Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Precast Concrete Products

Similar documents
PRE INSTALLATION MANUAL

Wastewater Capital Projects Management Standard Construction Specification

MATERIALS DIVISION MEMORANDUM

Georgia Department of Transportation. Office of Materials and Research. Standard Operating Procedure (SOP) 19

State of Illinois Department Of Transportation CONSTRUCTION INSPECTOR S CHECKLIST FOR STORM SEWERS

SECTION STORM DRAINAGE TABLE OF CONTENTS

Section 2100-Trenching and Tunneling

SECTION 36 - CAST-IN-PLACE CONCRETE PIPE (CIPCP) TABLE OF CONTENTS

DIVISION 2 - SEWERAGE AND DRAINAGE SECTION STORM DRAIN SYSTEMS PART 1 - GENERAL

DIVISION 4300 STORM DRAINAGE

DMS REINFORCED CONCRETE PIPE AND MACHINE-MADE PRECAST CONCRETE BOX CULVERT FABRICATION AND PLANT QUALIFICATION

Inspection Manual for Precast Concrete Pipe and Structures

SECTION PRECAST CONCRETE UTILITY STRUCTURES

SECTION STORM DRAINAGE SYSTEM

NAPCA BULLETIN APPLICATION PROCEDURES FOR CONCRETE WEIGHT COATING APPLIED BY THE COMPRESSION METHOD TO STEEL PIPE

Section 2 Specification 2.18 Concrete and/or Corrugated Steel Storm Sewer TABLE OF CONTENTS

The work of this Section includes furnishing and installing Reinforced Concrete Pressure Pipe as shown on the Drawings and as specified.

TECHNICAL SPECIFICATION SERIES 8000 PRECAST CONCRETE

SECTION SANITARY SEWER AND STORM DRAIN SYSTEMS

PERFORMANCE GUIDELINES

SECTION PUBLIC STORM UTILITY DRAINAGE PIPING

SECTION STORM DRAIN SYSTEM

SECTION STORM DRAINAGE STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

CCU Engineering Specifications. Section PRECAST CONCRETE PRODUCTS

C. Section TESTING LABORATORY SERVICE.

Metropolitan Builders Association Masonry & Concrete Standard

APPENDIX K PIPE INSPECTION

Specifications for Residential Property Owners Connection to New Public Sewer

SECTION NONREINFORCED CONCRETE SEWER PIPE

Specification for Cast-in-Place Concrete Pipe

San Antonio Water System Standard Specifications for Construction ITEM NO SLIP-LINING SANITARY SEWERS

Section 8.1 Volume I QUALITY ASSURANCE PROGRAM OF PRECAST PRESTRESSED CONCRETE PRODUCTS

Prequalification Requirements For Precast Concrete Drainage Products

SEDIMENT/STORMWATER MANAGEMENT BASIN CONSTRUCTION CHECKLIST

Waterproofing System for Wastewater Tanks in Petrochemical Industries and Refineries

SECTION 7- STORM SEWER

SECTION 724 PIPE CULVERTS

September 1, 2003 CONCRETE MANUAL CONCRETE PAVEMENT REHABILITATION

SECTION 9.02 BUILDING SUBSURFACE DRAINS (PERIMETER, ETC.)

SUBDRAINS AND FOOTING DRAIN COLLECTORS. A. Construct subdrains, subdrain cleanouts and outlets, and footing drain collectors.

SECTION CEMENT-MORTAR LINED AND COATED STEEL PIPE

City of West Linn Public Works Standard Construction Specifications. Table of Contents

SECTION POINT REPAIRS TO SANITARY SEWERS. A. Repairs to existing sewer lines by replacing short lengths of failed pipe.

Section SEWER PIPE INSTALLATION AND TESTING

AIR RELEASE, CLEANOUT, AND SEWER MANHOLES

IHSS-N1 WELDED HONEYCOMB CORE SPECIFICATION. Generated: Sergiy Papyshev Engineering. Approved: Don Prysi Manufacturing. Approved: Merzuk Ramic Quality

GUIDE SPECIFICATIONS FOR PRECAST CONCRETE PRODUCTS

SECTION GRAVITY SANITARY SEWERS

Transport and Main Roads Specifications MRTS25 Steel Reinforced Precast Concrete Pipes

SECTION CAST-IN-PLACE CONCRETE

SECTION REMOVAL OR ABANDONMENT OF EXISTING UTILITIES AND UNDERGROUND STRUCTURES. 1. Trench excavation, backfill, and compaction; Section

STANDARD SPECIFICATIONS SECTION PRECAST REINFORCED CONCRETE MANHOLES AND MANHOLE BASES. 1. Structure Earthwork: 02200

SPECIFICATION FOR PIPE SUBSOIL DRAIN CONSTRUCTION

SECTION III DRAINAGE

INDEX. Sec. No. Items Page Nos.

SECTION ABANDONMENT OF SEWER MAINS

A. Contractor shall furnish, to the Engineer, all materials certifications available from the manufacturer for all required materials.

Guide Specification Precast Concrete Products

Section 402. STORM SEWERS

SECTION 200: STORM SEWER CONSTRUCTION STANDARDS

PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007

SECTION LS 2530 SANITARY SEWERS. A. General: Submit the following in accordance with The General Conditions.

Table of Contents Con Cast Pipe Price List - Page 1

738-B-297 POLYMERIC CONCRETE BRIDGE DECK OVERLAY. (Adopted )

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

SECTION PRECAST CONCRETE STRUCTURES

4-02 Gravel Base Ballast and Crushed Surfacing

SECTION REINFORCED CONCRETE PIPE. A. The following is a list of SPECIFICATIONS, which may be related to this section:

Sewer Rehabilitation Design Requirements

STANDARD SPECIFICATIONS & CONSTRUCTION DETAILS MANUAL SECTION 5 - STORM DRAINAGE Design

CCTV of Stormwater Systems. Cairns Regional Council. Commentary Guidelines #

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING

PUBLIC WORKS DESIGN, SPECIFICATIONS & PROCEDURES MANUAL LINEAR INFRASTRUCTURE

SECTION 55 PIPE FOR STORM DRAINS AND CULVERTS (FAA D-701)

SECTION 600 INCIDENTAL CONSTRUCTION

SECTION EARTH MOVING

Unit Price Averages Reports

STANDARD SPECIFICATIONS FOR STORM SEWER CONSTRUCTION CITY OF PLYMOUTH, MINNESOTA

Williamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, (68 pages)

Concrete Repair. Applications and Procedures

HEDDERMAN ENGINEERING, INC. Office , Fax

Stormwater/Wetland Pond Construction Inspection Checklist

CW GRAVITY SEWERS TABLE OF CONTENTS

Measuring the Condition of Prestressed Concrete Cylinder Pipe

Rehabilitation of an Aging Concrete Reservoir Adit Tower

TECHNICAL NOTE Culvert Sliplining and Lining of Casings with HPPipe

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 11/5/13)

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 21

SECTION 9. All sewer laterals shall tie into the sewer main lines unless approved by the City Engineer.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

Design and Construction of Cantilevered Reinforced Concrete Structures

Section 600 Incidental Construction

SECTION PRECAST CONCRETE STRUCTURES

Lighthouse Engineering, L.L.C.

SECTION 623 CONCRETE BONDING COMPOUND, EPOXY MORTAR AND EPOXY POLYMER CONCRETE OVERLAY SECTION CONCRETE BONDING COMPOUND.

EAST LYME HIGH SCHOOL

For Asset Management

External Wrapping of Steel Riser Pipe. Case Study HJ3 CS200902

Transcription:

Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Precast Concrete Products A Visual Aid For: Bureau of Materials and Physical Research s (BMPR) Policy Memorandum, Quality Control/Quality Assurance Program for Precast Concrete Products Page 1 of 63

Revision History and Document Control Photographs: Acceptable, Unacceptable, and Unacceptably Repaired Products will be reviewed by the Concrete Products Engineer annually and updated as necessary to reflect current policy. Updates are made to the electronic file as needed and hard copies are uncontrolled. Archive versions are available to examine in the Bureau of Materials and Physical Research (BMPR). Revision Date Description Approval 1/1/10 Revised annotations to existing photos. JAB 1/1/10 Added approximately 30 new photos with annotations. JAB 3/15/13 Added 2 new photos with annotations. JAB 3/15/13 Revised annotations to existing photos. JAB 3/7/14 Revised annotations to existing photos. JAB Page 2 of 63

REINFORCED CONCRETE PIPE - CRACKS Unacceptable Product: Cracks passes entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 3 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Width of surface crack in pipe is 0.01 in. (0.30 mm) or greater and exceeds 12 in. (300 mm) in length. See BMPR Policy Memo, Section 23, Point 2.c. Page 4 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Width of surface cracks in pipe are 0.01 in. (0.30 mm) or greater and summation of crack lengths exceed 24 in. (600 mm) in length. See BMPR Policy Memo, Section 23, Point 2.c. Page 5 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Crack passes entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 6 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Crack passes entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 7 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Crack passes entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 8 of 63

REINFORCED CONCRETE PIPE CRACKS Unacceptable Product: Crack passes entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 9 of 63

FLARED END SECTION OF CULVERT - CRACKS Unacceptable Product: Crack passes entirely through wall of end section. See BMPR Policy Memo, Section 23, Point 2.a. Page 10 of 63

REINFORCED CONCRETE PIPE HONEYCOMB (Outside) Unacceptable Product: Honeycomb or voids are deeper than 3/4 the depth of the coarse aggregate and exceeds 5 percent of the surface area of the pipe. See BMPR Policy Memo, Section 23, Point 3. Page 11 of 63

REINFORCED CONCRETE PIPE - HONEYCOMB (Inside) Unacceptable Product: Pipe with honeycomb or voids on the inside. See BMPR Policy Memo, Section 23, Point 3. Page 12 of 63

REINFORCED CONCRETE PRODUCT IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Reinforcement is exposed on exterior of pipe. See BMPR Policy Memo, Section 23, Point 5. Page 13 of 63

REINFORCED CONCRETE PIPE IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Reinforcement is exposed on exterior of pipe. See BMPR Policy Memo, Section 23, Point 5. Page 14 of 63

REINFORCED CONCRETE PIPE IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Shadowing (ghosting) may indicate insufficient concrete cover over reinforcement. Further investigation of this pipe determined that the depth of cover did not meet the Specification requirements. One method to verify adequate cover is to remove the concrete and expose the reinforcement at one location. See BMPR Policy Memo, Section 23, Point 5. Page 15 of 63

REINFORCED CONCRETE PIPE IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Shadowing (ghosting) may indicate insufficient concrete cover over reinforcement. Further investigation of this pipe determined that the depth of cover did not meet the Specification requirements. One method to verify adequate cover is to remove the concrete and expose the reinforcement at one location. See BMPR Policy Memo, Section 23, Point 5. Page 16 of 63

REINFORCED CONCRETE BOX CULVERT IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Reinforcement is exposed on inside of culvert. See BMPR Policy Memo, Section 23, Point 5. Page 17 of 63

MANHOLE CONE IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Reinforcement is exposed on outside of manhole cone. See BMPR Policy Memo, Section 23, Point 5. Page 18 of 63

REINFORCED CONCRETE PIPE IMPROPER REINFORCEMENT PLACEMENT Unacceptable Product: Reinforcement is exposed on inside of pipe. See BMPR Policy Memo, Section 23, Point 5. Page 19 of 63

REINFORCED CONCRETE PIPE PROPER REINFORCEMENT PLACEMENT Acceptable Product: The exposed ends of longitudinal steel, stirrups, lift holes, or spacers used to position the reinforcement (cage) during concrete placement is not a cause for rejection of this pipe. See BMPR Policy Memo, Section 23, Point 5. Page 20 of 63

REINFORCED CONCRETE PIPE CHIPPED OR DAMAGED ENDS Unacceptable Product: The damage is more than halfway into the pipe joint and has a length more than 10 percent of the end circumference or perimeter. See BMPR Policy Memo, Section 23, Point 6. Page 21 of 63

REINFORCED CONCRETE PIPE - CHIPPED OR DAMAGED ENDS Unacceptable Product: The damage is more than halfway into the pipe joint and has a length more than 10 percent of the end circumference or perimeter. See BMPR Policy Memo, Section 23, Point 6. Page 22 of 63

REINFORCED CONCRETE PIPE - CHIPPED OR DAMAGED ENDS Repairable Product: The damage is more than halfway into the joint, but the length is less than 10 percent of the end circumference or perimeter. See BMPR Policy Memo, Section 23, Point 6. Page 23 of 63

REINFORCED CONCRETE PIPE CHIPPED OR DAMAGED ENDS Repairable Product: The damage is more than halfway into the joint, but the length is less than 10 percent of the end circumference or perimeter. See BMPR Policy Memo, Section 23, Point 6. Page 24 of 63

REINFORCED CONCRETE PIPE CHIPPED OR DAMAGED ENDS Repairable Product: The length of the damage is more than 10 percent of the end circumference or perimeter but is less than halfway into the joint. See BMPR Policy Memo, Section 23, Point 6. Page 25 of 63

REINFORCED CONCRETE PIPE CHIPPED OR DAMAGED ENDS Repairable Product: The damage is more than halfway into the joint but has a length of less than 10 percent of the end circumference or perimeter. See BMPR Policy Memo, Section 23, Point 6. Page 26 of 63

REINFORCED CONCRETE PIPE OTHER DEFECTS Unacceptable Product: Concrete fell off of reinforcement due to too wet of a mixture. See BMPR Policy Memo, Section 23, Point 9. Page 27 of 63

REINFORCED CONCRETE PIPE - OTHER DEFECTS Unacceptable Product: Example of concrete defect. See BMPR Policy Memo, Section 23, Point 9. Page 28 of 63

REINFORCED CONCRETE PIPE - OTHER DEFECTS Unacceptable Product: Example of concrete defect. See BMPR Policy Memo, Section 23, Point 9. Page 29 of 63

OFFSET MANHOLE CONES OTHER DEFECTS Unacceptable Product: This is known as a blow out concrete sticking to interior form or falling out during form removal. See BMPR Policy Memo, Section 23, Point 9. Page 30 of 63

FLARED END SECTION OF CULVERT OTHER DEFECTS Repairable Product : Damaged end section may be repaired. See BMPR Policy Memo, Section 23, Point 9. Page 31 of 63

REINFORCED CONCRETE PIPE PHYSICAL MEASUREMENTS Unacceptable Product: Overpacking is excess material being present in the bell end due to concrete pipe equipment problems. See BMPR Policy Memo, Section 23, Point 1. Page 32 of 63

REINFORCED CONCRETE PIPE PHYSICAL MEASUREMENTS Unacceptable Product: Example of overpacking and featheredge. Excess material is present in bell end of pipe caused by mix packed past the end of barrel during production. See BMPR Policy Memo, Section 23, Point 1. Page 33 of 63

REINFORCED CONCRETE PIPE PHYSICAL MEASUREMENTS Unacceptable Product: Pipe spigot is out of round and does not meet dimensions or dimensional tolerances. See BMPR Policy Memo, Section 23, Point 1. Page 34 of 63

REINFORCED CONCRETE PIPE PHYSICAL MEASUREMENTS Unacceptable Product: Pipe exhibits interior delamination. In this case, also called blow out of concrete. See BMPR Policy Memo, Section 23, Point 1. Page 35 of 63

REINFORCED CONCRETE PIPE PHYSICAL MEASUREMENTS Unacceptable Product: Pipe exhibits delamination. See BMPR Policy Memo, Section 23, Point 1. Page 36 of 63

REINFORCED CONCRETE PIPE SMOOTHNESS Acceptable Product: Rough interior of pipe is caused by dry casting moisture levels not at optimum. Voids may be approaching exceedance of 1 percent of the interior surface area. Very borderline on being substantially free from surface roughness. In this case, however, inspector can accept product. See BMPR Policy Memo, Section 23, Points 3 and 4. Page 37 of 63

REINFORCED CONCRETE PIPE SMOOTHNESS Unacceptable Product: Interior of pipe is not substantially free from surface roughness. See BMPR Policy Memo, Section 23, Point 4. Page 38 of 63

REINFORCED CONCRETE PIPE SMOOTHNESS Unacceptable Product: Interior of pipe is not substantially free from surface roughness. See BMPR Policy Memo, Section 23, Point 4. Page 39 of 63

REINFORCED CONCRETE PIPE - SMOOTHNESS AND OTHER DEFECTS Unacceptable Product: Example of unacceptable workmanship of pipe tee collar. See BMPR Policy Memo, Section 23, Points 4 and 9. Other Defects for this case include mortar used in joint contaminated with a foreign substance. The pipe tee collar looked acceptable when it arrived on jobsite but became unacceptable when mortar in joint of pipe tee collar expanded after being buried and exposed to ground moisture. Page 40 of 63

REINFORCED CONCRETE PIPE - ELBOW Acceptable Product: Example of good workmanship on elbow. Page 41 of 63

REINFORCED CONCRETE PIPE - ELBOW Acceptable Product: Example of good workmanship on elbow. Page 42 of 63

REINFORCED CONCRETE PIPE - ELBOW Unacceptable Product: Concrete material failure in joint resulting in cracks that pass entirely through wall of pipe. See BMPR Policy Memo, Section 23, Point 2.a. Page 43 of 63

REINFORCED CONCRETE PRODUCT - FLARED END SECTION OF CULVERT Acceptable Product: Example of an acceptable flared end section with grate and toe wall. Page 44 of 63

TEMPORARY CONCRETE BARRIER - CONNECTION DETAIL Acceptable Joint: Example of IDOT s joint design detail for temporary concrete barrier. See Highway Standard 704001-06. Page 45 of 63

REINFORCED CONCRETE PIPE - REPAIRS Acceptable Repair: Pipe joint repair shows good bond and conformance with physical dimensions. See BMPR Policy Memo, Section 24, Points 2 and 4. Page 46 of 63

REINFORCED CONCRETE PIPE REPAIRS Unacceptable Repair: Pipe joint repair indicates a poor bond and cracking. See BMPR Policy Memo, Section 24, Points 2 and 4. Page 47 of 63

REINFORCED CONCRETE PIPE REPAIRS Acceptable Repair: Example of acceptable patch. See BMPR Policy Memo, Section 24, Points 2 and 4. Page 48 of 63

REINFORCED CONCRETE PIPE REPAIRS Acceptable Repair: Example of acceptable patch. See BMPR Policy Memo, Section 24, Points 2 and 4. Page 49 of 63

REINFORCED CONCRETE PIPE - IDENTIFICATION MARKINGS Acceptable Markings: Example of complete and legible identification markings. Read pipe diameter (24 ), producer mark (ACPI), specification (C 76), class (III) and date (1-11-00). Reject product if the identification markings are not legible or absent. See BMPR Policy Memo, Section 19.5, Section 23 - Point 7 and Attachment C. Page 50 of 63

REINFORCED CONCRETE PIPE IDENTIFICATION MARKINGS Acceptable Markings: Example of complete and legible identification markings. Read pipe diameter (36 ), producer mark (NCP), specification (C 76), class (3) and date (5-29-09). Reject product if the identification markings are not legible or are absent. See BMPR Policy Memo, Section 19.5, Section 23 - Point 7 and Attachment C. Page 51 of 63

MANHOLE CONES - IDENTIFICATION MARKINGS Acceptable Markings: Example of complete and legible identification markings. Read producer mark (MBM), specification (M 199), pipe diameter (48 ), and date (4-22-00). Reject product if the identification markings are not legible or are absent. See BMPR Policy Memo, Section 19.5, Section 23 - Point 7 and Attachment C. Page 52 of 63

TEMPORARY CONCRETE BARRIER - IDENTIFICATION MARKINGS Unacceptable Markings: Example of illegible markings for barrier. See BMPR Policy Memo, Section 19.5, Section 23 - Point 7 and Attachment C. Page 53 of 63

REINFORCED CONCRETE PRODUCT REJECTED PRODUCT MARKINGS Acceptable Practice: Example of acceptable rejected product markings. See BMPR Policy Memo, Section 2.3. Page 54 of 63

REINFORCED CONCRETE PRODUCT REJECTED PRODUCT MARKINGS Acceptable Practice: Example of acceptable rejected product markings. See BMPR Policy Memo, Section 2.3. Page 55 of 63

REINFORCED CONCRETE PIPE PRODUCT STORAGE Acceptable Practice: Pipe storage yard. See BMPR Policy Memo, Section 21. Page 56 of 63

REINFORCED CONCRETE PIPE PRODUCT STORAGE Poor Practice: Example of poor practice. Excessively high pipe stacking can cause damage. See BMPR Policy Memo, Section 21. Page 57 of 63

REINFORCED CONCRETE PIPE PRODUCT STORAGE Acceptable Practice: Example of acceptable pipe stacking. See BMPR Policy Memo, Section 21. Page 58 of 63

MANHOLE CONES - PRODUCT STORAGE Acceptable Practice: Good yard stacking with gravel base. See BMPR Policy Memo, Section 21. Page 59 of 63

RISER COLLARS PRODUCT STORAGE Acceptable Practice: Example of assembled stack of riser collars. See BMPR Policy Memo, Section 21. Page 60 of 63

CATCH BASINS PRODUCT STORAGE Acceptable Practice: Good yard stacking with gravel base. See BMPR Policy Memo, Section 21. Page 61 of 63

TEMPORARY CONCRETE BARRIERS PRODUCT STORAGE Acceptable Practice: Example of temporary concrete barrier yard. See BMPR Policy Memo, Section 21. Page 62 of 63

TEMPORARY CONCRETE BARRIERS PRODUCT STORAGE Acceptable Practice: Example of temporary concrete barrier yard. See BMPR Policy Memo, Section 21. Page 63 of 63