WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING



Similar documents
BREEAM CRITERIA WATER LEAK DETECTION SYSTEM Type WG2 - CONTROL PANEL CONNECTIONS

OPL BASIC. Dosing System for Professional Laundry machines. Contents

TMS TANK MANAGEMENT SYSTEM

CB200W Water Leak Detection Panel Application Guide

HERZ-Thermal Actuators

FLOW CALCULATOR INSTRUCTION MANUAL MESURES BAMOPHOX M1 02 E MES FLOW CALCULATOR /1

FIREDEX Conventional Fire Panels

User Manual. Humidity-Temperature Chart Recorder. Model RH520

WD-AMX Water Detection Controllers

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Memcom Emergency Telephone

Electronics Ltd. Presenting. Power, Intelligence... with a sense of feeling

Switch Actuator, 8-fold, 10 A, MDRC AT/S , GH Q R0111

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

ACS-30-EU-EMDR-10-MOD

Multifunction devices

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

MILLENIUM INSTALLATION MANUAL NTR 735 A. Simple Automation Control Module (MAS)

ACTIVE 5 ENGINEERING MANUAL

is then retained absolutely without interruption.

TS510 & TS500. Installation & User Guide. Compatible Equipment

Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact

Disabled Toilet Alarm. Contractor Pack. Installation & Operating Instructions

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

Installation and User Guide

Fire Alarm Control Panel. Family. Operating Manual

Assisted lift operated 2/2-way solenoid valves Type EV250B

1115 4G SERIES GOVERNOR ma ANALOGUE DIGITAL SPEED SETTING

Safety Manual BT50(T) Safety relay / Expansion relay

Streaming Potential System (SPT1000, SPD1000)

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

ADM1TE 5/30A DIN rail single phase two wire energy meter

How To Power A Power Control On An Ip40 (Ipl) With A Power Supply (Iplug) With An Ip20 Controller (Iphones) With Power Control (Power Control) With No Antenna) With The Ip20 (Power)

How To Use A Ds340 (Dsp)

Digital Keypad Use s Manual

DRM75A 230V 20/100A DIN rail single phase two wire energy meter

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

CO2 Alarm. Operation. Application

USER MANUAL CHARGING STATIONS FOR ELECTRIC VEHICLES

Instruction Manual for Operating Panel 301 and 302

ALARMLINE ANALOGUE Linear Heat Detection System

Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual

BlueSolar Pro Remote Panel For BlueSolar PWM-Pro charge controllers 12/24V 5, 10, 20, 30A Article number SCC

LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems

Flexible Counter Series in DIN size 24 x 48 mm

Conventional Fire Detection and Extinguishant Control System Specification

EM-PQ 1500 Power Quality Monitor. Operating Manual

LIEBERT VNSA Installation Sheet

CONNECTOR AMPLIFIER FOR PROPORTIONAL VALVES (4-20 ma Input Version)

EK908FHL - Thermostat for floor heating

D-MAX WEB GUIDE CONTROLLER WITH OPERATOR INTERFACE PANEL QUICK START SETUP MANUAL

TCR easy Plus Alarm. Operating Instructions

Introduction. Refrigerant Leak Detecting System. Feature and Benefits

MAKING MODERN LIVING POSSIBLE. AK-SC255 On-Site Installation Guide DANFOSS ELECTRONIC CONTROLS & SENSORS

AC-115 Compact Networked Single Door Controller. Installation and User Manual

PSU-U-24V/AC-6A/10/FTA-TR-MC PSAC 0624

Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers

TECHNICAL DATASHEET #TD1404AX PWM CONTROLLED SOLENOID DRIVER

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

To Purchase This Item, Visit BMI Gaming Operation Manual

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

WE-350 Series ¼ Turn Electric Actuator

Automation System TROVIS 6400 TROVIS 6493 Compact Controller

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

LD2 One & Two Zone Water Detection Alarm Installation and Operation Manual

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

HM-W536 Install Guide

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

ALARMS-xx. Remote Alarm Unit Setup Guide RESET ALL

Limited Service Fire Pump Controllers Features

STERILIZERS, LABORATORY DRYING OVENS

GERONIMO ANALOGUE HEAVY DUTY TELEPHONE

The Child Reminder System Installation Manual

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

PC INTERFACE MODULES FOR TOLL-PLAZA CLASSIFICATION SENSORS

Industrial Ringdown/Autodialer Telephone SCR Series

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

How To Program An Autodialer

Active Speaker System LX523 AUDAC PROFESSIONAL AUDIO EQUIPMENT. Active Speaker System with remote input LX523. User Manual & Installation Guide

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

PK5500 v1.1 Installation Instructions

UM-X Field display for continous level sensors

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

Advantium 2 Plus Alarm

OPERATING INSTRUCTIONS (TRANSLATION OF THE ORIGINAL) SUPPLEMENTARY OPERATING INSTRUCTIONS FOR YOUR AIR CURTAIN SYSTEM. Serial number: Year: --- Page 1

Water Leak Detection System

PSDC PSDC 12V/8A/8x1A Power supply for up to 8 analog cameras PTC/TOPIC.

REGTRONIC OPERATING INSTRUCTIONS

Heating and Hot Water Services Controls General Technical Specification

DIGITAL ALARM CLOCK RADIO

* DISCLAIMER: Contents. How to Use This Guide: COMMERCIAL INSTALL GUIDE 2

D200+ Auto-Dialler Installation/Operators Manual

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

GSM Autodialer Professional GJD700 Speech & Text Autodialer

O C M III. Open Channel Flow Monitor

MOUNTING AND OPERATING INSTRUCTIONS

Transcription:

WATER LEAK DETECTION SYSTEM WLDS-10 INSTALLATION & COMMISSIONING DESCRIPTION: An electronic control panel used in conjunction with one pulse meter (water meter with pulse output proportional to flow rate) installed on the incoming water supply. The control monitors the flow of water through the meter and raises an alarm in the following situation: When a continuous flow of water passes through the Main water meter above a preset maximum for a preset period of time Hence by setting the flow rates and time periods (allowing for usual fluctuations in consumption) any increase above these norms may be detected and dealt with saving water and limiting damage caused by a major leaks. IMPORTANT: In order to enter meaningful parameters into the control panel we recommend that an initial Water Audit is undertaken using the water meter supplied. This will establish usual patterns of consumption over a given period of time (typically 1 week). Readings should include night/weekend, peak periods and other situations where differing consumption levels are expected. These readings and their interpretation will be unique to each installation. LCD display & keypad This incorporates a 2 line 16 character LCD display with LED backlighting. The keypad and display enable the user to enter parameters and monitor water flow. INSTALLATION: Fix the steel enclosure in a suitable position protected from the elements as close to the pulse meter as is practicable. A 240v 50Hz supply (5A spur) with means of disconnecting the power will be required.

Connect single phase supply to terminals E, L & N using 0.75 or 1.0 mm² cable - see wiring diagram - Fig 1 Connect Main (M1) pulse meter using 2 core 0.5 or 0.75mm² cable to terminals 1 & 2 - see wiring diagram - Fig 1 A Normally Open contact is available at terminals 11 & 12 used for alarm or BMS - see wiring diagram - Fig 2 & Fig 3 A Normally Closed contact is available at terminals 13 & 14 used for closing a solenoid shut off valve in the event of an alarm - see wiring diagram - Fig 4 A 24v DC supply is available on terminals marked - & + which can be used in conjunction with either contact to suit individual applications see specifications for ratings. The installation should comply with local and site regulations and be carried out by a qualified electrician. When the above steps have been completed turn on the electricity supply. After a brief welcome screen showing Watersavers WLDS-10 the Main screen will show as per the example below: Main screen M A I N 0 0 0 0 0 1 5 0 \ L 0 9 : 1 5 O K The top line shows TOTAL LITRES registered by the meter at the incoming water supply (similar to a car s milometer) The bottom line shows real time (for reference only) and status OK or HIGH. OK is flow rate below preset maximum rate, HIGH is flow rate above preset maximum rate and will alarm if it continues for the Time to Alarm period. Check that the Main display increments as water flows through the pulse meter. Note: Larger pulse meters (1 and above) may produce 1 pulse per 10 or 100 litres and the display will correspondingly be programmed to increment by 10 or 100 litres. Enter the actual number of litres into the preset fields - irrespective of the pulse per litres output. SETTING MAXIMUM FLOW RATE: M A X L / H H : M M : S S 0 0 0 5 0 0 0 0 1 0 0 Press key to show the above screen. Cursor will flash to prompt the user to enter the number of litres. Enter number of litres using the 0-9 numeric keys. Above example shows 50 litres. Confirm by pressing key. Next enter the time over which the litres are to be measured ie 50 litres per minute. Enter the required time using the 0-9 numeric keys then confirm by pressing key. Note: If the setting is already correct just press key.

SETTING TIME TO ALARM: S E T T I M E T O A L A R M H H : M M 0 0 3 0 Press to show above screen. Cursor will flash to prompt the user to enter a time period - from 1 min to 45 hours 59 mins (Example shows 30 minutes). Confirm by pressing key. ********************************************************* IMPORTANT: Reboot panel (turn power off / on again) after changing parameters ********************************************************* Alarm output: If the preset parameters are exceeded, the NO & NC contacts will change over and the following screen will be shown. If this situation occurs, reset the panel by rebooting (turning power off then on again) and investigate the possible cause by studying total litres on the Main screen together with the set parameters. Alarm screen 1 H I G H F L O W A L A R M! R E B 0 0 T T O R E S E T SETTING THE CLOCK: Press and hold the INFO key for approximately 5 seconds. Use key to scroll through INPUTS / OUTPUTS, MB/MI/SB/SI, TIMERS, SYSTEM. Press key at SYSTEM, press key to select TIME & DATE, press key again to select TIME: press key again to enable flashing cursor prompt, enter correct time (in 24Hr clock format) using 0 9 keypad. When correct press INFO key 3 times to revert back to Main screen. PULSE METER RESETTING: Main: Press keys 1 & 9 together to reset the total litres to 00000000 SETTING PULSE METER LITRES/PULSE: Caution: this setting is factory set and should not be changed unless the panel is used with a pulse meter with a different LPP output than specified/supplied. Press and keys together to enter SET PULSE METER LPP mode. Enter the digits required eg 1, 10 or 100 Litres per pulse then press Enter key. Press or key to return to Main screen. SERIAL NUMBER: Press keys 1 & i (info) together to display the Serial Number of the panel. The Main screen will be displayed again after 3 seconds.

TROUBLESHOOTING: Blank HMI display: Check power is present, check wiring, check mains fusing. Green light on PSU indicates 24v is OK. Check DC fuse. This is located at right hand side of PSU in grey housing. Lift grey lid at top edge to reveal fuse. Replace if necessary with spare 20x5mm 1A quick blow fuse located in upper compartment. LITRES display on Main screen not incrementing: check water is passing the pulse meter will indicate water flow on it s dial. To check the pulse meter disconnect from panel and check that its contacts open and close as water flows through it (1,10 or 100 litres per pulse). The panel can be checked by short circuiting terminals 1 & 2 and watching the Main screen. This should cause the litres display to increment each time the terminals are shorted. For technical help please call Watersavers Technical on 01603 720999 NOTE: IT IS THE RESPONSIBILITY OF THE INSTALLING CONTRACTOR TO ENSURE THAT THIS PANEL HAS BEEN COMMISSIONED AND SET UP CORRECTLY. THE INSTALLER MUST SATISFY HIMSELF THAT THE ALARM WILL BE RAISED IN THE EVENT OF EXCESSIVE WATER FLOW. THIS CAN BE ACHIEVED BY DELIBERATELY ENTERING LOW PARAMETERS TO VERIFY THAT THE ALARM WILL BE RAISED. TECHNICAL SPECIFICATIONS: Power requirements: Universal input 100-240v AC 50/60Hz, power consumption 30W Pulse Meter input: 24v DC 5mA maximum for one reed switch type pulse meter, suitable for 1, 10 or 100 litres per pulse output Alarm output: Normally open free relay contact rated at 5A resistive load 250V ac / 30V dc Valve output: Normally closed free relay contact rated at 5A resistive load 250V ac / 30V dc 24v DC PSU: 1.1A maximum available for powering alarm or valve Parameters: High Flow: Litres input range 1 32,767, time period range 10 seconds - 45 hours, time to alarm range 1 minute 45 hours. LCD display: 2x 16 ASCII character with LED backlight Keypad: with tactile feedback, 0-9 numeric keys plus navigation keys for parameter setting and monitoring Real Time clock: battery backed (10 year life) Connections: via DIN rail terminals maximum conductor size 4mm², cable entry via stuffing glands in gland plate Enclosure: Steel wall mounting overall dimensions 300 x 200 x 150mm (W x H x D) RAL7035 powder coated Protection: to IP65 (nearest NEMA 4X) overall weight 5kg Designed & Manufactured by: Watersavers, Earl Road Rackheath Industrial Estate Norwich Norfolk NR13 6NT T +44 (0) 1603 720999 F +44 (0) 1603 721499 E sales@watersavers.co.uk W watersavers.co.uk WLDS-10 installation instructions rev 1.0

WLDS-10 wiring diagram showing connections for supply and pulse meter Fig 1 Pulse Meter Located at Site Boundary or main intake Connection of electric supply and pulse water meter AC Supply 100-240v 50Hz Wiring alarm options for BMS, flasher/sounder and solenoid shut off valve: NO NC Fig 2 BMS Connection to Building Management System - BMS Normally open contact closes in Alarm situation Fig 3 Link + 24v - Flasher / Sounder local or remote Connection of 24v DC Flasher / Sounder - activated in Alarm situation Fig 4 24v solenoid shut off valve normally closed Valve Connect to terminals 1 & 2 of DIN connector (polarity not important) Shut off valve - valve is normally energised via NC contact allowing water to flow. In alarm situation valve closes - shutting off water.