Bigger is Better: Sizing Solar Modules for Microinverters

Similar documents
PVWATTS DERATING FACTORS FOR SOLARBRIDGE PANTHEON MICROINVERTERS AND ACPV SYSTEMS

Calculating Solar Energy System Performance & Payback

Application Note - How to Design a SolarEdge System Using PVsyst

SHARP SOLAR Frequently Asked Questions for PV Integrators Revised 05/04/2010

Irradiance. Solar Fundamentals Solar power investment decision making

Photovoltaic Systems II EE 446/646

Solar Electric Power System Owner s Manual

Replacing Fuel With Solar Energy

Auburn University s Solar Photovoltaic Array Tilt Angle and Tracking Performance Experiment

SOLAR RADIATION AND YIELD. Alessandro Massi Pavan

Preserve the sun s energy. BP Solar warranties

SUNPOWER CORPORATION Document # Rev *B Title: Page 1 of 8 Initial release: 17-Aug-09

How To Use The Csi Ebpp Calculator

VOLATILITY AND DEVIATION OF DISTRIBUTED SOLAR

Running the Electric Meter Backwards: Real-Life Experience with a Residential Solar Power System

Proposal prepared for Happy Solar Owner

ADB s Rooftop Solar Project. Aiming Zhou Senior Energy Specialist June th Asia Clean Energy Forum

For millennia people have known about the sun s energy potential, using it in passive

Gross/Active PV Surface Area: ,40 / ,29 m². Energy Produced by PV Array (AC):

EVALUATING SOLAR ENERGY PLANTS TO SUPPORT INVESTMENT DECISIONS

Your guide to electricity from Photovoltaic Panel systems

Yukon Government Solar Energy Pilot: Performance Monitoring Yukon Government s Energy Solutions Centre. February 2014

Dispelling the Solar Myth - Evacuated Tube versus Flat Plate Panels. W illiam Comerford Sales Manager Ireland Kingspan Renewables Ltd.

Solar Energy. Airports Going Green Aimee Fenlon

Design of Grid Connect PV systems. Palau Workshop 8 th -12 th April

Consumer guide. be brighter. actewagl.com.au/solar

APPLICATIONS OF RESOURCE ASSESSMENT FOR SOLAR ENERGY

Is Overproduction Costing You?

The Planning and Design of Photovoltaic Energy Systems: Engineering and Economic Aspects. William Nichols Georgia Southern University Atlanta, GA

Additional Solar System Information and Resources

Photovoltaic system sizing report

Performance ratio. Contents. Quality factor for the PV plant

Solar Energy Feasibility Study

8 Ways Power Optimizers are Better by Design

Photovoltaic Industry Technologies, Markets & Trends

Solar Power at Vernier Software & Technology

Comparison of Photovoltaic Models in the System Advisor Model

Fact Sheet March Solar Photovoltaic Systems Electricity from Sunshine

INSTALLER PARTNERS FOR THE PROGRAM

TIME IS RIGHT FOR SOLAR PANELS

MICRO-HYDROPOWER NEED FOR ENERGY FOR RURAL DEVELOPMENT. By: Payman Hassan Rashed

Small PV Systems Performance Evaluation at NREL's Outdoor Test Facility Using the PVUSA Power Rating Method

Photovoltaic String Inverters and Shade-Tolerant Maximum Power Point Tracking: Toward Optimal Harvest Efficiency and Maximum ROI

Stand Alone PV System Sizing Worksheet (example)

Solar Power HourSM. Solar educa on for your community.

Optimum Orientation of Solar Panels

SolarCity Partnership. Performance Review of Rooftop Solar Photovoltaic Projects in the Greater Toronto Area. Technology. Monitoring.

A SOLAR GUIDE - EVERYTHING YOU NEED TO KNOW

Mailing Address 4650 Adohr Ln. Camarillo, CA Year Financial Analysis. $1,051 / mo (avg) Cost Breakdown. System Description

Implementation of the Movable Photovoltaic Array to Increase Output Power of the Solar Cells

Energy Savings through Solar Energy for Municipalities

Electricity from PV systems how does it work?

Simulated PV Power Plant Variability: Impact of Utility-imposed Ramp Limitations in Puerto Rico

Solar Energy Systems. Matt Aldeman Senior Energy Analyst Center for Renewable Energy Illinois State University

Renewable Energy. Solar Power. Courseware Sample F0

Corona Department of Water & Power (DWP) Solar Partnership Program Guidelines and Application

Operational experienced of an 8.64 kwp grid-connected PV array

2 Absorbing Solar Energy

Understanding Tracker Accuracy and its Effects on CPV

SOLAR COOLING WITH ICE STORAGE

Using Renewable Energy to Pump Water

Breakeven Cost for Residential Photovoltaics in the United States: Key Drivers and Sensitivities (Report Summary)

Solar and Wind Energy for Greenhouses. A.J. Both 1 and Tom Manning 2

Self-consumption. that you need to purchase from your power company. Bosch Solar Energy recommends photovoltaic systems with self-consumption.

CLEAN ENERGY PROJECT ANALYSIS WITH RETSCREEN SOFTWARE

High Fraction Hybrid Solar in Canada s North

Siting of Active Solar Collectors and Photovoltaic Modules

Impact of Reflectors on Solar Energy Systems

SOLAR TECHNOLOGY CHRIS PRICE TECHNICAL SERVICES OFFICER BIMOSE TRIBAL COUNCIL

Solar Aquaponics Designing a 100% Solar Aquaponics Greenhouse

Technology Advantage

FREQUENTLY ASKED QUESTIONS

Introduction to Project Finance Analytic Methods

Solar Photovoltaic Basics

Thanks for your interest in going solar at one of our group off-site solar farms.

Everything you wanted to know (in simple language) about

Yield Reduction due to Shading:

HOMER Software Training Guide for Renewable Energy Base Station Design. Areef Kassam Field Implementation Manager

Avoiding Costs from Oversizing Data Center and Network Room Infrastructure

We're with you... solar. Call today FOR THE LIFE OF THE SYSTEM YEAR WARRANTY * YEAR OLD BACKED BY CSR BRADFORD CSR A AUSTRALIAN COMPANY

Solar Heating Basics Page 1. a lot on the shape, colour, and texture of the surrounding

EFFICIENT EAST-WEST ORIENTATED PV SYSTEMS WITH ONE MPP TRACKER

The Basics of Solar Power for Producing Electricity An excellent place to start for those just beginning. The basics of solar power: 1000 W/m²

Solar Up NH. Frequently Asked Questions

Solar Panels and the Smart Grid

Solar Cooling. Methods and Applications. Sargon Ishaya, PE, LEED AP

150 Watts. Solar Panel. one square meter. Watts

FIRST GRADE 1 WEEK LESSON PLANS AND ACTIVITIES

PV MODULE PERFORMANCE UNDER REAL-WORLD TEST CONDITIONS A DATA ANALYTICS APPROACH

Modelling of PV and Electricity Prices in the Australian Commercial Sector

VGB Congress Power Plants 2001 Brussels October 10 to 12, Solar Power Photovoltaics or Solar Thermal Power Plants?

Transcription:

Bigger is Better: Sizing Solar Modules for Microinverters Authors: David Briggs 1 ; Dave Williams 1 ; Preston Steele 1 ; Tefford Reed 1 ; 1 Enphase Energy, Inc. October 25, 2012 SUMMARY This study analyzed the impact of using high power solar modules with the M215 Microinverter in 15 different installation scenarios. The analysis demonstrated that using larger module sizes significantly improves annual energy production, even while inverter size remains unchanged. Gains in annual production were 25-100 times more significant than the losses associated with inverter saturation. This suggests that applying high power solar modules to microinverters leads to greater lifetime performance, lower installed cost per watt, and ultimately, the highest return on investment for the end-customer. INTRODUCTION Solar module output is a complex phenomenon that depends on many, fluctuating factors, such as sunlight, temperature, wind speed, optics (glass clarity, dust and soiling), and more. Yet, despite its variability, module output is consistent in one way: it s almost always less than the nameplate rating of the module. In fact, module output rarely exceeds 90% of the module s nameplate rating. Due to the significant discrepancy between module nameplate ratings and actual field performance, system designers are faced with a difficult question: How should I size the downstream components of the system? Sizing downstream components to match the module s nameplate rating is almost guaranteed to result in excessive cost to the end-customer. Conversely, while selecting smaller downstream components will lower the system cost, it can also limit the output of modules at select times, when conditions are optimal. Thus, it s important to develop guidelines for component selection that balance cost with performance. This paper evaluates the impact of using different module and microinverter sizes on system cost and performance, in a variety of climates and installations. METHODOLOGY Modeling Microinverter Behavior Using Enlighten, Enphase s web-based solar monitoring software, the output behaviors of installed microinverters were analyzed in multiple locations across the U.S., each with DC:AC ratios above 120%. The output characteristics were then compared to solar irradiance measurements from nearby weather stations to establish a performance ratio (PR) between incoming solar irradiance and outgoing AC power.

At times when the inverter was saturated (module output exceeded the M215 Microinverter s maximum output power of 225W), the PR was assumed to be constant relative to values recently observed (Fig. 1). [NOTE: This is a conservative assumption for modeling the energy lost to inverter saturation, considering that higher irradiance levels typically correlate with higher temperatures, which adversely affect module performance, and thus, should slightly decrease the PR at times of high irradiance.] Using the PR method, the effect of different module sizes can easily be estimated by adjusting the output in proportion to the module s power. For example, if a 240W module produced 212W at a given irradiance level, then a 280W module would produce approximately 247W at the same irradiance level. Figure 1: A single-day of output for an M215 paired with a 260W module is shown in orange. In grey, the projected behavior based on the PR method is shown. Figure 2 illustrates an example of three different module powers being modeled for a single day. Modeling Annual Impact To estimate the impact of module and microinverter sizes on annual energy production, the PVsyst performance modeling software was used. Adjustments were made to the default parameters in PVsyst to align its predictions with values observed in Enlighten. Alignment between PVsyst and the observed data was confirmed using the same weather files and installation locations as with the PR method. Table 1 shows the adjustments made to modeling parameters in PVsyst. Once adjusted, PVsyst was used to model annual performance in multiple geographic locations and at multiple tilt angles, all using default meteorological files in PVsyst. In total, 15 PVsyst simulations were performed, and for each, 8 module sizes were analyzed using the PR method. Table 2 explains the variables used in all 120 scenarios. The impact of inverter saturation was analyzed by limiting the hourly PVsyst predictions to the microinverter s maximum output rating. In the case of the M215, the maximum output was 225W; for the theoretical microinverter rated at 240W, the maximum output was assumed to be Figure 2: Using the PR method, the behavior of multiple module sizes on a single day is shown in grey. Inverter saturation behavior is shown above the M215's maximum output power of 225W.

250W. The difference between the original PVsyst prediction and the inverter-limited value was considered the loss to inverter saturation. It should be noted that these simulations did not include annual module degradation. It is reasonable to expect that module degradation would reduce the impact of inverter saturation, meaning that this analysis is conservative within the context of lifetime performance. Table 1: Adjustments made to parameters within the "Detailed Losses" section of PVsyst. Parameter Name Value Description Thermal Parameter Free Assumes good airflow (lower temp.) for module Ohmic Loss 0.0% Assumes no wire loss from module to microinverter Module Efficiency Loss -1.0% Assumes positive manufacturing tolerance of +1.0% Module Mismatch 0.0% Assumes no mismatch effects within the array Soiling Loss 0.0% Assumes no light is blocked by dust or dirt Table 2: PVsyst simulations were performed to address all combinations of these design factors. Location Tilt (deg.) Module Size (Watts @ STC) Los Angeles, CA 20 30 40 250 255 260 265 270 275 280 285 Toronto, ON 20 30 40 250 255 260 265 270 275 280 285 Denver, CO 20 30 40 250 255 260 265 270 275 280 285 Newark, NJ 20 30 40 250 255 260 265 270 275 280 285 Phoenix, AZ 20 30 40 250 255 260 265 270 275 280 285 Modeling Economic Impact A second analysis was performed to evaluate the cost-effectiveness of pairing different sizes of module and microinverter. The analysis compared the upfront cost of these components to their payback. Tables 3 and 4 show the component cost and financial assumptions used. [NOTE: Both sets of assumptions were designed to be conservative with respect to the M215 Microinverter. For example, electrical cost was held constant for both microinverters, despite higher AC current output with the 240W microinverter.] Table 3: Component cost assumptions used to analyze installed cost. Component Cost @250W Escalator Component Pricing Assumptions Module $0.90/W +2% / Size Efficiency premium relative to prior size Struc. BoS / Labor $0.50/W 0% No increase with module size Elec. BoS / Labor $0.50/W 0% No increase, despite AC current increase Microinverter $0.60/W -5% / Size Cost reduction for higher power device Table 4: Financial assumptions used to analyze lifetime value. Factor Assumption Description Degradation 0% No module degradation was included Inverter Efficiency 96% No difference in microinverter efficiency Energy Cost $0.20/kWh Above the U.S. average, similar to CA prices Energy Cost Escalator 3% Standard for energy price inflation Discount Rate 8% Standard for estimating present value of future returns Timeframe / O&M 20yr / $0 20yr financial term, no cost of warranty or servicing

RESULTS Annual Impact Overall, annual losses to inverter saturation were insignificant. In 90% of the scenarios using the M215 Microinverter, including all scenarios with module nameplate ratings below 275W, annual losses were less than 0.5% (Table 3). Conversely, increasing module size resulted in significant gains in annual production, even while inverter size remained unchanged. As can be seen in Figure 3, increasing module size had a nearly linear benefit to annual production, resulting in gains that were 25-100 times greater than the losses to inverter saturation. It s important to note, however, that annual losses to inverter saturation increased geometrically with module size, and at a certain point, the marginal losses would begin to exceed the marginal gains. This crossover typically occurs above 140% DC-to-AC ratio, or when pairing >300W modules with an M215 microinverter. Figure 3: The annual performance gain for different module sizes, relative to a 250W module in Denver, CO, is shown in orange. Total annual losses to inverter saturation are shown in grey. Microinverter Behavior In all scenarios, the M215 Microinverter was operating below its maximum output for more than 90% of the year. Figure 4 shows the total hours that the M215 spent throughout the year at each output power level, when paired with a 260W module in Denver, CO. As can be seen, the microinverter operated below its maximum output rating for more than 99.5% of the year. To assess the impact of inverter saturation, it s important to remember that the inverter continues to output at its maximum power rating during these times (Figure 1). For example, in

Figure 4, the inverter continued to produce 225W during the Inverter Saturation Hours, and as a result, it converted approximately 95% of the module s total output during these hours. Figure 4: The distribution of hours spent at each output power level throughout the year by a 260W module in Denver, CO at 30 degrees tilt. Inverter saturation hours are shown in grey. As can be seen in Table 3, location influenced the losses to inverter saturation. This is explained by the fact that certain locations are more likely to have sunny conditions at low temperatures. Typically, these are locations at high altitude or high latitude. Similarly, we see in Table 3 that high tilt angle led to more inverter saturation because cold temperatures and high irradiance are more likely to occur when the sun is low in the sky (either early in the day or during winter months). Conversely, it is likely that any tilt angle less than 20 degrees will result in a negligible amount of energy loss to inverter saturation. Table 5: The annual energy loss from inverter saturation is shown for 120 different installation scenarios. Location Los Angeles, CA Toronto, ON Denver, CO Newark, NJ Phoenix, AZ Tilt (deg.) Annual Loss to Inverter Saturation Module Sizes (Watts @ STC) 250 255 260 265 270 275 280 285 20 0.00% 0.00% 0.00% 0.01% 0.02% 0.04% 0.07% 0.13% 30 0.00% 0.00% 0.01% 0.02% 0.03% 0.07% 0.13% 0.23% 40 0.00% 0.00% 0.01% 0.04% 0.09% 0.16% 0.25% 0.37% 20 0.01% 0.03% 0.05% 0.09% 0.16% 0.25% 0.38% 0.53% 30 0.04% 0.07% 0.12% 0.19% 0.30% 0.43% 0.60% 0.80% 40 0.10% 0.16% 0.23% 0.32% 0.43% 0.58% 0.75% 0.96% 20 0.00% 0.00% 0.01% 0.02% 0.04% 0.08% 0.16% 0.27% 30 0.00% 0.01% 0.03% 0.07% 0.13% 0.23% 0.37% 0.56% 40 0.04% 0.08% 0.14% 0.22% 0.34% 0.49% 0.68% 0.90% 20 0.00% 0.00% 0.00% 0.00% 0.00% 0.01% 0.03% 0.07% 30 0.00% 0.01% 0.01% 0.02% 0.04% 0.07% 0.11% 0.17% 40 0.01% 0.03% 0.04% 0.07% 0.11% 0.16% 0.23% 0.31% 20 0.00% 0.00% 0.01% 0.03% 0.07% 0.13% 0.22% 0.34% 30 0.00% 0.00% 0.04% 0.09% 0.16% 0.28% 0.45% 0.66% 40 0.02% 0.04% 0.10% 0.20% 0.34% 0.54% 0.78% 1.06%

Economic Impact In all cases, the installed cost per watt declined as the module size was increased (Figure 5). This is explained by the fact that module cost was only a fraction of the total system cost, yet module size was the entire basis of system size. Thus, the denominator in the cost per watt equation increased faster than the numerator. Conversely, increasing the microinverter size increased the system cost, but had no affect on system size. Thus, the cost per watt of the system was consistently higher when using a larger microinverter. It s important to note that this effect could become more significant if the higher microinverter capacity also required increases in the size and cost of electrical components. From an investment standpoint, the system s rate of return increased with module size, but not microinverter size. This is consistent with the finding that the gains from increasing module size were more significant than the losses to inverter saturation. Thus, the value of additional production from using larger modules was greater than their additional cost, but the value of additional production from using a larger microinverter was not. Figure 7 directly compares the additional cost of the 240W microinverter to the value of additional production. Though the value of using a larger microinverter increased as module size increased, this value, in all cases, was less than the additional cost of the larger microinverter. Figure 5: Installed cost per watt is shown for different module and microinverter sizes. Figure 6: Expected rate of return is shown for different module and microinverter sizes. Figure 7: The additional value of a larger capacity microinverter is compared against the additional cost.

CONCLUSION It is clear from this study that using high power solar modules with the M215 Microinverter results in substantial gains in annual production and minimal losses to inverter saturation. This conclusion is furthered by the fact that lifetime losses to inverter saturation will likely be lower, due to module degradation and increased soiling over time. This study highlights the need to evaluate solar modules based on their expected field performance, rather than their nameplate rating. Solar modules will only perform to their nameplate rating during select weather conditions, when the sun shines brightly and the temperature is cold. Overall, these conditions are rare, only occurring on a small percentage of days in the late winter and early spring. Whereas, most sunny days throughout the year have higher temperatures, which typically reduce the module s output to 80% or less of its nameplate rating. In addition, this study has shown that there are substantial cost savings associated with applying high power modules to the M215 Microinverter. This finding is significant within today s industry environment, where solar module prices are declining rapidly and the cost of microinverters and electrical equipment is an increasingly important portion of system cost. These trends suggest that the optimal module-to-inverter sizing ratio will continue to increase over time, encouraging system designs that frequently saturate the microinverter s capacity due to its favorable impact on return on investment.