock Series AMT Multiple Input Electronic Appliances provide the industry with a UL Standard 1971 and UL Standard 464 combination audible/visual device that simplifies installation and offers three (3) distinct prioritized audible signals from three isolated inputs. Priority (1) will override all other commands upon activation. The AMT offers three preset prioritized sound combinations. The three preset priorities are Bell (Priority 1); 3 Horn (Priority 2); and Vibrating Chime (Priority 3). The AMT Strobes are designed for ADA applications with maximum performance, reliability and cost-effectiveness while meeting or exceeding the latest requirements of NFPA 72 (the National Fire Alarm ), ANSI 117.1 (the American National Standard For Accessible and Usable Buildings and Facilities) and UL Standard 1971 (Standard for Signaling Devices for the Hearing Impaired). AMT Strobes, when properly specified and installed in accordance with NFPA/ANSI Standards, can provide the Equivalent Facilitation allowed under ADA Accessibility Guidelines (ADAAG General Section 2.2) by meeting or exceeding the illumination which results from the ADA specified strobe intensity of 75 candela at 50 feet. This is an illumination of 0.030 lumens per square foot (footcandles). Each AMT Audible and AMT Strobe appliance has two user selective sound output levels: STANDARD dba and HIGH dba. The AMT Audible provides 12VDC or 24VDC operation, filtered or FWR. The AMT Strobe Electronic Appliances operate at 24VDC and may be used with filtered or unfiltered (full-wave-rectified) input voltages. Separate supervised sets of input terminals are available for each prioritized input. Jumper plugs are provided to enable both tone and strobe to operate simultaneously for all inputs. The AMT Multitone Strobe Appliances are UL Listed for indoor wall mount use under Standard 1971 for Signaling Devices for the Hearing Impaired and Standard 464 for Audible Signal Appliances, and use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum reliability for effective visible signaling. The Series AMT 15/75 candela wallmoutned strobes were tested at UL for 75cd on axis. They are Listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis for ADA guidelines with low current draw. Features: Approvals include: UL Standard 1971, UL Standard 464 and New York City (MEA) ULC Compliance with RFI limits in FCC Part 15, Class B for compatibility with sensitive detection and communication circuits Designed to meet or exceed NFPA/ANSI Standards and ADA Accessibility Guidelines. Meets OSHA 29 Parts 1910.165 Three separate prioritized inputs that will activate three isolated signals All inputs are supervised -3 Horn and Tone meet ANSI/NFPA/ISO temporal pattern. Two power taps for high dba and standard dba @ 10 feet Low current draw with low temperature compensation to reduce power consumption and wiring costs AMT Strobe models available with 15/75 and 75 candela ratings for independent or combination input activations AMT with strobe can flash independently or in unison with all audible signals 12VDC and 24VDC models with wide listed voltage range, filtered (DC) and FWR. (AMT Strobe version in 24 volts only.) Polarized inputs for compatibility with standard reverse polarity type supervision of circuit wiring by an alarm panel Low cost installation via standard electrical boxes. Attractive flush or surface mounting options No additional trimplate required for flush mounting. Fast installation with In/Out screw terminals using #12 to #18 AWG U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS E5946 151-92-E 7135-0785:127 (Horn) 7125-0785:160 (Horn Strobe)
General: The Series AMT Multitone Strobe Appliances are UL Listed under Standard 1971 for Emergency Devices for the Hearing Impaired and UL Standard 464 for Audible Signal Appliances. They are listed for indoor only use with the backboxes specified in these instructions (See Mounting Options). The AMT Multitone Strobe signals use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling. NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. REFER TO CURRENT INSTALLATION INSTRUCTION SHEET P82478. Table 1: Current Ratings for New York City AMT Multitone Audible Signals Tone Tone Description Rated Average Current (AMPS) 24 VDC Rated Average Current (AMPS) 12 VDC HI dba STD dba HI dba STD dba Bell 1560 Hz Modulated (0.07 Sec. On/Repeat).018.014.029.009-3 Horn Horn (ANSI S3.41 Temporal Pattern).046.025.095.019 Vibrating Chime 700 Hz (1.0 Sec. Decay, Repeat).013.010.026.009 Table 2: UL dba Ratings Tone Bell 3 Horn Vibrating Chimes HI/LO Volume dba Reverberant Ratings Per UL 464 24V dba Anechoic Ratings 24V HI 84 91 STD 78 86 HI 88 98 STD 81 92 HI 78 88 STD 71 82 Add 25% more input current than shown in Table 1 when operating the unit at maximum input voltage. Add average strobe current from Table 3 (ordering information) to average audible current from Table 1 to obtain total average current for each unit, if the strobe and audible are wired to operate in unison on a single circuit. Refer to Installation Instruction Sheet P83611(AMT- 12/24) or P84157A (AMT-241575W-FR) for rated average peak and inrush current across the UL listed voltage range for both filtered and unfiltered full-wave-rectified voltage. Wheelock s AMT Appliances are unique multitone alarm signals with separate input terminals for each sound. They are the ideal choice for suppression systems and emergency signaling systems where distinctive multiple alarm conditions are required. Eight groups of three self-prioritized sound outputs are provided with separate electrically isolated input terminals for each sound (see Table 2 and Table 4 for sound selections). Sound output can be field set to provide either HIGH (HI) dba or STANDARD (STD) dba sound output level. All AMT Multitone Strobe models are designed for use with either filtered or unfiltered Full-Wave-Rectified (FWR) input voltage. The AMT Multitone Strobe Appliances have separate input terminals for alarm tone activation and strobe activation. The strobes can be easily field programmed to operate independently or in unison with all of the audible alarms. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a fire Alarm Control Panel (F.A.C.P.). In the event that three simultaneous commands occur, priority one will activate. If priority 2 + priority 3 exist, priority 2 will activate. Anechoic dba is measured on axis in a non-reflective (free field) test room using fast meter response. For peak dba (measured with peak meter response), add 5 dba to typical anechoic values shown in Table 2. Reverberant dba is a minimum UL rating based on sound power measurements in a reverberant test room.
Table 3: Ordering and Specification Information Model Number Order Input Voltage Rated Candela Average* Strobe Current 24 VDC(AMPS) Mounting Options** AMT-12/24-R-NYC 7920 12/24 - - D,E,F,L,M,N,O,P,R AMT-241575W-FR-NYC 9465 24 15/75 0.072 D,E,F,L,M,N,O,P,R * Average current per Wheelock Production Testing at 12/24 VDC nominal voltage. For rated average, peak and in-rush current across the UL listed voltage range for both filtered DC and full wave rectified FWR refer to Installation Instruction Sheet P82478. ** Mounting Options: Refer to Data Sheet S7000 or current catalog for mounting options The UL Listed Rated Voltage range is 20-31 VDC for 24 VDC models and 10.5-15.6 VDC for 12 VDC audible only model using either filtered (DC) or unfiltered full-wave-rectified (FWR) voltage. Check the minimum and maximum output of the power supply and standby battery and subtract the voltage drop from the circuit wiring resistance to determine the applied voltage to the notification appliance. WARNING: ALTHOUGH UL TESTING HAS VERIFIED THAT THESE PRODUCTS FUNCTION EVEN AT 80% OF THEIR MINIMUM RATING AND 110% OF THEIR MAXIMUM RATING, WHEELOCK STRONGLY RECOMMENDS THAT THE VOLTAGE APPLIED TO THESE PRODUCTS BE WITHIN THEIR RATED VOLTAGE RANGE. THE APPLICATION OF IMPROPER VOLTAGE MAY RESULT IN DEGRADED OPERATION OR DAMAGE TO THESE PRODUCTS. WARNING: MAKE SURE THAT THE TOTAL CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM S PRIMARY AND SECONDARY POWER SOURCES AND NAC CIRCUITS DOES NOT EXCEED THEIR RATED CURRENT. OVERLOADING THESE SOURCES COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY. WARNING: MAKE SURE THAT ALL FUSES USED ON NAC CIRCUITS ARE RATED TO HANDLE THE MAXIMUM INRUSH OR PEAK CUR- RENT FROM ALL APPLIANCES ON THOSE CIRCUITS. FAILURE TO DO THIS MAY RESULT IN LOSS OF POWER TO THE NAC CIRCUIT AND THE FAILURE OF ALL APPLIANCES ON THAT CIRCUIT TO OPERATE. WARNING: THE STROBES ARE DESIGNED TO FLASH AS SPECIFIED WITH CONTINUOUS (NON-CODED) APPLIED VOLTAGE. THE STROBES MAY NOT FLASH IF USED IN CODED SYSTEMS. AMT Multitone strobe models are UL Listed for indoor use with a temperature rate of 32 F to 120 F (0 C to 49 C) and maximum humidity of 85%. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: 1) Reorient or relocate the receiving antenna, 2) Increase the separation between the equipment and receiver, 3) Connect the equipment into an outlet on a circuit different from that to which the receiver is connected, and 4) Consult the dealer or an experienced radio/tv technician for help. AMT Multitone Strobe Appliances are field set for any one of eight groups of self-prioritized tones by setting a four position switch (SW1) as shown in Table 4. Use SW1 POS 2,3,4 to select the desired alarm tones. Note: The prioritized tones contained in each group is factory pre-set which can not be changed. Table 4: Sequence of Tones for Various Systems using the AMT-NYC Priority and Tone Pre-Action Sprinkler Halon, FM-200 Inergen, etc. Lieu of 3 Separate and Distinct Signals at IPA Priority 1 (Bell Tone) Waterflow, Smoke Detector and Manual Pull Station Agent Discharge Waterflow Priority 2 3 Horn Valve Tamper Device and Low-Air Supervisory Cross-Zoned Smoke Detector Smoke Detector and Manual Pull Station Priority 3 Vibrating Chime Trouble Condition First Smoke Detector Valve Tamper Device or any Trouble Condition Strobe Activation Priority 1 & 2 Priority 1, 2 & 3 Priority 1 & 2 Note: The -3 Horn and -3 Tone (set on HIGH dba) incorporate the temporal pattern specified by ANSI/NFPA for standard emergency evacuation signaling. They should be used only for fire evacuation signaling and not for any other purpose. The Horn and Bell Tones can be used on coded systems with a minimum On-Time of 1/4 second if the audible and strobe are wired to operate independently. All other tones are recommended for use only on continuous (non-coded) systems.
Architects and Engineers Specifications When notification appliances are required for applications with more than one function, an appliance with multiple inputs and capable of being programmed shall be used. The notification appliance shall be capable of accepting three (3) individual DC signals and providing three (3) distinct audible signals. In the event the signals are simultaneous, the priority shall be as follows. Highest priority = PR1, Second priority = PR2 and the Third priority = PR3. With the addition of the Strobe, the appliance shall operate with an independent input DC voltage to the stro The notification appliance shall be a Wheelock Series AMT audible/visual appliance or equivalent. Notification appliance shall be electronic and use solid state components. Electromechanical alternatives are not approved. Tone selection shall be by durable dip switch assembly and not clips or jumpers. The audible and the strobe shall be able to operate from a single NAC circuit while producing any of these tones. The appliances shall provide two output sound levels: STANDARD and HIGH dba. The HIGH anechoic dba measurement at 10 feet at the alarm HORN SETTING shall be 98 dba for AMT and 98 dba for AMT Strobes, at nominal voltage. Operating voltages shall be either 12VDC (Audible only) or 24VDC using filtered power or unfiltered power supply (full-wave-rectified). All models shall have provisions for standard reverse polarity type supervision and IN/OUT field wiring using terminals that accept #12 to #18 AWG wiring. Combination audible/visual appliances shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens or equivalent with solid state circuitry. Strobe shall meet UL 1971 and produce a flash rate of one (1) flash per second minimum over the Listed input voltage (20VDC- 31VDC) range. The strobe intensity shall be rated per UL Standard 1971 for 15 or 75 Candela. The Series AMT-241575W-FR candela strobe shall be specified when 15 candela UL 1971 Listing with 75 candela intensity near-axis is required. All UL Standard 1971 Listed strobe appliances shall be verified to meet FCC Part 15, Class B and incorporate low temperature compensation to insure the lowest possible current consumption. Strobe activation shall be via independent input or from the same input circuit as the audible. The combination audible/visual appliances may be installed indoors and surface or flush mounted. They shall mount to standard electrical hardware requiring no additional trimplate or adapter. The aesthetic appearance shall not have any mounting holes or screw heads visible when the installation is completed. The appliance shall be finished in a textured red color. The audible appliance may be installed indoor or outdoor with the proper backbox. Supervised System Wiring Diagrams (for all models) Isolated inputs are provided for independent supervision and actuation of the three audible inputs. In case of simultaneous inputs, the three audible outputs are self-prioritized as follows: 1st priority = PRI 1; 2nd priority = PRI 2, 3rd priority = PRI 3. (See table 4 for tone selection). Leave any unused inputs disconnected. For applications not requiring supervision: connect all positive (+) terminals to the power source. The negative (-) terminal for each signal will actuate the device. FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) VVVVVVVV PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) Unsupervised System Common Negative Unsupervised System Common Positive PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - PRI 1 PRI 2 PRI 3 STROBE + - + - + - + - FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) V V V V V COMMON NEGATIVE COMMON NEGATIVE TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) 1. AMT Multitone appliances have in-out wiring terminals that accept two #12 to #18 American Wire Gauge (AWG) wires at each screw terminal. Strip leads 3/8 inches and connect to screw terminals. WARNING: NFPA CODES REQUIRE SIGNALING APPLIANCES TO BE SUPERVISED. CHECK TO BE CERTAIN THAT UNSUPERVISED SIGNALING APPLIANCES DO NOT VIOLATE ANY APPLICABLE CODES. FROM PRECEDING SIGNAL OR FIRE ALARM CONTROL PANEL (F.A.C.P.) V V V V V COMMON POSITIVE COMMON POSITIVE TO NEXT SIGNAL OR END-OF-LINE RESISTOR (E.O.L.R.) 2. Break all in-out wire runs on supervised circuits to assure integrity of circuit supervision as shown on left. The polarity shown in the wiring diagrams is for operation of the appliance. The polarity is reversed by the F.A.C.P. during supervision. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S4100 AMT-NYC 06/06
Series MPS-400X Explosion Proof Manual Pull Station MPS-400X Description: The MPS-400X Series is a high quality, die-cast metal manual alarm station, UL Listed for use in hardarous locations (explosoin-proof). The MPS-400X contains enhanced component features that allows the station to operate reliably within the uniquely difficult environs found in transportation tunnels. The MPS-400X is approved for use in Class I, Division I, Groups B, C and D; Class II, Division I, Groups E, F and G and Class III. The station enclosure is approved for indoor and outdoor use, NEMA 4X applications and is Marine rated. The MPS-400X is designed specifically for compliance with all applicable ADA requirements (Americans with Disabilities Act; 28 CFR Part 36). The station can be operated with a single hand without tight grasping, pinching or twisting of the wrist. The force required to operate the station has been tested by Underwriter s Labs for compliance with the 5 lbf pull force. When properly installed, the MPS-400X will protrude less than 4 inches into halls, corridors, etc. no matter the height at which it is installed. The MPS-400X is a single action explosion proof model. Station alarm contacts are DPDT, rated 10 amps @125 VAC and 1 amp @ 30 VDC. The alarm contacts are gold plated for corrosion resistance. The MPS-400X is configured with terminal connections and a key reset. For unique hazard protection, the MPS-400X is available in custom color options; blue, yellow or green. Custom colors provide distinct station identification for use in equipment shutdown, medical aid, fire suppression actuation and similar applications. The MPS-400X may be configured with stainless steel components that provide enhanced protection when used in extreme corrosive environments. Features: Special Hazard Protection Marine and NEMA 4X ratings DPDT Alarm Contacts Terminal Connections Key Lock Reset Custom Color Option ADA Compliant UL Listed Operation: The Series MPS is operated by pulling the handle on the station as far down as it will go, at which point the handle locks into place and is easily visible from up to 50 feet. The handle is reset by operating the station with a key, placing the handle in the normal upright position and re locking the station. Specification and Ordering Information: Model Number Order Description MPS-400X 8403 Explosion Proof, Single Action, Key Reset 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com U L WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S5008A Exp 5/06
Series MPS Manual Pull Stations MPS-100 MPS-200 MPS-400X Description: Wheelock Series MPS non-coded Manual Pull Stations are constructed of high quality, die-cast metal for long lasting performance and may be mounted on a single gang backbox. Available in either single or dual action configurations for indoor or outdoor use with SPST contacts and terminal strip connections. The normally open contact will close when the pull station is activated and is rated for 30 VDC @ 1 amp and/or 120 VAC @ 1 amp. The contacts are gold plated to avoid the risk of corrosion. The single action explosion-proof model Series MPS-400X is UL Listed and Factory Mutual approved for use in Class I, Division I, Groups B, C and D; Class II, Groups E, F and G; and Class III hazardous environments. It also has a marine rating and is approved for NEMA-4X applications. MPS Pull Stations are NEMA-3R listed when mounted to the MPS-WP weatherproof back box. All models are painted red with raised white lettering and a locking mechanism to prevent unauthorized reset. Features: Approvals Include: UL Standard, Factory Mutual (FM), California State Fire Marshal (CSFM) and New York City (MEA) Single or Dual Action Key Reset Terminal Strip Connections Corrosion resistant, gold plated SPST contacts Mounts on single gang backbox Surface and Weatherproof backboxes available Plastic breakrod High-gloss red enamel finish with raised white lettering Operation: The Series MPS is operated by pulling the handle on the front of the station as far down as it will go, at which point the handle locks into place and is easily visible from up to 50 feet. The handle is reset by opening the station with a key, placing the handle in the normal upright position and relocking the station. On dual action models (not shown), the push bar rotates inward allowing the Pull handle to be grasped in a one handed motion. Specification and Ordering Information: Model Number Order Description Mounting Options MPS-100 8400 SPST, Single Action, Terminals, Key Reset MPS-ISB, MPS-WP MPS-200* 8401 SPST, Double Action, Terminals, Key Reset MPS-ISB, MPS-WP MPS-300* 8402 DPST, Single Action, Terminals, Key Reset MPS-ISB, MPS-WP MPS-400X 8403 Explosion Proof, Single Action, Key Reset (Backbox provided) MPS-ISB 8404 Interior Surface Backbox, Red MPS-WP 8405 Weatherproof Backbox with Gasket Assembly MPS-RODS 8406 Scored Acrylic Breakrods (dozen) * Consult Customer Service for Availability Copyright 2004 Wheelock, Inc. All rights reserved. U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS 151.92-E 7150-0785:153
Architects and Engineers Specifications The non-coded Manual Pull Stations shall be Wheelock Series MPS Single Action, Double Action or approved equals. They shall be constructed of a rugged die-cast metal housing with key reset and corrosion resistant, gold plated single or double pole, single or double throw contacts. The wiring connections shall be made via a terminal strip and the unit shall mount to a single gang backbox and when Weatherproof Manual Pull Stations are required, the backbox shall be the Wheelock Series MPS-WP Backbox with Gasket Assembly. MPS Pull Stations shall be NEMA-3R listed when mounted to the MPS-WP weatherproof back box. The Series MPS-400X shall be installed in installations that require Explosion Proof, Marine or NEMA 4X rated initiating devices. Temperature rating -40 F to 150 F. MPS-ISB dimensions shall be 4-3/4 H x 3-1/4 W x 2-1/4 D. NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS (P84044 and P84045) CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION,INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. Wiring Diagrams MPS-100/200 PULL MPS-400X FROM PRECEDING PULL STATION OR FACP FROM PRE- CEDING PULL STATION OR FACP MPS-300 TO NEXT PULL STATION OR EOLR PULL TO NEXT PULL STATION OR EOLR FROM PRECEDING PULL STATION OR FACP AUXILIARY ALARM CIRCUIT TO NEXT PULL STATION OR EOLR TO NEXT PULL STATION OR EOLR Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, mainta a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standard the local authority having jurisdiction (AHJ). NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S5008 MPS 06/06
MOUNTING ACCESSORIES (A) UNIVERSAL MOUNTING PLATE (F) DOUBLE-GANG, FLUSH (BO) AS Mounting (B) SINGLE-GANG, FLUSH (BO) See Notes 4 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series AMT, AH, AS, HS4, HS, MT, NH, NS, RSS (G) DOUBLE-GANG, SURFACE (BO) D W L. W. See Notes 1 & 8 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series AH, AS, MIZ, NH, NS, RSS (D) 4 SQUARE, FLUSH (BO) 4-¾ 4-¾ D. GANG # 1-¾ 2 L See Note 5 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series AH, AS, NH, NS, RSS (H) NATP (Order s: Red 8440, White 8441) 5.25 1-1½ Deep See Note 2 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series 31T, 43T, AMT, AH, AS, HS4, HS, MB, MT, MT4, NH, NS, RSS (E) 4 SQUARE, DEEP, FLUSH (BO) Thickness: 13/64 Used with Series AH, AS, NH, NS, RSS (I) WPBB (Order : 9014) For surface mounting AS outdoor products. 5.25 1-11/16 5 21/32 3-3/8 2-1/8 Deep See Note 3 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 Used with Series 31T, 43T, AMT, AH, AS, ET-1010, HS4, HS, MB, MT, MT4, NH, NS, RSS, RSSP 2 19/32 5 3/16 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 Used with Series ASWP Weatherproof
(J) BB BACKBOX (Order s: Red 2830, Gray 2349) Standard steel backbox with knockouts for interior surface mounting, concealed conduit mounting or semi-flush applications. It is painted to match the signal. 5 3-3/8 (N) DBB BACKBOX (Order : 2955) Standard steel backbox provided with knockouts for interior surface mounting, concealed conduit mounting or semi-flush applications. It is painted to match the signal. 4 3-3/8 2-3/16 #8-32 TAP (2) HOLES 3-3/8 4 #8-32 TAP (2) HOLES 3-3/8 4 See Note 9 (K) WBB WEATHER RESISTANT BACKBOX (Order s: Red 2959, White 2411) Sturdy die cast housing, threaded conduit hole and knockout for outdoor applications. It is painted to match the signal. TAPPED FOR ½ CONDUIT ¼ DIA. (2) HOLES PROVIDED WITH KNOCKOUTS FOR ½ & ¾ CONDUIT MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series 31T, 43T, AH, AS, MB, MT4, NH, NS, RSS 5 4-1/8 3-3/8 3/8 4-1/8 2 0-1/4 8 PROVIDED WITH KNOCK- OUTS FOR ½ & ¾ CONDUIT (O) RP-R RETROFIT PLATE (Order : 5042) 3-3/8 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 Used with Series 31T, 43T, AMT, AH, AS, ET-1010, HS4, HS, MB, MT, MT4, NH, NS, RSS 5-7/8 3-3/8 3-13/16 13/32 2-1/16 ½ KNOCKOUT MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 4 4 4 4 Used with Series 31T, 43T, AHWP, ET-1010, MB, MT4 (L) ISP2 SURFACE ADAPTER (Order : Red 3194, White 3195) 5-1/4 SQ. 3-13/16 Used with Series 31T, 43T, AMT, AH, AS, CH70, E70, ET70, ET-1010, ET-1080, HS4, HS, MB, MT, MT4, NH, NS, RSS (P) SBB BACKBOX (Order s: Red 3204, White 3193) For surface mounting speakers, chimes, andelectronic applications. 5-9/16 3-9/16 See Note 11 3 45/64 4 5/32 5-1/2 3-3/8 29/32 1 3/16 4 5/32 Used with Series AMT, CH70, E70, ET70, HS4, HS, MT (M) IOB BACKBOX (Order s: Red 5046, White 5047) For surface mounting MT products. KNOCKOUTS FOR ½ CONDUIT (TOP, BOTTOM) 3-3/8 ¾ KNOCKOUTS (EACH SIDE) MAXIMUM NUMBER OF CONDUCTORS ½ KNOCKOUTS (EACH SIDE) AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 Used with Series 43T, AMT, CH70, E70, ET70, ET-1080, HS4, HS, MB, MT, NH, NS, RSS (Q) 4 SQUARE DEEP W/ EXTENSION RING, FLUSH (BO) 2-5/8 5-21/32 5-1/4 SQ. 3-3/8 SQ. TOP See Note 6 2-1/8 DEEP See Note 10 2-5/8 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 Used with Series AMT, ET70WP, HS4, HS, MT, MTWP EXT. RING DEPTH 1-1/2 2-1/8 AWG. #18 8 8 AWG. #16 8 8 AWG. #14 8 8 AWG. #12 4 8 1-1/2 DEEP Used with Series CH70, CH90, E70, ET70, E90, ET90, ET-1080
(R) SFP SEMI-FLUSH PLATE (Order s: Red 2957, White 2958) Stamped aluminum surface wall plate which mounts behind the basic unit and serves to cover recessed backboxes in semi-flush mounting applications. It is painted to match the signal. 6 3-3/8 5/16 (V) SSB-4 CEILING SUPPORT BRIDGE (Order : 3380) Provisions for (4) J-nuts #8-32 ib 3-3 / 8 square Material: Steel 6-1/2 #8-32 TAP (2) HOLES 3-3/8 6 23-3/4 Used with Series 31T, 43T, AMT, AH, AS, CH70, E70, ET70, ET-1010, ET-1080, HS4, HS, MB, MT, MT4, NH, NS, RSS (S) AP ADAPTER PLATE (Order : 2961) Stamped aluminum adapter plate designed for applications where semi-flush installations cannot be used. The plate can be mounted to standard octagon or round backboxes single or double gang boxes or plaster rings. The backbox and basic unit are then fastened to the plate. This type mounting is referred to as a concealed conduit installation. It is painted to match the signal. 5/16 6 3-3/8 TOP Used with Series CH70, CH90, E70, ET70, E90, ET90, ET-1080 (W) 4 11 / 16 SQUARE, DEEP SURFACE (B0) #8-32 TAP (4) HOLES 3-3/8 6 See Note 7 MAXIMUM NUMBER OF CONDUCTORS Used with Series 43T, MB AWG. #18 AWG. #16 AWG. #14 AWG. #12 10 10 10 10 Used with Series SM, DSM (T) WPSBB-R (Order s: Red 9751, White 3033) (X) SHBB SQUARE, SURFACE BACKBOX (Order s: Red 7254, White 7255) 1-11/16 1-9/16 11/16 5 21/32 3-3/8 1/2 5 3-3/8 Used with Series RSSWP Weatherproof 2 19/32 5 3/16 MAXIMUM NUMBER OF CONDUCTORS AWG. #18 AWG. #16 AWG. #14 AWG. #12 8 8 8 8 (U) 5 SQUARE BACKBOX W/ EXTENSION RING, FLUSH (BO) 5 3-3/8 5 Used with Series 43T, AH, AS, MB, NH, NS, RSS (Y) SER-R SQUARE SEMI-FLUSH EXTENSION RING (Order s: Red 3045, White 3049) 5 5 2-7/8 5 Used with Series CH70, CH90, E70, ET70, E90, ET90, ET-1080 Used with Series CH70 E70, ET70
(Z) SBL-2 BACKBOX (Order s: Red 6988, White 6989) 1-11/16 6 7/64 11-16 3-3/8 (DD) CBB-8 8 CEILING SPEAKER BACKBOX (Order : 3314) 12-5/16 9-3/4 3-3/8 4-1/16 10 15/16 11-1/4 See Note 12 Used with Series RSSP Used with Series S 8 Ceiling Speakers (AA) E50SB-R (Order s: Red 0230, White 0231) (EE) E60 EXTENSION RING (Order : Red 3578, White 3757) Used with Series E50 (BB) E50SSB-R (Order s: Red 0232, White 0233) (FF) ZBB (Order s: Red 6036, White 6045) Used with Series E50 (CC) SSB-8 8 CEILING SUPPORT BRIDGE (Order : 3573) 23.750 TYP 10.000 7.956 1 0.0 0 0 7.9 5 6 1.0 0 0 T Y P 8.5 0 0 1 4.4 6 3 8.500 Used with Series S 8 Ceiling Speakers U L S5391 S2652 THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS 151-92-E
(GG) WFP PLATE (Order s: Red 4696, White 4697) (HH) WFPA PLATE (Order s: Red 4696, White 4697) BACKBOX DIMENSIONS FOR MPS 4-3/4 H x 3-1/4 W x 2-1/4 D GENERAL NOTES 1. FIGURE B IS TYPICAL OF A STEEL CITY LXM-WOW BOX OR EQUAL. FIGURE B SHOULD BE A 3.5 DEEP BACKBOX FOR CONDUIT INSTALLTIONS AND IS TYPICAL OF A STEEL CITY CY-½ BOX OR EQUAL. 2. FIGURE D IS TYPICAL OF A STEEL CITY 52151 BOX OR EQUAL. 3. FIGURE E IS TYPICAL OF A STEEL CITY 52171 BOX OR EQUAL. 4. FIGURE F IS TYPICAL OF TWO STEEL CITY LXM-WOW BOXES OR EQUAL. 5. FIGURE G IS TYPICAL OF A WIREMOLD 5748-2 BOX OR EQUAL. 6. FIGURE Q IS TYPICAL OF A STEEL CITY 52171 BOX WITH A STEEL CITY 53151 EXTENSION RING OR EQUAL. 7. FIGURE W IS TYPICAL OF A STEEL CITY 72171-1 BOX OR EQUAL. 8. USE 3.5 DEEP BACKBOX ON ALL MIZ PRODUCTS WHEN EMT CONDUIT IS USED. 9. WHEN USED WITH AC HORN (J), BB MUST BE USED FOR SURFACE MOUNT. 10. HS4, HS, MT OR MTWP STROBE ARE FOR OUTDOOR MOUNTING. 11. USE WITH SERIES RSSP. 12. FIGURE U IS TYPICAL OF A RANDL INDUSTRIES BACKBOX. ( Total Number of conductors shall be in accordance with NEC table 314.16 (B) ).
MOUNTING MATRIX Series E90/ET90 Series RSS/RSSR Series RSSP Series 31T Series E50 Series 43T Bells Sereis CH Series ET80 Series ET1010 Series MB Motor Bells Series E70/ET70 Series E60 Series MIZ/MIZ-TC Series MT Series NH/NS Series HS4/HS Series SM/DSM Series AMT Series AS/AH Series RSSWP(1), ASWP(2), AHWP(3), MTWP(4), MT- 12/24(4), ET70WP(4) (A) Universal Mounting Plate X (B) 1-GANG x 2 Deep - Flush (BO) Note 1 & 8 X X X X X (D) 4 x 4 x 1.5 Deep - Flush (BO) Note 2 X X X X X X X X (E) 4 x 4 x 2.125 Deep - Flush (BO) Note 3 X X X X X X X X X X X X X (F) 2-Gang x 3.5 Deep - Flush (BO) Note 4 & 8 X X X X X X X (G) 2-Gang x 1.75 Deep - Surface (BO) Note 5 X X X (H) NATP Trim Plate X X X (I) WPBB-R Weatherproof Backbox for ASWP 2 (J) BB Surface (WSI) Note 9 X X X X X X (K) WBB Weatherproof (WSI) X X X X X 3 (L) ISP Adapter (WSI) for Square Products X X X X X (M) IOB Surface & Weatherproof (WSI) Note 10 X X X X 4 (N) DBB Surface (WSI) X X X X X X X X X X (O) RP-R Retrofit Plate X X X X X X X X X X X (P) SBB Surface (WSI) Note 11 X X X X X X X X X X X (Q) 4 x 4 x 2.125 Box w/ 1.5 Extension Ring- Flush X X X X X X (BO) Note 6 (R) SPT Semi-Flush Plate (WSI) X X X X X X X X X X X X (S) AP Adapter Plate (WSI) X X X X (T) WPSBB-R Weatherproof Backbox for RSSWP 1 (U) 5 Square Backbox w/ Extension Ring, Flush (BO) X X X X (V) SSB-4 Ceiling (WSI) Support Bridge X X X X X X (W) 4.6875 x 4.6785 x 2.125 Deep Surface (BO) X (X) SHBB (WSI) Shallow Surface X X X X X (Y) SER Semi-Flush Extension Ring (Retrofit Appl.) X X X (Z) SBL-2 Surface (WSI) Note 11 X X X X X X X (AA) E50SB Backbox for E50 Speaker X (BB) E50SSB Backbox for E50 Speaker Strobe X (CC) SSB-8 8 Speaker Support Tile Bridge (DD) CBB-8 8 Ceiling Speaker Backbox (EE) E60 Extension Ring X (FF) ZBB Series S X X Series Z X Data Sheet Number(s) S0310 S1610 S0410 S9008 S0410 S0500 S0510 S0600 S0710 S0800 S0800 S1500 S0310 S1610 S1611 S1700 S2000 S2100 S2400 S3000 S4000 S8100 S9004 S9006 S1100 Z1000 MOUNTING NOTES Caution: The mounting options figures show the maximum number of field wires (conductors) that can enter the backbox used with each mounting option. If these limits are exceeded, there may be insufficient space in the backbox to accommodate the field wires and stresses from the wires could damage the product. Although the limits shown for each mounting option comply with the National Electrical code (NEC), Wheelock recommends use of the largest backbox option and the use of approved stranded field wires whenever possible, to provide additional wiring room for easy installation and minimum stress on the product from wiring. Caution: Check that the installed product will have sufficient clearance and wiring room prior to installing backboxes and conduit, especially if sheathed multiconductor cable or 3/4 conduit fittings are used. 1. Mounting hardware for each mounting option is supplied. 2. Conduit entrances to the backbox should be selected to provide sufficient wiring clearance for the installed product. When extension rings are required, conduit should enter through the backbox, not the extension ring. Use Steel City #53151 (1-1/2 deep) or #53171 (2-1/8 deep) extension rings (as noted in the mounting options) or equal with the same cut-out area. 3. When terminating field wires, do not use more lead length than required. Excess lead length could result in insufficient wiring space for the appliance. 4. Use care and proper techniques to position the field wires in the backbox so that they use minimum space and produce minimum stress on the product. This is especially important for stiff, heavy gauge wires and wires with thick insulation or sheathing. 5. Do not pass additional wires (used for other than the appliance) through the backbox unless the backbox is of a sufficient size to permit additional wiring as described in NEC 314.16 (B). Such additional wires could result in insufficient wiring space for the appliance. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
BACKBOX MOUNTING HEIGHTS for WHEELOCK WALL MOUNTED HORIZONTAL STROBE APPLIANCES NFPA-72 (2002) 7.5.4* Appliance Location. Wall-mounted appliances shall be mounted such that the entire lens is not less than 2.0 m (80 in.) and not greater than 2.4 m (96 in) above the finished floor. Backbox Mounting Options* Series AS/AH Audible Strobe Series RSSP Flush and Surface Retrofit Plate Series NS Horn Strobe Series Z and RSS Strobe Series MT and AMT Multitone Strobe 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN (B) 1-Gang x 2 Deep - Flush (BO) 77 ½ 8 ½ 78 3 / 8 7 5 / 8 79 1 / 8 6 7 / 8 (D) 4 x 4 x 1.5 Deep - Flush (BO) 77 9 83 15 / 16 77 7 / 8 8 1 / 8 78 5 / 8 7 3 / 8 79 15 / 16 6 1 / 16 (E) 4 x 4 x 2.125 Deep - Flush (BO) 77 9 83 15 / 16 77 7 / 8 8 1 / 8 78 5 / 8 7 3 / 8 79 15 / 16 6 1 / 16 (F) 2-Gang x 3.5 Deep - Flush (BO) 77 ½ 8 ½ 78 3 / 8 7 5 / 8 79 1 / 8 6 7 / 8 80 9 / 16 5 7 / 16 (G) 2-Gang x 1.75 Deep - Surface (BO) 77 ½ 8 ½ 78 3 / 8 7 5 / 8 79 1 / 8 6 7 / 8 80 9 / 16 5 7 / 16 (M) IOB Surface & Weatherproof (WSI) 79 3 / 8 6 5 / 8 (P) SBB Surface (WSI) 79 1 / 4 6 3 / 4 (Q) 4 x 4 x 2.125 Box w/ 1.5 Extension Ring - Flush (BO) (U) 5 Square Backbox w/ Extension Ring, Flush (BO) 69 ½ 8 ½ 83 7 / 16 77 3 / 8 7 5 / 8 78 1 / 8 6 7 / 8 79 7 / 16 5 9 / 16 (X) SHBB (WSI) Shallow Surface 76 ½ 9 ½ 77 3 / 8 8 5 / 8 78 1 / 8 7 7 / 8 (Y) 4 x 4 x 1.5 Box w/ 1.5 Extension Ring Plate (BO) (Z) SBL-2 Surface (WSI) 78 (FF) ZBB 78 1 / 8 7 7 / 8 Backbox Mounting Options* * Measured from Bottom of Backbox NOTES: (BO) = By Others (WSI) = Wheelock Product Series CH70 Chime Strobe Series ET80 Speaker Strobe Series E70 Speaker Strobe Series ET70 Speaker Strobe Series SA-70S Self Amplified Speaker Strobe 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN 80 IN 6 IN (P) SBB Surface (WSI) 77 ¾ 8 ¼ 79 3 / 16 6 13 / 16 77 ¾ 8 ¼ 77 ¾ 8 ¼ 79 3 / 16 6 13 / 16 (Q) 4 x 4 x 2.125 Box w/ 1.5 Extension Ring - Flush (BO) (U) 5 Square Backbox w/ Extension Ring - Flush (BO) (X) SHBB (WSI) Shallow Surface (Y) 4 x 4 x 1.5 Box w/ 1.5 Extension Ring Plate - Flush (BO) 77 ½ 7 ½ 80 6 78 ½ 7 ½ 78 ½ 7 ½ 80 6 78 7 79 ½ 5 ½ 78 7 78 7 79 ½ 5 ½ 78 ½ 7 ½ 80 6
Series AS Audible Strobe Appliances and Series AH Auddibles SERIES AS SERIES AH Description The Wheelock patented 2-wire Series AS Audible Strobe Appliances and Series AH Audibles offer more features with low current draw. Strobe options for wall mount models include 1575cd or the Wheelock patented MCW multi-candela wall strobes with field selectable candela settings of 15/30/75/110cd, or the high intensity MCWH strobe with field selectable 135/185cd. Ceiling mount models incorporate Wheelock s patented MCC multi-candela ceiling strobe with field selectable intensities of 15/30/75/95cd or the high intensity MCCH strobe with field selectable 115/177cd. The audible provides a selectable choice of either a continuous horn or temporal pattern ( 3) when constant voltage from a Fire Alarm Panel (FACP) is applied. Each tone has 3 dba settings to choose from. When used with the Wheelock Series SM or DSM Sync Module or Wheelock PS-24-8MC Power Supplies with Patented Sync Protocol, synchronization of the continuous horn tone provides the temporal (code 3) tone (mandated by NFPA 72) simultaneously for all audible appliances. This ensures a distinct temporal (code 3) pattern when 2 or more audibles are within hearing distance. If not synchronized the temporal sound could overlap and not be distinctive. At the same time the strobes will be synchronized. This provides the ability to comply with ADA guidelines concerning photosensitive epilepsy and the NFPA standards when installing 2 or more visual appliances within the field of view all of this plus the ability to silence the audible is achieved by using only 2 wire. Features Approvals include: UL Standard 1971, UL Standard 464 New York City (MEA), California State Fire Marshal (CSFM), Factory Mutual (FM), and Chicago (BFP). See approvals by model in Specifications and Ordering Information ADA/NFPA/UFC/ANSI Compliant Wall mount models are available with Field Selectable Candela Settings of 15/30/75/110cd or 135/185cd (Multi- Candela models) or 1575cd (single candela model) Ceiling mount models are available with field selectable candela settings of 15/30/75/95cd or 115/177cd (multi-candela ceiling models) Selectable Continuous Horn or Temporal ( 3). 3 Selectable dba settings (99, 95 and 90 dba) in both tones Patented 2-Wire Audible Strobe Appliance. Patented Universal Mounting Plate Weatherproof models are available for outdoor use Strobes produce 1 flash per second over the regulated voltage range 12 and 24 VDC models with wide UL Regulated Voltage Range using filtered DC or unfiltered FWR input voltage The strobes can be synchronized using Wheelock s sync modules or power supplies with built in sync protocol Fast installation with IN/OUT screw terminals using #12 to #18 AWG wires For Weatherproof Series AS, See Datasheet S9004 U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS E5946 S5391 151-92-E 7125-0785:131
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their Regulated Voltage Range. Note that NFPA-72 specifies a flash rate of 1 to 2 flashes per second and ADA Guidelines specify a flash rate of 1 to 3 flashes per second. All candela ratings represent minimum effective Strobe intensity based on UL Standard 1971. Series NS Strobe products are listed under UL Standard 1971 for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Series NH horns are listed under UL Standard 464 for audible signal appliances (Indoor use only). Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change UL used the terminology Listed Voltage Range. Table 1: Ratings Per UL 1971 Model Number Input Voltage VDC Regulated Voltage Range VDC/FWR Strobe Candela (cd) AS-24MCW 24 16.0-33.0 15/30/75/110 AS-24MCCH 24 16.0-33.0 115/177 AS-241575W 24 16.0-33.0 15 (75 on Axis) AS-121575W 12 8.0 17.5 15 (75 on Axis) AS-24MCC 24 16.0-33.0 15/30/75/95 AS-24MCWH 24 16.0-33.0 135/185 ASWP-2475W 24 16.0-33.0 75 @ -31 F Table 2: dba Ratings for 12 VDC and 24 VDC Series AS/AH 12 and 24 VDC Audible Description Continuous Horn 3 Horn Volume Reverberant dba Per UL 464 @ 10 ft. Anechoic dba @ 10 ft. High 91 99 Medium 88 95 Low 83 90 High 87 99 Medium 84 95 Low 79 90 Table 3: Average RMS Current Audible Wall Mount Audible Strobe Models Ceiling Mount Audible Strobe Models 24 VDC Models AH-24 AS-241575W AS-24MCW AS-24MCWH AS-24MCC AS-24MCCH 1575cd 15cd 30cd 75cd 110cd 135cd 185cd 15cd 30cd 75cd 95cd 115cd 177cd High (99) dba Med (95) dba Low (90) dba 24 vdc 0.062 0.100 0.080 0.102 0.150 0.194 0.250 0.320 0.088 0.114 0.165 0.205 0.250 0.320 UL max* 0.080 0.121 0.088 0.125 0.200 0.267 0.355 0.480 0.095 0.138 0.221 0.285 0.355 0.480 24 vdc 0.033 0.080 0.060 0.084 0.132 0.173 0.230 0.305 0.066 0.092 0.145 0.186 0.230 0.305 UL max* 0.043 0.107 0.074 0.110 0.190 0.253 0.340 0.465 0.080 0.122 0.201 0.269 0.340 0.465 24 vdc 0.017 0.072 0.052 0.076 0.121 0.158 0.220 0.295 0.056 0.082 0.132 0.173 0.220 0.295 UL max* 0.021 0.100 0.068 0.105 0.182 0.245 0.335 0.460 0.074 0.113 0.198 0.263 0.335 0.460 12 VDC Models High (99) dba Med (95) dba Low (90) dba Audible AH-12 Wall Mount Audible Strobe AS-121575W 12 vdc 0.163 0.260 UL max* 0.192 0.320 12 vdc 0.076 0.195 UL max* 0.108 0.275 12 vdc 0.039 0.175 UL max* 0.058 0.265 Table 4: Average Current* (AMPS) For Series ASWP # Voltage High dba Setting (99) dba Medium dba Setting (95) dba Low dba Setting (90) dba 24.0 VDC 0.128 0.105 0.098 UL Max* 0.168 0.155 0.150 * RMS current ratings are per UL average RMS method. UL max current rating is the maximum RMS current within the listed voltage range (16-33v for 24v units). For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For audibles the max current is usually at the maximum listed voltage (33v for 24v units). For unfiltered FWR ratings, see installation instructions.
Wiring Diagrams # SERIES AS APPLIANCES NON-SYNCHRONIZED FROM PRECEDING APPLIANCE OR FACP + - + - + - TO NEXT APPLIANCE OR EOLR SERIES AS & RSS APPLIANCES SYNCHRONIZED WITH PS-12/24-8CP and PS-12/24-8MP SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SIN- GLE CLASS B NAC CIRCUIT WITH AUDIBLESILENCE FEATURE F A C P Strobe NAC Circuit Audible NAC Circuit SM + STROBE - STROBE + Audible EOLR - Audible AS AS F A C P OUTPUTS 1-4 4-CLASS "B" OR 2-CLASS "A" Series PS-12/24-8CP or PS-12/24-8MP AS AS AS RSS RSS RSS EOLR SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE CLASS A NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE SERIES AS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES DSM #1 F A C P Audible NAC Cir. Strobe NAC Cir. Audible NAC Cir. Sync + - DSM #2 Strobe NAC Cir. Sync + - Audible NAC Cir. DSM #3 Sync Strobe NAC Cir. + - DSM Interconnecting wiring shown. Maximum of twenty (20) AS AS AS AS AS AS # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring informationon the power supplies refer to Installation Instructions P84662 for PS-24-8MC. Specifications and Ordering Information Model Number Order Strobe Candela Sync w/sm, Non- DSM or Sync PS-24-8MC 24 VDC 12 VDC Wall Ceiling Mount Mount Mounting Options*** Agency Approvals UL MEA CSFM FM BFP AS-24MCW-FR 9024 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCW-FW 9025 15/30/75/110 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCWH-FR 3468 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X * AS-24MCWH-FW 3469 135/185 X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X * AS-241575W-FR 7405 15 (75 on Axis) X X X - X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-121575W-FR 7410 15 (75 on Axis) X X - X X - A,B,D,E,F,G,H,J,N,O,R,X X X X X X AS-24MCC-FR 3161 15/30/75/95 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X * AS-24MCC-FW 3162 15/30/75/95 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X * AS-24MCCH-FW 3467 115/177 X X X - - X A,B,D,E,F,G,H,J,N,O,R,X X X X X * ASWP-2475W-FR** 9012 75 @ -31 F X X X - X - I (see Data Sheet S9004) X X X X X AH-24-R 7892 - X X X - X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-24-W 7893 - X X X - X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-12-R 7891 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-12-W 7894 - X X - X X X A,B,D,E,F,G,H,J,N,O,R,X X X X X X AH-24WP-R** 7416 - X X X - X X K X X X X AH-12WP-R** 7415 - X X - X X X K X X X X **For Weatherproof Series AS/AH specifications see data sheet S9004. *PENDING ***Refer to Data Sheet S7000 for Mounting Options. Note: Models are available in either Red or White. Contact Customer Service for Order and Delivery. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
Architects and Engineers Specifications The notification appliances shall be Wheelock Series AS Audible Strobe appliances and Series AH Audible appliances or approved equals. The Series AS Audible be listed for UL Standard 1971 (Emergency Devices for the Hearing-Impaired) for Indoor Fire Protection Service. The Series AH Audible shall be UL Listed under Standard 464 (Fire Protective Signaling). Both shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). The audible portion of the appliance shall have a minimum of three (3) field selectable settings for dba levels and shall have a choice of continuous or temporal ( 3) audible outputs. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan lens. The Series AS shall be of low current design. Where Multi- Candela appliances are specified, the strobe intensity shall have field selectable settings and shall be rated per UL Standard 1971 at 15/30/75/110 or 135/185 candela for wall mount and 15/30/75/95 or 115/177 candela for ceiling mount. The selector switch for selecting the candela shall be tamper resistant. The 1575 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with 75 candela on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compatible with Wheelock s SM, DSM Sync Modules or Wheelock PS-24-8MC Power Supplies with built-in Patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. If the sync module or Power Supply fails to operate, (i.e., contacts remain closed), the strobe shall revert to a non-synchronized flashrate. The appliance shall also be designed so that the audible signal may be silenced while maintaining strobe activation when used with Wheelock synchronization. The Series AS Audible Strobe and Series AH Audible shall incorporate a Patented Universal Mounting Plate that shall allow mounting to a single-gang, double-gang, 4-inch square, 100mm European type backboxes, or the SHBB Surface Backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S8100 AS/AH 06/06
POWERPATH NAC POWER SUPPLIES PS-24-8MC Description POWERPATH Series PS-24-8MC is an 8 Amp, 24VDC, filtered and regulated, supervised remote power supply/charger used for supervision and expanded power driving capability for Fire Alarm Notification Appliance Circuits. The PS-24-8MC may be connected to any 12V or 24V (FWR or DC) Fire Alarm Control Panel (FACP) by using a Notification Appliance Circuit (NAC) or a Dry Contact. Primary applications include NAC expansion (supports ADA requirements) and auxiliary power to support system accessories. This unit provides filtered and regulated 24VDC, 8 Amp up to four (4) Class B, two (2) Class A, or two (2) Class B and one (1) Class A Notification Appliance Circuits. With the optional plug-in PS-4CA module the unit supports (4) Class A Notification Appliance Circuits. Additionally, an auxiliary power output of 3.5 Amps (disconnected upon AC power loss or an alarm condition) or 200 mamps (constant) is provided, which can be manually reset. The PS-24-8MC also contains a battery charger capable of charging either 7 or 12 Amp/Hour (AH) of battery backup. Two FACP NAC circuits or two Dry contact initiating circuits can be connected to the POWERPATH inputs. These inputs can then be directed to control supervision and power delivery to any combination of the four (4) outputs. Each output is rated at 3.0 Amps (Class B ) or (Class A ) and can be programmed to generate a steady or 3 Temporal Horn sound and a strobe output under alarm condition. Total load for the PS-24-8MC NAC circuits must not exceed 8.0 Amps. The PS-24-8MC under non-alarm condition provides independent supervision for Class A and Class B FACP NAC circuits. In the event of circuit trouble, the FACP will be notified via the POWERPATH steered input (IN1 or IN2). In addition there are two sets of trouble reporting terminals, one used for AC power loss reporting and the other for all troubles. The AC power loss reporting, on the common trouble terminals and on IN1 or IN2, can be delayed for either 30 seconds or 170 minutes. The AC power loss terminals will always report the trouble 30 seconds after loss of AC power. The PS-24-8MC POWERPATH is UL Listed under UL Standard 864, 9th Edition to be used with any 24 volt Listed Regulated notification appliances. It includes the capability to synchronize Wheelock strobes and horns and to silence the horn signal when horn/strobes are operating on two wires. Features Approvals Approvals Include: UL Standard 864 California State Fire Marshal (CSFM), New York City (MEA), Factory Mutual (FM), Chicago (BFP) See Approvals by model in Specification and Ordering Information Compliant with NFPA 72 Inputs 120VAC, 50/60Hz, 5.0 Amps Operating Power in Alarm 24VDC Battery Backup Connection Two (2), 12V or 24V NAC Initiating Circuits (8-33V at 5mA) FWR or DC Two (2) Dry Contact initiating Circuits Accepts two (2) Class A or two (2) Class B circuit inputs Built in battery charger for sealed lead acid or gel type batteries U L THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS 151.92-E...Features continued on next page
Outputs NAC outputs are 24VDC, 3.0 Amps each, power limited 8 Amps total alarm current Capable of four (4), Class B circuits Capable of two (2) Class A circuits Capable of four (4) Class A circuits with optional PS-4CA module Capable of one (1) Class A circuit and two (2) Class B circuits Temporal ( 3) or constant voltage output Built-in Wheelock synchronization mode that can be fed to any or all of the output circuits Input and output can be synchronized with IN>OUT SYNC mode (SM, DSM or 2nd PS-24-8MC is required) Audible silence capability Filtered and electronically regulated output 3.5 Amp auxiliary power limited output with reset capability. (Removed upon AC loss or alarm. Automatic reset 30 seconds after AC power returns or the alarm condition is over) or 200 mamps auxiliary power limited output which remains on during AC loss or an alarm condition Supervision Compatible with 12V or 24V (FWR or DC) FACP Signaling appliance circuits are supervised and steered to either IN1 or IN2 2.2K Ohm, 1 Watt (Wheelock Model #MPEOL) End of Line Resistor (EOLR) for supervision of all outputs AC loss trouble reported over a separate set of contacts (delay of 30 seconds) All troubles are reported over the common trouble contacts (AC loss can have a delay of 30 seconds or 170 minutes) Automatic switchover to standby battery when AC fails Thermal and short circuit protection with auto reset Input and output status LED indicators AC fail supervision Battery presence and low battery supervision Ground Fault Detection (60K ohms) 4 latching LED s for NAC trouble annunciation Power Not Battery Dependent - Full 8A even if battery is degraded Automatic switch over to standby batteries when AC fails Supports sealed lead acid or gel type batteries Fused battery protection Thermal and short circuit protection with auto reset Supports both 7AH or 12AH batteries in the same cabinet (Cabinet Size: 16.70 H x 12.83 W x 5 D) Normal Mode (Class B)
Normal Mode (Class A) POWERPATH Operating Modes (refer to Installation Manual): Normal Mode: Provides constant 24 VDC output upon initiation by a voltage to input IN1 or IN2 or by a contact opening on DRY1 or DRY2. The unit returns to standby mode when the input is deactivated. Wheelock Sync Mode: Provides signals for synchronization of patented Wheelock audible and strobe notification appliances. Audibles can also be silenced in this mode while the strobes continue to flash. In>Out Sync Mode: Accepts a coded signal or synchronization signal on the input to provide a coded output or synchronized output. This signal may come from a FACP, another POWERPATH or a Wheelock SM or DSM synchronization module. Caution: Do not use strobes on coded output circuits. Temporal Mode: s the output voltage in a code-3 temporal pattern to drive audible appliances such as horns, bells or chimes. Caution: Do not use strobes on coded output circuits. Specifications and Ordering Information Model Number Order Input Voltage/Current UL Approvals MEA CSFM FM BFP PS-24-8MC 0237 120/220 VAC @ 50/60 Hz; 5.0 amps max. X X X X * PS-4CA 1648 Four class A plug-in module for PS-24-8MC X X X X * Output NAC Circuit Four (4) Class B or Two (2) Class A or One (1) Class A and Two (2) Class B or Four (4) Class A (optional PS-4CA module) Standby Current Alarm Current Total NAC Current Standby Batteries 24 VDC/12 AH (uses two (2) 12 VDC batteries in series) Standby Time Output Voltage/Current 24 VDC @ 3 amps per Circuit 24 VDC @ 3 amps per Circuit 24 VDC @ 3 amps per Circuit (Class A ) 24 VDC @ 3 amps per Circuit (Class A ) 0.080 Amps 0.240 Amps 8 Amps Max. Alarm Output Total Amps/Minutes CP Mode Aux Output X= Approved *= Pending MP Mode 24 Hours 8 Amps/15 Minutes 200 ma 3.5A during 60 Hours 8 Amps/15 Minutes 60 ma nonalarm
Architects and Engineers Specifications The power supply shall be Wheelock POWERPATH Series PS-24-8MC, or equivalent. The unit shall be stand alone power supply intended for powering fire alarm notification appliances via its own Notification Appliance Circuit(s) (NAC). The unit shall be UL 864 Listed for power limited operation of outputs and comply with NFPA 70 (NEC), article 760. The power suppliy shall support a full 8A of notification power even if the battery is in a degraded mode and only AC power is connected. The power supply shall be activated by a standard Notification Appliance Circuit (NAC) from any Fire Alarm Control Panel (FACP) or a Dry contact opening. The units shall be 8 ampere, 24 VDC, regulated and filtered, supervised remote power supply/charger. It shall operate over the voltage range of 8 to 33 VDC or FWR. The primary application of the unit shall be able to expand fire alarm system capabilities for additional NAC circuits to support ADA requirements and to provide auxiliary power to support system accessories or functions. The power supply shall provide four Class B, two Class A, or two Class B and one Class A NAC circuit(s). Four Class A circuits shall be available with an optional PS-4CA module. The PS-24-8MC unit shall supply up to 200 ma of auxiliary power that is available during both nonalarm and alarm or auxiliary power of not less than 3.5A at 24 VDC during nonalarm. The power supply shall be capable of charging batteries of up to 12 ampere hours per NFPA 72. Input activation options shall be from not less than two NAC circuits or Dry Contact closures. These inputs shall have the capability of being directed to any combination of the four NAC circuit outputs. Each NAC circuit output shall be rated at 3 amperes for Class B applications or 3 amperes each for Class A. The outputs shall be programmable to generate a steady or Temporal ( 3) output and or a synchronized strobe or horn output. The power supply shall provide independent loop supervision for either Class A or Class B FACP NAC circuits and shall have the capability to steer all alarm or trouble conditions to either incoming NAC circuit. The units shall have common trouble terminals. The power supply shall be powered from a 120 VAC source with a current consumption of 5 amperes max. The unit shall incorporate short circuit protection with auto reset. The power supply shall incorporate a built in battery charger for lead acid or gel type batteries with automatic switchover to battery back up in the event of AC power failure. The charger shall incorporate fused protection for the batteries and have the ability to report low battery and/or no battery condition(s). Standby current for battery back up shall be 80 ma max. The power supply shall have the ability to latch trouble LED s so the circuit in trouble can be identified. The cabinet dimensions shall be 16.70 H x 12.83 W x 5 D. WARNING: PLEASE READ THESE SPECIFICATIONS AND INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLA- TION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S8900 PS-24-8MC 07/06
Audible Strobe and Strobe Appliance Enclosures EWR, EWP, EN4 EWR EN4 Description The Wheelock Series EWR, EWP and EN4 Enclosures are designed for use with Wheelock UL approved Audible Strobe and Strobe Appliances. Constructed of 1/8 thick polycarbonate material, the Enclosures are UL Listed for a temperature range from 0 C (32 F) to 49 C (120 F) for Indoor and Outdoor applications. Features Approvals Include: UL Listed, NEMA (EN4) Rated ADA and OSHA Compliant Vandal Resistant Easy installation and access for service Provides protection from incidental contact with equipment, falling dirt, falling liquids, light splashes, rain, etc. UV stabilized against discoloration Applications* Series EWR - Slotted, Weather-Resistant Indoor/Outdoor Enclosure with Drain Screen. Designed for use with Wheelock Series NS and Series AS Audible Strobe Appliances and with Series E or ET Speaker Strobe Appliances. Series EWP - Non-Slotted, Weather-Proof Indoor/Outdoor Enclosure with Drain Screen. Designed for use with Wheelock Series RSS Strobe Appliances. Series EN4 - NEMA-4 Rated, Non-Slotted, Weather-Proof, Dust- Proof Indoor/Outdoor Enclosure. Designed for use with Wheelock Series RSS Strobe Appliances. *See tables for UL Candela and Sound Pressure Ratings Architects and Engineers Specifications INDOOR/OUTDOOR APPLICATIONS VANDAL RESISTANT WASH DOWN AREAS WALK IN COOLERS CLEAN ROOM APPLICATIONS SCHOOLS FACTORIES WAREHOUSES Specifications and Ordering Information MODEL ORDER CODE Series EWR 8151 Series EWP 8150 Note: All Enclosures 9.5 H x 7.5 W x 8.25 D Shipping Weight: 3.60 lbs DESCRIPTION Slotted, Weather-Resistant Enclosure with Drain Screen Weather-Proof Enclosure with Drain Screen Series EN4 8152 NEMA-4 Rated Enclosure The Series EWR Weather-Resistant Enclosure shall be constructed of 1/89 thick, optically clear, polycarbonate material and shall measure 9.59H x 7.59W x 8.259D with front slots and a bottom Drain Screen. The enclosure shall be UL Listed for a temperature range from 0 C (32 F) to 49 C (120 F) for Indoor and Outdoor applications. The Series EWP Weather-Proof Enclosure shall be constructed of 1/89 thick, optically clear polycarbonate material and shall measure 9.59H x 7.59W x 8.259D and contain a bottom Drain Screen. The Enclosure shall be UL Listed for a temperature range from 0 C (32 F) to 49 C (120 F) for Indoor and Outdoor applications. The Series EN4 Enclosure shall be Weather-Proof, Dust-Proof and NEMA-4 Rated, constructed of 1/8 thick, optically clear polycarbonate material and shall measure 9.5 H x 7.5 W x 8.25 D. The Enclosure shall be UL Listed for a temperature range from 0 C (32 F) to 49 C (120 F) for Indoor and Outdoor applications. U L
NOTE: ALL CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in BOLD CAPITAL LETTERS. WARNING: PLEASE READ THESE SPECIFICATIONS AND THE MOST CURRENT INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICA- TION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. Table 1: UL Candela and Sound Pressure Ratings for the Series NS Notification Strobe Appliance and Series AS Audible Strobe when using EWR Enclosure Model Number* NS-24MCW NS4-24MCW AS-24MCW-FR Candela Setting Strobe Candela (cd) Continuous Horn db @ 24 VDC 3 Horn Low Med High Low* Med High 30cd 21.0 75 82 **69 75 75cd 52.5 75 82 **69 75 110cd 77.0 75 82 **69 75 30cd 21.0 75 82 85 69 75 79 75cd 52. 75 82 85 69 75 79 110cd 77.0 75 82 85 69 75 79 * Refer to Series NS P83518 and Series AS P83509 & P83609 Instruction Sheets for additional information. ** WARNING: SERIES NS AND AS SET ON CODE 3 TONE WITH MED OR LOW dba DO NOT MEET THE 75 dba MINIMUM UL REVERBERANT SOUND LEVEL REQUIRED FOR PUBLIC MODE FIRE PROTECTION SERVICE (NOTED BY ** IN TABLE 1). MODELS WITH SETTINGS WHICH PRODUCE LESS THAN 75 dba MAY NOT BE HEARD. THIS SETTING IS ACCEPTABLE ONLY FOR GENERAL SIGNALING (NON-FIRE ALARM) USE. USE THE HIGH dba SETTING WITH THIS TONE FOR PUBLIC MODE SERVICE. Table 2: UL Candela and Sound Pressure Ratings for the E and ET Speaker Strobe Series when using EWR Model Number*** E70-24MCW Candela Setting Strobe Candela (cd) ***Refer to Series E P83566 and ET P83567 Instruction Sheets for additional information. db @ 24 VDC 1/8W 1/4W 1/2W 1W 2W 4W 8W 30cd 21.0 75 78 81 84 87 75cd 52.5 75 78 81 84 87 110cd 77.0 75 78 81 84 87 E90-2430C 30cd 21.0 75 78 81 84 87 E90-2475C 75cd 52.5 75 78 81 84 87 E90-24100C 100cd 70.0 75 78 81 84 87 ET70-24MCW-FR 30cd 21.0 75 78 81 84 87 90 93 75cd 52.5 75 78 81 84 87 90 93 110cd 77.0 75 78 81 84 87 90 93 Table 3: UL Candela Ratings for Series RSS Strobe when using EWP Enclosure Model Number*** Candela Setting StrobeCandela (cd) 30cd 21.0 ****Refer to Series RSS P83500 Instruction Sheet for additional information. RSS-24MCW-FR 75cd 52.5 110cd 77.0 NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9002 Enclos. 06/06
Series STH Cluster Speakers STH-4MSR STH-3MSR STH-2MSR SHMP-R STH-4R STH-3R STH-2R STH-2G STH-4MSR Description: The Wheelock Series Cluster Speakers are designed for ceiling or wall mounting for high ambient noise environments. The Cluster Speakers are available in multiple configurations. A speaker/visual (Series STH-MSR) and speaker only (Series STH-R or STH-G) alerting system. All alerting systems are equipped with UL listed STH-15SR or STH-15S supervised horn loudspeakers and the speaker/visual system has a UL listed DC-MAX-C strobe, mounted to a steel enclosure. STH-4MSR and STH-4R supplied with four STH-15SR Horns STH-3MSR and STH-3R supplied with three STH-15SR Horns STH-2MSR and STH-2R supplied with two STH-15SR Horns STH-2G supplied with two STH-15S Horns All STH MSR Series Cluster Speakers are supplied with one DC-MAX-C strobe with clear lens. Applications for Series Cluster Speakers: Designed for use in Manufacturing Plants, Processing Plants and Factories with high ambient noise levels. Hazard warning / alerting Industrial audible and visual signaling Process control area notification Warning lights Security alert indication The SHMP- R is a UL listed adapter plate designed for mounting one STH-15SR horn to a series RSSP strobe mounting plate. For surface mount applications, the SBL-R surface mount backbox is required. Features for all Cluster Speaker Models: Complies with UL Standard 1480, NFPA 72, NFPA 101 and OSHA 1910.165. Speaker/visual system also complies with UL Standard 1638 Cluster Speaker systems come fully assembled. High efficiency unit for life safety and/or general communication announcing/notification Provides high-intelligibility voice reproduction and available high intensity visual alerting for emergency alarm and protective signaling Speakers and Strobes are prefabricated to a 10 x 10 x 6 steel enclosure for indoor use Mounts to ceiling or wall Only 1 pair of wires needed for audio connections. Each individual STH-15SR or STH-15S horn is capable of delivering up to 102 db at 15 watts at 10 feet Omni-directional sound Labor savings (both time and money) Conduit knockouts for ½ or ¾ coupling Shipped in one box SHMP-R U L
Architects and Engineers Specifications The Cluster Speaker shall be the STH-4MSR, STH-4R or STH-3MSR, STH-3R or STH-2MSR, STH-2R, STH-2G or approved equal. The Cluster Speaker shall consist of: four (4) STH-15SR supervised horns for the STH-4MSR, STH-4R or three (3) STH-15SR supervised horns for the STH-3MSR, STH-3R or two (2) STH-15SR or STH-15S (for the STH-2G) supervised horns for the STH-2MSR, STH-2R, STH-2G or equivalent. The Series STH-MSR Cluster speakers shall also consist of one (1) supervised 100 candela DC-MAX-C strobe or equivalent. The Cluster Speaker shall comply with UL Standard 1480, NFPA 72, NFPA 101 and OSHA 1910.165. The Cluster Speakers with strobe shall also comply with UL Standard 1638. The STH-15SR or STH-15S horns shall be supervised horns measuring 7.87 W x 8.75 H x 9.32 D and prefabricated on the sides of a 10 x 10 x 6 steel enclosure. The DC-MAX-C strobe shall be 6.2 diameter and prefabricated in the center of the cover of a 10 x 10 x 6 steel enclosure, for series STH-MSR. Mounting of the Cluster Speaker shall be accomplished by using the four pre-drilled holes in the enclosure or by drilling new holes in order to be compatible with other mounting conditions. The SHMP-R shall be a 4 x 4 UL listed adapter plate with pre drilled holes for mounting the STH-15SR or STH-15S to a Series RSSP plate. STH-15SR or STH-15S Horn Loudspeakers Supervised weather proof horn speaker Up to 15 watts RMS of power handling capability Superior intelligibility and sound dispersion Built-in 25/70 Volt transformer w/screwdriver adjustable wattage tape selector Frequency Response: 400 14,000 Hz Power taps: 25 Volts:.48,.94, 1.8, 7.5, and 15 70 Volts:.9, 1.8, 3.8, 7.5, and 15 Swivel mounted for easy angle adjustment Complies with UL Standard 1480 Refer to Data Sheet S0100 for detailed specs DC-MAX-C Strobe High intensity MAX strobe Clear lens made of Lexan Powerful 7.5 Joules double flash light burst 100 candela, 60 double flashes per minute Voltage range: 10.5 VDC to 31.0 VDC Complies with UL Standard 1638 Refer to Data Sheet I1008 for detailed specs Note: Special orders of different colored lenses are available in Blue, Red or Amber. Please contact Wheelock for details. Note: The Series Cluster speaker with MAX Strobe is NOT designed to operate on a synchronized circuit. Specifications and Ordering Information* Model Number Order Description STH-4MSR 8157 STH-3MSR 8156 STH-2MSR 8155 SHMP-R 8154 Speaker/visual systems supplied with four STH-15SR horns and one DC-MAX-C Strobe mounted to a NEMA Type 1 steel enclosure Speaker/visual systems supplied with three STH-15SR horns and one DC-MAX-C Strobe mounted to a NEMA Type 1 steel enclosure Speaker/visual systems supplied with two STH-15SR horns and one DC-MAX-C Strobe mounted to a NEMA Type 1 steel enclosure UL Listedadapter plate, designed to mount the STH-15SR horn speaker (7938) to a Series RSSP Strobe Mounting Plate. For surface mountapplications, the SBL2-R (6988) surface mount backbox is required. STH-4R 8186 Speaker System supplied with four STH-15SR horns mounted to a NEMA Type 1 steel enclosure STH-3R 9753 Speaker System supplied with three STH-15SR horns mounted to a NEMA Type 1 steel enclosure STH-2R 9752 Speaker System supplied with two STH-15SR horns mounted to a NEMA Type 1 steel enclosure STH-2G 0101 Speaker System supplied with two STH-15S horns mounted to a NEMA Type 1 gray steel enclosure *The Series Cluster Speakers with Max Strobe are a special order. NOTE: The Series Cluster Speakers with MAX Strobes (STH-4MSR, STH-3MSR, & STH-2MSR) are not intended for UL required Fire Life Safety applications. See Series STH Cluster Speaker with MCCH Strobe to meet Fire Life Safety Applications. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. NOTE: Not intended for washdown areas. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9003 STH Max 06/06
Weatherproof Appliances - Series AH Audibles, AS Audible Strobes, MT Multitone Strobes, RSS Strobes and ET70 Speaker Strobes and Weatherproof Mounting Accessories Description: Designed for life safety, performance and reliability, Cooper Wheelock s cost effective weatherpoof notification appliances include: Weatherproof Appliances Strobes Horn Strobes Horns Multitone Horn Strobes Multitone Horns Speaker Strobes Speakers Series RSSWP ASWP AH-24WP, AH-12WP MTWP MT ET70WP ET-1010 All strobe models are UL dual listed - meeting both UL1638 and UL1971 requirements. As dual listed appliances, these weatherproof strobes, horn strobes and speaker strobes are listed for outdoor applications under UL 1638 as well as under UL 1971, the Standard for Safety Signaling Devices for Hearing Impaired. With an extended temperature range of 31 F to 150 F (-40 C to 66 C), Wheelock weatherproof appliances meet or exceed UL outdoor test requirements for rain, humidity and corrosion resistance while providing multiple strobe intensity options, including the highest strobe ratings available for area coverage per NFPA 72 strobe spacing tables (up to 185 candela for wall mounting and 177 candela for ceiling mounting). To enable weatherproof mounting, Cooper-Wheelock provides the industry s widest choice of mounting options for surface or unique semi-flush installation. Models are available for surface mounting to Wheelock weatherproof backboxes on walls or ceilings. The optional WP-KIT allows the weatherproof backboxes (IOB, WPBB or WPSBB) to be mounted to a recessed electrical box for concealed conduit installation. For semi-flush installation, the WPA and WFPA kits allow a customer to mount the weatherproof appliances to a recessed electrical box without the need for an external weatherproof backbox. See the Backboxes, Plates and Gaskets Table on page three of this document for a summarization of these mounting options and the required accessories. When used in conjunction with Wheelock PS-24-8MC Power Supplies or SM/DSM Sync Modules, the Wheelock weatherproof appliances can be synchronized to meet NFPA 72 synchronization requirements. The horn output of horn strobes can be independently controlled on 2-wire circuits using the Wheelock patented sync protocol. MTWP horn strobe models are 4-wire appliances; the strobes can be synchronized while the audible can be connected to a coded fire alarm system or can be set to produce any of eight selectable tones. Features: Approvals include: UL Standards 1971, 1638, 464 and 1480 California State Fire Marshal (CSFM) and New York City (MEA), Factory Mutual (FM) and Chicago (BFP). See agency approvals by model number on page two of this document Compliance with the following requirements: NFPA, UFC, ANSI 117.1, OSHA Part 29, 1910.165, ADA Weatherproof with extended temperature range of 40 F to 150 F (-40 C to 66 C)* Dual Listed strobe models (UL 1638 and UL 1971) Industry s highest strobe candela options Synchronization capability using Series SM, DSM Synch Modules (MTWP and MT-12/24 audible is non-sync) Models with field selectable tone, dba and candela settings Wall or ceiling mounting options Surface of semi-flush mounting IN/OUT wiring termination accepting two #12-18 AWG wires at each terminal *The series RSSWP, ASWP, MTWP and ET70WP have UL approval down to -40 F. The AH-24WP, MT-12/24 and the ET-1010 have been ULC tested and approved to -40 F, but not submitted to UL. The AH-12WP has UL/ULC approval to -31 F. U L E5946 S5391 S2652 THE CITY OF NEW YORK DEPARTMENT OF BUILDINGS 151-92-E 7125-0785:131 (ASWP) 7125-0785:146 (ET70WP) 7125-0785:156 (MTWP) 7300-0785:154 (RSSWP)
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. VISIT WWW.COOPERWHEELOCK.COM OR CONTACT COOPER WHEELOCK FOR THE CURRENT INSTALLATION INSTRUCTIONS. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes: Strobes are designed to flash at 1 flash per second minimum over their UL Listed Regulated Voltage Range. All candela ratings represent minimum effective Strobe intensity based on UL Standards 1971 and 1638 as indicated in candela ratings table. Wall Mount Ceiling Mount Wall or Ceiling Mount RSSWP MTWP RSSWP MTWP MT AH ASWP ET70WP ASWP ET70WP ET-1010 Strobe Order RSSWP-2475W-FR Red 9013 RSSWP-2475W-FW White 3034 RSSWP-24MCWH-FR Red 5161 RSSWP-24MCWH-FW White 5165 Audible Strobe ASWP-2475W-FR Red 9012 ASWP-24MCHW-FR Red 5137 ASWP-24MCWH-FW White 5140 Multi-tone Strobe MTWP-2475W-FR Red 8420 MTWP-2475W-FW White 3112 MTWP-24MCWH-FR Red 5132 MTWP-24MCWH-FW White 5134 Speaker Strobe ET70WP-2475W-FR Red 9077 ET70WP-2475W-FW White 3179 ET70WP-24185W-FR Red 4885 ET70WP-24185W-FW White 4891 Series UL 1971 @ 32º- 120ºF UL Max. Current (Audible) UL 1638 @ 77 F MTWP/MT 24 VDC UL 1638 @ -40 F MT 12 VDC dba HI STD HI STD Horn 0.108 0.044 0.177 0.034 Bell 0.053 0.024 0.095 0.020 March Time 0.104 0.038 0.142 0.034 3 Horn 0.091 0.035 0.142 0.034 3 Tone 0.075 0.035 0.105 0.021 Slow Whoop 0.098 0.037 0.142 0.035 Siren 0.104 0.036 0.152 0.030 Hi/Lo 0.057 0.025 0.114 0.026 Strobe Order RSSWP-2475C-FR Red 4338 RSSWP-2475C-FW White 4446 RSSWP-24MCCH-FR Red 5167 RSSWP-24MCCH-FW White 5187 Candela Ratings RSS, ET70WP and MTWP UL Max Current (Strobe Only) Audible Strobe ASWP-2475C-FR Red 4251 ASWP-2475C-FW White 4502 ASWP-24MCCH-FR Red 5149 ASWP-24MCCH-FW White 5157 Multi-tone Strobe MTWP-2475C-FR Red 4457 MTWP-2475C-FW White 4478 MTWP-24MCCH-FR Red 5102 MTWP-24MCCH-FW White 5122 Speaker Strobe ET70WP-2475C-FR Red 4452 ET70WP-2475C-FW White 4454 ET70WP-24177C-FR Red 4845 ET70WP-24177C-FW White 4859 ASWP High Med Low 2475 30 180 115 0.138 0.168 0.155 0.150 MCWH MCCH 135 135 65 0.300 0.355 0.340 0.335 185 185 90 0.420 0.480 0.465 0.460 115 115 50 0.300 0.355 0.340 0.335 177 177 75 0.420 0.480 0.465 0.460 24185 185 185 90 0.420 24177 177 177 75 0.420 Audible Order AH-24WP-R Red 7416 AH-12WP-R Red 7415 Horn MT-12/24-R Red 5023 Speaker ET-1010-R Red 3135 ET-1010-W White 3137 UL Max. Current AH 24 VDC 12 VDC High (99) dba 0.080 0.192 Med (95) dba 0.043 0.108 Low (90) dba 0.021 0.058 UL Reverberant dba @ 10 Feet Watts 1/8 1/4 1/2 1 2 4 8 ET-1010 77 80 83 86 87 92 94 ET70WP 78 81 84 87 90 93 95 Model Number Agency Approvals Strobe UL MEA CSFM FM BFP RSSWP-2475 X X X X * RSSWP-24MCWH X * * * * RSSWP-24MCCH X * * * * Audible Strobe ASWP-2475 X X X X X ASWP-MCWH X * * * * ASWP-MCCH X * * * * Multitone Strobe MTWP-2475 X X X X * MTWP-MCWH X * * * * MTWP-MCCH X * * * * Horns/Audibles AH-24WP X X X - X AH-12WP X X X - X MT-12/24 X X X X X Speaker Strobe ET70WP-2475 X X X * * ET70WP-185 X * * * * ET70WP-177 X * * * * *Pending
Mounting Accessories WFP WFPA IOB WPSBB WPBB WBB Gasket Kit Order WP-KIT 4486 Flush Plates WFPA-R Red 4698 WFPA-W White 4701 WFP-R Red 4696 WFP-W White 4697 Backboxes IOB-R Red 5046 IOB-W White 5047 WPSBB-R Red 9751 WPSBB-W White 3033 WPBB-R Red 9014 WPBB-W White 4692 WBB-R Red 2959 WBB-W White 2960 Mounting Options: Backboxes, Plates, Gasket Kits Exposed Conduit Surface Mount Concealed Conduit Flush Mount RSSWP Strobes WPSBB WPSBB + WP-KIT WFP ET70WP Speaker Strobes IOB IOB + WP-KIT WFP ASWP Horn Strobes WPBB WPBB + WP-KIT WFPA AHWP Horns WBB - WFP ET-1010 Speakers WBB - WFP MTWP Multitone Horn Strobes IOB IOB + WP-KIT WFP Multitone Horn IOB IOB + WP-KIT WFP Wiring Diagrams SERIES MTWP APPLIANCES SYNCHRONIZED STROBE OPERATION WITH CODED FACP MTWP SERIES MTWP AUDIBLE APPLIANCE AND STROBE OPERATE IN UNISON. RED AND BLACK SHUNT-WIRES ARE SUPPLIED. FROM PRECEDING APPLIANCE OR FACP + RED - - BLACK + TO NEXT APPLIANCE OR EOLR NAC #1 FACP NAC #2 Sync Module or PS-12/24-8 Power Supply Strobe Circuit Audible Circuit Note: Strobe circuit requires constant voltage. + - STROBE + - AUDIBLE SERIES RSSWP, ASWP, AHWP, MTWP AND MT-12/24 APPLIANCES FROM PRECEDING APPLIANCE OR FACP + - + - TO NEXT APPLIANCE OR EOLR SERIES RSSWP/ASWP APPLIANCES SYNCHRONIZED W/ DSM MODULE SINGLE CLASS A NAC CIRCUIT FACP STROBE NAC CIRCUIT OUT DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 RSSWP ASWP RSS + - STROBE NAC CIRCUIT RETURN + IN 2 + OUT 2 RSS ASWP RSS Note: Models are available in Red or White. Contact Customer Service for Order and Delivery. #Refer to Data Sheet S7000 for Mounting Options NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions.
ARCHITECTS AND ENGINEERS SPECIFICATIONS General Weatherproof notification appliances shall be UL listed for outdoor use. Weatherproof Strobe appliances shall be listed under UL Standard 1638 (Standard for Visual Signaling Appliances) for Indoor/Outdoor use and UL Standard 1971 (Standard for Safety Signaling Devices for Hearing Impaired). The appliances shall be available for optional wall mounting or ceiling mounting to weatherproof backboxes using either exposed conduit or concealed conduit, or semi-flush mounting to a recessed electrical box in walls or ceilings using Wheelock mounting accessories. Weatherproof Strobes Weatherproof Strobe appliances shall produce a minimum flash rate of 60 flashes per minute over the UL Regulated Voltage Range of 16 to 33 VDC and shall incorporate a Xenon flashtube. The weatherproof strobes shall be available with UL 1971 candela ratings up to 185 cd for wall mounting and 177 cd for ceiling mounting. UL 1638 candela ratings up to 180 cd at 77 F shall be available. The strobes shall operate over an extended temperature range of 40 F to 150 F (-40 C to 66 C) and be listed for maximum humidity of 95% RH. Strobe inputs shall be polarized for compatibility with standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel (FACP). Weatherproof Audibles and Audible/Strobe Combinations Weatherproof horns and multitone audibles shall be listed for Indoor/Outdoor use under UL Standard 464. The horns shall be able to produce a continuous output or a temporal code-3 output that can be synchronized. T Multitone audibles shall be able to produce 8 distinct tones selectable by dip switch and shall have at least 2 sound level settings. Multitone Audible/Strobe combinations shall have independent inputs for the audible and strobe. The strobes shall be able to be synchronized. The audibles shall be able to be coded when operated on a separate NAC. Weatherproof Speakers and Speaker/Strobes Weatherproof speakers and speaker/strobes shall be listed for Indoor/Outdoor use under UL Standard 1480. All speakers shall provide field selectable taps for 1/8W to 8W operation for either 25 VRMS or 70 VRMS audio systems and shall incorporate a sealed back construction for extra protection and improved audibility. Speakers without strobes shall be Wheelock Series ET-1010. They shall be listed to produce up to 94 dba and shall incorporate a vandal resistant grille design. Speaker with strobes shall be Wheelock Series ET70WP. They shall be available for surface or semi-flush mounting to walls or ceilings and shall be listed to produce up to 93 dba. Synchronization Modules When synchronization of strobes or temporal code-3 audibles is required, the appliances shall be compatible with the Wheelock Series SM and DSM Sync Modules or the Wheelock PS-24-8MC Power Supply with built-in, patented sync protocol. The strobes and audibles shall not drift out of synchronization at any time during operation. Series ASWP audibles and strobes shall be able to be synchronized on a 2-wire circuit with the ability to silence the audible if required. The strobes on Series MT multitone audible/strobe appliances shall be able to be synchronized and shall be able to be operated on a separate circuit from the audibles while the audible circuit is connected to a coded or continuous NAC. Weatherproof Mounting Accessories Weatherproof mounting options shall include surface mounting or semi-flush mounting to walls or ceilings. Surface mounted appliances shall mount to Wheelock IOB, WBB, WPBB or WPSBB weatherproof backboxes using either exposed conduit or concealed conduit. For concealed conduit the weatherproof backbox shall be mounted to a recessed electrical box with Wheelock s WP-KIT to provide a weatherproof seal for the electrical box. Semi-flush mounted appliances shall mount to a recessed electrical box using Wheelock WFP or WFPA flush plates to provide a weatherproof seal between the electrical box and the appliance. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9004 WP 03/07
Series STH Cluster Speakers STH-4M30WC Description: The Wheelock Weatherproof STH-4M30WC Series Cluster Speaker is designed for ceiling, wall or roof mounting for high ambient noise and outdoor environments. The Cluster Speaker is a speaker/visual alerting system, equipped with four STH-30 horn loudspeakers, and a DC-MAX-C Strobe, mounted to a NEMA 4X rated fiberglass enclosure. Each horn can deliver 125 db of sound @ 1 watt, 1 meter. The Cluster Speakers can be connected to Wheelock SAFEPATH Systems. Capacitors are installed in line with the speakers to ensure speaker wire supervision. Applications for Cluster Speakers: Designed for use in Manufacturing Plants, Processing Plants and Factories with high ambient noise levels as well as for outdoor environments. Hazard warning / alerting Industrial audible and visual signaling Process control area notification Warning lights Security alert indication Personnel alerting Intrusion warning Piers or docks Features: Approvals Include: UL Standard 1638 for Visual Signaling Complies with OSHA 1910.165 The Series STH-4M30WC appliances are weatherproof Cluster Speaker system comes fully assembled High efficiency unit for announcing and notification Provides high-intelligibility voice reproduction and available high intensity visual alerting for emergency alarm and protective signaling Speakers and Strobe are prefabricated to a 13.50 x 15.50 x 6.25 NEMA 4X rated fiberglass enclosure Mounts to ceiling, wall or roof Only 2 pair of wires needed for audio connections The cluster speaker system is capable of delivering over 125 db @ 1 watt, 1 meter DC-MAX-C strobe has a 100 candela strobe at 60 double flashes per minute Omni-directional sound Speakers come preset at 30 watts each Labor savings (both time and money) Conduit knockouts for ½ coupling Shipped in one box U L
ARCHITECTS AND ENGINEERS SPECIFICATIONS The Cluster Speaker shall be the STH-4M30WC or approved equal. The Cluster Speaker shall consist of: four (4) STH-30 horns and one (1) supervised 100 candela DC-MAX-C strobe or equivalent. Each STH-4M30WC shall be capable of producing 125 dba @ 1 watt, 1 meter. The Cluster Speaker shall comply with OSHA 1910.165 and UL Standard 1638. The STH-30 horns shall measure 10 W x 10.5 L and shall be prefabricated on the sides of a 13.50 x 15.50 x 6.25 NEMA 4X fiberglass enclosure. The DC-MAX-C strobe shall measure 6.2 in diameter and be 5 in height, and shall be prefabricated in the center of the cover of a 13.50 W x 15.50 L x 6.25 H NEMA 4X fiberglass enclosure. Mounting of the Cluster Speaker shall be accomplished by using the four predrilled holes in the enclosure. The STH-4M30WC shall weigh approximately 45 lbs. The STH-4M30WC shall measure approximately 36.5 W x 34.5 L x 11 H STH-30 Horn Loudspeakers Up to 30 watts RMS of power handling capability Superior intelligibility and sound dispersion Built-in 70 Volt transformer 125 dba @ 1 watt, 1 meter Frequency Response: 375 10 KHz Power taps: 70 Volts: 2.0, 3.8, 7.5, 15.0 & 30.0 Swivel mounted for easy angle adjustment DC-MAX-C Strobe High intensity MAX strobe Clear lens made of Lexan Powerful 7.5 Joules double flash light burst 100 candela, 60 double flashes per minute Voltage range: 10.5 VDC to 31.0 VDC Complies with UL Standard 1638 Refer to Data Sheet I1008 for detailed specs Note: Special orders of different colored lenses are available in Blue, Red or Amber. Please contact Wheelock for details. Note: The Series Cluster speaker with MAX Strobe is NOT designed to operate on a synchronized circuit. SPECIFICATIONS AND ORDERING INFORMATION* Model Number Order Description STH-4M30WC 9762 Speaker/Visual system supplied with four STH-30 horns and one DC-MAX-C strobe mounted to a NEMA Type 4X fiberglass enclosure *The Series STH-4M30WC is a special order. Note: The STH-4M30WC is not intended for UL required Fire Life Safety applications. See Wheelock Catalog or Website for products to meet Fire Life Safety Applications. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9005 STH WP 06/06
Series STH Cluster Speakers with MCCH Strobe STH-4R24MCCH-NR Description: The Wheelock Series STH Cluster Speaker with MCCH Multi- Candela Strobe is designed for indoor ceiling mounting in high ambient noise environments. It is available with 2, 3 or 4 speakers for wide area coverage. The Cluster Speaker Strobe is supplied with STH-15SR, UL1480 Listed horns and one RSS- 24MCCH, UL1971 Listed ceiling strobe mounted to a NEMA 1 steel enclosure. The strobe is synchronizable. The Series STH Cluster Speaker with MCCH Strobe come fully assembled. Series STH Cluster Speaker with MCCH Strobes is designed for UL Required Fire Life Safety applications. STH-4R24MCCH Supplied with four STH-15SR horns and one RSS-24MCCH Strobe. The strobe plate has the following optioins: -Red with no lettering -Red with FIRE lettering -White with no lettering -White with FIRE lettering STH-3R24MCCH Supplied with three STH-15SR horns and one RSS-24MCCH Strobe. The strobe plate has the following options: -Red with no lettering -Red with FIRE lettering -White with no lettering -White with FIRE lettering STH-2R24MCCH Supplied with two STH-15SR horns and one RSS-24MCCH Strobe. The strobe plate has the following options: -Red with no lettering -Red with FIRE lettering STH-90-R24MCCH-NR Supplied with two STH-15SR horns and one RSS-24MCCH Strobe, designed for corner mount. The strobe plate has the following options: -Red with no lettering -Red with FIRE lettering Features for all Cluster Speaker Models: STH-15SR Speakers are UL Standard 1480 Listed. RSS-24MCCH Strobes are UL Standard 1971 Listed Compliant with ADA, OSHA 1910.165, ANSI 117.1, NFPA 72, NFPA 101, and IFC Cluster and Strobe wiring can be monitored for integrity by the Control Panel Cluster Speaker Strobes come fully assembled High efficiency unit for fire life safety and/or general communication announcing/notification Provides high-intelligibility voice reproduction and high intensity visual alerting for emergency life safety applications, alarm and protective signaling Speakers and Strobes are prefabricated to a 10 x 10 x 6 NEMA 1 steel enclosure for indoor use. Mounts to ceiling Only 1 pair of wires needed for audio connections Strobes are connected to the NAC Strobe Circuit and are selectable 115 or 177 cd Each individual STH-15SR horn is capable of delivering up to 102 db at 15 watts at 10 feet Omni-direction Conduit knockouts for ½ or ¾ coupling Labor Saving Applications for Series Cluster Speaker Strobes: Designed for use in Manufacturing Plants, and Factories with high ambient noise levels and for UL Required Fire Life Safety Applications. Hazard warning/alerting Industrial audible and visual signaling Process control area notification Warning lights Security alert indication Emergency notification Employee notification
Architects and Engineers Specifications The Cluster Speaker Strobe shall be the Series STH with MCCH Strobe or approved equal. The cluster speaker strobe shall be designed for indoor ceiling mounting for high ambient noise environments. The speaker strobe shall be supplied with UL Standard 1480 listed horn(s) and one UL Standard 1971 listed ceiling strobe mounted to a NEMA 1 steel enclosure. The strobe shall be a selectable 115 or 177 candela synchronizable strobe. The Cluster Speaker and Strobe shall be fully assembled. The Cluster Speaker and Strobe shall be capable of use for UL Required Fire Life Safety applications. The Cluster Speaker and strobe wiring shall be able to be monitored for integrity by the Control Panel. The Series STH Cluster Speaker with MCCH Strobe shall comply with NFPA 72, NFPA 101, OSHA 1910.165, ANSI 117.1, ADA, and IFC. The speaker horns shall measure 7.87 W x 8.75 H x 9.32 D each and shall be prefabricated on the sides of a 10 x 10 x 6 steel enclosure. The Strobe shall be a high intensity selectable 115 or 177 candela ceiling strobe with a current draw of 0.195 amps for 115cd @ 24 VDC or 0.270 amps for 177 cd @ 24VDC, and shall be prefabricated on the bottom of the steel enclosure. Mounting of the Cluster Speaker Strobe shall be accomplished by using pre-drilled holes in the enclosure or by drilling new holes in order to be compatible with other mounting conditions. STH-15SR Horn Loudspeakers UL Standard 1480 Listed Supervised weather proof horn speaker Up to 15 watts RMS of power handling capability Superior intelligibility and sound dispersion Built-in 25/70 Volt transformer w/screwdriver adjustable wattage tape selector Frequency Response: 400 14,000 Hz Power taps: 25 Volts:.48,.94, 1.8, 7.5, and 15 70 Volts:.9, 1.8, 3.8, 7.5, and 15 Swivel mounted for easy angle adjustment Refer to Data Sheet S0100 for detailed specs on horn RSS-24MCCH Strobe UL Standard 1971 Listed High intensity selectable115 or 177 candela ceiling strobe Factory setting is 177 candela Synchronizable when used with SM/DSM or Wheelock PS-24-8MC Power Supply or Wheelock s SAFEPATH or SAFEPATH4 24 VDC input voltage 2-Wire connection Current draw @ 24 VDC: 115cd - 0.195 177cd - 0.270 Strobes produce 1 flash per second over the regulated voltage range Refer to Data Sheet S0410 for detailed strobe specs Specifications and Ordering Information* Model Number Order Description Strobe Plate STH-4R24MCCH-NR 3089 Red with no lettering STH-4R24MCCH-FR 3090 Supervised Speaker Strobe supplied with four STH-15SR horns Red with FIRE lettering and one RSS-24MCCH ceiling strobe mounted to a NEMA 1 STH-4R24MCCH-NW 0239 steel enclosure. White with no lettering STH-4R24MCCH-FW 0235 White with FIRE lettering STH-3R24MCCH-NR 3144 Red with no lettering STH-3R24MCCH-FR 3145 Supervised Speaker Strobe supplied with three STH-15SR Red with FIRE lettering horns and one RSS-24MCCH ceiling strobe mounted to a STH-3R24MCCH-NW 0238 NEMA 1 steel enclosure. White with no lettering STH-3R24MCCH-FW 0234 White with FIRE lettering STH-2R24MCCH-NR 3146 Supervised Speaker Strobe supplied with two STH-15SR horns Red with no lettering and one RSS-24MCCH ceiling strobe mounted to a NEMA 1 STH-2R24MCCH-FR 3143 steel enclosure. Red with FIRE lettering STH-90-R24MCCH-NR 3227 Supervised Speaker Strobe supplied with two STH-15SR horns Red with no lettering mounted adjacent to each other, designed for a corner mount configuration and one RSS-24MCCH ceiling strobe mounted to STH-90-R24MCCH-FR 0522 a NEMA 1 steel enclosure. Red with FIRE lettering *The Series Cluster Speakers with RSS Strobe are a special order. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9009 STH RSS 06/06
Series Colored Lens Strobes: Amber, Blue, Green and Red Description: The Wheelock colored lens strobe products are available on Series RSS strobes and Series E speaker/strobes in amber, blue, green or red lens colors. These products are not Listed for fire alarm use, but they are built with the same high quality circuits and parts used in the Wheelock life safety strobes and speakers. They are designed for indoor use and can be either wall or ceiling mounted to standard electrical boxes or to Wheelock s surface mount boxes. The strobes operate from 16 to 33 vdc (using filtered or FWR voltage). Intensity options for amber, blue and green lens strobes include multi-candela models with four field-selectable settings or high intensity 110 candela models. Red lens strobes are available in 75 or 110 candela models and are Listed under UL Standard 1638. Series E speakers with colored lens strobes are field selectable for 25 or 70 VRMS operation with wattage taps of 1/8, 1/4, 1/2, 1 and 2 watts. Other Wheelock signaling products can also be provided with colored lens strobes - contact Customer Service for availability. Features: Choice of four strobe lens colors with wide range of intensity options Wide operating voltage range Strobes can be synchronized with Wheelock SM or DSM sync modules or POWERPATH power supplies Combination speaker/strobes available for voice messages with visual alerting Mount to standard electrical boxes High quality designs from the leader in fire notification alarms Applications: The Wheelock colored lens strobe products are designed for effective alerting of employees or personnel in industrial, military or government applications. They are ideal for Mass Notification systems and for emergency, warning or trouble notification in many industrial operations. U L S5391
NOTE: All CAUTIONS and WARNINGS are identified by the symbol. All warnings are printed in bold capital letters. WARNING: PLEASE READ THESE SPECIFICATIONS AND ASSOCIATED INSTALLATION INSTRUCTIONS CAREFULLY BEFORE USING, SPECIFYING OR APPLYING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THESE INSTRUCTIONS, CAUTIONS OR WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE, AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS. General Notes Regulated Voltage Range is the newest terminology used by UL to identify the voltage range. Prior to this change, UL used the terminology Listed Voltage Range. Strobes are designed to flash at 1 flash per second minimum over the Regulated Voltage Range. Series RSS & RSSP Strobe products are listed for indoor use with a temperature range of 32 F to 120 F (0 C to 49 C) and maximum humidity of 93% (± 2%). Specification and Ordering Information Order Lens Strobe Mounting Strobe Strobe Current Model Number Color Candela Options Voltage (RMS) note 1 note 2 note 3 16 vdc 24 vdc RSSA-24MCC-NW 0202 AMBER MCC wall or ceiling 24 vdc note 4 RSSB-24MCC-NW 0203 BLUE MCC wall or ceiling 24 vdc note 4 RSSG-24MCC-NW 0204 GREEN MCC wall or ceiling 24 vdc note 4 RSSR-24MCC-NW 3111 RED MCC wall or ceiling 24 vdc note 4 RSSPA-24MCC-NW 3308 AMBER MCC wall or ceiling 24 vdc note 4 RSSWPA-2475W-NW 0240 AMBER 75 Wall 24 vdc 0.138 E70A-24MCC-NW 0209 AMBER MCC wall or ceiling 24 vdc note 4 E70B-24MCC-NW 0210 BLUE MCC wall or ceiling 24 vdc note 4 E90A-24MCC-NW 0213 AMBER MCC ceiling 24 vdc note 4 E90B-24MCC-NW 0214 BLUE MCC ceiling 24 vdc note 4 MTWPA-2475W-NW 1649 AMBER 75 Wall 24 vdc 0.246 MTWPB-2475W-NW 1652 BLUE 75 Wall 24 vdc 0.246 1. Candela is measured on axis per UL 1638. Models with MCC strobes have 4 field-selectable candela settings. MCC settings are rated for clear lens - derate appoximately 25% for amber, 55% for green and 70% for blue lenses. 2. Backboxes (ordered separately Series Flush Surface RSS 4 x 1-1/2, 1-gang or 2-gang box SHBB-W E70 4 x 2-1/8 with extension ring SBB-W E90 4 x 2-1/8 with extension ring N/A * RMS current ratings are per UL average RMS method. For strobes the UL max current is usually at the minimum listed voltage (16v for 24v units). For unfiltered FWR ratings, see installation instructions. 3. All strobes operate from 16 to 33 volts at 1 flash/second using filtered or full-wave rectified DC voltage. (See Installation Instructions) 4. Strobe current for MCC Strobes: MCC Setting 15 30 75 95 current @ 24 vdc 0.045 0.07 0.119 0.159 UL Max* 0.065 0.105 0.189 0.249
Wiring Diagrams # SERIES RSS APPLIANCE FROM + PRECEDING - APPLIANCE, SYNC MODULE, POWER SUPPLY OR FACP + - + - TO NEXT APPLIANCE OR EOLR SERIES RSS APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS B NAC CIRCUIT F A C P Strobe NAC Circuit SM + STROBE - STROBE + Audible EOLR - Audible RSS RSS SERIES RSS APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS A NAC CIRCUIT FACP STROBE NAC CIRCUIT OUT STROBE NAC CIRCUIT RETURN DSM SYNC + - +OUT 1 + IN 1 MINUS 1 + AUDIBLE - MINUS 2 + IN 2 + OUT 2 RSS RSS RSS RSS RSS RSS SERIES RSS APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES F A C P Strobe NAC Cir. Strobe NAC Cir. DSM #1 Sync + - DSM #2 Sync + - RSS Strobe NAC Cir. Sync + - RSS DSM #3 RSS RSS RSS RSS DSM Interconnecting wiring shown. Maximum of twenty (20) # For detail using SM or DSM Sync Module refer to Data Sheet S3000 or Installation Instructions P83123 for SM and P83177 for DSM. For wiring information on the power supplies refer to Installation Instructions P84515 for PS-12/24-8CP and P84333 for PS- 12/24-8MP. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having
Architects and Engineers Specifications The visual notification appliances shall be Wheelock colored lens strobe products or approved equals. The strobe appliances shall operate from 16 to 33 VDC at 1 flash per second using filtered or FWR input voltage. They shall be compatible with reverse polarity supervision of circuit wiring when provided by the system control unit. Strobe intensity shall be 75 or 110 candela minimum or shall be field selectable for 4 intensity levels. All appliances shall be capable of being mounted to recessed standard electrical boxes. Surface mount boxes shall also be available. When synchronization is required, the strobes shall be compatible with Wheelock SM, DSM sync modules or the Wheelock POWERPATH power supplies with built-in patented Sync Protocol. The strobes shall not drift out of synchronization at any time during operation. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9020 Colored Lens 06/06
Series STH Cluster Speakers with Three Strobes STH-4R24MCCH110R-NR STH-4R24MCCH110B-NR STH-4R24MCCH110G-NR STH-4R24MCCH110A-NR Description: The Wheelock Series STH Cluster Speaker with three Strobes include: Four (4) STH-15SR, UL 1480 Listed horns One (1) RSS-24MCCH Multi-Candela, UL1971 Listed synchronizable ceiling strobe Two (2) RSS (red, blue, green or amber) colored strobes All horns and strobes are mounted to a NEMA 1 steel enclosure and come fully assembled. STH-4R24MCCH110R-NR Supervised Speaker Strobe with four STH-15SR horns and one RSS-24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with red lens mounted to NEMA 1 steel enclosure STH-4R24MCCH110B-NR Supervised Speaker Strobe with four STH-15SR horns and one RSS-24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with blue lens mounted to NEMA 1 steel enclosure STH-4R24MCCH110G-NR Supervised Speaker Strobe with four STH-15SR horns and one RSS-24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with green lens mounted to NEMA 1 steel enclosure STH-4R24MCCH110A-NR Supervised Speaker Strobe with four STH-15SR horns and one RSS-24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with amber lens mounted to NEMA 1 steel enclosure Features: STH-15SR Speakers are UL Standard 1480 Listed RSS-24MCCH Strobes are UL Standard 1971 Listed Two RSS ceiling strobes Note: RSS Strobe candela output is based on a clear lens, when a colored lens is used the candela output is de-rated to: Red Lens strobe, 22 candela Blue Lens strobe, 49.5 candela Green Lens strobe, 33 candela Amber Lens strobe, 82.5 candela Compliant with ADA, OSHA 1910.165, ANSI 117.1, NFPA 72, NFPA 101, and IFC Cluster and Strobe wiring can be monitored for integrity by the Control Panel Cluster Speaker Strobes come fully assembled High efficiency unit for fire life safety and/or general communication announcing/notification Provides for high-intelligibility voice reproduction and high intensity visual alerting for emergency life safety applications, alarm and protective signaling Speakers and Strobes are prefabricated to a 10 x 10 x 6 NEMA 1 steel enclosure for indoor use Mounts to ceiling Only 1 pair of wires needed for audio connections RSS-24MCCH Strobes are connected to the NAC Strobe Circuit and are selectable 115 or 177 candela Each individual STH-15SR horn is capable of delivering up to 102 db at 15 watts at 10 feet The Cluster Speakers delivers omni-directional sound Conduit knockouts for ½ or ¾ coupling Labor Saving
Architects and Engineers Specifications The Cluster Speaker Strobe shall be the Series STH speaker with three strobes or approved equal. The cluster speaker strobe shall be designed for indoor ceiling mounting for high ambient noise environments. The cluster speaker strobe shall be supplied with UL Standard 1480 listed speaker horn(s), one (1) UL Standard 1971 listed selectable 115 or 177 candela synchronizable ceiling strobe and two (2) UL Listed 1638 110 candela ceiling strobes (with either a Red, Blue, Green or Amber lens) mounted to a NEMA 1 steel enclosure. The Cluster Speaker and Strobe shall be fully assembled. The Cluster Speaker and Strobe shall be capable of use for UL Required Fire Life Safety applications. The Cluster Speaker and strobe wiring shall be able to be monitored for integrity by the Control Panel. The Series STH Cluster Speaker with three strobes shall comply with NFPA 72, NFPA 101, OSHA 1910.165, ANSI 117.1, ADA, and IFC. The speake The one (1) UL Standard 1971 listed strobe shall be a high intensity selectable 115 or 177 candela ceiling strobe with a current draw of 0.195 amps for 115cd @ 24 VDC or 0.270 amps for 177 cd @ 24VDC. The two (2) UL Standard 1638 listed strobes shall be a 110 candela ceiling strobe with a current draw of 0.195 amps @ 24 VDC. The colored lens strobes shall have following candela output ratings: Red lens: 22 candela, Blue lens: 49.5 candela, Green lens: 33 candela, Amber lens: 82.5 candela. All speaker horns and strobes shall be prefabricated on the bottom of the steel enclosure. Mounting of the Cluster Speaker Strobe shall be accomplished by using pre-drilled holes in the enclosure or by drilling new holes in order to be compatible with other mounting conditions. RSS 110 Colored Lens Strobe UL Standard 1638 Listed Strobe Candela output: Red Lens strobe, 22 candela Blue Lens strobe, 49.5 candela Green Lens strobe, 33 candela Amber Lens strobe, 82.5 candela Synchronizable when used with SM/DSM or Wheelock s PS-12/24-8MP Power Supply or Wheelock s SAFEPATH or SAFEPATH4 24 VDC input voltage 2-Wire connection Current draw @ 24 VDC is 0.195 Strobes produce 1 flash per second over the regulated voltage range Refer to Data Sheet S9020 for detailed strobe specs STH-4R24MCCH110R-NR STH-4R24MCCH110B-NR STH-4R24MCCH110G-NR STH-4R24MCCH110A-NR STH-15SR Horn Loudspeakers UL Standard 1480 Listed Supervised weather proof horn speaker Up to 15 watts RMS of power handling capability Superior intelligibility and sound dispersion Built-in 25/70 Volt transformer w/screwdriver adjustable wattage tape selector Frequency Response: 400 14,000 Hz Power taps: 25 Volts:.48,.94, 1.8, 7.5, and 15 70 Volts:.9, 1.8, 3.8, 7.5, and 15 Swivel mounted for easy angle adjustment Refer to Data Sheet S0100 for detailed specs on horn RSS-24MCCH Strobe UL Standard 1971 Listed High intensity selectable115 or 177 candela ceiling strobe Factory setting is 177 candela Synchronizable when used with SM/DSM or Wheelock s PS- 12/24-8MP Power Supply or Wheelock s SAFEPATH or SAFEPATH4 24 VDC input voltage 2-Wire connection Current draw @ 24 VDC: 115cd - 0.195 177cd - 0.270 Strobes produce 1 flash per second over the regulated voltage range Specifications and Ordering Information* Refer to Data Sheet S0410 for detailed strobe specs *The Series Cluster Speakers with Max Strobe are a special order.please consult customer service for availablility. Model Number Description Order Weight Supervised Speaker Strobe with four STH-15SR horns and one RSS- 24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with red lens mounted to NEMA 1 steel enclosure Supervised Speaker Strobe with four STH-15SR horns and one RSS- 24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with blue lens mounted to NEMA 1 steel enclosure Supervised Speaker Strobe with four STH-15SR horns and one RSS- 24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with green lens mounted to NEMA 1 steel enclosure Supervised Speaker Strobe with four STH-15SR horns and one RSS- 24MCCH ceiling strobe, no lettering, red plate and two RSS strobes with amber lens mounted to NEMA 1 steel enclosure 3810 40.0 3827 40.0 3826 40.0 3829 40.0 NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock, Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA S9030 STH MCCH110 06/06
Strobe, 5 Joules, Explosion Proof SM87 Description: These certified strobes have been designed for use in harsh environmental conditions. The marine grade alloy enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance and strength is required. Units can be painted to customer specification and fitted with identification labels. A high temperature unit is available. Features*: UL Listed for USA and Canada: Class I, Div. 1, Groups C & D Class I, Zone 1 AExd IIB CSA Certified cul Listed ATEX Approved NEMA 4x &6, IP66 and IP67 Certified temperature 67 F to +158 F ( 55 C to +70 C) High temperature unit (up to 185 F/85 C) available Various lens colors Optional lens guard 4 wire monitored connection 24 & 48 VDC 110, 120, 240 & 254 VAC Xenon 29 Candela with clear lens *Depending on version Architects and Engineers Specifications Explosion-proof strobes shall be UL and cul Listed for Class I, Division 1, Groups C&D, and Class I, Zone 1 hazardous locations. The strobes shall be constructed of marine grade alloy with an epoxy paint finish and shall meet NEMA 4x, NEMA6, IP 66 and IP 67 environmental requirements over a temperature range of -67 F to 158 F (-55 C to 70 C) in hazardous and harsh environments. The strobe shall be rated to flash at 1 Hz with 5 joules per flash. Rated current draw shall not exceed 320 ma at 24 vdc. The strobe shall be capable of direct surface mounting in any direction. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Specification DC AC 50/60 Hz Voltage 24 48 110 120 240 254 SM87 HXB XBT Tube Energy (Joules) 5 5 6 7 7 8 Peak Current Consumption (ma) 320 170 250 275 135 150 Effective Intensity (Cd) 29 29 32 39 39 44 Peak Intensity 22213 22213 25061 30187 30187 34174 Power Consumption (Watts) 7.2 7.6 25 27 27 35 Certification: UL Listed fro USA and Canada for Class I, Div I. Groups C & D and Class I, Zone 1. Listing No. E187894. CSA Certification to C22.2 Nos. 0, 0.4, 0.5, 9, 30-M 1986, 94-M91, 137-M 1981, Class 1, Div 1, Group 0, Enclosure 3/4, Cert. No. 96406 ATEX approved: EN50014, EN50018, EN50019. Cert. No. Baseefa 03ATEX0222, EExd IIC T6 Weight: Material: 4.4lb./2.0kg. approx. LM25 TF Marine Grade Alloy, Finish: Expoxy paint as standard or to customer's specification Lens - Toughened Glass Certified Temperature: Standard unit SM87 HXB: +70 C). Ingress Protection: Terminals: Labels: Entries: 67 F to +158 F ( 55 C to High temperature unit: 67 F to +185 F ( 55 C to +85 C) NEMA 4x & 6, IP66 & IP67 4 off suitable for up to 14AWG conductor size Duty & Tag Labels optional Up to 4 x 1 /2" or 3 /4" NPT FOR COLORED LENSES Color Red Blue Amber Green Yellow Multiplying Factor 0.15 0.12 0.51 0.49 0.86 Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Model Certification Voltage Lens/LEDcolor Lens Guard Entries Tag/Duty Label Other Options Finish Type Xenon (alloy) Xenon High Temp. (alloy) *XBT only available 24V d.c. SM87HXBA SM87XBTA* Certification UL CSA UL C Color Red Blue Green Amber Yellow Clear Voltage R B G A Y C 24V d.c. 024 48V d.c. 048 110V a.c. 110 120V a.c. 120 240V a.c. 240 254V a.c. 254 Entries 1 /2" NPT 3 3 /4" NPT 4 Top *T Bottom *B RHS *R LHS *L *prefix position with entry *size code. Guard None Yes N Y Standard Models Series Model Number Order Decription SM87 SM87HXBAUL024RN4L4RNNR 109200-001 Strobe, Red Lens, 29 Joules, 24 VDC, Red finish SM87 SM87HXBAUL024CN4L4RNNR 109200-002 Strobe, Clear Lens, 29 Joules, 24 VDC, Red finish SM87 SM87HXBAUL110AN3R3LNNR 109200-003 Strobe, Amber Lens, 29 Joules, 110 VAC, Red finish SM87 SM87HXBAUL110RN3R3LNNR 109200-004 Strobe, Red Lens, 29 Joules, 110 VAC, Red finish Option None Yes* *(Please specity) Label None N Yes* Y *(Please specify) N Y Finish Red R Blue B Yellow Y Yellow/Black Stripe X Grey G White W Special Finish *S *Please specify 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA SM87 04/07
Fire Alarm Call Points, Hazardous Location SM87 PBL Description: These fire alarm call points have been designed for the most arduous environmental conditions. The units are both easy to install and maintain. Versions of this model are available with various options including an addressable module. The marine grade alloy makes the unit suitable for offshore industries. Features*: UL Listed for USA and Canada Hazardous locations: Class I, Div. I, Groups C & D Class I, Zones 1 Ordinary locations: Audible-Signal Device ATEX approved CSA Certified NEMA 4x &6, IP66 and IP67 Certified temperature 67 F to +158 F ( 55 C to +70 C) Marine grade alloy Robust yet lightweight Easy to maintain *Depending on version Architects and Engineers Specifications Explosion-proof fire alarm call points or push buttons shall be UL listed for Class I, Division 1, Groups C&D, and Class I, Zone 1 hazardous locations. The call points or push buttons shall be constructed of marine grade alloy with an epoxy paint finish and shall meet NEMA 4x, NEMA6, IP 66 and IP 67 environmental requirements over a temperature range of -67 F to 158 F (-55 C to 70 C) in hazardous and harsh environments. Actuation of the call point or push button shall require the opening of a flap and depression of an actuator. An actuated unit shall remain latched until reset. A reset operation shall only take place through the use of a key. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Ingress Protection: NEMA 4x & 6, IP66 & 67. Terminals: Switch Rating: Cable Entries: Weight: Material: Finish: Resistors: Will accept up to 14AWG cable 2 amp, 2 pole c/o, wired to terminals Up to 4 entries 1 2 or 3/4 NPT. 5.5 lb/2.5kg (Varies with model & entries). LM25 TF Marine Grade Alloy Red epoxy painted finish as standard or to Customer s specification. 470R minimum. Optional Indicator: A red high intensity LED can be fitted for alarm indication Certified Temperature: -67 F to 158 F Configuration Options: Unit Type Model Certification Entries Duty Label Tag Label Features Finish SM87 Standard Models PBL Certification CSA Certified* UL Listed C UL Entries 1 /2" NPT 3 3 /4" NPT 4 Top *T Bottom *B RHS *R LHS *L *prefix position with size code i.e. 3T 3B = 1 /2" NPT Top and Bottom Series Model Number Order Decription SM87 PBL SM87PBLAUL3T3B3NNR 109211-002 Push button, Fire label, Red finish Tag Label Finish Required Not Required Y N Label Push Button 2 Fire-Push Button 3 ESDO-Abandon 4 Other O* Red (Standard) R Blue B Yellow Y Grey G Yellow/Black Stripes X Other specify S Features None N LED A Lift Flap (BG only) B Resistor Series *C Resistor EOL *D Break glass P *Specify values 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA BG and PB 09/06
Series MZC Zone Controller & Modules MZC-144 System Features Interface / Connection Options: Universal interface: Can be connected directly to a telephone for stand alone paging, unused CO line/trunk port, 600 ohm audio page port or analog station line. Compatible with PBX s and EKSU s Wheelock SAFEPATH Voice Evacuation systems for OSHA related applications Expandability / Optional Features: Each MZC-144 is expandable to 12 zones (MZEM-3) with 4 music inputs Up to 12 fully loaded MZC-144 s can be stacked to accommodate a 144-zone system of one-way paging, talkback, or relay control. Note: When more then 72 zones are required, contact Wheelock Technical support. A system booster and connection cable (MZC-Booster) is required and will be supplied. MZC-144 Features: System can provide for one-way communication or talkback DTMF tone access with 3 digit dialing All call and / or programmed zone paging Separate music sources can be inserted into each zone group Field programmable for fixed or logical zones Music muting by zone Tone and paging volume control Page alert tone Built in ring detection for ring start applications Provides talk battery for unused CO line/trunk port and standalone telephone applications Night ringer with contact closure activation Wall mountable Operates on 24 VDC, regulated and filtered power supply: RPS-2440A, can power up to 72 zones RPS-2406, can power up to 12 zones Specifications and Ordering Information Model Number Order Product Description MZC-144 7550 Programmable Modular Zone Control System, 3 Zones Expandable to 12 Zones. Up to (12) MZC-144's can be stacked to accomodate up to a 144 Zone System MZEM-3 7552 3 Zone Expansion Modules (Audio) TBM 7551 Talk-Back Modules MZC-RM 7555 Relay Module - Provides 3 Relay Contacts MZC-CAB 7553 Expansion Cable - Interconnects Multiple MZC-144's MZC-BOOSTER 7556 For use when more than 72 Zones are required - Includes Cable See page 4 for General and Technical Notes. 69
SPECIFICATION & ORDERING INFORMATION Model Number Order Remote Microphone Stations S AFEPATH Description Specification s RMS-3B 7374 Dual Circuit Remote Microphone Station, black RMS-3R 7375 Dual Circuit Remote Microphone Station, red RMS-1R 5473 Multi Circuit Remote Microphone Station, red RMS-1B 5474 Multi Circuit Remote Microphone Station, black Input Voltage: 20-28 VDC Supply Current @24 VDC: 100mA Output: 600 OHMS Frequency Range: 250-6000 Hz Audio Output Levels: 1Vrms Max. Dimensions: 5"H x 9"W x.5"d, Weight: 1lb., 8oz. Wiring: 3 Twisted Pairs, #22AWG up to 1000' Mounting: 4 Gang surface or flush backbox (Mounting backbox is by others) Power Supply/Chargers PSC-2420-R 7377 Power Supply/Charger, red, externa l Power Supply Portion: Input Voltage: 102-132 VAC Rated Voltage: 20.8 amps @24VDC Supply Current (Full Load) @ 120 VAC: 6.4 amps Charger Circuit Portion: DC Supply Circuit @24VDC, Bulk Rate Charge: 3.7 amps Fast Rate Charge @VBAT = 26VDC: 2.6 amps Overcharge Voltage: 28.9VDC Overcharge Terminiation Current: 468MA Float State Voltage: 20VDC Charge Enable Voltage: 20VDC Battery Type: Lead Acid Starved Electrolyte Maximum Battery Capacity: 72AH Power Distribution: number of Outputs: 8 Fuse Rating: 3.5 amps Power Capacity: 20.8 amps Size: 21"H x 16"W x 6"D, Weight: 26lbs., 6 oz. Batteries and Battery Cabinets BATC-B 5413 Steel, Lockable Battery Cabinet, Black BATC-R 5414 Steel, Lockable Battery Cabinet, Red BAT-1212 7390 12 Volt 12 Ampere Hour Battery BAT-1224 7391 12 Volt 24 Ampere Hour Battery BAT-1265 7392 12 Volt 65 Ampere Hour Battery Message Kits SMK 5082 Standard Message Kit (8 most common messages) SMK-OSHA 8191 Standard Message Kit for OSHA Applications - 8 Messages SMK-SP 8144 Spanish Standard Message Kit SMK-ENGSP 8148 English / Spanish Standard Message Kit CMK 8193 Common Message Kit consisting of choice messages as listed on form PMKOF PMK 5056 Factory Programmed Message Kit AM-SMK 7599 After MArketStandard Message Kit (8 most common messages) of any 3 messages from library of 25 commonly used AM-SMK-OSHA 8192 After Market Standard Message Kit for OSHA Applications - 8 Messages AM-SMK-SP 8117 After Market Spanish Standard Message Kit AM-SMK-ENGSP 8149 After Market English/Spanish Standard Message Kit AM-CMK 8194 After Market Common Message Kit consisting of choice commonly used messages as listed on form PMKOF AM-PMK 5062 After Market factory Programmed Message Kit of any 3 messages from library of 25 AM-MDV-PMK 5089 After Market factory Programmed Message Kit for Dual Packaged Systems MDV-PMK 5099 Programmed Message Kit for Dual Packaged Systems Additional Memory MEM-1 5054 1 Minute of EPROM Memory (2 megs) MEM-2 5055 2 Minutes of SRAM Memory (4 megs) AM-MEM-1 5060 After Market 1 Minute of EPROM Memory (2 megs) AM-MEM-2 5061 After Market 2 Minutes of SRAM Memory (4 megs) Dimensions: 9.5"H x 24"W x 9" D Weight: 20lbs. (empty) Lock: Keyed like the S AFEPATH Control Panel Dimensions: 4"H x 6"W x 4"D Weight: 20lbs., 6oz. Dimensions: 5"H x 7"W x 7"D Weight: 19lbs., 12oz. Dimensions: 7"H x 14"W x 7"D Weight: 50lbs., 5oz. See Pages 8 & 9 Additonal Memory 6
SPECIFICATION & ORDERING INFORMATION Model Number Order Multi-Circuit Output Channel Kits S AFEPATH Description Specification s OCK 5057 AM-OCK 5063 Output Channel Kit for DX-100 or DX-200 Maximum number of 4 Channels per System After Market Output Channel Kit for DX-100 or DX-200 Maximum number of 4 Channels per System IC's - 1st Channel included with System. Additional OCK's are required for 2nd, 3rd and 4th Channels. System Boards/Components MIC-400 5166 Hand held Push-To-Talk (PTT) Microphone DCMB 7372 Dual Circuit Mother Board SAMB-A 5486 Multi-Circuit Mother Board MDX-2 5094 Modular Digital Voice Module for Dual Circuit AM-MDV-OCM 5097 Output Channel Module for MDX-2 DX-100 5433 Multi-Circui t V oicelink Digital Voice Module (Playback only) Frequency Response: 250-6000Hz Impedance: 600 OHMS Sensitivity: -74dB ± 3dB Dimensions: 4"H x 2.5"W x 1.5"D Interlinks all the functions of the Dual Circuit System Interlinks all the functions of the Multi-Circuit System Please refer to Data Sheet V#1000 for additional information (MDX-2 is V oicelink MDV-2) Please refer to Data Sheet information on the DV-100 V#1000 for additional DX-200 5434 LLIM 7366 Multi-Circuit VoiceLink Digital Voice Module (Record/Playbac k fully field programmable) Lone Level Interface Module, used to interface the master S AFEPATH Control with any and all remote AFEPATH panels S Please refer to Data Sheet information on the DV-200 Input Voltage: 20.4-26.6 VDC Supply Current @24VDC: 25mA Audio Input Level: 5Vrms Audio Output Level: 1Vrms Audio Imput Impedence: 600OHMS V#1000 for additional DCDC 7373 Dual Circuit Disarrangement Control (Common Control Module) DCPS 7378 Dual Circuit Power Supply (Internal ) SADC 5485 Multi-Circuit Disarrangement Control (Common Control Module) Supply Current: 75mA - Standby; 130mA - Alarm Input Voltage: 102-132VDC Supply Current : 2.13 Amps Output: 6.0 amps @24 VDC continuous Battery Charger Size: 12AH Supervision: Low battery and no battery Weight: 8lbs., 6oz. Input Voltage: 20-28VDC Supply Current : 75mA - Standby 130mA - Alarm SAPS 5409 Multi-Circuit Power Supply Module SAPS-X 5489 UL Recognized Component Power Supply Module Input Voltage: 102-132VAC Rated Output: 20.8 amps @24VDC Supply Current (full load) @120VAC: 6.4amps SABC 5410 Multi-Circuit Battery Charger Module SABC-X 5490 UL Recognized Component Battery Charger Module BAT 5069 Spare Battery Pack for DX-200 Memory Retentio n AC Supply Voltage: 120VAC DC Supply Voltage Range: 20.4-26.4VDC DC Supply Current @24VDC, Bulk Rate Charge: 3.7amps Fast Charge Current @Vbat=6VDC: 2.6amps Overcharge Voltage: 28.9VDC Overcharge Terminiation Current: 469MA Float State Voltage: 27.3VDC Charge Enable Voltage: 20VDC Battery Type: Lead Acid Starved Electrolyte Maximum Battery Capacity: 72AH BAT can Retain Memory for up to 21 Days 7
SMK and AM-SMK Standard Messages in Standard Message Kit Message # Message Script 1 (3 rounds of code 3 horn) May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators. 2 (5 seconds of 1kHz tone) May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please stand by for further instructions. 3 (3 rounds of code 3 horn) May I have your attention please! A fire emergency has been reported in the building. Please leave the building by the nearest exit or exit stairway. Do not use the elevators. 4 (3 rounds of code 3 horn) May I have your attention please! An emergency has been reported in the building. While this is being verified, please leave the building and report to the designated assembly area for your group. 5 (5 seconds of 1kHz tone) May I have your attention please! The National Weather Service has issued a severe weather warning for our area. 6 (5 seconds of 1kHz tone) This is an audio system test. 7 (5 seconds of 1kHz tone) May I have your attention please! The building emergency has ended. An all clear has been given. Please resume normal activities. 8 (3 rounds of code 3 horn) May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. SMK-OSHA and AM-SMK-OSHA Standard Messages in OSHA Applications Message Kit Message # and Type Message Script 1 Fire Emergency (1 round code 3 temporal) Attention, Attention, a fire emergency has been reported. Please leave the building using the nearest exit. 2 Medical Emergency (5 seconds slow whoop) May I have your attention, a medical emergency has been reported, all EMT personnel report to your assigned stations. 3 Toxic Chemical Release (5 seconds fast whoop) Attention, Attention. A toxic chemical release has been reported, all personnel are to report to their designated emergency areas and await further instructions. 4 Tornado Warning (5 seconds 1,000Hz steady tone) The National Weather Service has issued a tornado alert for this area, further information will be broadcasted as it becomes available. 5 Flood Watch (5 second wail) A flash flood watch has been issued by the local weather service, further information will be broadcasted as it becomes available. 6 All Clear (5 second chime) The building emergency has now ended, please resume your normal duties. Thank you for your cooperation. 7 Bomb Threat (5 second hi-low) Attention, Attention, a bomb threat alert has been issued for this building, all personnel are to evacuate immediately using the nearest exit. Further instructions will be issued outside the building by emergency response teams. 8 Terrorist Threat (5 seconds fast whoop) May I have your attention please, a terrorist threat has been received. Effective immediately we are operating secure and lockdown procedures. All personnel should remain calm and stay where you are. Emergency response teams are active within the building. Please await further instructions. 8
Commonly Used Messages Selection Form Commonly Used Messages Used with CMK, AM-CMK, PMK, AM-PMK and MDV-PMK MESSAGE# MESSAGE CONTENT 1 May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators. 2 May I have your attention please! An emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators. 3 May I have your attention please! An emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. 4 May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please stand by for further instructions. 5 May I have your attention please! An emergency has been reported in the building. While this is being verified, please stand by for further instructions. 6 May I have your attention please! May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit or exit stairway. Do not use the elevators. 7 May I have your attention. May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit or exit stairway. Do not use the elevators. 8 May I have your attention please. A fire alarm has been reported in the building. While this is being verified, please leave the building by the nearest exit. 9 May I have your attention please. A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. 10 May I have your attention please. This is a fire alarm. Please leave the building immediately. 11 May I have your attention please! An emergency has been reported in the building. While this is being verified, please leave the building and report to the designated assembly area for your group. 12 Attention. The signal you have just heard indicates a report of an emergency in this building. Walk to the nearest exit and leave this building. 13 Your attention please, your attention please. There has been a fire alarm initiated in this building. The fire department has been notified and they are on their way. Please remain calm and exit the building. 14 Attention. An emergency situation exists in this building. Please evacuate this building immediately. 15 Attention please. Attention please. The fire alarm in this building has been activated. Cease all operations. Proceed immediately to the nearest fire exit or exit stairway and leave the building. Do not use the elevators. 16 There is a fire emergency in the building. Evacuate the building using the nearest exit. 17 May I have your attention please. The building emergency has ended. An all clear has been given. Please resume normal activities. 18 Attention. Attention. The fire life safety system has activated indicating a possible fire condition. Please proceed to exits and evacuate the building. 19 This is an audio system test. 20 Your attention please. Your attention please. This is a test of the fire alarm system. Repeat, this is only a test. 21 May I have your attention please. This is an evacuation drill. Please follow your evacuation procedures and exit the building. 22 May I have your attention please. The National Weather Service has issued a severe weather warning for our area. 23 May I have your attention please. There is a Tornado warning for our area. Please proceed to the tornado safe area. Stand clear of all windows and unsecured objects. 24 Your attention please. The fire emergency has been investigated. It is now clear to resume normal activities. 25 May I have your attention please. The severe weather warning is over. Please resume normal activities. Note 1: In addition to these messages there are a variety of tones that can be included with the messages either before or as a separate file. They include: Horn, Bell, March Time Horn, -3 Horn, -3 Tone, Slow Whoop, Siren, Hi / Lo. In addition any tone provided by the customer via standard cassette tape may be used. Note 2: All messages are available in both Male or Female voice. Male voice will be assumed unless otherwise specified. 9
SAFEPATH SAMPLE CONFIGURATION DRAWINGS Dual-Circuit SAFEPATH Headend with Multiple Remote Panel Distribution System One pair #16 awg twisted & shielded (typical) RSAPE Remote Panel 80 watt amplifier cards Contact Closure Inputs -or- RS-232 Input from Fire Alarm Control Panel SALL 15S HEADEND Dual Circuit Safepath Digital Voice Circuit # 1 4-way split Plant Building # 1 (4 remote panels) Speakers with Strobes SALL- 15S 4-way split Circuit # 7 RSAPE Remote Panel AIM-3 Module Plant Building # 2 (3 remote Panels) Telephone System PBX for general paging SAA-80S 80 watt ammplifier cards To remote microphone station(s) NOTES: 1. Speaker wiring to be #14 awg, twisted pair 2. All speaker circuits terminate with 10K ohm end of line resistor 3. All panels are powered by 120VAC with battery backup (not shown) 4. Strobe booster supplies are triggered from the FACP (not shown) Multi-Circuit SAFEPATH System with (4) Speaker/Strobe Circuits SAA-40/80S Amplifiers Contact Closure Inputs -or- RS-232 Input from Fire Alarm Panel Digital Voice Module Speaker/Strobe Circuits as Required Microphone AIM-3 Module 120 vac Telephone System PBX for General Paging Backup Batteries 10 NOTES: 1. Each audio ouput has an associated strobe output circuit. 2. The on-board microphone takes priority over pre-recorded messages, which in turn take priority over telephone paging.
Architects and Engineers Specifications DUAL-CIRCUIT SYSTEM The system shall be a Wheelock Supervised Audio, Fire and Emergency Evacuation System or approved equal. The system shall be a dual channel voice evacuation system incorporating user selectability of 8 distinct sounds for tone signaling, and the incorporation of a VoiceLink MDX-2 (MDV-2) module for prerecorded messaging. The system shall incorporate microphone override. The system shall have the capability of utilizing a remote microphone station with redundant controls of the evacuation system control panel. Two Notification Appliance Circuits (NAC) shall be provided for the activation of strobe appliances. The activation of the NAC Circuits shall follow the operation of the speaker NAC circuits. Audio output is determined by selecting the pre-engineered package with the supplied module for line level (600 ohms), 25, 70.7 or 100 volt output. The audio outputs shall provide either 40 or 80 watts RMS output or Line Level SALL- 15S module. The speaker NAC Circuits shall have the capability of being split into no more than 4 individual speaker NAC circuits by utilizing the 4-way splitter (SPL). The strobe NAC Circuits shall have the ability to control up to 2 amps of 24 VDC power each and have the ability of synchronization or non-synchronization. A hand held microphone shall be provided and, upon activation, shall take priority over any tone signal, recorded message or remote microphone operation in progress, while maintaining the strobe NAC Circuits activation. The system shall have the capability of being powered from the internal 6 amp 24 VDC power supply/battery charger module or from an external 20.8 amp 24 VDC power supply (PSC-2420-R). All outputs and operational modules shall be fully supervised with on-board diagnostics and trouble reporting circuits. Form C contacts shall be provided for system alarm and trouble conditions. A 100mA 24 VDC circuit shall be provided for operation of an auxiliary appliance during trouble conditions. The system shall be enclosed in a steel locking enclosure, painted red. The system shall have a weight of 60 lbs. and its dimensions shall be 21"H x 16"W x 6"D and be made in the USA. The system shall have a 3 YEAR WARRANTY. The approvals for this system shall be: UL Standard 864, ULC, MEA, CSFM & FCC Part 15. The Dual-Circuit System shall be capable of operating in a Master - Remote configuration utilizing the standard Dual-Circuit System equipped with (SPL) speaker splitter module and (SALL-15S) Line-Level Output Modules. Line-Level Modules shall be connected to up to 8 Remote Pre-Engineered Systems through the Line-Level Interface Module (LLIM). The Master - Remote configuration of the Dual-Circuit System shall have the capability of supporting 128 Speaker NAC Circuits and 8 Strobe Appliance NAC Circuits. DUAL-CIRCUIT REMOTE MICROPHONE STATION (RMS-3B/R) The Remote Microphone station shall be a Wheelock RMS-3B/R or approved equal. The unit shall be compatible with any Wheelock Dual-Circuit Supervised Audio, Fire and Emergency Evacuation System. The unit shall incorporate a Push-To-Talk (PTT) microphone, redundant controls and system status indicators of/for the system. The unit shall incorporate microphone override of any tone generation or Wheelock product for prerecorded messages. The unit shall be fully supervised from the control panel. The unit shall be made of steel and be flush mounted to a standard 4-gang electrical box. The unit shall come equipped with a keyed lock that, when activated allows the use of the unit. The locking arrangement shall be identical to the control unit. The unit shall be painted either black or red. The unit shall have a weight of 1 Lb., 8 oz. and its dimensions shall be 5"H x 9"W x.5"d. The unit shall be made in the USA and have a 3 YEAR WARRANTY. The approvals for this unit shall be: UL Standard 864, ULC, MEA, CSFM & FCC Part 15. AIM-3 Auxiliary Input Module (Data Sheet #V3900) The unit shall be a Wheelock AIM-3 or approved equal. It shall be designed to be an outboard expansion module to either expand the number of optional remote microphone stations from 1 to 3, or allow a telephone interface and up to 2 remote microphones. The unit shall be designed to interface with Wheelock SAFEPATH panels. The unit shall require input voltage of 24 VDC. The housing shall be black metal with knockouts for conduit; shall be designed for panel/wall mount installation, and the dimensions shall be 13.00 H x 7.64 W x 2.12 D. Weight shall be 3.8 lbs. The AIM-3 is approved under UL Standard 864, MEA, CSFM, cul, FCC Part 15 and CE. The unit shall comply with OSHA 1910.165. 11
Architects and Engineers Specifications MULTI-CIRCUIT SYSTEM The system shall be a Wheelock Supervised Audio, Fire and Emergency Evacuation System or approved equal. The system shall be capable of providing 4 channels of voice evacuation incorporating user select ability of 8 distinct sounds for tone signaling, and the incorporation of either DX-100 (DV-100) playback only module or the DX-200 (DV-200) record/playback (field programmable) module for prerecorded messaging. The system shall incorporate microphone override. The system shall have the capability of utilizing a remote microphone station with redundant controls of the evacuation system control panel. One to Four Notification Appliance Circuits (NAC) shall be provided for the activation of strobe appliances. The activation of the NAC Circuits shall follow the operation of the speaker NAC circuits. Audio output shall be selectable by the insertion of the specific module(s) for line level (600 ohms), 25, 70.7 or 100-volt output. The audio outputs shall provide either Line Level (600 Ohms), 40 or 80 watts RMS output. The speaker NAC Circuits shall have the capability of being split into no more than 4 individual speaker NAC circuits by utilizing the 4-way splitter (SPL) for a total of 16 available Speaker NAC Circuits within each system. One to four strobe NAC Circuits shall have the ability to control up to 2 amps of 24 VDC power each and have the capability of synchronization or non-synchronization. A hand held microphone shall be provided and, upon activation, shall take priority over any tone signal, recorded message or remote microphone operation in progress, while maintaining the strobe NAC Circuits activation. The system shall be powered from approved AC (building) electrical circuits. All inputs, outputs and operational modules shall be fully supervised with on-board diagnostics and trouble reporting circuits. Form C contacts shall be provided for system alarm and trouble conditions. A 100mA 24 VDC circuit shall be provided for operation of an auxiliary appliance during trouble conditions. The system shall be enclosed in a steel locking enclosure, painted either black or red. The system shall have a weight of (less amplification modules) 57 lbs. and its dimensions shall be 36.0"H x 24"W x 6"D. The system shall be made in the USA and have a 3 YEAR WARRANTY. The approvals for this system shall be: UL Standard 864 &1459, ULC, MEA, CSFM & FCC Parts 15 & 68. The Multi-Circuit System shall be capable of operating in a Master - Remote configuration utilizing the standard Multi-Circuit System equipped with SPL (speaker splitter module) and (SALL- 15S) Line-Level Output Modules. Line-Level Modules shall be connected to up to 16 Remote Pre-Engineered Systems through the Line-Level Interface Module (LLIM). The Master - Remote configuration of the Multi-Circuit System shall have the capability of supporting 256 Speaker NAC Circuits and 64 Strobe Appliance NAC Circuits. MULTI-CIRCUIT REMOTE MICROPHONE STATION (RMS-1B/R) The Remote Microphone station shall be a Wheelock RMS-1B/R or approved equal. The unit shall be compatible with any Wheelock Multi-Circuit Supervised Audio, Fire and Emergency Evacuation System. The unit shall incorporate a Push-To-Talk (PTT) microphone, redundant controls and system status indicators of/for the system. The unit shall incorporate microphone override of any tone generation or Wheelock product for prerecorded messages. The unit shall be fully supervised from the control panel. The unit shall be made of steel and be flush mounted to a standard 4-gang electrical box. The unit shall come equipped with a keyed lock that, when activated allows the use of the unit. The locking arrangement shall be identical to the control unit. The unit shall be painted either black or red. The unit shall have a weight of 1 Lb., 8 oz. and its dimensions shall be 5"H x 9"W x.5"d. The unit shall be made in the USA and have a 3 YEAR WARRANTY. The approvals for this unit shall be: UL Standard 864, ULC, MEA, CSFM & FCC Part 15. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com MADE IN THE USA 3 YEAR WARRANTY Distributed By: 12 V2000 09/03
Fire Alarm Systems INC. Helping People Take Action TM SERIES PSC-2420-R Description The PSC-2420-R is a special application 20 Amp, 24VDC Power Supply Battery Charger Unit. It is UL Listed under Standard 1481, Power Supplies for Fire and Emergency Protective Equipment. Features Up to 8 fused outputs, each with a maximum of 3.5 Amps, max total power supply output is 20 Amps Outputs are current limited with overload and short circuit protection Equipped with a battery charger capable of charging up to a 65 ampere hour battery load Fully Regulated and Filtered Can be used to power the Dual Circuit SAFEPATH - Supervised Audio, Fire and Emergency Evacuation Systems Wall mountable in a self contained 16 gauge enclosure with lock and key Meets UL 1481, Power Supplies for Fire Protective requirements Dimensions: 21" H x 16" W x 6" D 26 lbs. 6 oz Batteries and battery cabinet sold separately Made in USA 3 year warranty Cabinet painted red EXTERNAL POWER SUPPLY/CHARGER 20 AMP, 24 VDC POWER SUPPLY BATTERY CHARGER FOR FIRE PROTECTIVE EQUIPMENT Applications Can be used to power SAFEPATH - Supervised Audio, Fire and Emergency Evacuation Systems Utilized to power Access Control card readers, door strikes and accessories Supply power for fire alarm door holders Use with 4-wire smoke detectors Can supply power for Data Gathering Panels PSC-2420 SPECIFICATION & ORDERING INFORMATION MODEL ORDER CODE DESCRIPTION PSC-2420-R 7377 20 Amp, 24 VDC Power Supply / Charger - Red Cabinet BATTERY CABINETS AND BATTERIES BATC-B 5413 Battery Cabinet - Black BATC-R 5414 Battery Cabinet - Red BAT-1212 7390 12 Volt, 12 Ampere Hour Battery BAT-1224 7391 12 Volt, 24 Ampere Hour Battery BAT-1265 7392 12 Volt, 65 Ampere Hour Battery Copyright 2001 Wheelock Inc. All rights reserved.
Architects and Engineers Specifications The power supply shall be a Wheelock PSC-2420-R or approved equal. The power supply shall provide eight regulated and filtered fused outputs rated at 3.5 amps each. Total amperage output shall be 20 amps. All outputs shall be current limited with overload and short circuit protection. The unit shall be equipped with a battery charger capable of charging up to a 65 ampere hour battery load. The power supply shall accept 120 VAC line voltage and provide a single 24 VDC 500 watt isolated output. The power supply shall be 21 H X 16 W X 6 D and weigh 26 lbs. 6 oz. The unit shall be designed for wall mounting. The power supply shall be UL Listed under Standard 1481, Power Supplies for Fire Protective Equipment. Specifications Electrical (Power Supply) Input Parameters Supply Voltage (Nominal) Input Power at 120VAC, 20A Output Parameters Output Power at 50 C Natural Convection Cooling Output Voltage at 120VAC, No Load 120VAC/60 Hz 900W 500W 24.2 ±VDC CAUTION: The maximum current of all output circuits must not exceed 20A. Electrical (Battery Charger) Input Parameters Line Input Voltage, Nominal Power Supply Input Voltage, Nominal Power Supply Input Voltage, Minimum Power Supply Input Voltage, Maximum Power Supply Input Current at 24VDC, Standby Power Supply Input Current at 24VDC, Float Charge State Power Supply Input Current at 24VDC, Bulk Charge State Output Parameters Battery Charge Enable Voltage Battery Float State Voltage 120VAC/60 Hz 24VDC 20.4VDC 26.4VDC 40 ±4mA DC 1A Max DC 3.7 ±.56A DC 20 ±.5VDC 27.34 ±.27VDC B attery Float State Voltage, 0 C to 65 C V(Float)=(28.83-.047T) ± 2.5% Battery Low Detect Voltage Battery Open Detect Voltage Battery Capacity Battery Type Battery Charge Time, 12-65 AH s Trouble Output Sink Current at.2v Relay Delay, Turn On Relay Delay, Turn Off Relay Switching Time, Turn On Relay Switching Time, Turn Off 20.03 ±.50VDC 30.80 ±.77VDC 12 to 65 AH s Rechargeable Sealed Lead Acid Approximately 10-52 Hrs Max 120 ± 12mA DC 25 to 100mS 250 to 400mS 5 to 40mS 5 to 40mS NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION TION 3 YEAR WARRANTY MADE IN THE USA Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 V2002 2/01
SAFEPATH 4 Facility Communications System & Expansion Options SPB-320 SP40S SPB-80/4 SPB-160 SP4-APS SPRM SP4Z-A/B SP-SVC SP4-TZC Description Page SP40S Facility Communications System 2-4 Expansion Options SAFEPATH 4 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter 5 SAFEPATH 4 Audio Boosters 6-7 System Diagram 8-9 SAFEPATH 4 Addressable Paging Splitter and Telephone Zone Controller 10 SAFEPATH 4 Supervised Volume Control and Remote Microphone 11 Remote Microphone Expansion Module 12 S5361 151-92-E 6911-0785:157
SAFEPATH 4 Facility Communications SP40S Description The SP40S is a Multi-Function Supervised Paging, Messaging, Background Music delivery and Emergency Voice Evacuation System with 24 VDC battery backup. This single channel system is capable of delivering 40 watts of supervised high fidelity audio power and 2 amps of supervised 24 VDC synchronized strobe power. It comes standard with an on-board digital voice messaging system with 8 standard messages, a hand-held microphone, power supply/battery charger and numerous additional features. The SAFEPATH4 system is expandable to 5280 watts utilizing the SPB-80/4 (80 watts and 4 amps of strobe power), the SPB-160 (160 watts) or SPB-320 (320 watts) supervised audio power boosters. All models available in 115 VAC ir 220 VAC. Applications for the SP40S Multi-use applications The system can function as an evacuation system, an emergency messaging system, a paging system, an employee notification system and a background music system per NFPA 72 (2002), section 6.8.4 Combination Systems Fire code applications The system is listed under UL Standard 864, 9th edition delivering supervised audio and voice messaging with strobes and notification appliance circuits (NAC) for visual alerting Economic OSHA applications The system is OSHA 1910.165 compliant; this means that it does not require reliability inspections every two months, or the required spare parts inventory Wide ranging applications from small to large facilities Can connect to pagers for private alerting of emergency/ trouble conditions System Activation Contact closure message activation 2 Features Approvals & Compliance Approvals: UL Standard 864, 9th edition, UL Standard 1711, California State Fire Marshal (CSFM), New York City (MEA), FCC Part 15 OSHA 1910.165 and ADA Compliant 3 Year Warranty Made in the USA Background Music Capable of broadcasting from a supplied BGM source Unique supervision method allows for full system supervision even during background music (BGM) Line Level input for music source Frequency Response 100-15KHz General Paging Easily interfaces with most existing phone system page port, CO port and line level signals Automatically mutes BGM Frequency Response 275-6.5kHz Night ringer or security alert connection Voice Evacuation Complies to NFPA-72 requirements Supervised NAC speaker and strobe circuits Live microphone override 8 digitally pre-recorded voice messages Uses selectable pre-tones for messages Strobe Inputs and Activation 2 Amps of 24 VDC supervised strobe power with built-in Wheelock sync protocol. Power limited. Strobe output is selectable for control of Wheelock sync protocol or non-sync operation Strobe terminals have pass thru capability for Wheelock sync or non-sync operation Any of the 8 messages can be dip switch selected to activate strobes Microphone activation can be dip switch selected to activate strobes Auxiliary activation (Remote MIC) can be dip switch selected to activate strobes 24 VDC supervised and synchronized strobe power can be expanded to meet the requirements of the installation via Speaker Output 40 watts of supervised audio power Speaker outputs: 25V or 70.7V power limited
Audio Processing Volume and tone controls for general paging and BGM Connectability of optional speaker splitter modules Dual-tone tone generator with: 3 Tone and Slow Whoop for alerting of system trouble Night ringer/security alerting capability Audio power can be expanded by connecting to optional audio power boosters -SPB-80/4 80 Watt Supervised Audio Power Booster with 4 Amp of Synchronized Strobe Power -SPB-160 160 Watt Supervised Audio Power Booster -SPB-320 320 Watt Supervised Audio Power Booster Live & Pre-recorded Message Announcement Supplied with 8 pre-recorded emergency messages Capable of in-field recording of all messages via 1/8 line level audio input jack Preset audio levels for emergency messaging (prerecorded and live mic) - system reverts back to a pre set level regardless of the volume set for BGM or general paging On board Push-to-Talk Microphone Telephone paging input, disconnects BGM when in use Auxiliary input for Remote Microphone connection Benefits and Advantages of the Multi-Function SAFEPATH4 One System Multi-Function Facility Communications System Background Music (BGM) system, with patent pending supervision during BGM operation Supervised Emergency/Fire Voice Evacuation System Interfaces with telephone system for general paging requirements Built in power for visual notification appliances e.g., Strobes Expandable for larger system requirements (with optional equipment) Inputs Audio and Activation Priority Ordered Inputs Priority Level Type of Input On Board Microphone 1 Push to Talk (PTT) Microphone Auxiliary 2 Remote Microphone or Remote Microphone Expander Digital Message Input 1 3 Digital Message Input 2 4 Digital Message Input 3 5 Digital Message Input 4 6 Digital Message Input 5 7 Digital Message Input 6 8 Digital Message Input 7 9 Digital Message Input 8 10 Contact Closure activation Night Ringer Input 11 Contact Closure input Telephone Paging Input 12 Page port input Power Supply & Batteries 24 VDC, 33AH Max rechargeable battery back-up power circuitry built-in Batteries can be housed in the enclosure (Up to two (BAT-1212), 12 volt, 12 ampere hour batteries can fit in the enclosure. Actual battery size required will depend on speaker and/or strobe Installation/Maintenance Multiple trouble LED indicators for quick system diagnostics Fully supervised circuitry always in effect even during BGM and general paging (via patent pending technology) Removable quick connect/disconnect terminals for ease of wiring, accepts #12 to #22 AWG Power limited circuitry with Class B or Class A wiring. Class A only with use of Audio Splitter Surge protected circuitry Compatible Wheelock Products All Wheelock Speaker/Strobes All Wheelock Strobes All Wheelock Speakers All Cluster Speakers Wheelock Strobe Power Supply Background Music Input 13 Line Level Input, 600 ohm, input voltage must be less then 2.5 V peak to peak, or.3 volts RMS Audio/Technical Specifications Switch mode, Class D amplifier (40 Watts) Speaker Outputs Frequency Response Signal to Noise Ratio Dynamic Range 25V or 70.7V power limited Voice: 275 Hz 6.5 khz BGM: 100 Hz - 15 khz Meets UL Voice Evacuation Requirements of 800-2800 Hz better than 65 db better than 65 db Total Harmonic Distortion less than 2% Stand by Current Draw Alarm Current Draw 140 ma 4.7 amps Mechanical Dimensions Weight Finish Door Lock 3 21 H x 16 W x 6 D (wall mount) 36 lbs. (without batteries) Red or black exterior enclosure Wheelock Key-lock
Ordering Information Model Number Order SP40S 9929 Description Multi-Function Supervised Paging, Messaging, Background Music delivery and Emergency Voice Evacuation System with 24 VDC battery backup circuitry. Single channel system with 40 watts of supervised audio power and 2 amps of supervised 24 VDC synchronized strobe power and 8 standard messages. (batteries not included, 2 required) Red Enclosure SP40S-B 9935 Same as above but with black enclosure SP40SE 6138 Same as above but with 220 VAC input SP40SE-B 6139 Same as above but with 220 VAC input and black enclosure BAT-1212 7390 12 volt, 12-ampere hour battery SP40S-PMK 9936 SP40S 8 Message Programmed Message Kit AM-SP40S-SMK 9937 SP40S After Market 8 Message Standard Message Kit AM-SP40S-PMK 9938 SP40S After Market 8 Message Programmed Message Kit AM-SP40S-NBT 9939 SP40S After Market Narrow Band Signal Tone Kit SP-COA 9908 BATC-R 5414 Battery Cabinet, Red BATC-B 5413 Battery Cabinet, Black C.O. Port Adapter for the SP40S - Recommended 24 VDC Power Supply is Wheelock RPS-2406 (Order 3770) BAT-1224 7391 12 Volt, 24Ampere Battery Cell Message Capabilities Message and Priority # 1 2 Type of Message Fire (do not use elevators) Fire (do not use elevators) Voice Type Male Female 3 Fire Male 4 Emergency Female 5 Emergency Male 6 Weather Male 7 All Clear Male 8 Test Male Message Script Three (3) rounds of code 3 horn (followed by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators. Three (3) rounds of code 3 horn (followed by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Do not use the elevators. Three (3) rounds of code 3 horn (followed by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Three (3) rounds of code 3 horn (followed by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Three (3) rounds of code 3 horn (followed by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building and report to the designated assembly area for your group. Five (5) seconds of 1kHz tone (followed by): May I have your attention please! The National Weather Service has issued a severe weather warning for our area. Five (5) seconds of 1kHz tone (followed by): May I have your attention please! The building emergency has ended. An all clear has been given. Please resume normal activities. Five (5) seconds of 1kHz tone (followed by). May I have your attention please! This is a test of the Wheelock evacuation system, repeat, this is only a test. Each message can be selected to have a code 3 pre-alert tone, a 1kHz continuous pre-alert tone, or no pre-alert tone Post-tones are also selectable and match the pre-tones for individual messages Any of the 8 messages are field programmable to record your own custom message Each message length is 30 seconds A 1/8 line level audio input jack is supplied for message recording A two step recording procedure is required to ensure and verify that the standard message will be permanently erased Factory programmed messages are available for custom messages Contact customer service for additional information Form is required and can be downloaded from www.wheelockinc.com Note: For telephone (C.O. Port Adapter for the SP40S) may be used to connect the SP40S to an unused C.O. port or stand-alone telephone. Wheelock products must be used within their published specifications and must be PROPERLY specified, applied, installed, operated, maintained and operationally tested in accordance with their installation instructions at the time of installation and at least twice a year or more often and in accordance with local, state and federal codes, regulations and laws. Specification, application, installation, operation, maintenance and testing must be performed by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical (NEC), Occupational Safety and Health Administration (OSHA), local, state, county, province, district, federal and other applicable building and fire standards, guidelines, regulations, laws and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). 4
2-Zone Class A or 4-Zone Class B Speaker Audio Splitter SAFEPATH 4 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter For operation with SAFEPATH 4 Family of Products: SP40S, SP40/2, SPB-320, SPB-160, SPB-80/4 Description: Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2 or Audio Boosters. Enables a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Applications: Provides for expansion of one zone to up to 2 zones of supervised speaker audio output in Class A Provides for expansion of one zone to up to 4 zones of supervised speaker audio output in Class B Ordering Information: Model Order SP4Z-A/B 9900 SPMB4Z 9907 Description Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2 or Audio Boosters Mounting Bracket for the SP4Z-A/B is required when used with the Audio Boosters Note: The Speaker Splitter-Mounting Bracket (SPMB4Z) is required when the Speaker Splitter is used in Audio Boosters. The SPMB4Z can support two splitters. Features: Approvals: UL Standard 864, 9th edition, and California State Fire Marshal (CSFM), New York City (MEA) Expands one zone to up to 2 zones of supervised speaker audio output in Class A Expands one zone to up to 4 zones of supervised speaker audio output in Class B Each Class A zone can accept up to 40 watts of audio Each Class B zone can accept up to 40 watts of audio Operates on either 25V or 70.7V RMS Mounts inside the enclosure of the SP40S, SP40/2 or Audio Boosters Power and Trouble LED s Individual zone short and open LED indication Capable of detecting wiring faults Removable wiring terminals for quick connect/ disconnect accepting 12 22 AWG All output circuitry is Power Limited Space provided to allow for naming of the zones Powered by 24VDC, supplied by the either the SP40S, SP40/2 or Audio Boosters Standby and Alarm current at 24VDC is 15mA 5
SAFEPATH 4 Audio Boosters SPB-320 SPB-160 320 Watt Supervised Audio Power Booster (Four 80 watt circuits) 160 Watt Supervised Audio Power Booster (Two 80 watt circuits) SPB-320 SPB-80/4 SPB-160 SPB-80/4 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronizable Strobe Power (Two 2 Amp circuits) Description Supervised Facility Communication and Emergency Voice Evacuation Audio and Audio/Strobe Power Boosters, UL Standard 1711 and UL Standard 864, 9th edition with 24VDC battery backup capabilities. Designed to provide for additional supervised audio power for live voice, prerecorded messages or background music (BGM). Fully supervised patent pending circuitry is always in effect even during BGM. The SPB-80/4 also provides 4 Amps of 24 VDC Supervised and Synchronized Strobe Power. The SPB-320, SPB-160 and the SPB-80/4 easily connects to the Wheelock SP40S or SP40/2. Multiple SPB-320, SPB- 160 and SPB-80/4 Audio Boosters can be inter-connected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements. The SPB-320 draws 2.4 watts of audio input power to properly operate and provide additional supervised audio output power. The SPB-160 and the SPB-80/4 draws 1.2 watts of audio input power to properly operate and provide additional supervised audio output power. A maximum of 5,280 watts of supervised audio power can be achieved. Additional strobe power can be obtained via a combination of SPB-80/4 or Wheelock Power Supplies/Chargers. Applications Provides for additional supervised audio power for large installations Provides for additional supervised and synchronizable strobe power for large installations Can be used in new construction as well as in retrofit construction Features Approvals & Compliance Approvals: UL Standard 864, 9th edition, UL Standard 1711, California State Fire Marshal (CSFM), New York City (MEA) OSHA 1910.165, ADA and UFC compliant 3 year warranty System Activation: Audio 70V or 25V input from the SP40S or SP40/2 1 Volt input from SP4-RMX System Activation: Strobe (SPB-80/4) Power Supply & Batteries Fully supervised patent pending circuitry always in effect even during BGM Power limited circuitry Class D amplifiers Internal battery charger and power supply Required batteries fit inside the enclosure (sold separately) SPB-320 requires four 12 VDC, 12 AH batteries SPB-160 and SPB-80/4 require two 12 VDC, 12 AH batteries Outputs: SPB-320 has four 80 watt speaker output circuits SPB-160 has two 80 watt speaker output circuits SPB-80/4 has one 80 watt speaker output circuit and two 2 amp strobe circuits (4 amps total) Supervised Audio Speaker outputs: 70V or 25V field selectable (all boosters must be either 70 V or 25 V) Expansion output (supervised, 24VDC at.5a in alarm condition) used for connecting multiple boosters DC output (unsupervised for optional splitter power). Each speaker circuit (four for the SPB-320, two for the SPB-160, one for the SPB-80/4) can connect to speaker splitters 6
SPB-80/4 Strobe Features: Two 24VDC 2 Amps, NAC supervised, synchronizable, power limited, Class B strobe outputs Selectable outputs; Wheelock sync, pass through, or constant DC Trouble LED s for open and short output conditions Alarm indicator: LED s for Strobe and Expansion Outputs Inputs: Audio Speaker Inputs: 70V or 25V, field selectable Auxiliary in (for alarm input signal) Mechanical: SPB-160, SPB-80/4 Dimensions: 21 H x 16 W x 6 D (wall mount) Weight: 36 lbs. (without batteries) Finish: Red exterior enclosure Door Lock: Wheelock key-lock SPB-320 Dimensions: 36 H x 24 W x 6 D (wall mount) Weight: 80 lbs. (without batteries) Finish: Red or black exterior enclosure Door Lock: Wheelock key-lock Technical Specifications: 120VAC, 3.8A, 60 Hz input SP40SE Models 240 VAC, 2.5A, 50-60 Hz Standby current draw: 120mA, per amplifier board Alarm current draw: 9 Amps, per amplifier board SPB-80/4 and SPB-160 have one amplifier board SPB-320 has two amplifier boards System Frequency Response: Voice 400 Hz - 6.5 khz BGM 275 Hz - 15 khz Removable quick connect/disconnect terminals, accept 12-22 AWG Multiple LED s for easy indication of system diagnostic conditions Signal to Noise Ratio: > 70 db Dynamic Range: > 65 db Total Harmonic Distortion: 2% Note: The Speaker Splitter-Mounting Bracket (SPMB4Z) is required when the Speaker Splitter is used in Audio Boosters. The SPMB4Z can support two splitters. Ordering Information Model Order Description SPB-320 9918 320 Watt Supervised Audio Power Booster (Four 80 watt circuits) SPB-320E 6336 320 Watt Supervised Audio Power Booster (Four 80 watt circuits), 220 VAC input SPB-320E-B 6353 320 Watt Supervised Audio Power Booster (Four 80 watt circuits), 220 VAC input, black enclosure SPB-160 8989 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), red enclosure SPB-160-B 9930 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), black enclosure SPB-160E 6149 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), 220 VAC input SPB-160E-B 6150 SPB-80/4 8988 SPB-80/4-B 9931 SPB-80/4E 6147 SPB-80/4E-B 6148 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), 220 VAC input, black enclosure 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), red enclosure 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), black enclosure 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), 220 VAC input 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), 220 VAC input, black enclosure SPMB4Z 9907 Speaker Splitter Mounting Bracket for SPB-320, SPB-160 or SPB-80/4 7
BGM DV FACP MPS NPS Wheelock SP40S SPB-80/4 SPB-160 SPB-320 SPRM SP4-RMX SP4-TZC SP4-APS SP4Z-A/B SP4-SVC Legend: Background Music Digital Voice Message Expander Fire Alarm Control Panel Pull Station Push Station Strobe Power Supplies Supervised Multi-Function Communication System 80 Watt Audio Booster & 4 Amps of Strobe Power 160 Watt Audio Booster 320 Watt Audio Booster Remote Microphone Remote Microphone Expansion Module Telephone Zone Controller Addressable Paging Splitter Speaker Splitter Supervised Volume Control BGM SP4- TZC Telephone Strobe Speaker Speaker Strobe Cluster Speaker S V Volume Control NPS SP4-APS MPS SP40S FACP SP4- RMX SP4-3MEM DV SPRM SPRM SPRM T his drawing is for illustrative purposes only 8
SP4-APS SPB-160 SP4Z-A/B V Wheelock Strobe Power Supply Wheelock Strobe Power Supply SPB-320 SPB-320 SP4-APS SP4-APS SP4-APS SP4-APS SP4-APS SP4Z-A/B SP4Z-A/B SP4-APS V SP4-APS SPB-160 SP4-APS SPB-160 SP4-APS SP4-APS SPB-80/4 V SP4-APS 9
SP4-APS SP4-TZC Addressable Paging Splitter Telephone Zone Controller SAFEPATH 4 Addressable Paging Splitter and Telephone Zone Controller Applications: Connects to the SP40S or SP40/2 to control selectable paging and background music (BGM) Ability to access individual or multiple speaker zones throughout the SP40S or SP40/2 system via the telephone Features: Allows selections of speaker zones via a telephone keypad (DTMF tones) One SP4-TZC (controller) can control up to 17 SP4-APS (splitters) Telephone page input connects to stand alone telephone, unused CO port, page port USB connection for logical zone grouping and BGM programming (supports Windows 2000 and Windows XP) Up to 9 logical zones, (a logical zone is a user selected group of up to 5 zones, individual or fixed) RS-485 digital control to the SP4-APS speaker splitters Connects to the SP40S or SP40/2 via the BGM input The combination of 1 SP4-TZC (controller) and up to 17 SP4-APS (splitters) can provide: Class B 4 zones per splitter Up to 68 individual zones (17 splitters) 17 fixed zones (groups of 4) 9 logical zones Class A 2 zones per splitter Up to 34 individual zones (17 splitters) 17 fixed zones (groups of 2) 9 logical zones SP4-TZC Telephone Zone Controller: Connects to the SP40S or SP40/2 Auto programmable Custom user programmable (for logical zones) All call or selected zone(s) telephone paging Background music (BGM) zone(s) selectable Telephone input and background music (BGM) input Enclosure for the SP4-TZC (controller): Dimensions: 13 H x 7.6 W x 2.15 D Color: Black Wall mountable Requires 24 VDC, model RPS-2406 SP4-APS Addressable Paging Splitter: Addressable speaker zone splitter Mounts inside the SP40S, SP40/2, SPB-80/4, SPB-160 or SPB-320 Operates on 24 VDC, supplied by the SP40S, SP40/2, SPB-80/4, SPB-160, SPB-320 Handles 40 watts of supervised audio per zone UL Standard 864, 9th edition listed Ordering Information: Model Order Description SP4Z-APS 9920 Addressable Paging Splitter SP4-TZC 9921 Telephone Zone Controller TZC-USB 9923 SP4-TZC Programming Cable 10
SAFEPATH 4 Supervised Volume Control SAFEPATH 4 Remote Microphone SP-SVC Supervised Volume Control Applications: Allows manual volume setting for telephone paging and background music for a specific speaker or speaker zone The selected adjustment will not affect the volume setting of emergency prerecorded messages or live microphone usage Features: Supervised volume control for use with UL Listed Life Safety Applications Can handle up to 35 watts of 70.7 volt audio power input Adjustment settings: 0 10, in 3dB increments Operates in Class B or Class A wiring (for Class A, the SP4-APS is required) Requires a double gang, 3½ deep back box or 4 square and 1-1/2 deep box with a 1-1/2 extension ring Stainless steel mounting plate with a black knob UL Standard 864 and California State Fire Marshal (CSFM) listed for use with the SP40S, SP40/2 or SPB Audio Boosters OSHA 1910.165 and ADA compliant Maximum RMS current 10.0mA Ordering Information: Model Order SP-SVC 9926 Description Supervised Volume Control for use with the SAFEPATH 4 system Description: Remote Microphone for use with the SAFEPATH 4 Facility Communications System - SP40S, SP40/2 or SP4-RMX Applications: Provides for an additional microphone in a remote location Can be mounted up to 2,000 feet away from the SP40S or SP40/2 Features: Approvals: UL Standard 864, 9th edition and California State Fire Marshal (CSFM) Supervised hand held push to talk microphone Key required to enable remote microphone use Individual front panel LED indication for; System Normal, System Trouble and Alarm When used with the SP40S or SP40/2, the priority level is 2, the SP40S or SP40/2 on board microphone is always priority 1 Remote microphone usage disengages background music and general paging Voice frequency response: 275 Hz - 6.5 khz Requires 24VDC, supplied by the SP40S, Audio Boosters, or SP4-RMX Input current: Standby: 26mA Alarm: 38mA Audio output level: 1.05V RMS 6 wire connection to the SP40S, SP40/2 or SP4-RMX Mounting plate is red and measures, 8 3/4 x 5 ¼, fits into a 4 gang back box All output circuitry is Power Limited 11 Ordering Information: Model Order SPRM 8996 SPRM-GP 9927 Description Remote Microphone for use with the SP40S, SP40/2, SPB-320, SPB-160, SPB-80/4 or SP4-RMX, red plate General Paging Microphone for use with the SPB-320, SPB-160, or SPB-80/4, black plate
SP4-RMX Remote Microphone Expansion Module SAFEPATH 4 Remote Microphone Expansion Module Applications: Expands one remote microphone (SPRM) from the SP40S or SP40/2 to three remote microphones Two SP4-RMX modules can be cascaded together to provide up to six remote microphones from the SP40S or SP40/2 Provides for an auxiliary input for connection of an external VoiceLink message repeater for additional messages Ordering Information: Model Order SP4-RMX 9919 Description Remote Microphone Expansion Module Microphone and message priority levels when the SP4-RMX is used with the SP40S or SP40/2: Features: Priority Level Device Microphones 1 SP40 on board microphone 2 SP4-RMX, remote microphones #1, 2, 3 (set priority or First In First Out) 3 SP4-RMX, auxiliary input only SP40S Standard Messages 4 SP40S message 1 5 SP40S message 2 6 SP40S message 3 7 SP40S message 4 8 SP40S message 5 9 SP40S message 6 10 SP40S message 7 11 SP40S message 8 Wall mountable The SP4-RMX will provide the capability of connecting up to (3) three Remote Microphone Stations (SPRM) When connected to the SP40S or SP40/2, two SP4- RMX units can be cascaded together to provide up to six remote microphones Provides for an auxiliary input for connection of an external message repeater, for additional messages Can accept a line level input for broadcasting of other information When the SP4-RMX is connected to the SP40S or SP40/2, the entire system benefits from the additional microphone capability Can be connected to Audio Boosters for general (nonalarm) paging with use of SPRM-GP UL Standard 864 listed OSHA 1910.165, ADA and UFC compliant Multiple on board diagnostics with 3 status conditions: standby, alarm, and trouble Operates on 24 VDC, supplied by the SP40S, SP40/2, SPB-80/4, SPB-160, SPB-320 The SP4-RMX is an external module Enclosure dimensions: 13 H x 7.6 W x 2.15 D Color: Black 12
Ordering Information Model Number Order Description SP40S 9929 Multi-Function Supervised Paging, Messaging, Background Music and Emergency Voice Evacuation System with 24 VDC battery backup circuitry. Single channel system with 40 watts of supervised audio power and 2 amps of supervised 24 VDC synchronized strobe power and 8 standard messages. (batteries not included, 2 required) Red enclosure SP40S-B 9935 Same as above but with black enclosure SP40S-PMK 9936 SP40S 8 Message Programmed Message Kit AM-SP40S-SMK 9937 SP40S After Market 8 Message Standard Message Kit AM-SP40S-PMK 9938 SP40S After Market 8 Message Programmed Message Kit AM-SP40S-NBT 9939 Sp40S After Market Narrow Band Signal Tone Kit SP-COA SP4Z-A/B 9908 C.O. Port Adapter for the SP40S or SP40/2 - Recommended 24 VDC Power Supply is Wheelock RPS- 2406 (Order 3770) 9900 Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2 or Audio Boosters SPMB4Z 9907 Mounting Bracket for the SP4Z-A/B is required when used with the Audio Boosters SPB-320 9918 320 Watt Supervised Audio Power Booster (Four 80 watt circuits) SPB-160 8989 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), red enclosure SPB-160-B 9930 160 Watt Supervised Audio Power Booster (Two 80 watt circuits), black enclosure SPB-80/4 SPB-80/4-B 8988 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), red enclosure 9931 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits), black enclosure SP4Z-A/B 9900 Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40S, SP40/2, SPB-320, SPB-160 or SPB-80/4 SPMB4Z 9907 Speaker Splitter Mounting Bracket for SPB-320, SPB-160 or SPB-80/4 SP4Z-APS 9920 Addressable Paging Splitter SP4-TZC 9921 Telephone Zone Controller TZC-USB 9923 SP4-TZC Programming Cable SP-SVC 9926 Supervised Volume Control for use with the SAFEPATH 4 System SPRM 8996 Remote Microphone for use with the SP40S, SP40/2, SPB-320, SPB-160, SPB-80/4 or SP4-RMX, red plate SPRM-GP 9927 General Paging Microphone for use with the SPB-320, SPB-160 or SPB-80/4, black plate BATC-R 5414 Battery Cabinet, Red BATC-B 5413 Battery Cabinet, Black BAT-1212 7390 12 Volt, 12 Ampere Battery Cell BAT-1224 7391 12 Volt, 24Ampere Battery Cell BAT-1265 7392 12 Volt, 65 Ampere Battery Cell 13
Architects and Engineers Specifications SP40S Facility Communications System The system shall be a multi-purpose NFPA compliant, supervised, general-purpose audio, and fire/emergency evacuation system. The system shall be a single channel voice evacuation system incorporating supervision during the broadcasting of background music and general paging. The system shall be capable of delivering 40 watts of supervised audio power and 2 amps of supervised 24 VDC synchronized strobe power. Minimum supervised audio power shall be 40 watts, expandable to 5280 watts, depending on system configuration and with additional modules and power boosters. Supervised 24 VDC synchronized strobe power shall be 2 amps, expandable to the requirements of the installation. The system shall be capable of operating from a 120 VAC power source. E models shall be capable of operating from a 240 VAC power source. All models shall have a 24 VDC battery backup. Standard on-board system features shall include: digital voice messaging, a hand-held push-to-talk microphone with override priority, and a power supply/battery charger. The system shall be capable of interfacing with telephone systems for general paging announcements and will have night ringer capabilities. Form C contacts shall be provided for system alarm and trouble conditions. The system shall have 8 message contacts with contact closure activation. Background music input voltage shall be capable of handling less then 2.5 V peak to peak or less then.3 volts. The system shall have thirteen priority ordered inputs, including: On Board Microphone, Auxiliary Input (Line Level), 8 Digital Messages, Night Ringer Input, Telephone Paging Input, and Background Music Input. The system shall have preset audio levels for emergency messaging (prerecorded and live mic). The system shall revert back to a preset level regardless of the volume set for background music (BGM) or general paging. Background music inputs can be an AM/FM tuner, cassette, CD, MP3, or any other remote source. The system shall be supplied with 8 pre-recorded messages and be capable of in-field recording of customer unique messages. The system shall have a dual-tone tone generator with -3 Tone and Slow Whoop. When the system is on battery power, telephone page, night ring and background music shall be disengaged. The panel shall have power-limited circuitry with an internal battery charger and power supply. The power supply/charger section shall be able to charge 24 VDC batteries with a maximum capacity of 33 amp hours. Up to two 12 VDC, 12 AH batteries may be housed in the enclosure. Batteries larger than 12 Ah shall be housed in a separate enclosure such as the Cooper Wheelock BATC or equivalent. Batteris shall be supplied separately. The system shall have power limited circuitry and class B wiring. Wiring terminal blocks will be removable and accept #22 - #12 AWG wire. Audio output voltage shall be selectable for 25V or 70.7V. The voice (live microphone or recorded message) frequency response shall be 275 Hz 6.5 khz, background music frequency response shall be 100 Hz - 15 khz. Stand by current draw shall be 140mA. Alarm current draw shall be 4.7 amps. The signal to noise ratio shall be better than 65 db, dynamic range shall be better than 65 db, total harmonic distortion shall be less than 2%. The system shall be wall mountable, enclosed in a steel locking enclosure. The required batteries for 40-watt systems shall fit inside the enclosure. The 40 watt system shall weigh no more than 36 lbs (without batteries) and its dimensions shall not exceed 21 H x 16 W x 6 D. The system shall be made in the USA. Approvals for the system shall include: UL Standard 864, 9th edition, UL Standard 1711, FCC part 15, California State Fire Marshal (CSFM) and New York City (MEA). The system shall be OSHA 1910.165 and ADA compliant. 3 Year Warranty. SAFEPATH 4 Audio Boosters The Wheelock SPB-320, SPB-160 and SPB-80/4 Audio Boosters shall be NFPA compliant supervised audio and supervised 24VDC synchronized strobe power boosters (some models will have supervised 24VDC synchronized strobe booster capability). The booster shall have 24VDC battery backup capabilities. The booster shall have the capability to supervise the circuitry during playback of background music. The booster shall have the capability to be inter-connected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements. Three versions of the booster shall be made available: SPB-80/4, (80 watts of supervised audio power and 4 amps of supervised and synchronized strobe power), SPB-160 (160 watts of supervised audio) or SPB-320 (320 watts of supervised audio). Each booster shall use 1.2 watts of audio input power (The SPB-320 requires 2.4 watts of audio power) to properly operate and provide additional supervised audio output power. A combination of boosters can be added together to provide for a maximum of 5,280 watts of supervised audio power. Additional strobe power can be obtained via a combination of boosters. The audio section of the booster shall be connected via a selectable 70V or 25V input from the Wheelock SP40S. The strobe section of the booster shall be divided into two sections each supplying two Amps of 24VDC, NAC, supervised, synchronizable, power limited, Class B strobe outputs, with selectable outputs offering Wheelock sync, pass through, or constant DC and can be activated via 8-33VDC NAC input or contact closure. The internal battery charger/power supply shall be capable of charging 24 VDC batteries with a maximum capacity of 33 amp hours. The enclosure shall be capable of housing the correct number of 12 VDC rechargeable batteries (SPB-80/4 (2), SPB-160 (2), SPB-320 (4)) with a maximum capacity of 12 Amp hours. Batteries with a larger capacity require an external battery enclosure(s) such as the Cooper Wheelock BATC or equivalent. The boosters shall have power-limited circuitry and be a class D amplifier with an internal battery charger and power supply. The required batteries (purchased separately) shall fit inside the enclosure (two 12VDC, 12 AH for the SPB-80/4 or SPB-160 and four 12 VDC, 12 AH for the SPB-320). The booster shall operate on 120VAC, 3.8A, 50 60 Hz input. E model boosters shall operate on 240 VAC, 2.5A, 50 60 Hz input. The SPB-80/4 or SPB-160 standby current draw shall be 120mA and alarm current draw shall be 9 Amps. The SPB-320 consists of two SPB-160 s. Each SPB-160 shall have its own power supply and battery charger. The voice frequency response shall be 400 Hz 6.5 khz +/- 3 db, the BGM frequency response shall be 275 Hz - 15 khz +/- 3 db. Removable quick connect/disconnect terminals that accept 12-22 AWG shall be used. Multiple LED s for easy indication of system diagnostic conditions shall be present on the PC board. The Signal to Noise Ratio shall be > 70 db, the dynamic range shall be > 65 db, the Total Harmonic Distortion spec shall be 2%. The booster shall be wall mountable, enclosed in a steel locking enclosure, with a red finish. The booster shall be made in the USA. Approvals for the booster shall include; UL Standard 864, 9th edition, UL Standard 1711, CSFM and MEA. The booster shall be OSHA 1910.165 and ADA compliant. The booster shall carry a 3 year warranty. 14
Architects and Engineers Specifications 4 Zone Class B Speaker Splitter The Wheelock SP4Z-A/B shall be UL Standard 864, 9th edition, California State Fire Marshal (CSFM) and New York City (MEA) approved, 2-Zone Class A or 4-Zone Class B Speaker Splitter for operation with the Wheelock, SP40S, SP40/2, SPB-80/4, SPB- 160 and SPB-320. The SP4Z-A/B shall enable a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Each Class A zone shall be capable of accepting up to 40 watts and operate on either 25 or 70.7V RMS of audio input. Each Class B zone shall be capable of accepting up to 40 watts of audio and operate on either 25 or 70.7V RMS of audio input. The SP4Z-A/B shall be capable of supporting live microphone paging, prerecorded emergency voice evacuation messages, supervised background music and general paging announcements. The SP4Z-A/B shall mount inside the enclosure of the SP40S, SP40/2, SPB-80/4, SPB-160 and SPB-320 and shall have power and trouble LED s with individual zone short and open LED indication. The SP4Z-A/B shall be capable of detecting wiring faults. The SP4Z-A/B shall be powered by 24VDC, which is to be supplied by the SP40S, SP40/2, SPB-80/4, SPB-160 or SPB-320. Standby and Alarm current at 24VDC shall be 15mA. Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Space shall be provided to allow for naming of the zones. Addressable Paging Splitter and Telephone Zone Controller The Wheelock Addressable Paging Splitter (SP4-APS) and Telephone Zone Controller (SP4-TZC) shall be used to control and direct telephone paging and background music zones connected to the SAFEPATH4 Multi-Function Facility Communication System using an RS485 connection. The Addressable Paging Splitter (SP4-APS) shall be UL Standard 864, 9th edition and California State Fire Marshal (CSFM) approved, addressable and supervised 2-zone Class A or 4-zone Class B Speaker splitter. The SP4-APS shall be used with Wheelock s SP40S or SP40/2 panel and the Audio Booster (SPB-160, SPB-80/4, and SPB-320) panels. Each SP4-APS shall have a single audio input capable of 25 Vrms or 70.7 Vrms at a maximum of 80 Watts. The input audio power shall be distributed to the zone connections with the total not exceeding the input and no zone exceeding 40 Watts. When audio boosters are connected, each audio booster module shall consume 1.2 Watts from the total input power of the SP4-APS. The splitter shall be mounted inside the SP40S, SP40/2 or Audio Booster that it is associated with, and it shall operate on 24VDC supplied by the supported module. The SP4-APS shall contain 16 LED indicators used to monitor and troubleshoot the module. The Telephone Zone Controller Module (SP4-TZC) shall be used to address the output zones on the SP4-APS. The SP4-TZC shall be capable of supporting 17 SP4-APS speaker splitter modules and shall be capable of addressing all zones at once ( All Call ), a maximum of 68 separate zones, 17 fixed zone groups and 9 programmed logical zone groups. This shall be accomplished using two digit DTMF tones from a page port, an unused CO port, or a stand alone telephone with a loop start circuit. Also, the SP4- TZC shall be able to select zones for background music. The SP4-TZC has the following inputs: Power, USB port, Background Music (BGM), Page Audio in. The outputs are: Audio out and RS485 Digital Control. The basic operating parameters of the SP4- APS shall be pre-programmed. Customized programming shall be accomplished using a USB cable and programming computer software. The SP4-TZC shall be powered using a 24VDC filtered and regulated power supply such as the Wheelock RPS-2406. The Controller Module assembly is mounted in a metal enclosure measuring 13 L x 7 5/8 W x 2 D. Supervised Volume Control The Wheelock SP-SVC shall be UL Standard 864, 9th edition approved, supervised volume control for use with the SAPEPATH 4 Facility Communications System. The SP-SVC shall provide for manual volume setting for telephone paging and background music for a specific speaker or speaker zone. The selected adjustment will not affect the volume setting of emergency prerecorded messages or live microphone usage. The SP-SVC shall be capable of handling up to 35 watts of audio power @ 70.7 volts or 4 watts audio power @ 25 volts and shall operate on either 70.7 or 25 volt input from an SP40S or Audio Booster. The SP-SVC shall be capable of operating in Class B or Class A wiring configurations (for Class A, the SP4-APS is required). The SP-SVC shall receive operating power from an Audio Booster, SP40S or SP40/2. Volume adjustment settings shall be off, 1 10, in 3dB increments. The SP-SVC shall be supplied with a stainless steel mounting plate with a black knob and require a double gang, 3½ deep back box for mounting. Remote Microphone The Wheelock SPRM shall be UL Standard 864, 9th edition and California State Fire Marshal (CSFM) approved, Remote Microphone for use with the SAPEPATH 4 Facility Communications System. The SPRM shall be a supervised hand held push to talk microphone and a key shall be required to enable remote microphone use. (Same key as SP40S or SP40/2) Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Individual front panel LED s shall be provided for indication of System Normal, System Trouble and Alarm. Multiple on board diagnostic LED s shall be provided. When used with the SP40S or SP40/2, the priority level shall be number two. Remote microphone usage shall disengage background music and general paging. Voice frequency response shall be 275 Hz - 6.5 khz +/- 2.4 db. Power requirements shall be 24VDC and will be supplied by the SP40S or SP40/2. Input current for Standby shall be 26mA and for Alarm 38mA. Audio output level shall be 1.05V RMA. There shall be a 6-wire connection to the SP40S or SP40/2. The mounting plate shall be red and measure, 8 3/4 x 5 ¼, and shall fit into a 4 gang back box. 15
Remote Microphone Expansion Module The Wheelock SP4-RMX Remote Microphone Expansion Module shall be UL Standard 864, 9th edition and California State Fire Marshal (CSFM) approved for use with the SAPEPATH 4 SP40S Facility Communications System. The SP4-RMX shall be a supervised outboard expansion module for use with the SAPEPATH 4 system. It shall be used to expand the number of optional supervised Remote Microphone (SPRM) modules up to three. Two SP4-RMX Remote Microphone Expansion Modules can be connected to the SP40S or SP40/2 and shall have the capability of providing the SP40S or SP40/2 with up to six system wide All Call Remote Microphone (SPRM) modules*. The SP4-RMX can be programmed to provide either priority override for each SPRM module input or First In First Out. First In First Out allows the active SPRM to complete its communication before another SPRM can be used. All output circuitry shall be power limited. Multiple on board diagnostic LED indicators shall be provided. All wiring shall be connected to the module using quick connect/disconnect wiring terminals, capable of accepting 12 22 AWG wiring. The SP4-RMX PCB assembly is mounted in a metal enclosure measuring 13 L x 7 5/8 W x 2 D. The SP4-RMX can support each SPRM at a range up to 2000 feet. *The SP4-RMX can also be connected to Audio Booster for general (non-alarm) paging with use of SPRM-GP. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Note: Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com 16 WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA V2003-S 07/06
Series NPS Push Stations Description: Multipurpose push stations for manual activation of SAFEPATH and SAFEPATH 4 Voice Evacuation Systems prerecorded messages. Can be used to manually activate a message in the event of an emergency or for alerting. Applications: For use with and SAFEPATH 4 Multifunction Facility Communications System Manual activation of messages in the event of an emergency Manual activation of messages to alert or warn others Features: UL 2017 Listed switch assembly Available in five colors: Red, Green, Yellow, White, or Blue Custom wording available Polycarbonate faceplate Stainless steel backplate ADA Compliant Mounts to single gang electrical box Interchangeable or replaceable Normally Open (NO) and Normally Closed (NC) Single Pole, Single Throw gold plated contact blocks rated for 3 amps @ 600 VAC or 1 amp @ 250 VDC Can be reset by depressing the Push button, and turning clockwise a ¼ turn Comes with one (NO) contact and one (NC) contact Measurements: 5 H x 3¼ W x 1½ D U L
Architects and Engineers Specifications Push stations shall be designed for manual activation of SAFEPATH 4 Voice Evacuation Facility Communications System prerecorded messages. The faceplate shall be constructed of polycarbonate. The backplate shall be stainless steel. The switch assembly shall be a UL Standard 2017 listed Normally Open (NO) and Normally Closed (NC) Single Pole, Single Throw gold plated contact blocks rated for 3 amps @ 600 VAC or 1 amp @ 250 VDC. The push stations shall be ADA compliant. The push stations shall mount to a single gang electrical box. The push station shall be capable of being reset by depressing the Push button, and turning clockwise a ¼ turn. The push stations shall be available in five colors: red, green, yellow, white or blue. Custom word printing on the top of the push station shall be available. Ordering Information Model Number Wording Matrix for top of the Push Station Any wording suffix can be printed on any color push station. Examples: Order Color NPS-R 9767 Red NPS-G 9768 Green NPS-Y 9769 Yellow NPS-W 9770 White NPS-B 9771 Blue NPS-NO 0523 NPS-NC 0524 Description Push Station for manual message activation Push Station Normally Open Contact Push Station Normally Closed Contact 9767-003 NPS-R-003 Red Push Station, Colors 9771-010 NPS-B-010 Blue Push Station, Low Note: Custom wording is available, please contact customer service. Wording Model Suffix Land Attack -001 Sea Attack -002 Colors -003 Low Threat -004 Medium Threat -005 High Threat -006 Small Craft -007 Unknown Object -008 Bravo -009 Low -010 Medium -011 High -012 Water Attack -013 Chemical Spill -014 Gas Release -015 Evacuation -016 Help -017 Assistance -018 Severe Weather -019 Tornado -020 Medical Alert -021 Power Shut Down -022 Blank / No Wording -023 Strobe -024 Alert -025 Wording Model Suffix Emergencia -026 Alarm Yellow -027 Delta -028 Alarm Red -029 Withdrawel -030 Emergency -031 Audio Test -032 All Clear -033 Fire Test -034 Evac Drill -035 Weather -036 Chem-Bio -037 Suspicious -038 Fire* -039 All -040 Bomb -041 Test -042 Area -043 Bomb Threat -044 Terrorist Threat -045 Toxic Chemical -046 Disaster -047 *For non UL Life Safety Applications 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA V2004 NPS 06/06
2-Zone Class A or 4-Zone Class B Speaker Splitter SAFEPATH 4 Expansion Modules 2-Zone Class A or 4-Zone Class B Speaker Splitter and Remote Microphone For operation with SAFEPATH 4 Family of Products: SP40/2, SPB-80/4, & SPB-160 Description: Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2, SPB-80/4 or SPB-160. Enables a single supervised speaker audio output to drive up to two class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Applications: Provides for expansion of one zone to up to 2 zones of supervised speaker audio output in Class A Provides for expansion of one zone to up to 4 zones of supervised speaker audio output in Class B Ordering Information: Model Order SP4Z-A/B 9900 SPMB4Z 9907 Description Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2, SPB-80/4, or SPB-160 Mounting Bracket for the SP4Z-A/B when used with the SPB-80/4 or the SPB-160 Note: The SP4Z-A/B mounts inside the SP40/2 (a mounting bracket is not required). When mounting inside the SPB-80/4 or SPB-160, the additional mounting bracket, SPMB4Z is required and is sold separately. Architects and Engineers Specifications: Features: Approvals: UL Standard 864 listed, California State Fire Marshal (CSFM) Expands one zone to up to 2 zones of supervised speaker audio output in Class A Expands one zone to up to 4 zones of supervised speaker audio output in Class B Each Class A zone can accept up to 40 watts of audio Each Class B zone can accept up to 20 watts of audio Operates on either 25 volts or 70.7 volts RMS Mounts inside the enclosure of either the SP40/2, SPB-80/4 or SPB-160 Power and Trouble LED s Individual zone short and open LED indication Capable of detecting wiring faults Removable wiring terminals for quick connect/ disconnect accepting 12 22 AWG All output circuitry is Power Limited Space provided to allow for naming of the zones Powered by 24VDC, supplied by the either the SP40/2, SPB-80/4 or SPB-160 Standby/Alarm current at 24VDC is 15mA The Wheelock, SP4Z-A/B shall be a UL Standard 864 Listed and California State Fire Marshal (CSFM) approved, 2-Zone Class A or 4-Zone Class B Speaker Splitter for operation with the Wheelock, SP40/2 or SPB-80/4 or SPB-160. The SP4Z-A/B shall enable a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Each Class A zone shall be capable of accepting up to 40 watts and operate on either 25 or 70.7 volts RMS of audio input. Each Class B zone shall be capable of accepting up to 20 watts of audio and operate on either 25 or 70.7 volts RMS of audio input. The SP4Z-A/B shall be capable of supporting live microphone paging, prerecorded emergency voice evacuation messages, supervised background music and general paging announcements. The SP4Z-A/B shall mount inside the enclosure of the SP40/2, SPB-80/4 or SPB-160, and shall have power and trouble LED s with individual zone short and open LED indication. The SP4Z-A/B shall be capable of detecting wiring faults. The SP4Z-A/B shall be powered by 24VDC, which is to be supplied by the SP40/2, SPB-80/4 or SPB-160. Standby/Alarm current at 24VDC shall be15ma. Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Space shall be provided to allow for naming of the zones. Refer to products installation Instructions for proper installation, wiring procedures and any additional specifications. Copyright 2003 Wheelock, Inc. All rights reserved.
SAFEPATH 4 Expansion Modules Remote Microphone Description: Remote Microphone for use with the SAFEPATH 4 SP40/2 Facility Communications System Applications: Provides for an additional microphone in a remote location Can be mounted up to 2,000 feet away from the SP40/2 Ordering Information: Model Order SPRM 8996 Description Remote Microphone for use with the SP40/2 NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Refer to products installation Instructions for proper installation, wiring procedures and any additional specifications. Architects and Engineers Specifications: Features: Approvals: UL Standard 864 listed and California State Fire Marshal (CSFM) Supervised hand held push to talk microphone Key required to enable remote microphone use (same key as SP40/2) Removable wiring terminals for quick connect/disconnect accepting 12-22 AWG Individual front panel LED indication for System Normal, System Trouble, Alarm Multiple on board diagnostic LED s When used with the SP40/2, the priority level is 2, the SP40/2 on board microphone is priority 1 Remote microphone usage disengages background music and general paging Voice frequency response: 275 Hz - 6.5 khz +/- 2.4 db Requires by 24VDC, supplied by the SP40/2 Input current: Standby: 26mA Alarm: 38mA Audio output level: 1.05V RMA 6 wire connection to the SP40/2 Mounting plate is red and measures, 8 3/4" x 5 ¼, fits into a 4 gang back box All output circuitry is Power Limited The Wheelock, SPRM shall be a UL Standard 864 listed and California State Fire Marshal (CSFM) approved, Remote Microphone for use with the SAFEPATH4 SP40/2 Facility Communications System. The SPRM shall be a supervised hand held push to talk microphone and a key shall be required to enable remote microphone use. (Same key as SP40/2) Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Individual front panel LED s shall be provided for indication of System Normal, System Trouble and Alarm. Multiple on board diagnostic LED s shall be provided. When used with the SP40/2, the priority level shall be number two. Remote microphone usage shall disengage background music and general paging. Voice frequency response shall be 275 Hz - -6.5 khz +/- 2.4 db. Power requirements shall be 24VDC and will be supplied by the SP40/2. Input current for Standby shall be 26mA and for Alarm 38mA. Audio output level shall be 1.05V RMA. There shall be a 6-wire connection to the SP40/2. The mounting plate shall be red and measure, 8 3/4" x 5 ¼, and shall fit into a 4 gang back box. NATIONAL SALES OFFICE 800-631-2148 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com MADE IN THE USA 3 YEAR WARRANTY Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 V2005 04/03
Helping People Take Action SM INDUSTRIAL SYSTEMS PRODUCTS Description: Provides for control of making emergency voice announcements, manual activation of up to five automated messages and control of up to four zones plus all call from an auxiliary/remote location. Reset button can be programmed for system reset. Designed to be used with Wheelock s SAFEPATH Voice Evacuation Panels. Intended applications include OSHA, employee evacuation, emergency facility communication and Personnel Alert Systems (PAS). Features: Up to five pre-recorded messages can be activated Pre recorded messages / tones can be activated by five independent latching push buttons One reset button Four zone selectable switches and all call switch Removable push-to-talk, hand-held micro phone with supervised circuitry Status and zone LED s Terminal block connector for easy installation 19 Rack Mountable (2 RU), with matte black faceplate - can be console mounted Built-in pre-amplifier SD-RMS-1RMB Special Design Rack Mount Remote Microphone Station with 5 Message Activation Buttons. Applications Uses: Military Personnel Alert Systems (PAS): TerroristThreat, Security Breach, Bomb Threat, Chemical or Biological Weapons Attack, etc. Natural Disaster Warnings: Tornado Warning, Flood Watch, Earthquake Alert, etc. Security/Access Control: specific message control from guard station when main panel is located in an inaccessible location. For additional control of main panel in larger installations Copyright 2002 Wheelock, Inc. All rights reserved.
Architects and Engineers Specifications The Remote Microphone station shall be a Wheelock SD-RMS-1RMB or approved equal. The unit shall be compatible with Wheelock SafePath Supervised Audio, Fire and Emergency Evacuation Systems. The unit shall have five latching push button message / tone activation buttons, one reset button, four zone selectable switches and an all call switch. The unit shall have the capability of having programmed activation of up to five different pre-recorded messages. The unit shall incorporate a removable Push-To-Talk (PTT) microphone and system status indicators of/for the system. The unit shall incorporate live microphone override of any tone generation or Wheelock product for prerecorded messages. The unit shall be made of steel and be rack mountable in a 19 rack, or console mountable. The unit shall be painted black. The unit shall have a weight of approximately 5 lb., and its dimensions shall be 19 W x 3.5 H x 4.5 D (2 RU). The unit shall be made in the USA and have a 3 YEAR WARRANTY. Specifications: Audio Output Level: 1.0V RMS Input Current: 50mA Output Impedance: 600 Ohms Dimensions: 19 W x 3.5 H x 4.5 D (2 RU) The SD-RMS-1RM is not intended for UL required fire life-safety applications. Specifications and Ordering Information Model Number Order Description SD-RMS-1RM 8962 Special Design Rack Mount Remote Microphone Station with 5 Message Activation Buttons Notes: When used with Single- Circuit SafePath, only zone one will operate, other zones will be inoperable. When used with Dual- Circuit SafePath, only zone 1 and 2 (2 nd amplifier required) will operate, other zones will be inoperable. When used with Multi- Circuit SafePath, zones 1-4 will operate (additional amplifiers are required) Programmed Message kit (PMK) is required for all message and reset options. Contact Wheelock technical support (1-800-631-2148) for specific programming and wiring. Type of message can be labeled above the buttons, contact customer service for further information. Optional external mounting hardware may be required for console mounting. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 V2006 02/02
SPB-160 SPB-80/4 160 Watt Supervised Audio Power Booster (Two 80 watt circuits) 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronizable Strobe Power (Two 2 amp circuits) SAFEPATH 4 Audio Boosters Description Supervised Facility Communication and Emergency Voice Evacuation Audio and Audio/Strobe Power Boosters, UL Standard 1711 and UL Standard 864 Listed with 24 VDC battery backup capabilities. Designed to provide for additional supervised audio power for live voice, pre-recorded messages or background music (BGM). Fully supervised patent pending circuitry is always in effect even during BGM. The SPB-80/4 also provides 4 Amps of Supervised and Synchronized Strobe Power. The SPB-160 and the SPB-80/4 easily connects to the Wheelock SP40/2. Multiple SPB-160 and SPB-80/4 can be inter-connected to accommodate large installations with supervised audio power and supervised/synchronized strobe power requirements. The SPB-160 and the SPB-80/4 draws 1.2 watts of audio input power to properly operate and provide additional supervised audio output power. When connected to the Wheelock SP40/2, up to a combination of thirty three (33) boosters can be added. A maximum of 5,280 watts of supervised audio power can be utilized. Additional strobe power can be obtained via a combination of SPB-80/4 and PS-12/24-8 boosters. Applications Provides for additional supervised/synchronizable strobe power for large installations Can be used in new construction as well as in retrofit construction Copyright 2002 Wheelock Inc. All rights reserved. SPB-160 and SPB-80/4 Features Approvals & Compliance Approvals: UL Standard 864, UL Standard 1711 Pending: CSFM OSHA 1910.165 and ADA compliant 3 year warranty System Activation: Audio 70V or 25V input from the SP40/2 System Activation: Strobe (SPB-80/4) 8-33 VDC NAC input contact closure connected to the strobe input Power Supply & Batteries Fully supervised patent pending circuitry always in effect even during BGM Power limited circuitry Class D amplifier Internal battery charger and power supply Required batteries fit inside the enclosure (two 12 VDC, 12 AH) sold separately Outputs: SPB-160 has two 80 watt speaker output circuits Supervised Audio/Speaker outputs: 70V or 25V field selectable Expansion output (supervised, 24 VDC at.5a in alarm condition) used for connecting multiple SPB-160 or SPB-80/4 boosters DC output (unsupervised for optional SP4Z-B splitter power). Each speaker circuit (two for the SPB-160, one for the SPB-80/4) can connect to a SP4Z-B speaker splitter
SPB-80/4 Strobe Features: Two 24 VDC 2 Amps, NAC supervised, synchronizable, power limited, Class B strobe outputs Selectable outputs; Wheelock sync, pass through, or constant DC Trouble LED s for open and short output conditions Alarm indicator: LED s for Strobe and Expansion Outputs Inputs: Audio/Speaker Inputs: 70V or 25V, field selectable Auxiliary in (for alarm input signal) Technical Specifications: 120 VAC, 3.8A, 50 60 Hz input Standby current draw: 125 ma Alarm current draw: 9 Amps System Frequency Response: Voice 400 Hz - 6.5 khz +/- 3 db BGM 275 Hz - 15 khz +/- 3 db Removable quick connect/disconnect terminals, accept 12-22 AWG Multiple LED s for easy indication of system diagnostic conditions Signal to Noise Ratio: > 70 db Dynamic Range: > 65 db Total Harmonic Distortion: 2% Mechanical: Dimensions: 21" H x 16" W x 6" D (wall mount) Weight: 36 lbs. (without batteries) Finish: Red exterior enclosure Door Lock: Wheelock key-lock Options: A 4-Zone Class-B Speaker Splitter (SP4Z-B) can be connected to either the SPB-160 or SPB-80/4 Two SP4Z-B Speaker Splitters can be added to the SPB-160 One SP4Z-B Speaker Splitter can be added to the SPB-80/4 Note: The Speaker Splitter-Mounting Bracket (SPMB4Z) is required when the Speaker Splitter is used. The SPMB4Z can support two splitters. Wiring Options: There are two modes of operation for the audio input, Two Wire and Four Wire. Two Wire Audio Mode Supervision of the audio booster is performed over the same wires as the audio input signal, this means that if any one audio booster connected in the system goes into trouble, all secondary operations (BGM, telephone paging) will disengage from all audio boosters connected in the system. This method conserves battery backup power, if AC power is lost. When an alarm message or a live voice message from the microphone is broadcast by the SP40/2, the amplifier section is energized and the message is broadcast through the Audio Booster. Four Wire Audio Mode Alarm signal is input to the audio boosters via an additional pair of 2 wires. If any audio booster connected in the system goes into trouble, only that audio booster will loose secondary operations and BGM will disengage on that audio booster only. When using the SPB-80/4 strobe outputs, two additional wires are required for connection of strobes.
Ordering Information Model Order Description SPB-160 8989 160 Watt Supervised Audio Power Booster (Two 80 watt circuits) SPB-80/4 8988 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 amp circuits) SP4Z-B 8995 4-Zone Class B Speaker Audio Splitte r SPMB4Z 9907 Speaker Splitter Mounting Bracket for SPB-160 or SPB-80/ 4 Wheelock SAFEPATH 4 System Architecture SP40/2 Strobe Circuit Telephone System PBX for Telephone Paging Night Ring Circuit Contact Closure Digital Voice Strobe Out 2 amps Aux Input Audio Source 40 Watts Speaker Circuit Background Music On-Board Microphone Alarm Input(s) from Fire Panel 70 Volt line continues to Audio Power Boosters 70 volt speaker line from SP- 40/2 Audio Power Boosters Speaker Load Input Return 80 Watts 4 amps 2 Circuits Strobes Input 160 Watts 80 Watts 2 Circuits Speaker Load 80 Watts For illustration purposes only.
Architects and Engineers Specifications The booster system shall be NFPA compliant supervised audio and supervised 24 VDC synchronized strobe power boosters (some models will have supervised 24 VDC synchronized strobe booster capability). The booster system shall have 24 VDC battery backup capabilities. The booster systems shall have the capability to supervise the circuitry during playback of background music. The booster shall have the capability to be inter-connected to accommodate large installations with supervised audio power and supervised/synchronized strobe power requirements. The booster system shall use 1.2 watts of audio input power to properly operate and provide additional supervised audio output power. A combination of thirty three (33) boosters can be added to provide for a maximum of 5,280 watts of supervised audio power. Additional strobe power can be obtained via a combination of boosters. The audio section of the booster shall be connected via a selectable 70V or 25V input from the Wheelock SP40/2. The strobe section of the booster shall be divided into two sections each supplying two Amps of 24 VDC, NAC, supervised, synchronizable, power limited, Class B strobe outputs, with selectable outputs offering Wheelock sync, pass through, or constant DC and can be activated via 8-33 VDC NAC input or contact closure. The system shall have power-limited circuitry and be a class D amplifier with an internal battery charger and power supply. The required batteries shall fit inside the enclosure (two 12 VDC, 12 AH) batteries shall be purchased separately. The booster system shall operate on 120 VAC, 3.8A, 50 60 Hz input. Standby current draw shall be 125 ma and alarm current draw shall be 9 Amps. The voice frequency response shall be 400 Hz 6.5 khz +/- 3 db, the BGM frequency response shall be 275 Hz - 15 khz +/- 3 db. Removable quick connect/disconnect terminals that accept 12-22 AWG shall be used. Multiple LED s for easy indication of system diagnostic conditions shall be present on the PC board. The Signal to Noise Ratio shall be > 70 db, the dynamic range shall be > 65 db, the Total Harmonic Distortion spec shall be 2%. The booster system shall be wall mountable, enclosed in a steel locking enclosure, with a red finish, weighing no more then 36 lbs. (without batteries) and its dimensions shall not exceed 21" H x 16" W x 6" D. The system shall be made in the USA. Approvals for the system shall include; UL Standard 864, UL Standard 1711, and CSFM. The system shall be OSHA 1910.165 and ADA compliant. The booster system shall carry a 3-year warranty. NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Note: Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications. National Sales Office 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA Distributed By: 273 Branchport Avenue Long Branch, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 V2007 05/03
Helping People Take Action SM INC. SAFEPATH 4 Expansion Options SAFEPATH 4 Audio Boosters SPB-320* 320 Watt Supervised Audio Power Booster (Four 80 watt Circuits) SPB-160 SPB-80/4 160 Watt Supervised Audio Power Booster (Two 80 wat circuits) 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronizable Strobe Power (Two 2 Amp circuits) Page 2-3 SAFEPATH 4 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter SP4Z-A/B Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2, SPB-80/4, SPB-160 or SPB-320 Page 4 SAFEPATH 4 Addressable Paging Splitter and Telephone Zone Controller SP4-APS* Addressable Paging Splitter SP4-TZC* Telephone Zone Controller Page 5 SAFEPATH 4 Remote Microphone and Remote Microphone Remote Microphone Expansion Expansion Module Module SPRM SPRM Remote Microphone for use with the SAFEPATH 4 System SP4-RMX* SAFEPATH 4 Supervised Volume Control SP-SVC* Supervised Volume Control Remote Microphone for use with the SAFEPATH 4 System SP4-RMX* Remote Microphone Expansion Module for use with the Remote Microphone Expansion Module for use with the SAFEPATH SAFEPATH 4 System 4 System Page 8 Page 8-9 SAFEPATH 4 3 Message Expander Module SP4-3MEM-SMK 3-Message Expander Modules designed SP4-3MEM-PMK for use with the SP40/2 Page 10 *New Copyright 2004 Wheelock Inc. All rights reserved. 1
SAFEPATH 4 Audio Boosters SPB-320 SPB-160 320 Watt Supervised Audio Power Booster (Four 80 watt circuits) 160 Watt Supervised Audio Power Booster (Two 80 watt circuits) SPB-80/4 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronizable Strobe Power (Two 2 Amp circuits) Description Supervised Facility Communication and Emergency Voice Evacuation Audio and Audio/Strobe Power Boosters, UL Standard 1711 and UL Standard 864 with 24VDC battery backup capabilities. Designed to provide for additional supervised audio power for live voice, pre-recorded messages or background music (BGM). Fully supervised patent pending circuitry is always in effect even during BGM. The SPB-80/4 also provides 4 Amps of Supervised and Synchronized Strobe Power. The SPB-320, SPB-160 and the SPB-80/4 easily connects to the Wheelock SP40/2. Multiple SPB-320, SPB-160 and SPB-80/4 Audio Boosters can be inter-connected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements. The SPB-320 draws 2.4 watts of audio input power to properly operate and provide additional supervised audio output power. The SPB-160 and the SPB-80/4 draws 1.2 watts of audio input power to properly operate and provide additional supervised audio output power. A maximum of 5,280 watts of supervised audio power can be utilized. Additional strobe power can be obtained via a combination of SPB-80/4 and PS-12/24-8CP or PS-12/24-8MP boosters. Applications Provides for additional supervised and synchronizable strobe power for large installations Can be used in new construction as well as in retrofit construction 2 Features Approvals & Compliance Approvals: UL Standard 864, UL Standard 1711, California State Fire Marshal (CSFM) OSHA 1910.165 and ADA compliant 3 year warranty System Activation: Audio 70V or 25V input from the SP40/2 System Activation: Strobe (SPB-80/4) 8-33VDC NAC input contact closure connected to the strobe input Power Supply & Batteries Fully supervised patent pending circuitry always in effect even during BGM Power limited circuitry Class D amplifiers Internal battery charger and power supply Required batteries fit inside the enclosure sold separately SPB-320 requires four 12 VDC, 12 AH batteries SPB-160 and SPB-80/4 require two 12 VDC, 12 AH batteries Outputs: SPB-320 has four 80 watt speaker output circuits SPB-160 has two 80 watt speaker output circuits SPB-80/4 has one 80 watt speaker output circuit and two 2 amp strobe circuits (4 amps total) Supervised Audio Speaker outputs: 70V or 25V field selectable (all boosters must be either 70 V or 25 V) Expansion output (supervised, 24VDC at.5a in alarm condition) used for connecting multiple boosters DC output (unsupervised for optional splitter power). Each speaker circuit (four for the SPB-320, two for the SPB-160, one for the SPB-80/4) can connect to speaker splitters
SPB-80/4 Strobe Features: Two 24VDC 2 Amps, NAC supervised, synchronizable, power limited, Class B strobe outputs Selectable outputs; Wheelock sync, pass through, or constant DC Trouble LED s for open and short output conditions Alarm indicator: LED s for Strobe and Expansion Outputs Inputs: Audio Speaker Inputs: 70V or 25V, field selectable Auxiliary in (for alarm input signal) Mechanical: SPB-160, SPB-80/4 Dimensions: 21" H x 16" W x 6" D (wall mount) Weight: 36 lbs. (without batteries) Finish: Red exterior enclosure Door Lock: Wheelock key-lock SPB-320 Dimensions: 36" H x 24" W x 6" D (wall mount) Weight: 80 lbs. (without batteries) Finish: Red exterior enclosure Door Lock: Wheelock key-lock Technical Specifications: 120VAC, 3.8A, 50 60 Hz input Standby current draw: 120mA, per amplifier board Alarm current draw: 9 Amps, per amplifier board SPB-80/4 and SPB-160 have one amplifier board SPB-320 has two amplifier boards System Frequency Response: Voice 400 Hz - 6.5 khz +/- 3 db BGM 275 Hz - 15 khz +/- 3 db Removable quick connect/disconnect terminals, accept 12-22 AWG Multiple LED s for easy indication of system diagnostic conditions Signal to Noise Ratio: > 70 db Dynamic Range: > 65 db Total Harmonic Distortion: 2% Note: The Speaker Splitter-Mounting Bracket (SPMB4Z) is required when the Speaker Splitter is used. The SPMB4Z can support two splitters. Wiring Options: There are two modes of operation for the audio input, Two Wire and Four Wire. Two Wire Audio Mode Supervision of the audio booster is performed over the same wires as the audio input signal, this means that if any one audio booster connected in the system goes into trouble, all secondary operations (BGM, telephone paging) will disengage from all audio boosters connected in the system. This method conserves battery backup power, if AC power is lost. When an alarm message or a live voice message from the microphone is broadcast by the SP40/2, the amplifier section is energized and the message is broadcast through the Audio Booster. Four Wire Audio Mode Alarm signal is input to the audio boosters via an additional pair of 2 wires. If any audio booster connected in the system goes into trouble, only that audio booster will loose secondary operations and the BGM will disengage on that audio booster only. When using the SPB-80/4 strobe outputs, two additional wires are required for connection of strobes. Ordering Information Model Order Description SPB-320 9918 320 Watt Supervised Audio Power Booster (Four 80 watt circuits) SPB-160 8989 160 Watt Supervised Audio Power Booster (Two 80 watt circuits) SPB-80/4 8988 SP4Z-A/B 9900 80 Watt Supervised Audio Power Booster with 4 Amps of Supervised and Synchronized Strobe Power (Two 2 Amp circuits) Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2, SPB-320, SPB-160 or SPB-80/4 SPMB4Z 9907 Speaker Splitter Mounting Bracket for SPB-320, SPB-160 or SPB-80/ 4 3
2-Zone Class A or 4-Zone Class B Speaker Audio Splitter SAFEPATH 4 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter For operation with SAFEPATH 4 Family of Products: SP40/2, SPB-320, SPB-160, SPB-80/4 Description: Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2 or Audio Boosters. Enables a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Applications: Provides for expansion of one zone to up to 2 zones of supervised speaker audio output in Class A Provides for expansion of one zone to up to 4 zones of supervised speaker audio output in Class B Ordering Information: Model Order SP4Z-A/B 9900 SPMB4Z 9907 Description Supervised 2-Zone Class A or 4-Zone Class B Speaker Audio Splitter for the SP40/2 or Audio Boosters Mounting Bracket for the SP4Z-A/B is required when used with the Audio Boosters Note: The SP4Z-A/B mounts inside the SP40/2 (a mounting bracket is not required). When mounting inside the Audio Boosters, the additional mounting bracket, SPMB4Z is required and is sold separately. Features: Approvals: UL Standard 864 and California State Fire Marshal (CSFM) Expands one zone to up to 2 zones of supervised speaker audio output in Class A Expands one zone to up to 4 zones of supervised speaker audio output in Class B Each Class A zone can accept up to 40 watts of audio Each Class B zone can accept up to 20 watts of audio Operates on either 25V or 70.7V RMS Mounts inside the enclosure of either the SP40/2 or Audio Boosters Power and Trouble LED s Individual zone short and open LED indication Capable of detecting wiring faults Removable wiring terminals for quick connect/ disconnect accepting 12 22 AWG All output circuitry is Power Limited Space provided to allow for naming of the zones Powered by 24VDC, supplied by the either the SP40/2 or Audio Boosters Standby and Alarm current at 24VDC is 15mA 4
SP4-APS* SP4-TZC* Addressable Paging Splitter Telephone Zone Controller SAFEPATH 4 Addressable Paging Splitter and Telephone Zone Controller Applications: Connects to the SP40/2 to control selectable paging and background music (BGM) Ability to access individual or multiple speaker zones throughout the SP40/2 system via the telephone Features: Allows selections of speaker zones via the telephone keypad (DTMF tones) One SP4-TZC (controller) can control up to 17 SP4-APS (splitters) Telephone page input connects to stand alone telephone, unused CO port, page port USB connection for logical zone grouping and BGM programming (supports Windows 2000 and Windows XP) Up to 8 logical zones, a logical zone is a user selected group of up to 5 zones (individual or fixed) RS-485 digital control to the SP4-APS speaker splitters Connects to the SP40/2 via the BGM input The combination of 1 SP4-TZC (controller) and up to 17 SP4-APS (splitters) can provide: Class B 4 zones per splitter Up to 68 individual zones (17 splitters) 17 fixed zones (groups of 4) 8 logical zones Class A 2 zones per splitter Up to 34 individual zones (17 splitters) 17 fixed zones (groups of 2) 8 logical zones SP4-TZC Telephone Zone Controller: Connects to the SP40/2 Auto programmable Custom user programmable (for logical zones) All call or selected zone(s) telephone paging Background music (BGM) zone(s) selectable Telephone input and background music (BGM) input Enclosure for the SP4-TZC (controller): Dimensions: 13"H x 7.6"W x 2.15"D Color: Black Wall mountable Requires 24 VDC, model RPS-2406 SP4-APS Addressable Paging Splitter: Addressable speaker zone splitter Mounts inside the SP40/2, SPB-80/4, SPB-160 or SPB-320 Operates on 24 VDC, supplied by the SP40/2, SPB-80/4, SPB-160, SPB-320 Handles 40 watts of supervised audio per zone UL Standard 864 listed Ordering Information: Model Order Description SP4Z-APS* 9920 Addressable Paging Splitte r SP4-TZC* 9921 Telephone Zone Controlle r TZC-USB* 9923 SP4-TZC Programming Cable 5 *Available Q4/2004
BGM DV FACP MPS NPS PS-12/24-8CP PS-12/24-8MP SP40/2 SPB-80/4 SPB-160 SPB-320 SPRM SP4-RMX SP4-TZC SP4-APS SP4Z-A/B SP4-SVC Legend: Background Music Digital Voice Message Expander Fire Alarm Control Panel Pull Station Push Station 8 Amp Strobe Power Supply (Continuous Power) 8 Amp Strobe Power Supply (Managed Power) Supervised Multi-Function Communication System 80 Watt Audio Booster & 4 Amps of Strobe Power 160 Watt Audio Booster 320 Watt Audio Booster Remote Microphone Remote Microphone Expansion Module Telephone Zone Controller Addressable Paging Splitter Speaker Splitter Supervised Volume Control BGM SP4- TZC Telephone Strobe Speaker Speaker Strobe Cluster Speaker V Volume Control NPS SP4-APS MPS SP40/2 FACP SP4- RMX SP4-3MEM DV SPRM SPRM SPRM This drawing is for illustrative purposes only 6
SP4-APS SPB-160 V PS-12/24-8MP SP4Z-A/B PS-12/24-8CP SPB-320 SPB-320 SP4-APS SP4-APS SP4-APS SP4-APS SP4-APS SP4Z-A/B SP4Z-A/B SP4-APS V SP4-APS SPB-160 SP4-APS SPB-160 SP4-APS SP4-APS SPB-80/4 SP4-APS V 7
SAFEPATH 4 Supervised Volume Control SAFEPATH 4 Remote Microphone SP-SVC* Supervised Volume Control Applications: Allows manual volume setting for telephone paging and background music for a specific speaker or speaker zone The selected adjustment will not affect the volume setting of emergency prerecorded messages or live microphone usage Features: Supervised volume control for use with UL Listed Life Safety Applications Can handle up to 35 watts of audio power input Operates on either 70.7 or 25 volt audio input from an SP40/2 or Audio Booster Adjustment settings: off, 1 10, in 3dB increments Operates in Class B or Class A wiring (for Class A, the SP4-APS is required) Requires a double gang, 3½" deep back box Stainless steel mounting plate with a black knob UL Standard 1480 listed OSHA 1910.165 and ADA compliant Model Order SP-SVC* 9926 Preliminary Ordering Information: Description Supervised Volume Control for use with the SP40/2 *Available Q1/2005 Description: Remote Microphone for use with the SAFEPATH 4 Facility Communications System - SP40/2 or SP4-RMX. Applications: Provides for an additional microphone in a remote location Can be mounted up to 2,000 feet away from the SP40/2 Features: Approvals: UL Standard 864 and California State Fire Marshal (CSFM) Supervised hand held push to talk microphone Key required to enable remote microphone use (same key as SP40/2) Removable wiring terminals for quick connect/ disconnect accepting 12-22 AWG Individual front panel LED indication for System Normal, System Trouble, Alarm Multiple on board diagnostic LED s When used with the SP40/2, the priority level is 2, the SP40/2 on board microphone is priority 1 Remote microphone usage disengages background music and general paging Voice frequency response: 275 Hz - 6.5 khz +/- 2.4dB Requires 24VDC, supplied by the SP40/2 or Audio Boosters Input current: Standby: 26mA Alarm: 38mA Audio output level: 1.05V RMS 6 wire connection to the SP40/2 or SP4-RMX Mounting plate is red and measures, 8 3/4" x 5 ¼, fits into a 4 gang back box All output circuitry is Power Limited Ordering Information: Model Order Description 8 SPRM 8996 Remote Microphone for use with the SP40/2 or SP4-RMX
SP4-RMX Remote Microphone Expansion Module SAFEPATH 4 Remote Microphone Expansion Module Applications: Expands one remote microphone (SPRM) from the SP40/2 to three remote microphones Two SP4-RMX modules can be ganged together to provide up to six remote microphones from the SP40/2 Provides for an auxiliary input for connection of an external message repeater for additional messages Features: Ordering Information: The SP4-RMX will provide the capability of connecting Model up to (3) three Remote Microphone Stations (SPRM) Order Description When connected to the SP40/2, two SP4-RMX units can be ganged together to provide up to six remote SP4-RMX 9919 microphones Remote Microphone Expansion Provides for an auxiliary input for connection of an Module external message repeater, (MDV-2, DV-100, DV-200) for additional messages Can accept a line level input for broadcasting of other Microphone and message priority levels when information the SP4-RMX is used with the SP40/2: When the SP4-RMX is connected to the SP40/2, the entire system benefits from the additional microphone Priority Level Device capability Microphones UL Standard 864 listed 1 SP40/2 on board microphone OSHA 1910.165 and ADA compliant 2 SP4-RMX, remote microphones #1, 2, 3 (first remote microphone SPRM, to Multiple on board diagnostics with 3 status conditions: standby, alarm, and trouble connect to the SP40/2 has highest priority) Operates on 24 VDC, supplied by the SP40/2, SPB- 80/4, SPB-160, SPB-320 3 SP4-RMX, auxiliary input** Optional SP4-3MEM The SP4-RMX is an external module Enclosure dimensions: 13"H x 7.6"W x 2.15"D Message Expander Color: Black 4 SP4-3MEM message 1 Wall mountable 5 SP4-3MEM message 2 6 SP4-3MEM message 3 SP40/2 Standard Messages 7 SP40/2 message 1 8 SP40/2 message 2 9 SP40/2 message 3 Note: If the SP4-3MEM is not used, then the SP40/2 standard messages move up in priority level **The auxiliary input message device (MDV-2, DV-100, DV-200 or other external device) must have an external UL listed battery backed up power supply for use in UL Life Safety Installations 9
SP4-3MEM-SMK 3 Message Expander Module with 3 standard messages for use with the SP40/2 SAFEPATH 4 3 Message Expander Module SP4-3MEM-PMK 3 Message Expander Module with custom programmed messages for use with the SP40/2 Description: The SP4-3MEM-SMK and the SP4-3MEM-PMK are 3-message expander modules designed for use with the SP40/2. The SP4-3MEM-SMK and the SP4-3MEM-PMK provide a means of expanding the number of digital voice messages by as many as three. When used with the SP40/2 a maximum of 6 digital voice messages will be available for UL Life Safety applications. Applications: Provides for the addition of up to 3 digital voice messages Ordering Information Model Number Order SP4-3MEM-SMK 9913 SP4-3MEM-PMK 9915 Description 3-message expander module designed for use with the SP40/2, with 3 standard messages (see standard messages) 3-message expander module designed for use with the SP40/2, with 3 custom programmed messages Features Approvals: UL Standard 864 Pending: California State Fire Marshal (CSFM) 3 message expander module Expands the message capability of the SP40/2 to six (6) messages for UL Life Safety applications Each message has the capability of strobe activation selection strobe on/off The messages on the SP4-3MEM-SMK or the SP4-3MEM-PMK will have higher priority levels than the on board messages in the SP40/2 Priority Levels when the SP4-3MEM is used: 1. SP40/2 On Board Microphone 2. SP40/2 Remote Microphone (optional) 3. SP40/2-3MEM-SMK or SP4-3MEM-PMK, Message 1 4. SP40/2-3MEM-SMK or SP4-3MEM-PMK, Message 2 5. SP40/2-3MEM-SMK or SP4-3MEM-PMK, Message 3 6. SP40/2, Message 1 7. SP40/2, Message 2 8. SP40/2, Message 3 9. Night Ringer 10. Telephone Page 11. BGM The SP4-3MEM-SMK or SP4-3MEM-PMK mount to the SP40/2 motherboard and fit inside the enclosure All messages are pre-programmed from the factory 10 The standard messages for the SP4-3MEM-SMK are as follows: Message 1: Three (3) rounds of code 3 horn (followed (Fire) by): May I have your attention please! A fire emergency has been reported in the building. While this is being verified, please leave the building by the nearest exit. Message 2: (Alert) Message 3: (All Clear) Three (3) rounds of code 3 horn (followed by): May I have your attention please! An emergency has been reported in the building. While this is being verified, please stand by for further instructions. Five (5) seconds of 1kHz tone (followed by) May I have your attention please! The build ing emergency has ended. An all clear has been given. Please resume normal activities. Note: These are the same messages as the standard messages for the SP40/2. Custom messages will need to be ordered by ordering the SP4-3MEM-PMK. This will avoid duplicate messages. The maximum length of message options are as follows: Option 1 3 messages with a maximum of 20 seconds each (Standard) Option 2 2 messages, 1 message with a maximum of 40 seconds and 1 message with a maximum of 20 seconds Option 3 1 message with a maximum of 60 seconds Removable wiring terminals for quick connect/ disconnect accepting 12 18 AWG When the optional Remote Microphone (SPRM) is used, it is connected into the auxiliary input of the SP4-3MEM-SMK or SP4-3MEM-PMK
Architects and Engineers Specifications SAFEPATH 4 Audio Boosters The Wheelock SPB-320, SPB-160 and SPB-80/4 Audio Boosters shall be NFPA compliant supervised audio and supervised 24VDC synchronized strobe power boosters (some models will have supervised 24VDC synchronized strobe booster capability). The booster shall have 24VDC battery backup capabilities. The booster shall have the capability to supervise the circuitry during playback of background music. The booster shall have the capability to be inter-connected to accommodate large installations with supervised audio power and also supervised and synchronized strobe power requirements. Three versions of the booster shall be made available: SPB-80/4, (80 watts of supervised audio power and 4 amps of supervised and synchronized strobe power), SPB-160 (160 watts of supervised audio) or SPB-320 (320 watts of supervised audio). Each booster shall use 1.2 watts of audio input power (The SPB-320 requires 2.4 watts of audio power) to properly operate and provide additional supervised audio output power. A combination of boosters can be added together to provide for a maximum of 5,280 watts of supervised audio power. Additional strobe power can be obtained via a combination of boosters. The audio section of the booster shall be connected via a selectable 70V or 25V input from the Wheelock SP40/2. The strobe section of the booster shall be divided into two sections each supplying two Amps of 24VDC, NAC, supervised, synchronizable, power limited, Class B strobe outputs, with selectable outputs offering Wheelock sync, pass through, or constant DC and can be activated via 8-33VDC NAC input or contact closure. The boosters shall have power-limited circuitry and be a class D amplifier with an internal battery charger and power supply. The required batteries (purchased separately) shall fit inside the enclosure (two 12VDC, 12 AH for the SPB-80/4 or SPB-160 and four 12 VDC, 12 AH for the SPB-320). The booster shall operate on 120VAC, 3.8A, 50 60 Hz input. The SPB-80/4 or SPB-160 standby current draw shall be 120mA and alarm current draw shall be 9 Amps. The SPB-320 consists of two SPB-160 s. Each SPB-160 shall have its own power supply and battery charger. The voice frequency response shall be 400 Hz 6.5 khz +/- 3 db, the BGM frequency response shall be 275 Hz - 15 khz +/- 3 db. Removable quick connect/disconnect terminals that accept 12-22 AWG shall be used. Multiple LED s for easy indication of system diagnostic conditions shall be present on the PC board. The Signal to Noise Ratio shall be > 70 db, the dynamic range shall be > 65 db, the Total Harmonic Distortion spec shall be 2%. The booster shall be wall mountable, enclosed in a steel locking enclosure, with a red finish. The booster shall be made in the USA. Approvals for the booster shall include; UL Standard 864, UL Standard 1711, and CSFM. The booster shall be OSHA 1910.165 and ADA compliant. The booster shall carry a 3 year warranty. 4 Zone Class B Speaker Splitter The Wheelock SP4Z-A/B shall be UL Standard 864 and California State Fire Marshal (CSFM) approved, 2-Zone Class A or 4-Zone Class B Speaker Splitter for operation with the Wheelock, SP40/2, SPB-80/4, SPB-160 and SPB-320. The SP4Z-A/B shall enable a single supervised speaker audio output to drive up to two Class A supervised speaker audio outputs or four Class B supervised speaker audio outputs. Each Class A zone shall be capable of accepting up to 40 watts and operate on either 25 or 70.7V RMS of audio input. Each Class B zone shall be capable of accepting up to 20 watts of audio and operate on either 25 or 70.7V RMS of audio input. The SP4Z-A/B shall be capable of supporting live microphone paging, prerecorded emergency voice evacuation messages, supervised background music and general paging announcements. The SP4Z-A/B shall mount inside the enclosure of the SP40/2, SPB-80/4, SPB-160 and SPB-320 and shall have power and trouble LED s with individual zone short and open LED indication. The SP4Z-A/B shall be capable of detecting wiring faults. The SP4Z-A/B shall be powered by 24VDC, which is to be supplied by the SP40/2, SPB-80/4, SPB-160 or SPB-320. Standby and Alarm current at 24VDC shall be 15mA. Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Space shall be provided to allow for naming of the zones. Addressable Paging Splitter and Telephone Zone Controller The Wheelock Addressable Paging Splitter (SP4-APS) and Telephone Zone Controller (SP4-TZC) shall be used to control and direct telephone paging and background music zones connected to the SAFEPATH4 Multi-Function Facility Communication System using an RS485 connection. The Addressable Paging Splitter (SP4-APS) shall be UL Standard 864 and California State Fire Marshal (CSFM) approved, addressable and supervised 2-zone Class A or 4-zone Class B Speaker splitter. The SP4-APS shall be used with Wheelock s SP40/2 panel and the Audio Booster (SPB-160, SPB-80/4, and SPB-320) panels. Each SP4-APS shall have a single audio input capable of 25 Vrms or 70.7 Vrms at a maximum of 80 Watts. The input audio power shall be distributed to the zone connections with the total not exceeding the input and no zone exceeding 40 Watts. When audio boosters are connected, each audio booster module shall consume 1.2 Watts from the total input power of the SP4-APS. The splitter shall be mounted inside the SP40/2 or Audio Booster that it is associated with, and it shall operate on 24VDC supplied by the supported module. The SP4- APS shall contain 16 LED indicators used to monitor and troubleshoot the module. The Telephone Zone Controller Module (SP4-TZC) shall be used to address the output zones on the SP4-APS. The SP4-TZC shall be capable of supporting 17 SP4-APS speaker splitter modules and shall be capable of addressing all zones at once ( All Call ), a maximum of 68 separate zones, 17 fixed zone groups and 9 programmed logical zone groups. This shall be accomplished using two digit DTMF tones from a page port, an unused CO port, or a stand alone telephone with a loop start circuit. Also, the SP4-TZC shall be able to select zones for background music. The SP4-TZC has the following inputs: Power, USB port, Background Music (BGM), Page Audio in. The outputs are: Audio out and RS485 Digital Control. The basic operating parameters of the SP4- APS shall be pre-programmed. Customized programming shall be accomplished using a USB cable and programming computer software. The SP4-TZC shall be powered using a 24VDC filtered and regulated power supply such as the Wheelock RPS-2406. The Controller Module assembly is mounted in a metal enclosure measuring 13"L x 7 5/8"W x 2"D. 11
Architects and Engineers Specifications Supervised Volume Control The Wheelock SP-SVC shall be UL Standard 1480 and CSFM approved, supervised volume control for use with the SAFEPATH 4 SP40/2 Facility Communications System. The SP-SVC shall provide for manual volume setting for telephone paging and background music for a specific speaker or speaker zone. The selected adjustment will not affect the volume setting of emergency prerecorded messages or live microphone usage. The SP-SVC shall be capable of handling up to 35 watts of audio power and shall operate on either 70.7 or 25 volt input from an SP40/2 or Audio Booster. The SP-SVC shall be capable of operating in Class B or Class A wiring configurations (for Class A, the SP4-APS is required). The SP-SVC shall receive operating power from an Audio Booster. Volume adjustment settings shall be off, 1 10, in 3dB increments. The SP-SVC shall be supplied with a stainless steel mounting plate with a black knob and require a double gang, 3½" deep back box for mounting. Preliminary Remote Microphone The Wheelock SPRM shall be UL Standard 864 and California State Fire Marshal (CSFM) approved, Remote Microphone for use with the SAFEPATH4 SP40/2 Facility Communications System. The SPRM shall be a supervised hand held push to talk microphone and a key shall be required to enable remote microphone use. (Same key as SP40/2) Removable wiring terminals for quick connect/disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Individual front panel LED s shall be provided for indication of System Normal, System Trouble and Alarm. Multiple on board diagnostic LED s shall be provided. When used with the SP40/2, the priority level shall be number two. Remote microphone usage shall disengage background music and general paging. Voice frequency response shall be 275 Hz - -6.5 khz +/- 2.4 db. Power requirements shall be 24VDC and will be supplied by the SP40/2. Input current for Standby shall be 26mA and for Alarm 38mA. Audio output level shall be 1.05V RMA. There shall be a 6- wire connection to the SP40/2. The mounting plate shall be red and measure, 8 3/4" x 5 ¼, and shall fit into a 4 gang back box. Remote Microphone Expansion Module The Wheelock SP4-RMX Remote Microphone Expansion Module shall be UL Standard 864 and California State Fire Marshal (CSFM) approved for use with the SAFEPATH4 SP40/2 Facility Communications System. The SP4-RMX shall be a supervised outboard expansion module for use with the SAFEPATH4 system. It shall be used to expand the number of optional supervised Remote Microphone (SPRM) modules up to three. Two SP4-RMX Remote Microphone Expansion Modules can be connected to the SP40/2 and shall have the capability of providing the SP40/2 with up to six system wide All Call Remote Microphone (SPRM) modules. The SP4-RMX can be programmed to provide either priority override for each SPRM module input or First In First Out. First In First Out allows the active SPRM to complete its communication before another SPRM can be used. All output circuitry shall be power limited. Multiple on board diagnostic LED indicators shall be provided. All wiring shall be connected to the module using quick connect/disconnect wiring terminals, capable of accepting 12 22 AWG wiring. The SP4-RMX PCB assembly is mounted in a metal enclosure measuring 13"L x 7 5/8"W x 2"D. The SP4-RMX can support each SPRM at a range up to 2000 feet. 3 Message Expansion Module The Wheelock SP4-3MEM-SMK and the SP4-3MEM-PMK shall be UL Standard 864 three (3) message expander modules for use with the Wheelock SP40/2. The SP4-3MEM-SMK or the SP4-3MEM-PMK shall provide for a maximum of three additional messages when utilized with the SP40/2 for use in UL Life Safety applications. The SP4-3MEM-SMK or the SP4-3MEM-PMK shall fit within the enclosure of the SP40/2. Removable wiring terminals for quick connect/disconnect accepting 12 18 AWG shall be incorporated. When either the SP4-3MEM-SMK or the SP4-3MEM-PMK is used with the SP40/2, the message priority levels shall be: (1) SP40/ 2 On Board Microphone, (2) SP40/2 Remote Microphone (optional), (3) SP4-3MEM-SMK or the SP4-3MEM-PMK, Message 1, (4) SP4-3MEM-SMK or the SP4-3MEM-PMK, Message 2, (5) SP4-3MEM-SMK or the SP4-3MEM-PMK, Message 3, (6) SP40/2, Message 1, (7) SP40/2, Message 2, (8) SP40/2, Message 3, (9) Night Ringer, (10) Telephone Page and (11) Background Music. The SP4-3MEM-SMK or the SP4-3MEM-PMK shall have the following maximum length of message options: Option 1 3 messages with a maximum of 20 seconds each (Standard) Option 2 2 messages, 1 message with a maximum of 40 seconds and 1 message with a maximum of 20 seconds Option 3 1 message with a maximum of 60 seconds NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. Note: Refer to the products Installation Instructions for proper installation, wiring procedures and any additional specifications. National Sales Office 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION YEAR 3 WARRANTY Made in USA Distributed By: 273 Branchport Avenue Long Branch, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 12 V2010 10/04
Batteries and Battery Cabinet BAT-1212 BATC-R Description The Wheelock BAT -(#) sealed lead acid batteries are leak-proof and maintenance free. They are based on a unique efficient oxygen recombination technology. Oxygen evolves from the positive plates and diffuses through the microporous glass fibers to the negative plates where it is changed back to water by recombination reaction. This process eliminates the need for water replacement. All battery models are designed per NFPA 72 (2002) Section (6.9.4.5) for use with engine driven generators, local central station or proprietary systems and auxiliary or remote station systems. The (BACT-R) enclosure is constructed of steel and its door hinges fold downward for easy loading of the batteries. It also comes with a lockable door that is keyed like the SAFEPATH control panel. Specification and Ordering Information Model Number Order Description BATC-R 5414 Battery Cabinet, Red Specifications Dimensions: 9.5 H x 24 W x 9 D Weight: 20lbs. (Empty) Lock: Keyed like the SAFEPATH Control Panel BAT-1212 7390 12 Volt, 12 Ampere Battery Cell Dimensions: 4 H x 6 W x 4 D Weight: 8lbs., 6oz. BAT-1224 7391 12 Volt, 24Ampere Battery Cell Dimensions: 5 H x 7 W x 7 D Weight: 19lbs., 12oz. BAT-1265 7392 12 Volt, 65 Ampere Battery Cell Dimensions: 7 H x 14 W x 7 D Weight: 50lbs., 5oz. NOTE: Care must be given when determining the size of the battery system. Larger applications might require more than one battery cabinet.
Architects and Engineers Specifications The Battery Standby System shall consist of a Wheelock BATC-B/R (Battery Cabinet) and the appropriate battery cell size to accomplish the specified standby requirements of the system. The Battery Cabinet shall be available in red (BATC-R). It shall be constructed of steel and have a locking downward folding hinged door. The lock shall be keyed lock the SAFEPATH Control Panel. The dimensions of the unit shall be 9.5 H x 24 W x 9 D and weight 20.0 lbs (empty). Three separate battery cells shall be available, each with specific ampere-hour capacity for specific SAFEPATH System requirements that are consistent with NFPA 72 (2002) section (6.9.4.5). The battery shall be of leak-proof, sealed lead acid construction and shall be maintenance free. The ampere hour ratings of each cell type shall be: 12 ampere hour (BAT-1212), 24 ampere hour (BAT-1224) and 65 ampere hour (BAT-1265). These components of the Battery Standby System shall have UL component recognition. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA V3000 Batteries 06/06
AIM-3 Auxiliary Input Module Description The AIM-3 is an outboard expansion module designed to either expand the number of optional remote microphone stations from 1 to 3, or allows a telephone interface and up to two remote microphones. It is used with SAFEPATH panels. Features Approvals include: UL Standard 864, FCC Part 15. Complies with OSHA L1910.165 Expands SAFEPATH microphone inputs to Three (3) remote microphones or One (1) telephone paging port & two (2) remote microphones. Remote Microphones can be installed up to 1000 feet away from the AIM-3. For telephone paging, the AIM-3 can be connected to a CO port, page port, analog station port or the MZC-144 zone controller. The first remote microphone going into live voice has priority. Wall mount in a self contained 16-gauge metal enclosure. Incorporates signal verification. Internal noise filtering. Music muting for the selected zone. Dimensions: (13.0" H x 7.6" W x 2.15" D (33.0 H x 19.4 W x 5.4 D cm) RM PORT SAFEPATH PANEL INPUT PORT AIM-3 AIM-3 RM PORT 1 RM PORT 2 RM PORT 3 Block diagram of AIM-3 connection Remote Microphone 1 Remote Microphone 2 Remote Microphone 3 Telephone Paging Applications When the SAFEPATHsystem requires additional remote microphones. When telephone paging is required. Specification & Ordering Information Model Number Order Description AIM-3 7387 Auxiliary Input Module for Telephone system Interface & Multiple Remote Microphones Copyright 2002 Wheelock Inc. All rights reserved.
Architects and Engineers Specifications AIM-3 Auxiliary Input Module The unit shall be a Wheelock AIM-3 or approved equal. It shall be designed to be an outboard expansion module to either exapnd the number of optional remote microphone stations from 1 to 3, or allow a telephone interface and up to 2 remote microphones. The unit shall be designed to interface with Wheelock SAFEPATH panels. The unit shall require input voltage of 24VDC. Input current shall be 100mA telephone page, 60mA remote microphone page, 40mA standby. Audio input shall be 1Vrms. The housing shall be black metal with knockouts for conduit; shall be designed for panel/wall mount installation, and the dimensions shall be 13.00" H x 7.64" W x 2.12" D. Weight shall be 3.8 lbs. The unit shall be registered under part 15 of FCC rules. The unit shall be UL Standard 864 approved. The unit shall comply with OSHA L1910.165. SAFEPath Panel + - RM Audio RM TXD RM RXD + - RM Power RM Audio RM TXD RM RXD RM Power RMS #1 TB1 + - + - TB2 + - RM Audio RM TXD RM RXD + - RM Power RMS #2 TB3 + - RM Audio RM TXD RM RXD + - RM Power REMOTE MICROPHONE 1 2 3 4 5 6 - - + RM Power+ RM TXD RM RXD RM Audio REMOTE MICROPHONE 1 2 3 4 5 6 - - + RM Power+ RM TXD RM RXD RM Audio AUDIO TXD RXD/CC POWER CC + - + - NC NC NC NC RMS-3 OF AIM-3 TIP RING UNUSED CO PORT NC = NO CONNECTION Wiring diagram for unused CO port RMS #3 AIM-3 TB4 + - RM TXD RM RXD + - RM Audio RM Power REMOTE MICROPHONE 1 2 3 4 5 6 - - + RM Power+ RM TXD RM RXD RM Audio AUDIO TXD RXD/CC + - + - AUDIO Wiring diagram with up to 3 remote microphones. POWER CC + - RMS-3 OF AIM-3 CONTACT CLOSURE PAGE PORT Wiring diagram for page port Wiring Specifications: See Installation Instructions (P83667A) for detailed wiring specifications. Cable size & maximum length: 14-22 AWG shielded, 6 conductor, 1000 feet. (For additional wiring diagrams, see Installation Instructions P83667A) NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY MADE IN THE USA Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 V3900 07/02
SP4-LOC Remote Microphone and Local Operator Console Description: The SP4-LOC Remote Microphone and Local Operator Console is designed for indoor use with the SafePath4 SP40/2 and the SP40S panels for mass notification applications. The SP4-LOC contains the SafePath4 SPRM Remote Microphone module and eight black push on/push off buttons which provide a contact closure used to activate the SP40/2 or SP40S digital messages in the ON position. The buttons change color from black in the OFF position to green in the ON position. A message name plate holder is located above the pushbuttons. An optional HVAC Emergency Shutoff red, mushroom type cutoff pushbutton and labeling is available as a seperate kit. The Remote Microphone module (SPRM) incorpoates a Push- To-Talk (PTT) microphone and system status LED indicators. The SPRM provides a microphone override for any tone generation, digitak voice module prerecorded message, background music, or telephone paging. It is equipped with a keyed lock that, when activated, allows the use of the module. The SPRM is fully supervised from the SP40/2 or the SP40S panel and contains front panel LEDs for remote indications of System Normal, System Trouble, and Alarm conditions. Voice frequency response shall be 275 Hz-6.5 khz +/- 2.4 db. Power requirements shall be 24VDC and will be supplied by the SP40/2 or SP40S. Input current for standby mode shall be 26mA and 38mA in the alarm mode. Shielded 6-wire cable shall be used. Approvals for the system shall include; UL Standard 864, UL Standard 1711, FCC Part 15, and CSFM. The panel shall be OSHA 1910.165 and ADA compliant. The SP4-LOC is available in two models. The flush mount model has a 1/2 inch skirt around the door section, while the surface mount model door section is flush with the back box. Both models use the same white 4 inch deep backbox with a single 1/2 inch/ 3/4 inch double knockout on the back center, and top and bottom of the backbox. The flush mount door section has exterior dimensions of 15-1/2 inches wide and 16-1/4 inches high. The surface mount model has dimensions of 14-1/2 inches wide, 15-1/2 inches high and 4 inches deep. Both models have a pull slam latch to open the continuous hinged door. Both models are available in white. The SP4-LOC can be installed up to 2,000 feet from the SP40/2 or SP40S panel using 14-18 AWG wiring. Shielded wire is only required for the 1Vrms output from the SPRM. Features: All message wiring is pre-wired to a terminal block Internal terminal block accepts up to 16 AWG wiring for filed wiring Built-in SPRM requires 24VDC, supplied by the SP40/2 or SP40S SPRM Input current: Standby: 26mA Alarm: 38mA All output circuitry is Power Limited SP4 LOC is available in flush and surface models Backbox for both models are identical with knockout mounting holes in the sides and back Backbox contains three (3) double knockouts for 1/2 or 3/4 conduit fittings. Knockouts are located in the center top and bottom and one in the center top back Optional HVAC Emergency Shutoff mushroom pushbutton kit Can be mounted up to 2,000 feet away from the SP40/2 or SP40S Remote microphone usage disengages background music and general paging Eight (8) push on/push off pushbuttons that provide a contact closure in the ON position. Pushbuttons are balck in the OFF position and green in the ON position.
ARCHITECTS AND ENGINEERS SPECIFICATIONS The Remote Microphone and Local Operator Console shall be the SafePath4 SP4 LOC for use with a Facility Communications System using the SafePath4 SP40/2 and the SP40S panels. It shall contain the SafePath4 SPRM Remote Microphone Module and eight black Push On /Push Off buttons which provide a contact closure. The pushbuttons shall change color from black in the OFF position to green in the ON position. A message name plate holder shall be located above the pushbuttons. An optional red mushroom type, cutoff pushbutton and nameplate shall be available for HVAC emergency shutoff. Built-In Remote Microphone (SPRM) The SPRM shall be a supervised hand held push to talk microphone and a key shall be required to enable remote microphone use. (Same key as SP40/2) Removable wiring terminals for quick connect /disconnect accepting 12 22 AWG shall be incorporated. All output circuitry shall be power limited. Individual front panel LED s shall be provided for indication of System Normal, System Trouble and Alarm. Multiple on board diagnostic LED s shall be provided. When used with the SP40/2, the priority level shall be number two. Remote microphone usage shall disengage background music and general paging. Voice frequency response shall be 275 Hz - 6.5 khz +/- 2.4 db. Power requirements shall be 24VDC and will be supplied by the SP40/2. Input current for Standby shall be 26mA and for Alarm 38mA. Audio output level shall be 1.05V RMA. There shall be a 6-wire connection to the SP40/2. The mounting plate shall be red and measure, 8 3/4 x 5 ¼, and shall fit into a 4 gang back box. The SP4-LOC shall be available in two models. The flush mount model shall have a 1/2 inch skirt around the door section, while the surface mount model door section shall be flush with the back box. Both models use the same white 4 inch deep backbox with a single 1/2 inch/ 3/4 inch double knockout on the back center, and top and bottom of the backbox. The flush mount door section has exterior dimensions of 15-1/2 inches wide and 16-1/4 inches high. The surface mount model has dimensions of 14-1/2 inches wide, 15-1/2 inches high and 4 inches deep. Both models have a pull slam latch to open the continuous hinged door. Both models are available in white. An optional HVAC Emergency Shutoff red, mushroom type cutoff pushbutton and labeling shall be available as a seperate kit. The SP4-LOC shall be capable of being installed up to 2,000 feet from the SP40/2 or SP40S panel using 14-18 AWG wiring. Shielded wire is only required for the 1Vrms output from the SPRM. SPECIFICATION & ORDERING INFORMATION Model Number Order Nomenclature SP4-LOC-SB 4120 Surface Mount Local Operator Console SP4-LOC shown with optional HVAC Emergency shutoff switch SP4-LOC-FB 4121 Flush Mount Local Operator Console SP4-LOC-KIT 4122 HVAC Emergency Shutoff Switch Kit NOTE: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Wheelock Inc. standard terms and conditions. 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA V4000 LOC 07/06
WIRELESS /ATI CCSWH Central Control Station Description The Central Control Station (CCSWH) is designed to meet the requirements of military and industrial facilities for reliable Outdoor and Indoor Emergency Notification. The Central Control Station consists of a Central Control Unit that interfaces with a computer PC station running Wheelock Wireless Software. The Wheelock Wireless Software Package displays control and status activities, stores information and displays system operations. Interfaced with the Central Control Unit, the software processes and displays the FSK data received and transmitted. Standard Equipment The CCSWH includes Wheelock s Central Control Unit, Wheelock Wireless Software Package, Windows Operating System, computer, keyboard, monitor, printer, mouse, cables, and multi-outlet strip. Application The Central Control Station (CCSWH) is used to remotely activate and manage a virtually limitless number of independent SAFEPATH Evacuation Systems located throughout a facility, military base, or campus environment. The CCSWH communicates with each remote SAFEPATH unit via radio frequency data transfer, using highly secure Frequency Shift Keying (FSK) signaling technology. SAFEPATH units are interfaced directly with the CCSWH utilizing proprietary wireless Remote Controller interface units (RCIWH) installed alongside the SAFEPATH Evacuation Systems at remote field locations. The CCSWH provides a fully supervised two-way control communication link with each RCIWH and SAFEPATH, ensuring that the operator is immediately informed of any system status changes that may occur between supervisory interrogation periods. Critical alarms, including system activation, low battery and system trouble are immediate. Multiple CCSWH units can be configured to assure system redundancy. Features Performs Alarms, Public Address, Silent Test and Cancel Operations Operator interface requires minimal training Activates the system speakers and strobes and displays results Operates all Wheelock Outdoor and Indoor Emergency Notification Equipment Monitors unsolicited messages from remote sites (AC Fail, Intrusion, Sound, Battery Low, etc.). Single (Individual), group (Zone), or facility wide (Total) activations Manual polling on Individual, Zone, or Total indoor and outdoor equipment Configurable automatic scheduled polling or silent test operations Configurable alarm activations. The alarm configuration includes the alarm tone type, tone duration, pre-recorded messages (optional) and number of cycles the alarm is to be played Archives and prints reports for all system activities Automatic or manual operation reports Supervises communication between the Central Control Unit, Software and all remotely located equipment Simple to use activation alarm buttons Three levels of password protection (Activation, Services, and Configuration) Drop down menu displaying speaker status Supervised communications with additional Central Control Stations Ability to place Wheelock equipment out of service without disturbing Central Control Station Operations. VHF or UHF or trunked radio operation CCSWH-PORTLT can be powered by a standard 120 VAC or 13.5 VDC vehicle source Copyright 2002 Wheelock, Inc. All rights reserved.
Data Integrity The FSK encoding/decoding data communications format is transmitted over a conventional or trunked two-way RF system. For data error detection and integrity, extended parity check and redundant messaging systems are utilized. Each eight-bit block of information in the message is transmitted along with an eight-bit parity check. If the transmitted data does not match the parity code, the message is ignored, and therefore no remote alarm is detected, greatly eliminating the chances of false activation. Each data packet consists of three redundant messages to assure that at least one secure message will be received to properly activate the system. Added data security is obtained by the use of a timed synchronization code, which occurs upon system power-up, but is completely unrelated to the time of day. RCIWH s independently keep track of the unique synch code, along with the CCSWH. If the synch codes between the CCSWH an RCIWH s do not match, activation cannot occur. This prevents someone from recording an alarm message and playing it back later with the intention of falsely activating the system. Optional Features and Upgrades Touch Screen Monitor Upgrade Flat Screen Monitor Upgrade Laser Jet Printer Upgrade Pager Interface Allows alphanumeric pagers to display emergency information when the system is activated. Weather Station Interface Allows the computer to display weather information. Push Button Interfaces Allows remote Hardwired and Wireless Push Button Stations to activate the Emergency Notification System Message Sign Interface Allows outdoor facility message signs to display large alphanumeric emergency information when the system is activated Customized Map Displaying the facility and the location of the indoor and outdoor equipment Ordering and Description Information Model Number Order Description CCSWH 9950 Central Control Station Includes: (1) desk top receiver cabinet, system controller hardware & basic system software, alarm screen touchpad/ display, hand held (PTT) microphone, (1) 25 watt UHF or VHF radio, antenna polyphasor, power cord, 12 VDC/7AH battery, Pentium II 350 MHz computer, 17 color monitor, 32X CD ROM, Mouse, Windows 98 or NT, (1) Dot Matrix Printer, RS-232 Serial Port, Cables & Multi-outlet power strip. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8000 11/05
/ATI CCSWH-PORTLT PORTABLE CENTRAL CONTROL STATION Description The Portable Central Control Station (CCSWH-PORTLT) is designed to meet the requirements of the military and industrial facilities for reliable mobile command for emergency notification. Ordering and Description Information Model Number Order CCSWH-PORTLT 9952 Description Mobile Central Control Station Includes: (1) Panasonic Toughbook 48 laptop computer, system controller hardware & basic software, alarm screen touchpad/ display, handheld (PTT) microphone, (1) 25 watt UHF or VHF radio, magnetic mount vehicle antenna. The CCSWH-PORT central control station comes with a handle for easy transportation. Features Panasonic Toughbook 48 Lap Top Computer Computer Complies with Mil Spec: 8-10S Operates on 120 VAC or 13.5 VDC System controller hardware & basic software Alarm screen touch pad/display Handheld (PTT) microphone 25 watt UHF or VHF radio Magnetic Mount Vehicle Antenna Includes Handle for Easy Transportation From Vehicle to Vehicle NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8000_Port 11/05
WIRELESS /ATI CCUWH Central Control Unit Description The CCUWH Central Control Unit (CCU) is used to activate a system via the push buttons on its front panel or through the system software running on a connected computer. The CCU communicates via radio frequency with all of the system s Remote Controller Interface Units (RCIWH). The RCIWH interface with field devices to the Central Control System (CCS) and control outdoor speaker stations and internal SAFEPATH panels. Two-Way communication between the CCUWH and RCIWH s insures that you are informed on any changes in status that occur between interrogation periods. The time interval for interrogation is defined by the user. For critical alarms such as a low battery, a warning is immediately reported back to the CCUWH. Application The Central Control Unit (CCUWH) is used to remotely activate and manage multiple Evacuation Systems located throughout a facility, military base, or campus environment. The CCUWH communicates with each remote SAFEPATH unit via radio frequency data transfer, using highly secure Frequency Shift Keying (FSK) signaling technology. SAFEPATH units are interfaced directly with the CCUWH utilizing proprietary wireless Remote Controller Interace units (RCIWH) installed alongside the SAFEPATH Evacuation Systems at remote field locations. The CCUWH provides a fully supervised two-way control communication link with each RCIWH and SAFEPATH, ensuring that the operator is immediately informed of any system status changes that may occur between supervisory interrogation periods. Critical alarms, including system activation, low battery and system trouble are immediate. Multiple CCUWH units can be configured to assure system redundancy. Copyright 2002 Wheelock, Inc. All rights reserved. Features 8 Field programmable digital messages Simple front panel controls allow the user to select the activation and address (Total, Group, or Single) using only a few simple steps Cancel function to terminate an alarm Silent function allows diagnostic testing of speakers LCD display guides the user through the necessary steps to activate and report status information Desktop microphone to perform live public address Includes eight SPST relays and eight opto-coupler inputs to interface with external devices Uses Wheelock s advanced and secure FSK protocol for activating and status monitoring Configuration program allows the user to construct alarm sequences. Programmable for: Alarm tone types, tone durations, pre-recorded messages, and number of cycles The FSK transmissions include a security method to prevent unauthorized activations Interface to a conventional radio system, base station or leased line circuit Operates on internal UHF or VHF conventional radio to communicate with the speaker or SAFEPATH Evacuation Systems. Can be upgraded to a trunked radio system of 800 or 900 MHz
Data Integrity The FSK encoding/decoding data communications format is transmitted over a conventional or trunked two-way RF system. For data error detection and integrity, extended parity check and redundant messaging systems are utilized. Each eight-bit block of information in the message is transmitted along with an eight-bit parity check. If the transmitted data does not match the parity code, the message is ignored, and therefore no remote alarm is detected, greatly eliminating the chances of false activation. Each data packet consists of three redundant messages to assure that at least one secure message will be received to properly activate the system. Added data security is obtained by the use of a timed synchronization code, which occurs upon system power-up, but is completely unrelated to the time of day. RCIWH s independently keep track of the unique synch code, along with the CCUWH. If the synch codes between the CCUWH an RCIWH s do not match, activation cannot occur. This prevents someone from recording an alarm message and playing it back later with the intention of falsely activating the system. Optional Features and Upgrades Trunked Radio Upgrade Replaces standard radio with an 800 or 900MHz trunked radio to interface with an existing trunked system Lease Line Interface Upgrade Replaces conventional radio with a 2 pair (TX/RX) 600 ohm lease line interface. Mobile Upgrade Allows the CCUWH to operate in a vehicle CCSWH Central Station Upgrade Includes Wheelock Wireless Software Package, Windows Operating System, computer, monitor, printer, keyboard, mouse, cables and multi-outlet strip Rack Mount Station Upgrade Includes a vertical rack mount cage, shelves, and glass door which holds the CCUWH, computer equipment, and printer. Additional Messages can be added (up to 999 message files) Ordering and Description Information Model Number Order Description Size Weight LCD Display Size Operating Temperature CCUWH 9953 Stand Alone Central Control Unit (No Software Required) 6 H x 21 W x 16 D 23 LBS 20 character x 4 line -20 to 85 C ENGWHCCU 9987 Enginnering Charge for Stand Alone Central Control Unit NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8001 11/05
/ATI Description The Remote Controller Interface Unit (RCIWH) is a fully supervised wireless alarm monitoring station and two-way communications controller installed at independent fieldlocated SAFEPATH Evacuation System Panels. The RCIWH communicates with the Wireless Central Control Station (CCSWH) via radio frequency data transfer, using highly secure Frequency Shift Keying (FSK) signaling technology. Each RCIWH is identified as an independent addressable control point. Remote alarm activation signals, low battery signals, and system trouble conditions to the CCSWH(s) initiated by the SAFEPATH Evacuation System are transmitted via the RCIWH. The RCIWH s internal self-diagnostic watch dog circuitry also monitors tamper, system power conditions and data communication integrity. The RCIWH interfaces with each independent SAFEPATH to stream selectable voice commands, digital messaging and system control data directly from the CCSWH(s) over either conventional licensed radio frequencies (UHF, VHF, 800MHz and 900MHz ranges) or trunked RF communications systems. Superior internal surge suppression meets IEEE 587 and ANSI C37.90 standards for both the mother board and the antenna system. Each RCIWH is housed in a standard NEMA1-rated painted steel enclosure, or in an optional NEMA4 or stainless steel enclosure for severe weather resistance applications. Features Single Board Remote Controller Design Integral Radio for Communications with CCSWH Onmi-Directional Antenna System 24VDC or 120V AC options Eight (8) Standard System Alarm Inputs One (1) Standard System Trouble Input Eight (8) Standard System Outputs Expandable Alarm Initiation Points Wheelock Wireless Remote Controller (RCIWH) RCIWH Copyright 2002 Wheelock, Inc. All rights reserved.
Ordering and Description Information Model Number Order Description Weight (lbs.) RCIWH 9954 Remote Controller Interface standard configuarion includes: (1) cabinet, (1) 25 watt UHF or VHF radio, Antenna w/20 of Coaxial Cable, Antenna surge supressor, (1) 12 VDC, 7 AH Battery, (1) cabinet tamper switch, (8) 20 relay outputs, (8) inputs, a serial data port, (1) FSK Communications Modem & (1) system trouble circuit RCI14XWH 9956 Same as RCIWH but with a Stainless Steel Enclosure 60 IM15WH 9957 Input Module with 15 additional Inputs 2 OM8WH 9958 Output Module with 8 additional SPST Relays 2 ENGWHxx 99xx Engineering Charge for remote controllers (varies per applicaiton) N/A ASUTAWH 9988 Daily Charge for additional Start-up, training Assistance or Field Non-Warranty Service. Actual Expenses are additional. N/A Radio Frequency Licensing Fee. Note: This fee is only required when the system application requires a dedicated UHF or VHF Frequency. This fee covers the cost of preparing and submitting all necessary documentation to the FCC for approval. A site could already have an active frequency that is currently registered with the FCC thus eliminating the cost. RFLWH 9990 DTMFPROG 9993 The site can dedicate a frequency to the system as a segment of a master trunking radio system which they operate and it is registered with the FCC. These systems require radio upgrades in the Central Control as well as in the Remote Control Interface Panels and the High Power Speaker Stations. DTMF Software Programming for DTMF Handheld Radio (Note: Class of Service is supplied by user) N/A N/A NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8002 11/04
/ATI Description The Series HPSS High Power Speaker Stations provide reliable directional alarm tone notification and emergency voice instructions for industrial and facilities. High Power Speaker Stations Series HPSS HPSS8WH HPSS12WH HPSS16WH HPSS24WH HPSS32WH 800 watt speaker system, two 400 watt speakers 1200 watt speaker system, three 400 watt speakers 1600 watt speaker system. four 400 watt speakers 2400 watt speaker system, six 400 watt speakers 3200 watt speaker system, eight 400 watt speakers HPSS32WH Speaker Assembly Speaker Assembly: Includes mounting bracket, 50 feet of speaker and speaker pole mount kit. Control Enclosure: Includes NEMA4 stainless steel enclosure with ventilated battery compartment and mounting hardware. Siren control contains a microprocessor controller, conventional VHF or UHF radio, antenna with 20 of coaxial cable, antenna surge suppressor, local control push button alarms, tone generator, automatic gain control for live P.A., intrusion sensor, Class-D amplifiers, amplifier tray and battery charger. Battery compartment contains battery power switch, intrusion sensor, ventilation louvers, battery fuse and battery cables. Battery Requirements Model # of Batteries # of Amplifiers HPSS8WH 2 1 HPSS12WH 2 1 HPSS16WH 2 1 HPSS24WH 4 2 HPSS32WH 4 2 Radio and Radio Bracket Charger Circuit Breaker Voice and Tone Message Board Batteries RTU and Amplifier Combination Unit HPSS32WH Control & Battery Cabinet Features Omni sound pattern of 121-127 dbc measured at 100 ft. (Depending on model) Directional sound pattern can be configured for 90, 180, 270 or 360 degrees Directional sound pattern can be configured for 121dBC or 127dBC Speaker head provides vertical tilt to control sound spilling outside an industrial facility property line Speaker head direction provides intelligible sound due to minimization of sound reflection Produces ten standard alarm tones and live P.A. broadcast Automatic gain control for live voice Local and remote status reporting Copyright 2002 Wheelock, Inc. All rights reserved. Local and remote Silent Tests Patented Class-D Amplifier uses a unique drive that reduces both stress & heating, and improves the output effeciency of the audio transducer PC boards are conformal coated preventing damage from harsh environments Local and remote alarm tone and pre-recorded message broadcasts Radio is used to receive and transmit FSK data signals The FSK transmissions include a security method to prevent unauthorized activations Temperature-compensated battery charger Push button
Ordering and Description Information Model Number Order Description Weight (lbs.) HPSS8WH4X 9961 High Power Speaker Station equipped with (1) 800 Watt Speaker Head Assembly, NEMA-4 Stainless Steel Control Cabinet and Cabinet Mounting Bracket. The Control Cabinet contains: (1) Wireless Controller, (1) UHF or VHF Radio, Antenna with 20 of Coaxial Cable, Antenna Surge Supressor, (1) Push Button for local activation, tone generator, automatic gain control for live 70 Microphone operation, tamper switch, amplification tray, digital messaging module for up to 10 messages, battery charger, Battery compartment which contains a battery power switch, intrusion sensor, ventilation louvers, fuse set and cables. Unit oeprates on either 120 or 240 VAC. HPSS12WH4X 9963 Same as the HPSS8WH except the power is 1,200 Watts 250 HPSS16WH4X 9965 Same as the HPSS8WH except the power is 1,600 Watts 300 HPSS24WH4X 9967 Same as the HPSS8WH except the power is 2,400 Watts 400 HPSS32WH4X 9969 Same as the HPSS8WH except the power is 3,200 Watts 500 DMRTWH 9973 Digital Message Recording Time per Message N/A ENGWHxx 99xx Engineering charge (varies per installation) BAT-12100M 9959 12 VDC 100 AH Marine Battery Specifications: General Operating Temperature -30 C to +85 C Humidity 0% to 95% Non-Condensing Standby w/out AC 2.5 days (2 batteries) 5 days (4 batteries) Alarm Duration 30 minute duration Weight 187 lbs. (without batteries) 800W Speaker Weight 70 lbs. Controller Cabinet (top) H 24 in. x W 30 in. x D 13 in. Battery Cabinet (bottom) H 15 in. x W 30 in. x D 15 in. Electrical AC Input Voltage Operating Current 120VAC/240VAC 50-60 Hz 3.5 Amps for 120VAC/2.0 Amps for 240VAC Communications Communications FSK (Frequency Shift Key) Radio Output Power 2-25 Watt Antenna Surge Protection 50,000 Amps IEC Amplifier Frequency Operating Range 250 to 5kHz Output Impedence 0.5 ohms Thermal Shutdown Protection 90 C Total Harmonic Distortion 5% NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8003 11/05
/ATI CUSTWH Wireless Emergency Warning System Software and Engineering Design Description The windows-based Wireless Emergency Warning System Software acts as an interactive operator control system. The Graphical User Interface (GUI) and a system programming tool can be installed at one or more host computer systems at the Wireless Central Control Station(s) (CCSWH). The software provides the user with several programmable tiers of operator security and password protection, while identifying and managing remote alarm points and trouble conditions via wireless Remote Controller Interface Units (RCIWH) which integrate with the SAFEPATH Evacuation Systems. Using a standard mouse or an optional touch screen interface, the operator can perform various automatic test, verification and control functions, including selectable system activation (individually by RCIWH, by pre-defined groups of RCIWH s, or via system-wide All Call), selectable public addressing override functions and custom digital messaging functions at the Wireless Central Control Station(s). The software also provides standard configurable performance parameters, system status reporting, system trouble indications, pull down operator menus and easy to understand help files for simplicity of operation. Functionality When an alarm condition is initiated in the field, the wireless RCIWH will transmit a unique signal to the Wireless Central Control Station(s), identifying the location of the alarm, and the specific type of alarm condition. The control system will either automatically respond to the alarm based on a pre-determined conditional response, or it can be manually over-riden by the operator. The operator can select remote SAFEPATH location or zones of protection and provide live Public Addressing functions throughout the system on command. Emergency tones and digital messages can also be initiated automatically or manually from the master Wireless Central Control Station, to complete the systemwide integration and operation of all remote sites. Specialized Services & Options Comprehensive Acoustic Analysis and Modeling Customized software engineering Turn key integration and locally authorized services Trunking radios for communication with 800 MHz and 900MHz systems Customized digitalized messaging Start-up assistance, training and documentation Lease-to-own purchasing options
Ordering and Description Information Model Number Order Description CUSTWH 9978 System Software Customization The Engineering, Software Customization, System Start-up & Training Fees are an initial charge which must be included as a separate line item on every system. This fee covers initial system software engineering costs to customize the user software to every sites s specific needs. Initial start-up costs include the services of a qualified project engineer onsite with the installation entity to assist in putting the system on line & one full day of user training on the system. System documentation will include user manuals, a system software manual & executable software disks. Note: Software changes not included in the initial specification will be negotiated on a case-by-case basis. System start-up assistance and 1 day of user training. Additional time for start-up assistance or training will be negotiated on a case-by-case basis. NATIONAL SALES OFFICE 800-631-2148 Canada 800-397-5777 E-Mail: Info@wheelockinc.com http://www.wheelockinc.com WE SUPPORT AND ENCOURAGE NICET CERTIFICATION MADE IN THE USA 3 YEAR WARRANTY Distributed By: 273 BRANCHPORT AVENUE LONG BRANCH, NJ 07740 TEL: 732-222-6880 FAX: 732-222-2588 WW8004 11/05
Strobe - 5 Joules, Hazardous Location XB11 Strobe/Sounder Combination Unit Description: These certified strobes have been designed for use in potentially explosive gas and dust atmospheres and harsh environmental conditions. The glass reinforced polyester enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The strobe housing is manufactured completely from a U.V. stable, glass reinforced polyester. Stainless steel screws and mounting bracket are incorporated ensuring a totally corrosion free product. Units can be painted to customer specification and supplied with identification labels. Features*: UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups C & D Class I, Zones 1 & 2, AExd IIB T4/T5 Ordinary locations: Visual-Signal Device ATEX approved NEMA 4x & 6, IP66 and IP67 Certified temperature 67 F to +158 F ( 55 C to +70 C) Corrosion resistant GRP Optional stainless steel backstrap Various lens colors Optional lens guard Output 22,000 candela 4 wire monitored connection Available as a status light Xenon 24 VDC, 110 and 240 VAC *Depending on version Architects and Engineers Specifications Strobes for hazardous locations and harsh environments shall be UL and cul Listed for Class I, Division 2, Groups C&D, and Class I, Zones 1&2, AExd IIB T5 applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. The strobe appliances shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67 F to 158 F (-55 C to 70 C). The strobe shall be rated to flash at 1 Hz with 5 joules per flash. Rated current draw shall not exceed 320 ma at 24 vdc. The strobe shall be capable of direct surface mounting in any direction. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
ALL DIMENSIONS IN MILLIMETRES Specification Certification: Material: Finish: UL Listed for USA and Canada to: Hazardous locations: Class I, Div 2 Groups C & D. Class I, Zones 1 & 2 AExd IIB T4/T5. UL Listing No: E187894. Ordinary locations: Visual-Signal Device. UL listing No. S8128. ATEX approved: EExd IIB T5/T6 Cert. No. 99 ATEX 2195X CENELEC EN50014 and EN50018 Body: Glass reinforced polyester (GRP). Lens: Glass. Cover Screws + Backstrap: Stainless steel 316. Natural black or painted to customer specification. DC AC50/60 Hz Voltage 24 110 240 XB11 Tube Energy (Joules) 5 5 5 Peak Current Consumption (ma) 320 100 60 Effective Intensity (Cd) 29 29 29 Peak Intensity (Cd) 22213 22213 22213 Power Consumption (Watts) 8 11 14.4 NOTE: The Cd figures are for a clear lens @ 1Hz flash rate. Weight: Certified Temperature: Ingress Protection: Terminals: Labels: Entries: Strobe/Sounder Unit: FOR COLORED LENSES 5-1/2lb./2.5Kg. 67 F to +158 F ( 55 C to +70 C) hazardous locations 67 F to +131 F ( 55 C to +55 C) ordinary locations NEMA 4x & 6, IP66 & IP67. 6 off suitale for up to 14 AWG conductor size Duty/Tag Label optional. 2 x 1/2" NPT The strobe may be combined with an MEDC sounder to create a visual/audible alarm. Contact MEDC for price and specification. Color Red Blue Amber Green Yellow Multiplying Factor 0.15 0.12 0.51 0.49 0.86 The photometric data has been verified by BSI. A report is available if required. Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Certification Voltage Flash Rate Lens Color Lens Guard Unit Fixing Earth Continuity Tag/Duty Label Other Options Unit Finish XB11 N Certification UL UL UL (Ordinary location) UW Voltage 24V d.c. 024 110V a.c. 110 240V a.c. 240 Color Red Blue Green Amber Yellow Clear R B G A Y C Flash Rate 60/min 06 Other flash rates available, please specify. Guard None Yes N Y Unit Fixing Direct Mounting D Backstrap B Continuity None Label None N Yes Y (Please specify) N Finish Option Natural Black Red Blue Yellow Grey White Special Finish Blanking Plug None Standard Models Series Model Number Order Decription XB11 XB11UL02406RNBNNNR 109201-001 Strobe, Red lens, 5 Joules, 24 VDC, Red Finish XB11 XB11UL02406CNBNNNR 109201-002 Strobe, Clear lens, 5 Joules, 24 VDC, Red Finish XB11 XB11UL02406RNBNNNN 109201-003 Strobe, Red lens, 5 Joules, 24 VDC, Black Finish N R B Y G W S P N 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XB11 08/06
Strobe - 21 Joules, Hazardous Location XB12 Description: These high output certified strobes have been designed for use in potentially explosive atmospheres and harsh environmental conditions. The enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The strobe housing is manufactured completely from a U.V. stable, glass reinforced polyester. Stainless steel screws and mounting bracket are incorporated ensuring a totally corrosion free product. Units can be painted to customer specification and supplied with identification labels. Features*: UL Listed for USA and Canada Hazardous locations: Class I, Div 2, Groups C & D. Class I, Zones 1 & 2, AExd IIB T4 & T5. Ordinary locations: Visual-Signal Device ATEX approved High Output (124,000 candela) NEMA 4x & 6, IP66 and IP67 Certified temperature 67 F to +158 F ( 55 C to +70 C) Corrosion resistant GRP Optional stainless steel backstrap Various lens colors Optional lens guard 4 wire monitored connection 24 VDC, 110 & 240 VAC Xenon Twin replaceable tubes Architects and Engineers Specifications Strobes for hazardous locations and harsh environments shall be UL and cul listed for Class I, Division 2, Groups C&D, and Class I, Zones 1&2, AExd IIB T4/T5 applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67 F to +158 F (-55 C to +70 C). The strobes shall be rated to flash at 1 Hz with 21 joules per flash. Rated current draw shall not exceed 1400 ma at 24 vdc. The strobe shall be capable of direct surface mounting in any direction. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Specification Certification: Material: Finish: Weight: Certified Temperature: Ingress Protection: Terminals: Labels: Entries: Configuration Options: Voltage 24V d.c. 024 110V a.c. 110 240V a.c. 240 Guard None Yes N Y Continuity None DC AC50/60 Hz Voltage 24 110 240 XB12 Tube Energy (Joules) 21 21 21 Peak Current Consumption (ma) 1400 350 185 Effective Intensity (Cd) 355 355 355 Peak Intensity (Cd) 123691 123691 123691 Power Consumption (Watts) 33.6 38.5 44.4 NOTE: The Cd figures are for a clear lens @ 1Hz flash rate. The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Certification Voltage Flash Rate Lens Color Lens Guard Unit Fixing Earth Continuity Tag/Duty Label Options Unit Finish XB12 N Certification UL UL UL (ordinary locations) UW Flash Rate 60/min 06 Other flash rates available, please specify. Color Red Blue Green Amber Yellow Clear R B G A Y C Unit Fixing Direct Mounting D Backstrap B For Colored Lenses Color Red Blue Amber Green Yellow Multiplying Factor 0.15 0.12 0.51 0.49 0.86 The photometric data has been verified by BSI. A report is available if required. Label None N Yes Y* *(Please specify) Standard Models Series Model Number Order Decription XB12 XB12UL02406RNBNNNR 109204-001 Strobe, Red Lens, 21 Joules, 24 VDC, Red finish XB12 XB12 UL Listed for USA and Canada: Hazardous locations: Class I, Div 2 Groups C & D. Class I, Zones 1 & 2 AExd IIB T4/T5. UL Listing No: E187894. Ordinary locations: Visual-Signal Device. UL listing No. S8128. ATEX approved: EExd IIB T4/T5 Cert. No. 99 ATEX 2196 Body: Glass reinforced polyester (GRP). Lens: Toughened Glass. Cover Screws + Backstrap: Stainless steel 316. Natural black or painted to customer specification. 15-1/2lb./7.0Kg. 67 F to +158 F ( 55 C to +70 C) hazardous locations 67 F to +131 F ( 55 C to +55 C) ordinary locations NEMA 4x & 6, IP66 & IP67. 6 off suitale for up to 10 AWG conductor size Duty/Tag Label optional. 2 x 1/2" NPT XB12UL02406CNBNNNR 109204-002 Strobe, Clear Lens, 21 Joules, 24 VDC, Red finish XB12UL02406RNBNNNN 109204-003 Strobe, Red Lens, 21 Joules, 24 VDC, Black finish N Finish Natural Black Red Blue Yellow Grey White Special Finish Options Blanking Plug None P N N R B Y G W S 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XB12 08/06
Strobe - 355 Candela, Hazardous Location XB15 XB15 Pipe Mount (with cast guard) XB15 Direct Mount (with wire guard) Description: These listed strobes have been designed for use in potentially explosive atmospheres and harsh environmental conditions. The enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The housings are manufactured completely from a U.V. stable, glass reinforced polyester. Stainless steel screws and mounting bracket are available ensuring a totally corrosionfree product. The model XB15 contains a polarization diode and four wire lead connections for fire alarm applications. Units can be painted to customer specification and supplied with identification labels. Features*: UL listed for USA and Canada Hazardous locations: Class I, Div. 2, Groups A, B, C & D. Class I, Zone 1, AExd IIC T5/T6 Class II, Div. 2, Groups F & G Ordinary locations: Visual-Signal Device ATEX approved NEMA 4x & 6, IP66 & 67 Certified temperature 67 F to +158 F ( 55 C to +70 C) 520,000 peak candlepower Pipe mount or direct mount enclosure Corrosion-free GRP Four wire monitored connection Optional stainless steel backstrap (direct mount version only) Various lens colors Optional relay Optional cast or wire lens guard Up to 3 x 3/4" NPT entries Filament version available (100W max) *Depends on version Architects and Engineers Specifications Strobes for hazardous locations and harsh environments shall be UL and cul Listed for Class I, Division 2, Groups A,B,C&D, and Class I, Zones 1, Class II, Div 2, Groups F & G, AExd IIC T5/T6 applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 & IP 67 environmental requirements over a temperature range of -67 F to +158 F (-55 C to +70 C). The strobes shall be rated to flash at 1 Hz with 15 joules per flash. Rated current draw shall not exceed 780 ma at 24 vdc. The strobes shall be available for direct surface mounting or pipe mounting and shall be able to mount in any direction Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Specification Certification: UL Listed for USA and Canada: Hazardous locations Class I, Div 2, groups A, B, C & D. Class 1, Zone 1 Class II, Div 2, groups F & G, AExd IIC T4/T5. UL listing No. E187894. Ordinary locations: Visual Signal Device. UL listing No. S8128 CENELEC EN50014 & EN50018. ATEX Cert. No. Baseefa 04ATEX0009X. Material: Finish: Voltage: Tube Energy: 15 Joules. Tube Life: Flash Rate: Body: Glass reinforced polyester. Lens: Glass. Backstrap: stainless steel 316. Wire Guard (optional): Stainless steel wire. Cast Guard (optional): Aluminium LM25M. Natural black or epoxy painted to customer specification. 24, 48V d.c. 110, 120, 230, 240, 254V a.c. >1 x 10 6 flashes. 60, 80, 120 fpm. Certified -67 F to +104 F (T6) -55 C to +40 C (T6) Temperature: -67 F to +131 F (T5) -55 C to +55 C (T5) Weight: Pipe mount: 5.75lb./2.6kg; Direct mount: 6.5lb./3.0kg. Ingress Protection: Entries: Terminals: NEMA 4x &6, IP66 & IP67. Supplied as 2 x ¾" NPT (direct mount) or ¾" (pipe mount) as standard. Other options available: Up to 3 x ½" NPT or 3 x ¾" NPT (direct mount); ½" NPT (pipe mount) contact sales office to order. Direct mount: 12 x 14AWG Pipe mount: 8 x 14AWG Relay Initiate: Available on all units suitable for 24V d.c. supplies only. Labels: Tag/Duty label option. Electrical Ratings: d.c Voltage 24 48 110 120 230 240 254 Current (ma) 780 670 400 400 200 200 170 Effective Candela - 330 Tube Energy (Joules) 15 15 15 15 15 15 15 Multiplying Factor for Colored Lenses: Red Blue Amber Green Yellow 0.15 0.12 0.51 0.49 0.86 a.c Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Lens Lens Unit Other Model Certification Voltage Flashrate Color Guard Fixing Options Finish XB15 Certification UL UL (ordinary location) UL UW Voltage 24V d.c. 024 48V d.c. 048 110V a.c. 110 120V a.c. 120 230V a.c. 230 240V a.c. 240 254Va.c. 254 Fpm 60 06 80 08 120 12 Color Red Blue Green Amber Yellow Clear Guard None Cast Wire Standard Models Series Model Number Order Decription XB15 XB15UL02406RWPNN 109203-001 330 candela Red Lens, Black finish, 24 VDC XB15 XB15UL02406RWBNN 109203-002 330 candela Red Lens, Black finish, 24 VDC R B G A Y C XB15 XB15UL02406CWBNR 109203-205 Clear Lens, 330 candela, 24 VDC, Pipe mount, Black finish XB15 XB15UL12006AWBNN Amber Lens, 330 candela, 120 VAC, backstrap mount, Black 109202-005 finish XB15 XB15UL12006AWPNN Amber Lens, 330 candela, 120 VAC, Pipe mount, Black 109202-006 finish XB15 XB15UL12006RWBNN Red Lens, 330 candela, 120 VAC, backstrap mount, Black 109202-007 finish XB15 XB15UL12006RWPNN 109202-208 Red Lens, 330 candela, 120 VAC, Pipe mount, Black finish N C W Option None Tag label Duty label Relay initiate* Blanking Plug Unit Fixing N T D R P *Suitable for 24V d.c. supplies only. Pipe mount P Direct mount D Direct w/backstrap B Contact Sales Office if ½" NPT is required. Finish Natural Black Red Blue Yellow Green White Special Finish N R B Y G W S 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XB15 04/07
Strobe - 10 Joules, Hazardous Location XB16 Description: These listed strobes have been designed for use in potentially explosive atmospheres and harsh environmental conditions. The enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance is required. The housing is manufactured from a U.V. stable, glass reinforced polyester, with the lens manufactured from a U.V. stable polycarbonate. Stainless steel screws are used ensuring a totally corrosion-free product. The model XB16 contains supervisory diode and four wire leads for fire alarm applications. This strobe is also available UL 1971 (ADA) listed for hearing impaired applications. Units can be painted to customer specification and supplied with identification labels. Features*: UL listed for USA and Canada Hazardous locations for USA and Canada Class I, Div. 2, Groups A, B, C & D Class II, Div. 2, Groups F & G UL 1971 compliant version available Ordinary locations: Visual Signal Device T Rating model dependent. Contact sales office for information NEMA 4x & 6, IP66 & 67 Certified temperature 67 F to +158 F ( 55 C to +70 C) Pipe mount with ¾" NPT entry Corrosion-free GRP enclosure 580,000 peak candlepower Polycarbonate lens, various colors available 4 wire diode monitored board Optional relay initiate Optional lens guard *Depends on version UL 1971 version available with clear lens only. Architects and Engineers Specifications Strobes for hazardous locations and harsh environments shall be UL and cul listed for Class I, Division 2, Groups A,B,C&D applications and shall be listed under UL Standard 1638 for Indoor/Outdoor use. The strobes shall be available with UL 1971 Listing (Standard for Safety Signaling Devices for Hearing Impaired). They shall be constructed of lightweight, UV stable glass reinforced polyester, shall be corrosion resistant, and shall meet NEMA 4x, NEMA 6, IP 66 and IP 67 environmental requirements over a temperature range of -67 F to 158 F (-55 C to 70 C). The strobes shall be rated to flash at 1 Hz with 10 joules per flash. Rated current draw shall not exceed 890 ma at 24 vdc. The strobes shall be pipe mounted and shall be capable of mounting in any direction. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions.
XB16 RANGE (Shown with optional guard fitted) All dimensions in millimetres Specification Certification: UL Listed for USA and Canada: Hazardous locations for USA and Canada: UL1604. Class I, Div 2, groups A, B, C & D. Class II, Div. 2, groups F & G UL listing No. E251185. Ordinary locations: Visual Signal Device: UL1638. UL listing No. E251185. Hazardous locations for hearing impaired: UL1971. UL listing No. E251185. Material: Finish: Voltage: Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Other Model Certification Voltage Flashrate Lens Color Guard Options Finish XB16 Body: Glass reinforced polyester. Lens: U.V. stable polycarbonate. Lens screws: stainless steel 316. Natural black or painted to customer specification. 24, 48V d.c. 110, 120, 230, 240, 254V a.c. Conforms to UL regulated voltage output (24Vdc, 120Vac, 240Vac). Certified -67 F to +158 F ( 55 C to +70 C) Temperature: Tube Energy: 10 Joules. Tube life: Weight: >1 x 10 6 flashes. 2.2lb./1.0 Kg. Ingress Protection: NEMA 4x & 6, IP66 & IP67. Entries: Standard 1 x ¾" NPT pipe mount. (Contact Sales Office if ½" NPT is required). Terminals: Labels: Electrical ratings: 8 x 14AWG Tag/Duty label option. DC Voltage 24 48 110 120 230 240 254 Current 0.89 0.30 0.38 0.38 0.22 0.22 0.18 Effective candlepower (Cd): 285 at 60 f.p.m. Peak candlepower: 580,000 (Peak candlepower is the maximum light intensity generated by a flashing light during its light pulse) UL 1971 On-axis output: 15 Cd. Multiplying factor for colored lenses: Red Blue Amber Green Yellow 0.15 0.12 0.51 0.49 0.86 Relay Initiate: 24V dc relay initiate only. AC Certification UL UL (ordinary locations) UL 1971 UL UW US Voltage 24 VDC 024 48 VDC 048 110 VAC 110 120 VAC 120 230 VAC 230 240 VAC 240 254 VAC 254 Flashrate 60 fpm 60 80 fpm 80 120 fpm 120 Standard Models Series Model Number Order Decription XB16 XB16UL02460RYNN Strobe, Red lens, 10 Joules, 24 VDC, 109202-001 black finish XB16 XB16US04860CYNR Strobe, Clear lens, 10 Joules, 24 VDC, 109202-002 black finish Color Red R Blue B Green G Amber A Yellow Y Clear C* *UL 1971 version available with clear lens only Guard Yes None Option Y N Finish Tag label T Duty label D Relay initiate* R None N *Suitable for 24V dc supplies only. Natural Black Red Blue Yellow Green White Special Finish N R B Y G W S 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XB16 08/06
Strobe, 21 Joules, Explosion Proof XB4 Description: These high output (21 Joule) strobes have been designed for use in potentially explosive atmospheres and harsh environmental conditions. The marine grade alloy or stainless steel enclosures are suitable for use offshore or onshore, where light weight combined with corrosion resistance and strength is required. Units can be painted to customer specification and fitted with identification labels. Features*: UL Listed for USA and Canada Hazardous locations: Class I, Div 1, Groups C & D Class I, Zone 1, AExd IIB T4 Ordinary locations: Visual-Signal Device ATEX approved Certified temperature 67 F to +158 F ( 55 C to +70 C) NEMA 4x & 6, IP67 and IP66 Various lens colors Twin replaceable tubes Tapered spigot flamepath. 4 wire monitored connection Optional lens guard 24 VDC 110 & 240 VAC Xenon *Depending on version. Architects and Engineers Specifications Explosion-proof strobes shall be UL and cul Listed for Class I, Division 1, Groups C&D, and Class I, Zone 1, AExd IIB T4 hazardous locations and shall be listed under UL Standard 1638 for Indoor/Outdoor use. The strobes shall be constructed of marine grade alloy with an epoxy paint finish and shall meet NEMA 4x, NEMA6, IP 66 and IP 67 environmental requirements over a temperature range of -67 F to 158 F (-55 C to 70 C) in hazardous and harsh environments. The strobe shall be rated to flash at 1 Hz with 21 joules per flash. Rated current draw shall not exceed 1400 ma at 24 vdc. The strobe shall be capable of direct surface mounting in any direction. Note: Due to continuous development of our products, specifications and offerings are subject to change without notice in accordance with Cooper Wheelock standard terms and conditions. ATEX
Specification DC AC 50/60 Hz Voltage 24 110 240 254 Tube Energy (Joules) 21 21 21 21 Peak Current Consumption 1400 350 185 210 (ma) Effective Intensity (Cd) 355 355 355 355 NOTE: The above figures (Cd) are for a clear lens @ 1Hz flash rate. The photometric data has been verified by BSI. A report is available if required. FOR COLORED LENSES Color Red Blue Amber Green Yellow Multiplying Factor 0.15 0.12 0.51 0.49 0.86 (Approximate) Terminals: Entries: Materials: Weights: Finish: Up to 8 x 8 AWG Up to 3 x 1/2" or 3/4" NPT LM25TF Marine Grade Alloy body. Grade 316 ANC4B Stainless Steel body. Toughened Wellglass. LM25: 14.5lb./6.6kg. Stainless Steel: Add 18.5lb./8.5kg. Red epoxy paint finish as standard or to customer's specification. Certification: UL Listed for USA and Canada Hazardous locations: Class I, Div 1 Groups C-D Class I, Zone 1 AExd 11B T4 Listing No. E187894. Ordinary locations: Visual-Signal Device. Listing No. S8128. ATEX approved: EExd IIC T5 Cert. No. Baseffa 02ATEX0224X Certified Temperature: 67 F to +158 F ( 55 C to +70 C) Ingress Protection: NEMA 4x & 6, IP66 & 67 Configuration Options: The following code is designed to help in the selection of the correct unit. Build up the reference number by inserting the code for each component into the appropriate box. Cable Flash Other Lens Lens Tag/Duty Type Certification Voltage Terminals Entries Rate Options Guard Color Label Material Finish XB4 Voltage 24VDC B 110VAC E 240VAC H Certification UL UL UL (ordinary locations) UW Entries 1 /2" NPT *D 3 /4" NPT *E *prefix entry size (see diagram above) with entry position code e.g. 1D2D. Flash Rate 60/min. 06 120/min. 12 240/min. 24 Terminals & Type 8 x 8 AWG 8D Options None Yes* *Please specify Lens Guard None Yes N Y A Y Color Red R Blue B Green G Yellow Y Amber A Clear C Duty Label None N Yes* Y *(Please specify) Finish Red Blue Yellow Grey White Other specify R B Y G W S Material Stainless steel 0 Alloy 1 Standard Models Series Model Number Order Decription Strobe, Red Lens, 21 Joules, 24 XB4 XB4ULB8D2E3E06ANRN1R 109205-001 VDC, Red finish XB4 XB4ULB8D2E3E06ANCN1R 109205-001 Strobe, Clear Lens, 21 Joules, 24 VDC, Red finish 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XB4 04/07
Series XRT Explosion Proof Relay XRT-T-40 Description: Cooper Wheelock s Explosion Proof Relays are precision built of extremely rugged materils for long, trouble-free life in hazardous and diffi cult enviornmentjs. Designed primarily for telephone systems, they sense low voltage AC or DC and switch 115 and 220 volts AC at 60 Hz or 115 volts DC with contact arrangement; single-pole, normally open, double A (double make in parallel). The XRT-T-40 has a 0.45 microfared blocking capacitor in series with the coil and a one megohm resistor across the capacitor. The XRT-T-40 is FCC registered. The XRT Explosion Proof Relay is designed to switch high (115 or 220) voltage using low voltage, such as ringing current in telephone systems, as the controlling voltage. These units can switch devices controlled by low current controlling systems. The units are easy to handle and install, and provide convenient access to coil and contact terminals. The units are UL listed and CSA approved for the following hazardous atmospheres: CLASS I, GROUP C Atmospheres containing ethyl and ether vapors CLASS I, GROUP D Atmospheres containing gasoline, petroleum, naphtha, alcohols, acetone, benzene, lacquer solvent vapors, and natural gas CLSSS II, GROUP F Atmospheres containing carbon black, coal, or coke dust CLASS II, GROUP G Atmospheres containing fl our, starch, and grain dusts Specification and Ordering Information: Model Number Order Operating Voltage XRT-T-40 0221 90V-20 Hz 273 Branchport Avenue Long Branch, NJ 07740 Phone: (800) 631-2148 Fax: (732) 222-2588 www.cooperwheelock.com U L WE ENCOURAGE AND SUPPORT NICET CERTIFICATION 3 YEAR WARRANTY Made in USA XRT 5/06