MESSENGERS FOR AERIAL CABLE

Similar documents
Cable Installation Notes

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

AMP Standard Terminals and Splices. RoHS. Ready

Voltage Loss Formula s

AERIAL FIBER OPTIC CABLE PLACEMENT

Installation and Application Guide. for 600V Conductors

CIR. Index. Gexol. Standard CIR UL Listed Type TC-ER. Crush and Impact Resistant Without External Armoring. Arctic CIR UL Listed Type TC-ER-HL*

Gexol. Gexol. The Global Cable Solutions Company. Designed for safe, reliable performance in the harshest oil and gas operating environments

GUY-GRIP Dead-end NOMENCLATURE GENERAL INFORMATION SAFETY CONSIDERATIONS (440)

3M Scotchcast Mine and Portable Cable Splice Kit

WIRE, TERMINAL AND CONNECTOR REPAIR CONDUCTORS

Outside Telephone Cable

2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

Industrial Cable Solutions for Variable Frequency Drives

Copper wire figures. AWG Table

100% EMI Emission Containment

Instrumentation Cable Power Cable Assembly Solutions...32

Our full line of JS Popper test products enables you to monitor circuits without taking them offline

TCTC Cabling Specifications

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

SECTION MEDIUM VOLTAGE CABLE

Armor Rods. Armor Rods NOMENCLATURE GENERAL RECOMMENDATIONS

5.2. Overview. The better method to install solderless compression connectors on power cable

Generator DoCKInG StatIonS

DESIGN OF PRESTRESSED BARRIER CABLE SYSTEMS

KNOW YOUR OPTIONS: 230 KV POWER CABLES

Installation Guide. WSD-100 Wind Speed and Direction Sensor For XR5 Data Loggers. February, 2011

A magician showed a magic trick where he picked one card from a standard deck. Determine what the probability is that the card will be a queen card?

STABILOY BRAND FeeDeR SOLuTIONS

IRRIGATION PUMPING Table of Contents - Section 900

Cables and Accessories Selection Guide

Section kv Power Cables

STABILOY BRAND FeeDeR SOLuTIONS

Network Standard Advice No. 1420C 9/6/2011

118 One hundred Eighteen

EcoFlex Cable. Smaller. Lighter. Tougher. 100% Recyclable.

General Calculations. Excerpt from PRYSMIAN S WIRE AND CABLE ENGINEERING GUIDE

Panduit 28 AWG Patch Cords Installation Guideline

Appendix C: Conversions and Calculations

MDM-5000 DIRECT DRIVE SETS

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

MEASUREMENT CONVERSION CHARTS

GUIDELINES FOR UTILITY INSTALLATIONS Part 1 - Wire Lines and Communications Cables

MICROCABLES. A complete vision of your connectivity needs. Catalogue

STABILOY BRAND FEEDER SOLUTIONS ASSISTED LIVING FACILITIES

POWER CABLE INSTALLATION GUIDE

Unarmored Variable Frequency Drive (VFD) Cable Termination Guide

Security & Control Cables

Global V-Belt Sheaves Industry 2015 Market Research. Report

Voltage Drop. Voltage Drop 1

CTI TECHNICAL BULLETIN Number 9: A publication of the Cable Tray Institute

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

Underground Cable Installation

AwanaGames Circle. Official. Diagram 1. Key to diagram: Pin & Striped Bean Bag C Diagonal or Starting Line. B Scoring Pins, or Center.

MGO Insulated Thermocouples Index

SECTION SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

CCW Continuously Corrugated Welded Cable A RMORED CAB LE FO R HAZAR D O U S LOCATI O N S

E-Line and Braided Line. E-Line Open Hole wireline

Cable Tray Selection-

One basic concept in math is that if we multiply a number by 1, the result is equal to the original number. For example,

For a building with a crawl space, see Figure

Electromotive Systems Flat Festoon and Round Pendant Cable Application Bulletin #: FS-Cable1

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

DOUBLE DRUM TRACTION WINCH SYSTEMS FOR OCEANOGRAPHIC RESEARCH 1.0 TRACTION WINCH SYSTEM ADVANTAGES 11-2

SECTION GUARDRAILS

MONTGOMERY COUNTY EXECUTIVE REGULATION Offices of the County Executive. 101 Monroe Street. Rockville, Maryland 20850

The Adventures of Conduit Phil

BENDING CONDUIT / TUBING Jan 2012 USING HAND BENDERS

SYSTEM 1850-SE SERVICE ENTRANCE CABLE SYSTEM

Super-Flex Traveling Cable Type ETT/300V

Measurement of Length, Mass, Volume and Density

STREETLIGHT SYSTEM GROUNDING AND BONDING

Installation Instructions Hustler 6-BTV Trap Vertical

Broadcast and Commercial AV Cabling MASTER CATALOG

Boom and fly capacities for this machine are listed by the following sections:

ETHERLINE Ethernet Cable, Connectors & Tools

Quali cations. Forename(s) Surname Number of seat

Belt and Roller Conveyor for boxes and containers

TubeTrace, ThermoTube

Voltage Drop (Single-Phase)

A. Shop Drawing submittals shall include, but not be limited to, the following:

Lightweight, Heavy Duty

CCTV System Troubleshooting Guide

Quali cations. Forename(s) Surname Number of seat

Charts (Section XI) Ph. (713) Fax (713) Main PAGE #

4 Installation Requirements

Reliable, Consistent, Quality

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Micrio WS1 Replacement Wind Speed Sensor and WC1 Replacement Wind Compass Sensor for Raymarine ST50 and ST60 Wind Instruments. Rev 4.

Welcome: What is U Drain? Drain Materials. Flow

Conduit Tubing Electrical Metallic Tubing (EMT) Intermediate Metal Conduit (IMC) Hot-Dip Galvanized Steel Rigid Metal Conduit (RMC)

QR12 (1.22 ) Diameter Optical Encoder

PHOTOVOLTAIC ARRAY WIRING HANDBOOK FOR STANDARD NOMINAL 6, 12, 24, AND 48 VOLT SYSTEMS. (for SX-60 series or smaller and MSX-120 solar modules)

Wind Generator. NEMO400 Instruction Manual. Suzhou Shoot Power Equipment Co., Ltd. Serial number:

Magnum Magnetizers. Print Magnum's magnet media on your digital press and magnetize post press with Magnum Magnetics magnetizer.

Transcription:

MESSENGERS FOR AERIAL CABLE COPPERWELD - EHS, 30% CONDUCTIVITY MES(size)CUWELD Size O.D. Stranding Breaking Strength Wgt./Mft. MES1/4CUWELD 1/4".242 7 #12 5,783 lbs. 128 MES5/16CUWELD 5/16".306 7 # 10 9,196 lbs. 204 MES3/8CUWELD 3/8".385 7 # 8 13,890 lbs. 324 MES1/2CUWELD 1/2".486 7 # 6 20,460 lbs. 515 MES9/16CUWELD 9/16".546 7 # 5 24,650 lbs. 650 GALVANIZED - EHS MES(size)EHSGAL Size O.D. Stranding Breaking Strength Wgt./Mft. MES1/4EHSGAL 1/4".242 7 # 12 6,650 lbs. 121 MES5/16EHSGAL 5/16".306 7 # 10 11,200 lbs. 205 MES3/8EHSGAL 3/8".385 7 # 8 15,400 lbs. 273 MES1/2EHSGAL 1/2".486 7 # 6 26,900 lbs. 517 STAINLESS STEEL - TYPE 302 MES(size)SS Size O.D. Stranding Breaking Strength Wgt./Mft. MES1/4SS 1/4".242 7 # 12 8,500 lbs. 135 MES3/8SS 3/8".385 7 # 8 18,000 lbs. 282 MES1/2SS 1/2".486 7 # 6 33,700 lbs. 535 NOTE: The data shown is approximate and subject to standard industry tolerances. 88

ICEA Method 1 ( K-1 ) (Colored Compounds with Stripes) Conductor Number Conductor Color COLOR CODES Stripe Color 1 Black - 2 White - 3 Red - 4 Green - 5 Orange - 6 Blue - 7 White Black 8 Red Black 9 Green Black 10 Orange Black 11 Blue Black 12 Black White 13 Red White 14 Green White 15 Blue White 16 Black Red 17 White Red 18 Orange Red 19 Blue Red 20 Red Green 21 Orange Green Conductor Number ICEA Method 4 (Black Compound with Numbers) ICEA Method 2 ( K-2 ) (Colored Compounds with Stripes) Conductor Color Stripe Color 1 Black - 2 Red - 3 Blue - 4 Orange - 5 Yellow - 6 Brown - 7 Red Black 8 Blue Black 9 Orange Black 10 Yellow Black 11 Brown Black 12 Black Red 13 Blue Red 14 Orange Red 15 Yellow Red 16 Brown Red 17 Black Blue 18 Red Blue 19 Orange Blue 20 Yellow Blue 21 Brown Blue Conductor Number Printing Conductor Number Printing 1 1-One 12 12-Twelve 2 2-Two 13 13-Thirteen 3 3-Three 14 14-Fourteen 4 4-Four 15 15-Fifteen 5 5-Five 16 16-Sixteen 6 6-Six 17 17-Seventeen 7 7-Seven 18 18-Eighteen 8 8-Eight 19 19-Nineteen 9 9-Nine 20 20-Twenty 10 10-Ten 21 21-Twenty-One 11 11-Eleven 89

MINIMUM BENDING RADII FOR CABLES This section contains the minimum values for the radii to which cables may be bent for permanent training during installation. These limits do not apply to conduit bends, sheaves, or other curved surfaces around which the cable may be pulled under tension while being installed. Larger radii bends are required for such conditions. The minimum radii specified refers to the inner surface of the cable and not to the axis of the conductor. POWER & CONTROL CABLES WITHOUT METALLIC SHIELDING OR ARMOR Overall Diameter of Cable (Inches) Insulation Thickness (Inches) 1.000" & less 1.001" - 2.000" 2.001" & over MINIMUM BENDING RADIUS AS A MULTIPLE OF CABLE DIAMETER.169" & less 4 5 6 POWER & CONTROL CABLES WITH METALLIC SHIELDING &/OR ARMOR Cable Description Minimum Bending Radius as a Multiple of Cable Diameter Interlocked Armor (with non-shielded cond.) Metallic Tape Shielded (conductors or cable) 7 12/7 (1) (1) 12 x individual shielded conductor diameter, or 7 x overall cable diameter, whichever is greater Above tables per ICEA S-95-658/NEMA WC70, Appendix F 90

MAXIMUM PULLING TENSIONS 1. Pulling Eye Maximum pulling tension for use with a pulling eye can be determined from the following formula: Tmax = k x n x CA Where: k =.008 for copper.006 for aluminum n = number of conductors CA = conductor area of one conductor, in circular mils Tmax should not exceed 6,000 lb. for a single conductor cable. Tmax should not exceed 10,000 lb. for 2 or more conductors. 2. Pulling Grip Maximum pulling tension when using a basket type grip should not exceed 1,000 lb. or the value determined in the above formula, whichever is smaller. NOTE 1: Do not exceed the load stated by the manufacturer of the pulling device. NOTE 2: Do not consider the area of neutral or grounding conductors in cable(s) when calculating maximum pulling tensions. NOTE 3: Pulling tensions should be reduced by 20% to 40% when several conductors are being pulled simultaneously (in parallel) since the tension will not be distributed evenly among conductors. NOTE 4: The above procedure pertains to straight pulls, and does not consider side wall loading. See pages 81-84 for additional details. 91

Maximum Cable Diameter per Sheave Sheave diameter Single/multi Conductor power Sheave Selection Chart Control Cable Shielded 600 V Power MV Power Shielded Armor 6 0.375 0.214 0.150 0.107 0.125 12 0.984 0.563 0.940 0.281 0.328 18 1.750 1.000 0.700 0.500 0.583 24 2.453 1.402 0.981 0.701 0.818 Examples of Minimum Bend Radii 600 V Cable Multiply Sample diameter Calcuation Resulting Minimum Bend Radii Less than 1 inch 4.75 in. OD 4 x.75= 3 in. radius 1 to 2 inches 5 1.5 in. OD 5 x 1.5= 7.5 in. radius 2 in. or larger 6 3.0 in. OD 6 x 3= 18 in. radius Interlock Armor 7 3.0 in. OD 7 x 3= 21 in. radius Pull considerations: 1. Plan direction of cable pulls to minimize tension by putting as many bends as possible early in the pull. 2. Proper setups cost initially, but will save by creating safer and easier pulls. 3. Published allowable conductor tensions are for STRAIGHT PULLS ONLY. 4. Published allowable equipment loading does not apply to the SWP of the cable pull. Notes: 1.) You must select the sheave by radius NOT diameter. 2.) Sidewall limits for most cables are 500 lbs. per foot radius maximum. 3.) All tensions on a cable pull are additive. 92

Cable Installation Tips Sheave strength ratings are for straight pulls only. Always refer to allowable tensions for each radius. Most single and conveyor sheaves are rated at 4000 lbs or more, but these ratings can only be used for the pulling rope, not the cable. Single sheaves are best for guiding and supporting cable. For cable bends use conveyor sheave assemblies to control sidewall pressure. 24" 6" 18" 12" Cable damage can occur when too small of a radius wheel is used. NOTE: When using conveyor sheave equipment, it is critical for set up that the lead and exit sheaves not have a bending radius smaller than the center wheels. (see below left) Danger Too small! Don't confuse the diameter of the sheave with the radius. The radius MUST match the cable's bending radius 93

Cable Installation Tips Stringing Aerial cables on poles (this applies to pulling in or out) Wrong: This method can cause sidewall pressure and crush the cable. Right: Create a smooth radius with sheaves using temporary messengers and proper spacing. Anchor spud or Line truck This method will support and distribute all bearing loads for successful cable installation. Loading cable into tray Wrong: This method can cause sidewall pressure and crush the cable at the leading point. Lack of rollers will increase drag creating more tension. Right: Rollers Use a large multi-wheel conveyor to distribute sidewall pressure. Lead and exit wheels must meet minimum cable bend. Use tray rollers to eliminate cable drag. 94

Tray Roller Assembly It is important that these assemblies be aligned and secure. Shifting of roller assemblies can cause the cable to climb over sheave edge and cut the cable. All rollers to be free rolling to eliminate friction. Space tray rollers to minimize cable drag. Use greater bending radii than allowed. Good but cable can drag Good for tray defection Better reduces cable drag Best with more elevation For cable loading and corners 95

Manufacturing quality. Delivering service. USEFUL CONVERSION FACTORS AWG to METRIC DIAMETER AWG MM 2 CMIL INCHES 22 0.32 640 0.029 20 0.52 1020 0.036 18 0.82 1620 0.046 16 1.31 2580 0.058 14 2.08 4110 0.073 12 3.31 6530 0.092 10 5.26 10380 0.116 9 6.63 13090 0.130 8 13.20 16510 0.146 6 13.20 26240 0.184 4 21.20 41740 0.232 3 26.70 52620 0.260 2 33.60 66360 0.292 1 42.40 83690 0.332 1/0 53.50 105600 0.373 2/0 67.40 133100 0.419 3/0 85.00 167800 0.470 4/0 107.00 211600 0.528 DIAMETER KCMIL MM 2 CMIL INCHES 250 126 250000 0.575 300 152 300000 0.630 350 177 350000 0.681 400 202 400000 0.728 500 253 500000 0.813 550 278 550000 0.855 600 304 600000 0.893 700 354 700000 0.964 750 380 750000 0.998 900 456 900000 1.094 1000 506 1000000 1.152 MISCELLANEOUS CONVERSIONS UNIT MULTIPLY BY TO GET Centimeters 0.3937 Inches Circular Mils 0.7854 Square Mils 5.0671x10-4 Square Millimeters Cubic Centimeters 0.0610 Cubic Inches Cubic Inches 16.386 Cubic Centimeters Inches 2.54 Centimeters Kilograms 2.2046 Pounds Kilograms/Kilometers 0.6720 Pounds/1000ft. Kilometers 0.6214 Miles 3280.8 Feet Meters 3.2808 Feet Mils 0.001 Inches 0.0254 Millimeters Miles 0.03937 Kilometers Millimeters 0.03037 Inches Ohms/Kilometer 0.3048 Ohms/1000ft. Ohms/1000ft. 3.2808 Ohms/Kilometer Pounds 0.4536 Kilograms Pounds/1000ft. 1.4881 Kilograms/Kilometer Square Centimeters 1.55x10 5 Square Mils 1.97x10 5 Circular Mils Square Inches 1.2732x10 6 Circular Mils 645.16 Square Millimeter Square Millimeter 1973.5 Circular Mils All available data industry and information data. However no in warranties, this section either is expressed based or on implied, information are made as currently to the accuracy available or completeness and is believed of any to liability be whatsoever reliable. in Service connection with Wire this Company information. makes no guarantee the results and assumes no obligation or 2008 7/13/12 1 Phoenix, AZ Culloden, WV Houston, TX Phoenix, 877-623-9473 AZ Culloden, WV 800-624-3572 Houston, TX Pittsburgh, 800-231-9473 PA