// Version 102 //Absolute Starting Register Number, (Hexadecimal) Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005 Absolute Starting Register Number, (Decimal) Data Point Length Units Valid Response // ISX 0000 0 EMS-EMU2 DEVICE TYPE ISX 1 ENUM 11 = EMS 15 = EMU2 0001 1 EMS-EMU2 DEVICE STATUS ISX 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical 0002 2 EMS-EMU2 PROBE 1 TEMP ISX 1 DEGREES Celsius Temperature 0003 3 EMS-EMU2 PROBE 2 TEMP ISX 1 DEGREES Celsius Temperature 0004 4 EMS-EMU2 PROBE 1 HUMIDITY ISX 1 PERCENT Humidity 0005 5 EMS-EMU2 PROBE 2 HUMIDITY ISX 1 PERCENT Humidity 0006 6 EMS-EMU2 ISX RESERVED REGISTERS 250 NA Reserved // EMS 0100 256 EMS-EMU2 DEVICE TYPE 1 ENUM 11 = EMS 15 = EMU2 0101 257 EMS-EMU2 DEVICE STATUS 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical 0102 258 EMS-EMU2 NAME 11 ASCII EM Device Name 010D 269 EMS-EMU2 INTERNAL MODEL NUMBER 1 ENUM 01 = EMS 03 = EMU2 010E 270 EMS-EMU2 PRODUCT NUMBER 9 ASCII TBD 0117 279 EMS-EMU2 FIRMWARE REV 6 ASCII TBD 011D 285 EMS-EMU2 HARDWARE REV 9 ASCII TBD 0126 294 EMS-EMU2 MANUFACTURE DATE 6 ASCII TBD 012C 300 EMS-EMU2 SERIAL NUMBER 8 ASCII TBD 0134 308 EMS-EMU2 PROBES OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 0135 309 EMS SENSORS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 0136 310 EMS-EMU2 CONTACTS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm 0137 311 EMS-EMU2 RELAYS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm 0138 312 EMS-EMU2 ARUS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 0139 313 EMS CHECKLOGLIGHT 1 ENUM 01 = Disabled 02 = Informational 03 = Warning 04 = Severe 013A 314 EMS-EMU2 TEMP DISPLAY TYPE 1 ENUM 01 = Celsius 02 = Farenheit 013B 315 EMS-EMU2 MAJOR ALARM 1 ENUM 01 = On 02 = Off 013C 316 EMS-EMU2 MINOR ALARM 1 ENUM 01 = On 02 = Off 013D 317 EMS HARDWARE STATE (see Note 5.) 1 ENUM 00 = No Alarms 01 = Alink Fault 02 = Connector Sense Fault 013E 318 EMS-EMU2 SYSTEM RESERVED REGISTERS 194 NA Reserved // Probe 1 0200 512 EMS-EMU2 PROBE 1 NAME 11 ASCII Probe 1 Name 020B 523 EMS-EMU2 PROBE 1 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 020C 524 EMS-EMU2 PROBE 1 LOW TEMP ALARM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 020D 525 EMS-EMU2 PROBE 1 LOW TEMP THOLD 1 DEGREES Probe 1 Low Temperature Threshold 020E 526 EMS-EMU2 PROBE 1 TEMP 1 DEPENDENCY Probe 1 Temperature 020F 527 EMS-EMU2 PROBE 1 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0210 528 EMS-EMU2 PROBE 1 HIGH TEMP THOLD 1 DEGREES Probe 1 High Temperature Threshold 0211 529 EMS-EMU2 PROBE 1 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0212 530 EMS-EMU2 PROBE 1 LOW HUM THOLD 1 PERCENT Probe 1 Low Humidity Threshold 0213 531 EMS-EMU2 PROBE 1 HUM 1 PERCENT Probe 1 Humidity 0214 532 EMS-EMU2 PROBE 1 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0215 533 EMS-EMU2 PROBE 1 HIGH HUM THOLD 1 PERCENT Probe 1 High Humidity Threshold 0216 534 EMS-EMU2 PROBE 1 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0217 535 EMS-EMU2 PROBE 1 MAXIMUM TEMP THOLD 1 DEGREES Probe 1 Maximum Temperature Threshold 0218 536 EMS-EMU2 PROBE 1 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0219 537 EMS-EMU2 PROBE 1 MINIMUM TEMP THOLD 1 DEGREES Probe 1 Minimum Temperature Threshold 021A 538 EMS-EMU2 PROBE 1 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021B 539 EMS-EMU2 PROBE 1 MAXIMUM HUM THOLD 1 PERCENT Probe 1 Maximum Humidity Threshold 021C 540 EMS-EMU2 PROBE 1 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021D 541 EMS-EMU2 PROBE 1 MINIMUM HUM THOLD 1 DEGREES Probe 1 Minimum Humidity Threshold 021E 542 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Short-term Increasing Variance 021F 543 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING TIME 1 SECONDS Probe 1 Short-term Increasing Time 0220 544 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0221 545 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Short-term Decreasing Variance 0222 546 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING TIME 1 SECONDS Probe 1 Short-term Decreasing Time 0223 547 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0224 548 EMS-EMU2 PROBE 1 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance 0225 549 EMS-EMU2 PROBE 1 LONG-TERM INCREASING TIME 1 HOURS Probe 1 Long-term Increasing Time 0226 550 EMS-EMU2 PROBE 1 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0227 551 EMS-EMU2 PROBE 1 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance 0228 552 EMS-EMU2 PROBE 1 LONG-TERM DECREASING TIME 1 HOURS Probe 1 Long-term Increasing Time 0229 553 EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 022A 554 EMS-EMU2 PROBE 1 RESERVED REGISTERS 22 NA Reserved // Probe 2 0240 576 EMS-EMU2 PROBE 2 NAME 11 ASCII Probe 2 Name 024B 587 EMS-EMU2 PROBE 2 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 024C 588 EMS-EMU2 PROBE 2 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 024D 589 EMS-EMU2 PROBE 2 LOW TEMP THOLD 1 DEGREES Probe 2 Low Temperature Threshold 024E 590 EMS-EMU2 PROBE 2 TEMP 1 DEPENDENCY Probe 2 Temperature 024F 591 EMS-EMU2 PROBE 2 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0250 592 EMS-EMU2 PROBE 2 HIGH TEMP THOLD 1 DEGREES Probe 2 High Temperature Threshold 0251 593 EMS-EMU2 PROBE 2 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0252 594 EMS-EMU2 PROBE 2 LOW HUM THOLD 1 PERCENT Probe 2 Low Humidity Threshold 0253 595 EMS-EMU2 PROBE 2 HUM 1 PERCENT Probe 2 Humidity 0254 596 EMS-EMU2 PROBE 2 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm
0255 597 EMS-EMU2 PROBE 2 HIGH HUM THOLD 1 PERCENT Probe 2 High Humidity Threshold 0256 598 EMS-EMU2 PROBE 2 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0257 599 EMS-EMU2 PROBE 2 MAXIMUM TEMP THOLD 1 DEGREES Probe 2 Maximum Temperature Threshold 0258 600 EMS-EMU2 PROBE 2 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0259 601 EMS-EMU2 PROBE 2 MINIMUM TEMP THOLD 1 DEGREES Probe 2 Minimum Temperature Threshold 025A 602 EMS-EMU2 PROBE 2 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025B 603 EMS-EMU2 PROBE 2 MAXIMUM HUM THOLD 1 PERCENT Probe 2 Maximum Humidity Threshold 025C 604 EMS-EMU2 PROBE 2 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025D 605 EMS-EMU2 PROBE 2 MINIMUM HUM THOLD 1 DEGREES Probe 2 Minimum Humidity Threshold 025E 606 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Short-term Increasing Variance 025F 607 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING TIME 1 SECONDS Probe 2 Short-term Increasing Time 0260 608 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0261 609 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Short-term Decreasing Variance 0262 610 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING TIME 1 SECONDS Probe 2 Short-term Decreasing Time 0263 611 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0264 612 EMS-EMU2 PROBE 2 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance 0265 613 EMS-EMU2 PROBE 2 LONG-TERM INCREASING TIME 1 HOURS Probe 2 Long-term Increasing Time 0266 614 EMS-EMU2 PROBE 2 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0267 615 EMS-EMU2 PROBE 2 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance 0268 616 EMS-EMU2 PROBE 2 LONG-TERM DECREASING TIME 1 HOURS Probe 2 Long-term Increasing Time 0269 617 EMS-EMU2 PROBE 2 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 026A 618 EMS-EMU2 PROBE 2 RESERVED REGISTERS 22 NA Reserved // Probe 3 0280 640 EMS-EMU2 PROBE 3 NAME 11 ASCII Probe 3 Name 028B 651 EMS-EMU2 PROBE 3 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 028C 652 EMS-EMU2 PROBE 3 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 028D 653 EMS-EMU2 PROBE 3 LOW TEMP THOLD 1 DEGREES Probe 3 Low Temperature Threshold 028E 654 EMS-EMU2 PROBE 3 TEMP 1 DEPENDENCY Probe 3 Temperature 028F 655 EMS-EMU2 PROBE 3 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0290 656 EMS-EMU2 PROBE 3 HIGH TEMP THOLD 1 DEGREES Probe 3 High Temperature Threshold 0291 657 EMS-EMU2 PROBE 3 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0292 658 EMS-EMU2 PROBE 3 LOW HUM THOLD 1 PERCENT Probe 3 Low Humidity Threshold 0293 659 EMS-EMU2 PROBE 3 HUM 1 PERCENT Probe 3 Humidity 0294 660 EMS-EMU2 PROBE 3 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0295 661 EMS-EMU2 PROBE 3 HIGH HUM THOLD 1 PERCENT Probe 3 High Humidity Threshold 0296 662 EMS-EMU2 PROBE 3 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0297 663 EMS-EMU2 PROBE 3 MAXIMUM TEMP THOLD 1 DEGREES Probe 3 Maximum Temperature Threshold 0298 664 EMS-EMU2 PROBE 3 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0299 665 EMS-EMU2 PROBE 3 MINIMUM TEMP THOLD 1 DEGREES Probe 3 Minimum Temperature Threshold 029A 666 EMS-EMU2 PROBE 3 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029B 667 EMS-EMU2 PROBE 3 MAXIMUM HUM THOLD 1 PERCENT Probe 3 Maximum Humidity Threshold 029C 668 EMS-EMU2 PROBE 3 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029D 669 EMS-EMU2 PROBE 3 MINIMUM HUM THOLD 1 DEGREES Probe 3 Minimum Humidity Threshold 029E 670 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Short-term Increasing Variance 029F 671 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING TIME 1 SECONDS Probe 3 Short-term Increasing Time 02A0 672 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A1 673 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Short-term Decreasing Variance 02A2 674 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING TIME 1 SECONDS Probe 3 Short-term Decreasing Time 02A3 675 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A4 676 EMS-EMU2 PROBE 3 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A5 677 EMS-EMU2 PROBE 3 LONG-TERM INCREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A6 678 EMS-EMU2 PROBE 3 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A7 679 EMS-EMU2 PROBE 3 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A8 680 EMS-EMU2 PROBE 3 LONG-TERM DECREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A9 681 EMS-EMU2 PROBE 3 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02AA 682 EMS-EMU2 PROBE 3 RESERVED REGISTERS 22 NA Reserved // Probe 4 02C0 704 EMS-EMU2 PROBE 4 NAME 11 ASCII Probe 4 Name 02CB 715 EMS-EMU2 PROBE 4 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 02CC 716 EMS-EMU2 PROBE 4 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02CD 717 EMS-EMU2 PROBE 4 LOW TEMP THOLD 1 DEGREES Probe 4 Low Temperature Threshold 02CE 718 EMS-EMU2 PROBE 4 TEMP 1 DEPENDENCY Probe 4 Temperature 02CF 719 EMS-EMU2 PROBE 4 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D0 720 EMS-EMU2 PROBE 4 HIGH TEMP THOLD 1 DEGREES Probe 4 High Temperature Threshold 02D1 721 EMS-EMU2 PROBE 4 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D2 722 EMS-EMU2 PROBE 4 LOW HUM THOLD 1 PERCENT Probe 4 Low Humidity Threshold 02D3 723 EMS-EMU2 PROBE 4 HUM 1 PERCENT Probe 4 Humidity 02D4 724 EMS-EMU2 PROBE 4 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D5 725 EMS-EMU2 PROBE 4 HIGH HUM THOLD 1 PERCENT Probe 4 High Humidity Threshold 02D6 726 EMS-EMU2 PROBE 4 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D7 727 EMS-EMU2 PROBE 4 MAXIMUM TEMP THOLD 1 DEGREES Probe 4 Maximum Temperature Threshold 02D8 728 EMS-EMU2 PROBE 4 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D9 729 EMS-EMU2 PROBE 4 MINIMUM TEMP THOLD 1 DEGREES Probe 4 Minimum Temperature Threshold 02DA 730 EMS-EMU2 PROBE 4 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DB 731 EMS-EMU2 PROBE 4 MAXIMUM HUM THOLD 1 PERCENT Probe 4 Maximum Humidity Threshold 02DC 732 EMS-EMU2 PROBE 4 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DD 733 EMS-EMU2 PROBE 4 MINIMUM HUM THOLD 1 DEGREES Probe 4 Minimum Humidity Threshold 02DE 734 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Short-term Increasing Variance 02DF 735 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING TIME 1 SECONDS Probe 4 Short-term Increasing Time 02E0 736 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E1 737 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Short-term Decreasing Variance 02E2 738 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING TIME 1 SECONDS Probe 4 Short-term Decreasing Time 02E3 739 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E4 740 EMS-EMU2 PROBE 4 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E5 741 EMS-EMU2 PROBE 4 LONG-TERM INCREASING TIME 1 HOURS Probe 4 Long-term Increasing Time
02E6 742 EMS-EMU2 PROBE 4 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E7 743 EMS-EMU2 PROBE 4 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E8 744 EMS-EMU2 PROBE 4 LONG-TERM DECREASING TIME 1 HOURS Probe 4 Long-term Increasing Time 02E9 745 EMS-EMU2 PROBE 4 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02EA 746 EMS-EMU2 PROBE 4 RESERVED REGISTERS 22 NA Reserved // Probe 5 0300 768 EMS PROBE 5 NAME 11 ASCII Probe 5 Name 030B 779 EMS PROBE 5 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 030C 780 EMS PROBE 5 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 030D 781 EMS PROBE 5 LOW TEMP THOLD 1 DEGREES Probe 5 Low Temperature Threshold 030E 782 EMS PROBE 5 TEMP 1 DEPENDENCY Probe 5 Temperature 030F 783 EMS PROBE 5 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0310 784 EMS PROBE 5 HIGH TEMP THOLD 1 DEGREES Probe 5 High Temperature Threshold 0311 785 EMS PROBE 5 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0312 786 EMS PROBE 5 LOW HUM THOLD 1 PERCENT Probe 5 Low Humidity Threshold 0313 787 EMS PROBE 5 HUM 1 PERCENT Probe 5 Humidity 0314 788 EMS PROBE 5 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0315 789 EMS PROBE 5 HIGH HUM THOLD 1 PERCENT Probe 5 High Humidity Threshold 0316 790 EMS PROBE 5 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0317 791 EMS PROBE 5 MAXIMUM TEMP THOLD 1 DEGREES Probe 5 Maximum Temperature Threshold 0318 792 EMS PROBE 5 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0319 793 EMS PROBE 5 MINIMUM TEMP THOLD 1 DEGREES Probe 5 Minimum Temperature Threshold 031A 794 EMS PROBE 5 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031B 795 EMS PROBE 5 MAXIMUM HUM THOLD 1 PERCENT Probe 5 Maximum Humidity Threshold 031C 796 EMS PROBE 5 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031D 797 EMS PROBE 5 MINIMUM HUM THOLD 1 DEGREES Probe 5 Minimum Humidity Threshold 031E 798 EMS PROBE 5 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Short-term Increasing Variance 031F 799 EMS PROBE 5 SHORT-TERM INCREASING TIME 1 SECONDS Probe 5 Short-term Increasing Time 0320 800 EMS PROBE 5 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0321 801 EMS PROBE 5 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Short-term Decreasing Variance 0322 802 EMS PROBE 5 SHORT-TERM DECREASING TIME 1 SECONDS Probe 5 Short-term Decreasing Time 0323 803 EMS PROBE 5 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0324 804 EMS PROBE 5 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance 0325 805 EMS PROBE 5 LONG-TERM INCREASING TIME 1 HOURS Probe 5 Long-term Increasing Time 0326 806 EMS PROBE 5 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0327 807 EMS PROBE 5 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance 0328 808 EMS PROBE 5 LONG-TERM DECREASING TIME 1 HOURS Probe 5 Long-term Increasing Time 0329 809 EMS PROBE 5 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 032A 810 EMS PROBE 5 RESERVED REGISTERS 22 NA Reserved // Probe 6 0340 832 EMS PROBE 6 NAME 11 ASCII Probe 6 Name 034B 843 EMS PROBE 6 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 034C 844 EMS PROBE 6 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 034D 845 EMS PROBE 6 LOW TEMP THOLD 1 DEGREES Probe 6 Low Temperature Threshold 034E 846 EMS PROBE 6 TEMP 1 DEPENDENCY Probe 6 Temperature 034F 847 EMS PROBE 6 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0350 848 EMS PROBE 6 HIGH TEMP THOLD 1 DEGREES Probe 6 High Temperature Threshold 0351 849 EMS PROBE 6 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0352 850 EMS PROBE 6 LOW HUM THOLD 1 PERCENT Probe 6 Low Humidity Threshold 0353 851 EMS PROBE 6 HUM 1 PERCENT Probe 6 Humidity 0354 852 EMS PROBE 6 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0355 853 EMS PROBE 6 HIGH HUM THOLD 1 PERCENT Probe 6 High Humidity Threshold 0356 854 EMS PROBE 6 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0357 855 EMS PROBE 6 MAXIMUM TEMP THOLD 1 DEGREES Probe 6 Maximum Temperature Threshold 0358 856 EMS PROBE 6 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0359 857 EMS PROBE 6 MINIMUM TEMP THOLD 1 DEGREES Probe 6 Minimum Temperature Threshold 035A 858 EMS PROBE 6 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035B 859 EMS PROBE 6 MAXIMUM HUM THOLD 1 PERCENT Probe 6 Maximum Humidity Threshold 035C 860 EMS PROBE 6 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035D 861 EMS PROBE 6 MINIMUM HUM THOLD 1 DEGREES Probe 6 Minimum Humidity Threshold 035E 862 EMS PROBE 6 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Short-term Increasing Variance 035F 863 EMS PROBE 6 SHORT-TERM INCREASING TIME 1 SECONDS Probe 6 Short-term Increasing Time 0360 864 EMS PROBE 6 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0361 865 EMS PROBE 6 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Short-term Decreasing Variance 0362 866 EMS PROBE 6 SHORT-TERM DECREASING TIME 1 SECONDS Probe 6 Short-term Decreasing Time 0363 867 EMS PROBE 6 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0364 868 EMS PROBE 6 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance 0365 869 EMS PROBE 6 LONG-TERM INCREASING TIME 1 HOURS Probe 6 Long-term Increasing Time 0366 870 EMS PROBE 6 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0367 871 EMS PROBE 6 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance 0368 872 EMS PROBE 6 LONG-TERM DECREASING TIME 1 HOURS Probe 6 Long-term Increasing Time 0369 873 EMS PROBE 6 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 036A 874 EMS PROBE 6 RESERVED REGISTERS 22 NA Reserved // Probe 7 0380 896 EMS PROBE 7 NAME 11 ASCII Probe 7 Name 038B 907 EMS PROBE 7 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 038C 908 EMS PROBE 7 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 038D 909 EMS PROBE 7 LOW TEMP THOLD 1 DEGREES Probe 7 Low Temperature Threshold 038E 910 EMS PROBE 7 TEMP 1 DEPENDENCY Probe 7 Temperature 038F 911 EMS PROBE 7 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0390 912 EMS PROBE 7 HIGH TEMP THOLD 1 DEGREES Probe 7 High Temperature Threshold 0391 913 EMS PROBE 7 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0392 914 EMS PROBE 7 LOW HUM THOLD 1 PERCENT Probe 7 Low Humidity Threshold 0393 915 EMS PROBE 7 HUM 1 PERCENT Probe 7 Humidity 0394 916 EMS PROBE 7 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm
0395 917 EMS PROBE 7 HIGH HUM THOLD 1 PERCENT Probe 7 High Humidity Threshold 0396 918 EMS PROBE 7 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0397 919 EMS PROBE 7 MAXIMUM TEMP THOLD 1 DEGREES Probe 7 Maximum Temperature Threshold 0398 920 EMS PROBE 7 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0399 921 EMS PROBE 7 MINIMUM TEMP THOLD 1 DEGREES Probe 7 Minimum Temperature Threshold 039A 922 EMS PROBE 7 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039B 923 EMS PROBE 7 MAXIMUM HUM THOLD 1 PERCENT Probe 7 Maximum Humidity Threshold 039C 924 EMS PROBE 7 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039D 925 EMS PROBE 7 MINIMUM HUM THOLD 1 DEGREES Probe 7 Minimum Humidity Threshold 039E 926 EMS PROBE 7 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Short-term Increasing Variance 039F 927 EMS PROBE 7 SHORT-TERM INCREASING TIME 1 SECONDS Probe 7 Short-term Increasing Time 03A0 928 EMS PROBE 7 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A1 929 EMS PROBE 7 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Short-term Decreasing Variance 03A2 930 EMS PROBE 7 SHORT-TERM DECREASING TIME 1 SECONDS Probe 7 Short-term Decreasing Time 03A3 931 EMS PROBE 7 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A4 932 EMS PROBE 7 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A5 933 EMS PROBE 7 LONG-TERM INCREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A6 934 EMS PROBE 7 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A7 935 EMS PROBE 7 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A8 936 EMS PROBE 7 LONG-TERM DECREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A9 937 EMS PROBE 7 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03AA 938 EMS PROBE 7 RESERVED REGISTERS 22 NA Reserved // Probe 8 03C0 960 EMS PROBE 8 NAME 11 ASCII Probe 8 Name 03CB 971 EMS PROBE 8 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 03CC 972 EMS PROBE 8 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03CD 973 EMS PROBE 8 LOW TEMP THOLD 1 DEGREES Probe 8 Low Temperature Threshold 03CE 974 EMS PROBE 8 TEMP 1 DEPENDENCY Probe 8 Temperature 03CF 975 EMS PROBE 8 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D0 976 EMS PROBE 8 HIGH TEMP THOLD 1 DEGREES Probe 8 High Temperature Threshold 03D1 977 EMS PROBE 8 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D2 978 EMS PROBE 8 LOW HUM THOLD 1 PERCENT Probe 8 Low Humidity Threshold 03D3 979 EMS PROBE 8 HUM 1 PERCENT Probe 8 Humidity 03D4 980 EMS PROBE 8 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D5 981 EMS PROBE 8 HIGH HUM THOLD 1 PERCENT Probe 8 High Humidity Threshold 03D6 982 EMS PROBE 8 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D7 983 EMS PROBE 8 MAXIMUM TEMP THOLD 1 DEGREES Probe 8 Maximum Temperature Threshold 03D8 984 EMS PROBE 8 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D9 985 EMS PROBE 8 MINIMUM TEMP THOLD 1 DEGREES Probe 8 Minimum Temperature Threshold 03DA 986 EMS PROBE 8 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DB 987 EMS PROBE 8 MAXIMUM HUM THOLD 1 PERCENT Probe 8 Maximum Humidity Threshold 03DC 988 EMS PROBE 8 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DD 989 EMS PROBE 8 MINIMUM HUM THOLD 1 DEGREES Probe 8 Minimum Humidity Threshold 03DE 990 EMS PROBE 8 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Short-term Increasing Variance 03DF 991 EMS PROBE 8 SHORT-TERM INCREASING TIME 1 SECONDS Probe 8 Short-term Increasing Time 03E0 992 EMS PROBE 8 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E1 993 EMS PROBE 8 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Short-term Decreasing Variance 03E2 994 EMS PROBE 8 SHORT-TERM DECREASING TIME 1 SECONDS Probe 8 Short-term Decreasing Time 03E3 995 EMS PROBE 8 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E4 996 EMS PROBE 8 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E5 997 EMS PROBE 8 LONG-TERM INCREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E6 998 EMS PROBE 8 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E7 999 EMS PROBE 8 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E8 1000 EMS PROBE 8 LONG-TERM DECREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E9 1001 EMS PROBE 8 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03EA 1002 EMS PROBE 8 RESERVED REGISTERS 22 NA Reserved // Probe 9 0400 1024 EMS PROBE 9 NAME 11 ASCII Probe 9 Name 040B 1035 EMS PROBE 9 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 040C 1036 EMS PROBE 9 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 040D 1037 EMS PROBE 9 LOW TEMP THOLD 1 DEGREES Probe 9 Low Temperature Threshold 040E 1038 EMS PROBE 9 TEMP 1 DEPENDENCY Probe 9 Temperature 040F 1039 EMS PROBE 9 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0410 1040 EMS PROBE 9 HIGH TEMP THOLD 1 DEGREES Probe 9 High Temperature Threshold 0411 1041 EMS PROBE 9 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0412 1042 EMS PROBE 9 LOW HUM THOLD 1 PERCENT Probe 9 Low Humidity Threshold 0413 1043 EMS PROBE 9 HUM 1 PERCENT Probe 9 Humidity 0414 1044 EMS PROBE 9 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0415 1045 EMS PROBE 9 HIGH HUM THOLD 1 PERCENT Probe 9 High Humidity Threshold 0416 1046 EMS PROBE 9 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0417 1047 EMS PROBE 9 MAXIMUM TEMP THOLD 1 DEGREES Probe 9 Maximum Temperature Threshold 0418 1048 EMS PROBE 9 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0419 1049 EMS PROBE 9 MINIMUM TEMP THOLD 1 DEGREES Probe 9 Minimum Temperature Threshold 041A 1050 EMS PROBE 9 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041B 1051 EMS PROBE 9 MAXIMUM HUM THOLD 1 PERCENT Probe 9 Maximum Humidity Threshold 041C 1052 EMS PROBE 9 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041D 1053 EMS PROBE 9 MINIMUM HUM THOLD 1 DEGREES Probe 9 Minimum Humidity Threshold 041E 1054 EMS PROBE 9 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Short-term Increasing Variance 041F 1055 EMS PROBE 9 SHORT-TERM INCREASING TIME 1 SECONDS Probe 9 Short-term Increasing Time 0420 1056 EMS PROBE 9 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0421 1057 EMS PROBE 9 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Short-term Decreasing Variance 0422 1058 EMS PROBE 9 SHORT-TERM DECREASING TIME 1 SECONDS Probe 9 Short-term Decreasing Time 0423 1059 EMS PROBE 9 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0424 1060 EMS PROBE 9 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance 0425 1061 EMS PROBE 9 LONG-TERM INCREASING TIME 1 HOURS Probe 9 Long-term Increasing Time
0426 1062 EMS PROBE 9 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0427 1063 EMS PROBE 9 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance 0428 1064 EMS PROBE 9 LONG-TERM DECREASING TIME 1 HOURS Probe 9 Long-term Increasing Time 0429 1065 EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 042A 1066 EMS PROBE 9 RESERVED REGISTERS 22 NA Reserved // Probe 10 0440 1088 EMS PROBE 10 NAME 11 ASCII Probe 10 Name 044B 1099 EMS PROBE 10 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 044C 1100 EMS PROBE 10 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 044D 1101 EMS PROBE 10 LOW TEMP THOLD 1 DEGREES Probe 10 Low Temperature Threshold 044E 1102 EMS PROBE 10 TEMP 1 DEPENDENCY Probe 10 Temperature 044F 1103 EMS PROBE 10 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0450 1104 EMS PROBE 10 HIGH TEMP THOLD 1 DEGREES Probe 10 High Temperature Threshold 0451 1105 EMS PROBE 10 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0452 1106 EMS PROBE 10 LOW HUM THOLD 1 PERCENT Probe 10 Low Humidity Threshold 0453 1107 EMS PROBE 10 HUM 1 PERCENT Probe 10 Humidity 0454 1108 EMS PROBE 10 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0455 1109 EMS PROBE 10 HIGH HUM THOLD 1 PERCENT Probe 10 High Humidity Threshold 0456 1110 EMS PROBE 10 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0457 1111 EMS PROBE 10 MAXIMUM TEMP THOLD 1 DEGREES Probe 10 Maximum Temperature Threshold 0458 1112 EMS PROBE 10 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0459 1113 EMS PROBE 10 MINIMUM TEMP THOLD 1 DEGREES Probe 10 Minimum Temperature Threshold 045A 1114 EMS PROBE 10 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045B 1115 EMS PROBE 10 MAXIMUM HUM THOLD 1 PERCENT Probe 10 Maximum Humidity Threshold 045C 1116 EMS PROBE 10 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045D 1117 EMS PROBE 10 MINIMUM HUM THOLD 1 DEGREES Probe 10 Minimum Humidity Threshold 045E 1118 EMS PROBE 10 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Short-term Increasing Variance 045F 1119 EMS PROBE 10 SHORT-TERM INCREASING TIME 1 SECONDS Probe 10 Short-term Increasing Time 0460 1120 EMS PROBE 10 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0461 1121 EMS PROBE 10 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Short-term Decreasing Variance 0462 1122 EMS PROBE 10 SHORT-TERM DECREASING TIME 1 SECONDS Probe 10 Short-term Decreasing Time 0463 1123 EMS PROBE 10 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0464 1124 EMS PROBE 10 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance 0465 1125 EMS PROBE 10 LONG-TERM INCREASING TIME 1 HOURS Probe 10 Long-term Increasing Time 0466 1126 EMS PROBE 10 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0467 1127 EMS PROBE 10 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance 0468 1128 EMS PROBE 10 LONG-TERM DECREASING TIME 1 HOURS Probe 10 Long-term Increasing Time 0469 1129 EMS PROBE 10 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 046A 1130 EMS PROBE 10 RESERVED REGISTERS 22 NA Reserved // Sensor 1 0480 1152 EMS SENSOR 1 DESCRIPTION NAME 3 ASCII Sensor 1 Descriptive Name 0483 1155 EMS SENSOR 1 NAME 11 ASCII Sensor 1 Custom Name 048E 1166 EMS SENSOR 1 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 048F 1167 EMS SENSOR 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0490 1168 EMS SENSOR 1 NORMAL 1 ENUM 01 = Closed 02 = Open 0491 1169 EMS SENSOR 1 DELAY 1 SECONDS Sensor 1 Delay 0492 1170 EMS SENSOR 1 RESERVED REGISTERS 46 NA Reserved // Sensor 2 04C0 1216 EMS SENSOR 2 DESCRIPTION NAME 3 ASCII Sensor 2 Descriptive Name 04C3 1219 EMS SENSOR 2 NAME 11 ASCII Sensor 2 Custom Name 04CE 1230 EMS SENSOR 2 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 04CF 1231 EMS SENSOR 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 04D0 1232 EMS SENSOR 2 NORMAL 1 ENUM 01 = Closed 02 = Open 04D1 1233 EMS SENSOR 2 DELAY 1 SECONDS Sensor 2 Delay 04D2 1234 EMS SENSOR 2 RESERVED REGISTERS 46 NA Reserved // Sensor 3 0500 1280 EMS SENSOR 3 DESCRIPTION NAME 5 ASCII Sensor 3 Descriptive Name 0505 1285 EMS SENSOR 3 NAME 11 ASCII Sensor 3 Custom Name 0510 1296 EMS SENSOR 3 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 0511 1297 EMS SENSOR 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0512 1298 EMS SENSOR 3 NORMAL 1 ENUM 01 = Closed 02 = Open 0513 1299 EMS SENSOR 3 DELAY 1 SECONDS Sensor 3 Delay 0514 1300 EMS SENSOR 3 RESERVED REGISTERS 44 NA Reserved // Sensor 4 0540 1344 EMS SENSOR 4 DESCRIPTION NAME 3 ASCII Sensor 4 Descriptive Name 0543 1347 EMS SENSOR 4 NAME 11 ASCII Sensor 4 Custom Name 054E 1358 EMS SENSOR 4 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 054F 1359 EMS SENSOR 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0550 1360 EMS SENSOR 4 NORMAL 1 ENUM 01 = Closed 02 = Open 0551 1361 EMS SENSOR 4 DELAY 1 SECONDS Sensor 4 Delay 0552 1362 EMS SENSOR 4 RESERVED REGISTERS 46 NA Reserved // Sensor 5 0580 1408 EMS SENSOR 5 DESCRIPTION NAME 3 ASCII Sensor 5 Descriptive Name 0583 1411 EMS SENSOR 5 NAME 11 ASCII Sensor 5 Custom Name 058E 1422 EMS SENSOR 5 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 058F 1423 EMS SENSOR 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0590 1424 EMS SENSOR 5 NORMAL 1 ENUM 01 = Closed 02 = Open 0591 1425 EMS SENSOR 5 DELAY 1 SECONDS Sensor 5 Delay 0592 1426 EMS SENSOR 5 RESERVED REGISTERS 46 NA Reserved // Sensor 6 05C0 1472 EMS SENSOR 6 DESCRIPTION NAME 2 ASCII Sensor 6 Descriptive Name 05C2 1474 EMS SENSOR 6 NAME 11 ASCII Sensor 6 Custom Name 05CD 1485 EMS SENSOR 6 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 05CE 1486 EMS SENSOR 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 05CF 1487 EMS SENSOR 6 NORMAL 1 ENUM 01 = Closed 02 = Open 05D0 1488 EMS SENSOR 6 DELAY 1 SECONDS Sensor 6 Delay
05D1 1489 EMS SENSOR 6 RESERVED REGISTERS 47 NA Reserved // Sensor 7 0600 1536 EMS SENSOR 7 DESCRIPTION NAME 2 ASCII Sensor 7 Descriptive Name 0602 1538 EMS SENSOR 7 NAME 11 ASCII Sensor 7 Custom Name 060D 1549 EMS SENSOR 7 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 060E 1550 EMS SENSOR 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 060F 1551 EMS SENSOR 7 NORMAL 1 ENUM 01 = Closed 02 = Open 0610 1552 EMS SENSOR 7 DELAY 1 SECONDS Sensor 7 Delay 0611 1553 EMS SENSOR 7 RESERVED REGISTERS 47 NA Reserved // Contact 1 0640 1600 EMS-EMU2 CONTACT 1 NAME 11 ASCII Contact 1 Name 064B 1611 EMS-EMU2 CONTACT 1 STATE 1 ENUM 01 = Closed 02 = Open 064C 1612 EMS-EMU2 CONTACT 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 064D 1613 EMS-EMU2 CONTACT 1 NORMAL 1 ENUM 01 = Closed 02 = Open 064E 1614 EMS-EMU2 CONTACT 1 RESERVED REGISTERS 50 NA Reserved // Contact 2 0680 1664 EMS-EMU2 CONTACT 2 NAME 11 ASCII Contact 2 Name 068B 1675 EMS-EMU2 CONTACT 2 STATE 1 ENUM 01 = Closed 02 = Open 068C 1676 EMS-EMU2 CONTACT 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 068D 1677 EMS-EMU2 CONTACT 2 NORMAL 1 ENUM 01 = Closed 02 = Open 068E 1678 EMS-EMU2 CONTACT 2 RESERVED REGISTERS 50 NA Reserved // Contact 3 06C0 1728 EMS-EMU2 CONTACT 3 NAME 11 ASCII Contact 3 Name 06CB 1739 EMS-EMU2 CONTACT 3 STATE 1 ENUM 01 = Closed 02 = Open 06CC 1740 EMS-EMU2 CONTACT 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 06CD 1741 EMS-EMU2 CONTACT 3 NORMAL 1 ENUM 01 = Closed 02 = Open 06CE 1742 EMS-EMU2 CONTACT 3 RESERVED REGISTERS 50 NA Reserved // Contact 4 0700 1792 EMS-EMU2 CONTACT 4 NAME 11 ASCII Contact 4 Name 070B 1803 EMS-EMU2 CONTACT 4 STATE 1 ENUM 01 = Closed 02 = Open 070C 1804 EMS-EMU2 CONTACT 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 070D 1805 EMS-EMU2 CONTACT 4 NORMAL 1 ENUM 01 = Closed 02 = Open 070E 1806 EMS-EMU2 CONTACT 4 RESERVED REGISTERS 50 NA Reserved // Contact 5 0740 1856 EMS CONTACT 5 NAME 11 ASCII Contact 5 Name 074B 1867 EMS CONTACT 5 STATE 1 ENUM 01 = Closed 02 = Open 074C 1868 EMS CONTACT 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 074D 1869 EMS CONTACT 5 NORMAL 1 ENUM 01 = Closed 02 = Open 074E 1870 EMS CONTACT 5 RESERVED REGISTERS 50 NA Reserved // Contact 6 0780 1920 EMS CONTACT 6 NAME 11 ASCII Contact 6 Name 078B 1931 EMS CONTACT 6 STATE 1 ENUM 01 = Closed 02 = Open 078C 1932 EMS CONTACT 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 078D 1933 EMS CONTACT 6 NORMAL 1 ENUM 01 = Closed 02 = Open 078E 1934 EMS CONTACT 6 RESERVED REGISTERS 50 NA Reserved // Contact 7 07C0 1984 EMS CONTACT 7 NAME 11 ASCII Contact 7 Name 07CB 1995 EMS CONTACT 7 STATE 1 ENUM 01 = Closed 02 = Open 07CC 1996 EMS CONTACT 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 07CD 1997 EMS CONTACT 7 NORMAL 1 ENUM 01 = Closed 02 = Open 07CE 1998 EMS CONTACT 7 RESERVED REGISTERS 50 NA Reserved // Contact 8 0800 2048 EMS CONTACT 8 NAME 11 ASCII Contact 8 Name 080B 2059 EMS CONTACT 8 STATE 1 ENUM 01 = Closed 02 = Open 080C 2060 EMS CONTACT 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 080D 2061 EMS CONTACT 8 NORMAL 1 ENUM 01 = Closed 02 = Open 080E 2062 EMS CONTACT 8 RESERVED REGISTERS 50 NA Reserved // Relay 1 0840 2112 EMS-EMU2 RELAY 1 NAME 11 ASCII Relay 1 Name 084B 2123 EMS-EMU2 RELAY 1 STATE 1 ENUM 01 = Closed 02 = Open 084C 2124 EMS-EMU2 RELAY 1 NORMAL 1 ENUM 01 = Closed 02 = Open 084D 2125 EMS-EMU2 RELAY 1 RESERVED REGISTERS 51 NA Reserved // Relay 2 0880 2176 EMS RELAY 2 NAME 11 ASCII Relay 2 Name 088B 2187 EMS RELAY 2 STATE 1 ENUM 01 = Closed 02 = Open 088C 2188 EMS RELAY 2 NORMAL 1 ENUM 01 = Closed 02 = Open 088D 2189 EMS RELAY 2 RESERVED REGISTERS 51 NA Reserved // Outlet 1 08C0 2240 EMS OUTLET 1 NAME 11 ASCII Outlet 1 Name 08CB 2251 EMS OUTLET 1 STATE 1 ENUM 01 = On 02 = Off 08CC 2252 EMS OUTLET 1 NORMAL 1 ENUM 01 = On 02 = Off 08CD 2253 EMS OUTLET 1 RESERVED REGISTERS 51 NA Reserved // Outlet 2 0900 2304 EMS OUTLET 2 NAME 11 ASCII Outlet 2 Name 090B 2315 EMS OUTLET 2 STATE 1 ENUM 01 = On 02 = Off 090C 2316 EMS OUTLET 2 NORMAL 1 ENUM 01 = On 02 = Off 090D 2317 EMS OUTLET 2 RESERVED REGISTERS 51 NA Reserved // Beacon (or Fan), see Note 6 0940 2368 EMS-EMU2 BEACON STATE 1 ENUM 01 = On 02 = Off 03 = Not Installed 0941 2369 EMS-EMU2 BEACON RESERVED REGISTERS 15 NA Reserved // ARU 1 0950 2384 EMS-EMU2 ARU 1 NAME 11 ASCII ARU 1 Name 095B 2395 EMS-EMU2 ARU 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 095C 2396 EMS-EMU2 ARU 1 TEMP1 1 DEGREES ARU 1 - Fan 1 Temperature 095D 2397 EMS-EMU2 ARU 1 TEMP2 1 DEGREES ARU 1 - Fan 2 Temperature 095E 2398 EMS-EMU2 ARU 1 TEMP3 1 DEGREES ARU 1 - Fan 3 Temperature
095F 2399 EMS-EMU2 ARU 1 RESERVED 1 NA Reserved 0960 2400 EMS-EMU2 ARU 1 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0961 2401 EMS-EMU2 ARU 1 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0962 2402 EMS-EMU2 ARU 1 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0963 2403 EMS-EMU2 ARU 1 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0964 2404 EMS-EMU2 ARU 1 DIP SWITCH 1 BINARY See Note 4. 0965 2405 EMS-EMU2 ARU 1 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0966 2406 EMS-EMU2 ARU 1 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0967 2407 EMS-EMU2 ARU 1 RESERVED REGISTERS 41 NA Reserved // ARU 2 0990 2448 EMS-EMU2 ARU 2 NAME 11 ASCII ARU 2 Name 099B 2459 EMS-EMU2 ARU 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 099C 2460 EMS-EMU2 ARU 2 TEMP1 1 DEGREES ARU 2 - Fan 1 Temperature 099D 2461 EMS-EMU2 ARU 2 TEMP2 1 DEGREES ARU 2 - Fan 2 Temperature 099E 2462 EMS-EMU2 ARU 2 TEMP3 1 DEGREES ARU 2 - Fan 3 Temperature 099F 2463 EMS-EMU2 ARU 2 RESERVED 1 NA Reserved 09A0 2464 EMS-EMU2 ARU 2 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09A1 2465 EMS-EMU2 ARU 2 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09A2 2466 EMS-EMU2 ARU 2 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09A3 2467 EMS-EMU2 ARU 2 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09A4 2468 EMS-EMU2 ARU 2 DIP SWITCH 1 BINARY See Note 4. 09A5 2469 EMS-EMU2 ARU 2 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09A6 2470 EMS-EMU2 ARU 2 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09A7 2471 EMS-EMU2 ARU 2 RESERVED REGISTERS 41 NA Reserved // ARU 3 09D0 2512 EMS-EMU2 ARU 3 NAME 11 ASCII ARU 3 Name 09DB 2523 EMS-EMU2 ARU 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 09DC 2524 EMS-EMU2 ARU 3 TEMP1 1 DEGREES ARU 3 - Fan 1 Temperature 09DD 2525 EMS-EMU2 ARU 3 TEMP2 1 DEGREES ARU 3 - Fan 2 Temperature 09DE 2526 EMS-EMU2 ARU 3 TEMP3 1 DEGREES ARU 3 - Fan 3 Temperature 09DF 2527 EMS-EMU2 ARU 3 RESERVED 1 NA Reserved 09E0 2528 EMS-EMU2 ARU 3 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09E1 2529 EMS-EMU2 ARU 3 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09E2 2530 EMS-EMU2 ARU 3 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09E3 2531 EMS-EMU2 ARU 3 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09E4 2532 EMS-EMU2 ARU 3 DIP SWITCH 1 BINARY See Note 4. 09E5 2533 EMS-EMU2 ARU 3 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09E6 2534 EMS-EMU2 ARU 3 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09E7 2535 EMS-EMU2 ARU 3 RESERVED REGISTERS 41 NA Reserved // ARU 4 0A10 2576 EMS-EMU2 ARU 4 NAME 11 ASCII ARU 4 Name 0A1B 2587 EMS-EMU2 ARU 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A1C 2588 EMS-EMU2 ARU 4 TEMP1 1 DEGREES ARU 4 - Fan 1 Temperature 0A1D 2589 EMS-EMU2 ARU 4 TEMP2 1 DEGREES ARU 4 - Fan 2 Temperature 0A1E 2590 EMS-EMU2 ARU 4 TEMP3 1 DEGREES ARU 4 - Fan 3 Temperature 0A1F 2591 EMS-EMU2 ARU 4 RESERVED 1 NA Reserved 0A20 2592 EMS-EMU2 ARU 4 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A21 2593 EMS-EMU2 ARU 4 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A22 2594 EMS-EMU2 ARU 4 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A23 2595 EMS-EMU2 ARU 4 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A24 2596 EMS-EMU2 ARU 4 DIP SWITCH 1 BINARY See Note 4. 0A25 2597 EMS-EMU2 ARU 4 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A26 2598 EMS-EMU2 ARU 4 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A27 2599 EMS-EMU2 ARU 4 RESERVED REGISTERS 41 NA Reserved // ARU 5 0A50 2640 EMS-EMU2 ARU 5 NAME 11 ASCII ARU 5 Name 0A5B 2651 EMS-EMU2 ARU 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A5C 2652 EMS-EMU2 ARU 5 TEMP1 1 DEGREES ARU 5 - Fan 1 Temperature 0A5D 2653 EMS-EMU2 ARU 5 TEMP2 1 DEGREES ARU 5 - Fan 2 Temperature 0A5E 2654 EMS-EMU2 ARU 5 TEMP3 1 DEGREES ARU 5 - Fan 3 Temperature 0A5F 2655 EMS-EMU2 ARU 5 RESERVED 1 NA Reserved 0A60 2656 EMS-EMU2 ARU 5 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A61 2657 EMS-EMU2 ARU 5 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A62 2658 EMS-EMU2 ARU 5 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A63 2659 EMS-EMU2 ARU 5 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A64 2660 EMS-EMU2 ARU 5 DIP SWITCH 1 BINARY See Note 4. 0A65 2661 EMS-EMU2 ARU 5 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A66 2662 EMS-EMU2 ARU 5 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A67 2663 EMS-EMU2 ARU 5 RESERVED REGISTERS 41 NA Reserved // ARU 6 0A90 2704 EMS-EMU2 ARU 6 NAME 11 ASCII ARU 6 Name 0A9B 2715 EMS-EMU2 ARU 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A9C 2716 EMS-EMU2 ARU 6 TEMP1 1 DEGREES ARU 6 - Fan 1 Temperature 0A9D 2717 EMS-EMU2 ARU 6 TEMP2 1 DEGREES ARU 6 - Fan 2 Temperature 0A9E 2718 EMS-EMU2 ARU 6 TEMP3 1 DEGREES ARU 6 - Fan 3 Temperature 0A9F 2719 EMS-EMU2 ARU 6 RESERVED 1 NA Reserved 0AA0 2720 EMS-EMU2 ARU 6 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AA1 2721 EMS-EMU2 ARU 6 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AA2 2722 EMS-EMU2 ARU 6 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AA3 2723 EMS-EMU2 ARU 6 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AA4 2724 EMS-EMU2 ARU 6 DIP SWITCH 1 BINARY See Note 4. 0AA5 2725 EMS-EMU2 ARU 6 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AA6 2726 EMS-EMU2 ARU 6 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AA7 2727 EMS-EMU2 ARU 6 RESERVED REGISTERS 41 NA Reserved // ARU 7 0AD0 2768 EMS-EMU2 ARU 7 NAME 11 ASCII ARU 7 Name
0ADB 2779 EMS-EMU2 ARU 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0ADC 2780 EMS-EMU2 ARU 7 TEMP1 1 DEGREES ARU 7 - Fan 1 Temperature 0ADD 2781 EMS-EMU2 ARU 7 TEMP2 1 DEGREES ARU 7 - Fan 2 Temperature 0ADE 2782 EMS-EMU2 ARU 7 TEMP3 1 DEGREES ARU 7 - Fan 3 Temperature 0ADF 2783 EMS-EMU2 ARU 7 RESERVED 1 NA Reserved 0AE0 2784 EMS-EMU2 ARU 7 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AE1 2785 EMS-EMU2 ARU 7 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AE2 2786 EMS-EMU2 ARU 7 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AE3 2787 EMS-EMU2 ARU 7 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AE4 2788 EMS-EMU2 ARU 7 DIP SWITCH 1 BINARY See Note 4. 0AE5 2789 EMS-EMU2 ARU 7 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AE6 2790 EMS-EMU2 ARU 7 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AE7 2791 EMS-EMU2 ARU 7 RESERVED REGISTERS 41 NA Reserved // ARU 8 0B10 2832 EMS-EMU2 ARU 8 NAME 11 ASCII ARU 8 Name 0B1B 2843 EMS-EMU2 ARU 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0B1C 2844 EMS-EMU2 ARU 8 TEMP1 1 DEGREES ARU 8 - Fan 1 Temperature 0B1D 2845 EMS-EMU2 ARU 8 TEMP2 1 DEGREES ARU 8 - Fan 2 Temperature 0B1E 2846 EMS-EMU2 ARU 8 TEMP3 1 DEGREES ARU 8 - Fan 3 Temperature 0B1F 2847 EMS-EMU2 ARU 8 RESERVED 1 NA Reserved 0B20 2848 EMS-EMU2 ARU 8 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0B21 2849 EMS-EMU2 ARU 8 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0B22 2850 EMS-EMU2 ARU 8 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0B23 2851 EMS-EMU2 ARU 8 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0B24 2852 EMS-EMU2 ARU 8 DIP SWITCH 1 BINARY See Note 4. 0B25 2853 EMS-EMU2 ARU 8 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0B26 2854 EMS-EMU2 ARU 8 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0B27 2855 EMS-EMU2 ARU 8 RESERVED REGISTERS 41 NA Reserved // Logging Registers FFEE 65518 APC RX CRC ERRORS 2 LONG RX CRC ERRORS FFF0 65520 APC RX PACKET COUNTER 2 LONG RX PACKET COUNTER FFF2 65522 APC TX PACKET COUNTER 2 LONG TX PACKET COUNTER FFF4 65524 APC SER FRAME ERRORS 2 LONG SER FRAME ERRORS FFF6 65526 APC SER OVERRUN ERRORS 2 LONG SER OVERRUN ERRORS FFF8 65528 APC SER PARITY ERRORS 2 LONG SER PARITY ERRORS FFFA 65530 APC SER RX15 ERRORS 2 LONG SER RX15 ERRORS FFFC 65532 APC SER RX35 ERRORS 2 LONG SER RX35 ERRORS FFFE 65534 APC SER BAUD RATE 1 INTEGER SER BAUD RATE // END OF DATA Note 1: The temperature value returned will be either in Celsius or Fahrenheit depending on the value read from Modbus Register EMS TEMP DISPLAY TYPE. Note 2: The "Alarm Map" represents a bit map of the alarm state(s) Only Beacon (or Fan) and Relay1 are available for EMU2. 01 = No Alarms (bit 0) 02 = Major Alarm (bit 1) 04 = Minor Alarm (bit 2) 08 = Outlet 1 Alarm (bit 3) 16 = Outlet 2 Alarm (bit 4) 32 = Beacon (or Fan) Alarm (bit 5) 64 = Relay 1 Alarm (bit 6) 128 = Relay 2 Alarm (bit 7) Note 3. This value may be in units of DEGREES or Kilowatts. Note 4. The 4 least significant bits of this register define the following: 0000 wxyz - w is the temperature override bit. If w is set, the temperature override condition exists. - x is the least significant bit of the 3 bit ARU CAN bus address - y is the middle bit of the 3 bit ARU CAN bus address - z is the most significant bit of the 3 bit ARU CAN bus address Note 5. The Hardware State is defined as follows: 00 = No Fault. 01 = Alink Fault. (Current Overload condition on the Alink ports.) 02 = Sensor Connection Fault.( Motion or Smoke Alarm port does not have the correct sensor.) 03 = Both Alink and Sensor Connection Fault. Note 6. On some model SKUs, Beacon functionality is replaced by a Fan.