Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005



Similar documents
Alarm Messages Clearing the Hardware Alarms How to Log On Summary Page Navigation Menu... 24

Environmental Management System

Visa Smart Debit/Credit Certificate Authority Public Keys

USER S GUIDE. Contents. NetBotz Rack Monitor 200. Introduction--1. Control Console--8

Features and Benefits

The ASCII Character Set

WeatherLink for Alarm Output. Introduction. Hardware Installation and Requirements. Addendum

Rev 0 25-AUG ipro HVAC and Lighting Installation and Operation Manual

Community College of Philadelphia Calling Code 218 Employer Scan Client Approved: November 17, 2005 Region (CIRCLE) City MSA

GE Security. FHSD Monitor / Web Server user manual

TOTALLY SOLID STATE NON-DIRECTIONAL RADIO BEACONS khz

Controller Automation, Model II+

USER MANUAL. Model U ForeFront Alarm Card SALES OFFICE (301) TECHNICAL SUPPORT (301) An ISO-9001 Certified Company

APC APPLICATION NOTE #156

SERVER CERTIFICATES OF THE VETUMA SERVICE


MPC 4. Machinery Protection Card Type MPC 4 FEATURES. Continuous on-line Machinery Protection Card

Technical Overview Add-on Sensors - Smoke Alarm. Get yours direct at:

INSTALLATION AND OPERATION MANUAL

Current Monitoring Kit QUICK START GUIDE

Current Monitoring Kit

SERVER CERTIFICATES OF THE VETUMA SERVICE

IntesisBox Modbus Server SAMSUNG Air Conditioners

NL708 (XWA11V) Walk-In Temp / Door /Alarm / Light Module

INSTALLATION OPERATING & MAINTENANCE MANUAL

Energy Management System CANBUS Interface Specification

EMDX3 Multifunction meter Cat No ModbusTable LGR EN v1.01.xls

Ambient Temperature In Range Probe X

Kendrick Astro Instruments

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS 16400(LED TYPES) EXAMINED BY : FILE NO. CAS ISSUE : JAN.19,2000 TOTAL PAGE : 7 APPROVED BY:

PE6108/PE6208/PE8108/PE8208

CROSS REFERENCE. Cross Reference Index Cast ID Number Connector ID Number 111 Engine ID Number Ford Motor Company 109

Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

EMERGING DISPLAY CUSTOMER ACCEPTANCE SPECIFICATIONS (LED TYPES) EXAMINED BY : FILE NO. CAS ISSUE : DEC.01,1999 TOTAL PAGE : 7 APPROVED BY:

APPENDIX A: ERROR CODES

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

Pattern Co. Monkey Trouble Wall Quilt. Size: 48" x 58"

Panasonic/Sanyo A/C Interface Modbus RTU Installation Instructions

PN5212/PN5320/PN7212/PN7320

Modbus Tutorial 7/30/01. Tutorial on TTDM-PLUS and TTSIM System Integration using Modbus

NIC Controller & Web Interface

How To Run An Nport I5000A Device Server

How To Set The Sensor On A Powerpoint 3.5 (Powerpoint) On A Blackberry 2.5A (Powerplant) On An Iphone Or Ipad (Powerplant) On The Blackberry 3.2 (

SMART SENSOR COLLECTION

Ademco Vista-20P/First Alert FA-168C Basic Commands

Configuring Alarms & Relays in the Enhanced Transformer Advantage

Configurator Software Manual

URL encoding uses hex code prefixed by %. Quoted Printable encoding uses hex code prefixed by =.

Configuration of the Sentry firmware parameters used in the Bluetooth solution.

SL-8800 HDCP 2.2 and HDCP 1.x Protocol Analyzer for HDMI User Guide

Appendix for Tx5xx and P85x1 manuals

Mobrey Hydrastep and Hydratect

pco 2 Standard Application Pack Control Code: FLSTDMFC0A Version 1.2 s manual

Using the STC firmware

Workshop 7 PC Software - Tracker

Table of Contents. 1. Introduction PDU Package Function Installation Web Interface...7

JNIOR. Overview. Get Connected. Get Results. JNIOR Model 310. JNIOR Model 312. JNIOR Model 314. JNIOR Model 410

Configurable Events for APC Network Management Card

Integration Note. Manufacturer: OVERVIEW AND SUPPORTED FEATURES. OMNISTAT 2 (RC-1000 and RC-2000) WIRED MODELS ONLY.

USB3.0 Docking Station. User Manual (DA-70546)


Technical Information

Modbus Communications for PanelView Terminals

IES-3080/3062 Series. Industrial 8-port managed Ethernet switch. Features. Introduction

How to create OpenDocument URL s with SAP BusinessObjects BI 4.0

HTML Codes - Characters and symbols

SPC-1. Single Point Controller. Operation Manual

Dyeing Programmer DP - 01

Heller Industries, Inc. PN: Rev-I Heller Oven Windows-XP Software Version log for HC1 controller

F453. TiF453. User guide 10/11-01 PC

USB-500 Series Stand-Alone, Low-Cost Data Loggers

Cat Electronic Technician 2015A v1.0 Product Status Report 4/20/2016 2:49 PM

"HIGHER EDUCATION VALUES AND OPINIONS SURVEY" ADVANCED PLACEMENT TEACHERS and GUIDANCE COUNSELORS May-June 1994

2. Terminal arrangement. Default (PV display) (SV display) Communication protocol selection Selects the Communication protocol. Modbus ASCII mode:

SOLARCARE SERIES PRODUCT AND APPLICATION GUIDE

Technical Support Bulletin Nr.18 Modbus Tips

Design of WSN-Based Remote Monitoring System for Environmental Parameters in Substation

E E V R E - R S - O S L O A L R

UPSMON PRO Linux --- User Manual

MIC-3920/MIC-3921 Intelligent system monitor and alarm module for CompactPCI TM

COPAN 400M PSM Service GUI User Guide

Battery Xplorer Enterprise Software Release Notes 3.2

Kurz Instruments Inc. Document AV Document Title: MFTB Event Code Definitions. MFT B-Series Event Codes

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Product Description... 1 Internal Management Features... 3 Front Panel... 5 Watchdog Features... 7

Application Note RMF Magic 5.1.0: EMC Array Group and EMC SRDF/A Reporting. July 2009

Temp. & humidity Transmitter Instructions

ASCII CODES WITH GREEK CHARACTERS

INSTALLATION MANUAL. Address card EKAC10B

PolyGard Carbon Monoxide CO Transmitter ADTX3 1110

QuickSpecs. HP Managed and Unmanaged Notebook Charging Carts. Models HP 30-Notebook Charging Cart

QuickSpecs. HP Managed Power Distribution Units (mapdu) Overview

USB HID to PS/2 Scan Code Translation Table

KLQ750CO controller temp/intensity/feedback/24v/usb/rs622/analog trigger

Contents. Introduction

HP Managed and Unmanaged Notebook Charging Carts Overview. Models HP 30-Notebook Charging Cart. HP 30-Notebook Managed Charging Cart

RadioRA 2 (QS) Lighting and Climate Control. g! 5.4 Fan Controller: g! RadioRA2 Inclusive Software v5.0.8 or newer

T360 Barbecue. Assembly Manual (G30531) Propane 1 YEAR LIMITED WARRANTY

Transcription:

// Version 102 //Absolute Starting Register Number, (Hexadecimal) Modbus Register Map: Environmental Management System and Environmental Monitoring Unit 990-0589A 02/2005 Absolute Starting Register Number, (Decimal) Data Point Length Units Valid Response // ISX 0000 0 EMS-EMU2 DEVICE TYPE ISX 1 ENUM 11 = EMS 15 = EMU2 0001 1 EMS-EMU2 DEVICE STATUS ISX 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical 0002 2 EMS-EMU2 PROBE 1 TEMP ISX 1 DEGREES Celsius Temperature 0003 3 EMS-EMU2 PROBE 2 TEMP ISX 1 DEGREES Celsius Temperature 0004 4 EMS-EMU2 PROBE 1 HUMIDITY ISX 1 PERCENT Humidity 0005 5 EMS-EMU2 PROBE 2 HUMIDITY ISX 1 PERCENT Humidity 0006 6 EMS-EMU2 ISX RESERVED REGISTERS 250 NA Reserved // EMS 0100 256 EMS-EMU2 DEVICE TYPE 1 ENUM 11 = EMS 15 = EMU2 0101 257 EMS-EMU2 DEVICE STATUS 1 ENUM 00 = Unknown 02 = Informational 04 = Warning 08 = Critical 0102 258 EMS-EMU2 NAME 11 ASCII EM Device Name 010D 269 EMS-EMU2 INTERNAL MODEL NUMBER 1 ENUM 01 = EMS 03 = EMU2 010E 270 EMS-EMU2 PRODUCT NUMBER 9 ASCII TBD 0117 279 EMS-EMU2 FIRMWARE REV 6 ASCII TBD 011D 285 EMS-EMU2 HARDWARE REV 9 ASCII TBD 0126 294 EMS-EMU2 MANUFACTURE DATE 6 ASCII TBD 012C 300 EMS-EMU2 SERIAL NUMBER 8 ASCII TBD 0134 308 EMS-EMU2 PROBES OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 0135 309 EMS SENSORS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 0136 310 EMS-EMU2 CONTACTS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm 0137 311 EMS-EMU2 RELAYS OVERALL STATE 1 ENUM 02 = Normal 03 = Alarm 0138 312 EMS-EMU2 ARUS OVERALL STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 0139 313 EMS CHECKLOGLIGHT 1 ENUM 01 = Disabled 02 = Informational 03 = Warning 04 = Severe 013A 314 EMS-EMU2 TEMP DISPLAY TYPE 1 ENUM 01 = Celsius 02 = Farenheit 013B 315 EMS-EMU2 MAJOR ALARM 1 ENUM 01 = On 02 = Off 013C 316 EMS-EMU2 MINOR ALARM 1 ENUM 01 = On 02 = Off 013D 317 EMS HARDWARE STATE (see Note 5.) 1 ENUM 00 = No Alarms 01 = Alink Fault 02 = Connector Sense Fault 013E 318 EMS-EMU2 SYSTEM RESERVED REGISTERS 194 NA Reserved // Probe 1 0200 512 EMS-EMU2 PROBE 1 NAME 11 ASCII Probe 1 Name 020B 523 EMS-EMU2 PROBE 1 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 020C 524 EMS-EMU2 PROBE 1 LOW TEMP ALARM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 020D 525 EMS-EMU2 PROBE 1 LOW TEMP THOLD 1 DEGREES Probe 1 Low Temperature Threshold 020E 526 EMS-EMU2 PROBE 1 TEMP 1 DEPENDENCY Probe 1 Temperature 020F 527 EMS-EMU2 PROBE 1 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0210 528 EMS-EMU2 PROBE 1 HIGH TEMP THOLD 1 DEGREES Probe 1 High Temperature Threshold 0211 529 EMS-EMU2 PROBE 1 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0212 530 EMS-EMU2 PROBE 1 LOW HUM THOLD 1 PERCENT Probe 1 Low Humidity Threshold 0213 531 EMS-EMU2 PROBE 1 HUM 1 PERCENT Probe 1 Humidity 0214 532 EMS-EMU2 PROBE 1 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0215 533 EMS-EMU2 PROBE 1 HIGH HUM THOLD 1 PERCENT Probe 1 High Humidity Threshold 0216 534 EMS-EMU2 PROBE 1 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0217 535 EMS-EMU2 PROBE 1 MAXIMUM TEMP THOLD 1 DEGREES Probe 1 Maximum Temperature Threshold 0218 536 EMS-EMU2 PROBE 1 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0219 537 EMS-EMU2 PROBE 1 MINIMUM TEMP THOLD 1 DEGREES Probe 1 Minimum Temperature Threshold 021A 538 EMS-EMU2 PROBE 1 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021B 539 EMS-EMU2 PROBE 1 MAXIMUM HUM THOLD 1 PERCENT Probe 1 Maximum Humidity Threshold 021C 540 EMS-EMU2 PROBE 1 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 021D 541 EMS-EMU2 PROBE 1 MINIMUM HUM THOLD 1 DEGREES Probe 1 Minimum Humidity Threshold 021E 542 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Short-term Increasing Variance 021F 543 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING TIME 1 SECONDS Probe 1 Short-term Increasing Time 0220 544 EMS-EMU2 PROBE 1 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0221 545 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Short-term Decreasing Variance 0222 546 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING TIME 1 SECONDS Probe 1 Short-term Decreasing Time 0223 547 EMS-EMU2 PROBE 1 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0224 548 EMS-EMU2 PROBE 1 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance 0225 549 EMS-EMU2 PROBE 1 LONG-TERM INCREASING TIME 1 HOURS Probe 1 Long-term Increasing Time 0226 550 EMS-EMU2 PROBE 1 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0227 551 EMS-EMU2 PROBE 1 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 1 Long-term Increasing Variance 0228 552 EMS-EMU2 PROBE 1 LONG-TERM DECREASING TIME 1 HOURS Probe 1 Long-term Increasing Time 0229 553 EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 022A 554 EMS-EMU2 PROBE 1 RESERVED REGISTERS 22 NA Reserved // Probe 2 0240 576 EMS-EMU2 PROBE 2 NAME 11 ASCII Probe 2 Name 024B 587 EMS-EMU2 PROBE 2 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 024C 588 EMS-EMU2 PROBE 2 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 024D 589 EMS-EMU2 PROBE 2 LOW TEMP THOLD 1 DEGREES Probe 2 Low Temperature Threshold 024E 590 EMS-EMU2 PROBE 2 TEMP 1 DEPENDENCY Probe 2 Temperature 024F 591 EMS-EMU2 PROBE 2 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0250 592 EMS-EMU2 PROBE 2 HIGH TEMP THOLD 1 DEGREES Probe 2 High Temperature Threshold 0251 593 EMS-EMU2 PROBE 2 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0252 594 EMS-EMU2 PROBE 2 LOW HUM THOLD 1 PERCENT Probe 2 Low Humidity Threshold 0253 595 EMS-EMU2 PROBE 2 HUM 1 PERCENT Probe 2 Humidity 0254 596 EMS-EMU2 PROBE 2 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm

0255 597 EMS-EMU2 PROBE 2 HIGH HUM THOLD 1 PERCENT Probe 2 High Humidity Threshold 0256 598 EMS-EMU2 PROBE 2 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0257 599 EMS-EMU2 PROBE 2 MAXIMUM TEMP THOLD 1 DEGREES Probe 2 Maximum Temperature Threshold 0258 600 EMS-EMU2 PROBE 2 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0259 601 EMS-EMU2 PROBE 2 MINIMUM TEMP THOLD 1 DEGREES Probe 2 Minimum Temperature Threshold 025A 602 EMS-EMU2 PROBE 2 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025B 603 EMS-EMU2 PROBE 2 MAXIMUM HUM THOLD 1 PERCENT Probe 2 Maximum Humidity Threshold 025C 604 EMS-EMU2 PROBE 2 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 025D 605 EMS-EMU2 PROBE 2 MINIMUM HUM THOLD 1 DEGREES Probe 2 Minimum Humidity Threshold 025E 606 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Short-term Increasing Variance 025F 607 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING TIME 1 SECONDS Probe 2 Short-term Increasing Time 0260 608 EMS-EMU2 PROBE 2 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0261 609 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Short-term Decreasing Variance 0262 610 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING TIME 1 SECONDS Probe 2 Short-term Decreasing Time 0263 611 EMS-EMU2 PROBE 2 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0264 612 EMS-EMU2 PROBE 2 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance 0265 613 EMS-EMU2 PROBE 2 LONG-TERM INCREASING TIME 1 HOURS Probe 2 Long-term Increasing Time 0266 614 EMS-EMU2 PROBE 2 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0267 615 EMS-EMU2 PROBE 2 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 2 Long-term Increasing Variance 0268 616 EMS-EMU2 PROBE 2 LONG-TERM DECREASING TIME 1 HOURS Probe 2 Long-term Increasing Time 0269 617 EMS-EMU2 PROBE 2 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 026A 618 EMS-EMU2 PROBE 2 RESERVED REGISTERS 22 NA Reserved // Probe 3 0280 640 EMS-EMU2 PROBE 3 NAME 11 ASCII Probe 3 Name 028B 651 EMS-EMU2 PROBE 3 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 028C 652 EMS-EMU2 PROBE 3 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 028D 653 EMS-EMU2 PROBE 3 LOW TEMP THOLD 1 DEGREES Probe 3 Low Temperature Threshold 028E 654 EMS-EMU2 PROBE 3 TEMP 1 DEPENDENCY Probe 3 Temperature 028F 655 EMS-EMU2 PROBE 3 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0290 656 EMS-EMU2 PROBE 3 HIGH TEMP THOLD 1 DEGREES Probe 3 High Temperature Threshold 0291 657 EMS-EMU2 PROBE 3 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0292 658 EMS-EMU2 PROBE 3 LOW HUM THOLD 1 PERCENT Probe 3 Low Humidity Threshold 0293 659 EMS-EMU2 PROBE 3 HUM 1 PERCENT Probe 3 Humidity 0294 660 EMS-EMU2 PROBE 3 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0295 661 EMS-EMU2 PROBE 3 HIGH HUM THOLD 1 PERCENT Probe 3 High Humidity Threshold 0296 662 EMS-EMU2 PROBE 3 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0297 663 EMS-EMU2 PROBE 3 MAXIMUM TEMP THOLD 1 DEGREES Probe 3 Maximum Temperature Threshold 0298 664 EMS-EMU2 PROBE 3 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0299 665 EMS-EMU2 PROBE 3 MINIMUM TEMP THOLD 1 DEGREES Probe 3 Minimum Temperature Threshold 029A 666 EMS-EMU2 PROBE 3 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029B 667 EMS-EMU2 PROBE 3 MAXIMUM HUM THOLD 1 PERCENT Probe 3 Maximum Humidity Threshold 029C 668 EMS-EMU2 PROBE 3 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 029D 669 EMS-EMU2 PROBE 3 MINIMUM HUM THOLD 1 DEGREES Probe 3 Minimum Humidity Threshold 029E 670 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Short-term Increasing Variance 029F 671 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING TIME 1 SECONDS Probe 3 Short-term Increasing Time 02A0 672 EMS-EMU2 PROBE 3 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A1 673 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Short-term Decreasing Variance 02A2 674 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING TIME 1 SECONDS Probe 3 Short-term Decreasing Time 02A3 675 EMS-EMU2 PROBE 3 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A4 676 EMS-EMU2 PROBE 3 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A5 677 EMS-EMU2 PROBE 3 LONG-TERM INCREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A6 678 EMS-EMU2 PROBE 3 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02A7 679 EMS-EMU2 PROBE 3 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 3 Long-term Increasing Variance 02A8 680 EMS-EMU2 PROBE 3 LONG-TERM DECREASING TIME 1 HOURS Probe 3 Long-term Increasing Time 02A9 681 EMS-EMU2 PROBE 3 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02AA 682 EMS-EMU2 PROBE 3 RESERVED REGISTERS 22 NA Reserved // Probe 4 02C0 704 EMS-EMU2 PROBE 4 NAME 11 ASCII Probe 4 Name 02CB 715 EMS-EMU2 PROBE 4 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 02CC 716 EMS-EMU2 PROBE 4 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02CD 717 EMS-EMU2 PROBE 4 LOW TEMP THOLD 1 DEGREES Probe 4 Low Temperature Threshold 02CE 718 EMS-EMU2 PROBE 4 TEMP 1 DEPENDENCY Probe 4 Temperature 02CF 719 EMS-EMU2 PROBE 4 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D0 720 EMS-EMU2 PROBE 4 HIGH TEMP THOLD 1 DEGREES Probe 4 High Temperature Threshold 02D1 721 EMS-EMU2 PROBE 4 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D2 722 EMS-EMU2 PROBE 4 LOW HUM THOLD 1 PERCENT Probe 4 Low Humidity Threshold 02D3 723 EMS-EMU2 PROBE 4 HUM 1 PERCENT Probe 4 Humidity 02D4 724 EMS-EMU2 PROBE 4 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D5 725 EMS-EMU2 PROBE 4 HIGH HUM THOLD 1 PERCENT Probe 4 High Humidity Threshold 02D6 726 EMS-EMU2 PROBE 4 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D7 727 EMS-EMU2 PROBE 4 MAXIMUM TEMP THOLD 1 DEGREES Probe 4 Maximum Temperature Threshold 02D8 728 EMS-EMU2 PROBE 4 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02D9 729 EMS-EMU2 PROBE 4 MINIMUM TEMP THOLD 1 DEGREES Probe 4 Minimum Temperature Threshold 02DA 730 EMS-EMU2 PROBE 4 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DB 731 EMS-EMU2 PROBE 4 MAXIMUM HUM THOLD 1 PERCENT Probe 4 Maximum Humidity Threshold 02DC 732 EMS-EMU2 PROBE 4 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02DD 733 EMS-EMU2 PROBE 4 MINIMUM HUM THOLD 1 DEGREES Probe 4 Minimum Humidity Threshold 02DE 734 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Short-term Increasing Variance 02DF 735 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING TIME 1 SECONDS Probe 4 Short-term Increasing Time 02E0 736 EMS-EMU2 PROBE 4 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E1 737 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Short-term Decreasing Variance 02E2 738 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING TIME 1 SECONDS Probe 4 Short-term Decreasing Time 02E3 739 EMS-EMU2 PROBE 4 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E4 740 EMS-EMU2 PROBE 4 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E5 741 EMS-EMU2 PROBE 4 LONG-TERM INCREASING TIME 1 HOURS Probe 4 Long-term Increasing Time

02E6 742 EMS-EMU2 PROBE 4 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02E7 743 EMS-EMU2 PROBE 4 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 4 Long-term Increasing Variance 02E8 744 EMS-EMU2 PROBE 4 LONG-TERM DECREASING TIME 1 HOURS Probe 4 Long-term Increasing Time 02E9 745 EMS-EMU2 PROBE 4 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 02EA 746 EMS-EMU2 PROBE 4 RESERVED REGISTERS 22 NA Reserved // Probe 5 0300 768 EMS PROBE 5 NAME 11 ASCII Probe 5 Name 030B 779 EMS PROBE 5 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 030C 780 EMS PROBE 5 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 030D 781 EMS PROBE 5 LOW TEMP THOLD 1 DEGREES Probe 5 Low Temperature Threshold 030E 782 EMS PROBE 5 TEMP 1 DEPENDENCY Probe 5 Temperature 030F 783 EMS PROBE 5 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0310 784 EMS PROBE 5 HIGH TEMP THOLD 1 DEGREES Probe 5 High Temperature Threshold 0311 785 EMS PROBE 5 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0312 786 EMS PROBE 5 LOW HUM THOLD 1 PERCENT Probe 5 Low Humidity Threshold 0313 787 EMS PROBE 5 HUM 1 PERCENT Probe 5 Humidity 0314 788 EMS PROBE 5 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0315 789 EMS PROBE 5 HIGH HUM THOLD 1 PERCENT Probe 5 High Humidity Threshold 0316 790 EMS PROBE 5 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0317 791 EMS PROBE 5 MAXIMUM TEMP THOLD 1 DEGREES Probe 5 Maximum Temperature Threshold 0318 792 EMS PROBE 5 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0319 793 EMS PROBE 5 MINIMUM TEMP THOLD 1 DEGREES Probe 5 Minimum Temperature Threshold 031A 794 EMS PROBE 5 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031B 795 EMS PROBE 5 MAXIMUM HUM THOLD 1 PERCENT Probe 5 Maximum Humidity Threshold 031C 796 EMS PROBE 5 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 031D 797 EMS PROBE 5 MINIMUM HUM THOLD 1 DEGREES Probe 5 Minimum Humidity Threshold 031E 798 EMS PROBE 5 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Short-term Increasing Variance 031F 799 EMS PROBE 5 SHORT-TERM INCREASING TIME 1 SECONDS Probe 5 Short-term Increasing Time 0320 800 EMS PROBE 5 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0321 801 EMS PROBE 5 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Short-term Decreasing Variance 0322 802 EMS PROBE 5 SHORT-TERM DECREASING TIME 1 SECONDS Probe 5 Short-term Decreasing Time 0323 803 EMS PROBE 5 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0324 804 EMS PROBE 5 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance 0325 805 EMS PROBE 5 LONG-TERM INCREASING TIME 1 HOURS Probe 5 Long-term Increasing Time 0326 806 EMS PROBE 5 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0327 807 EMS PROBE 5 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 5 Long-term Increasing Variance 0328 808 EMS PROBE 5 LONG-TERM DECREASING TIME 1 HOURS Probe 5 Long-term Increasing Time 0329 809 EMS PROBE 5 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 032A 810 EMS PROBE 5 RESERVED REGISTERS 22 NA Reserved // Probe 6 0340 832 EMS PROBE 6 NAME 11 ASCII Probe 6 Name 034B 843 EMS PROBE 6 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 034C 844 EMS PROBE 6 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 034D 845 EMS PROBE 6 LOW TEMP THOLD 1 DEGREES Probe 6 Low Temperature Threshold 034E 846 EMS PROBE 6 TEMP 1 DEPENDENCY Probe 6 Temperature 034F 847 EMS PROBE 6 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0350 848 EMS PROBE 6 HIGH TEMP THOLD 1 DEGREES Probe 6 High Temperature Threshold 0351 849 EMS PROBE 6 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0352 850 EMS PROBE 6 LOW HUM THOLD 1 PERCENT Probe 6 Low Humidity Threshold 0353 851 EMS PROBE 6 HUM 1 PERCENT Probe 6 Humidity 0354 852 EMS PROBE 6 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0355 853 EMS PROBE 6 HIGH HUM THOLD 1 PERCENT Probe 6 High Humidity Threshold 0356 854 EMS PROBE 6 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0357 855 EMS PROBE 6 MAXIMUM TEMP THOLD 1 DEGREES Probe 6 Maximum Temperature Threshold 0358 856 EMS PROBE 6 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0359 857 EMS PROBE 6 MINIMUM TEMP THOLD 1 DEGREES Probe 6 Minimum Temperature Threshold 035A 858 EMS PROBE 6 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035B 859 EMS PROBE 6 MAXIMUM HUM THOLD 1 PERCENT Probe 6 Maximum Humidity Threshold 035C 860 EMS PROBE 6 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 035D 861 EMS PROBE 6 MINIMUM HUM THOLD 1 DEGREES Probe 6 Minimum Humidity Threshold 035E 862 EMS PROBE 6 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Short-term Increasing Variance 035F 863 EMS PROBE 6 SHORT-TERM INCREASING TIME 1 SECONDS Probe 6 Short-term Increasing Time 0360 864 EMS PROBE 6 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0361 865 EMS PROBE 6 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Short-term Decreasing Variance 0362 866 EMS PROBE 6 SHORT-TERM DECREASING TIME 1 SECONDS Probe 6 Short-term Decreasing Time 0363 867 EMS PROBE 6 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0364 868 EMS PROBE 6 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance 0365 869 EMS PROBE 6 LONG-TERM INCREASING TIME 1 HOURS Probe 6 Long-term Increasing Time 0366 870 EMS PROBE 6 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0367 871 EMS PROBE 6 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 6 Long-term Increasing Variance 0368 872 EMS PROBE 6 LONG-TERM DECREASING TIME 1 HOURS Probe 6 Long-term Increasing Time 0369 873 EMS PROBE 6 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 036A 874 EMS PROBE 6 RESERVED REGISTERS 22 NA Reserved // Probe 7 0380 896 EMS PROBE 7 NAME 11 ASCII Probe 7 Name 038B 907 EMS PROBE 7 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 038C 908 EMS PROBE 7 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 038D 909 EMS PROBE 7 LOW TEMP THOLD 1 DEGREES Probe 7 Low Temperature Threshold 038E 910 EMS PROBE 7 TEMP 1 DEPENDENCY Probe 7 Temperature 038F 911 EMS PROBE 7 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0390 912 EMS PROBE 7 HIGH TEMP THOLD 1 DEGREES Probe 7 High Temperature Threshold 0391 913 EMS PROBE 7 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0392 914 EMS PROBE 7 LOW HUM THOLD 1 PERCENT Probe 7 Low Humidity Threshold 0393 915 EMS PROBE 7 HUM 1 PERCENT Probe 7 Humidity 0394 916 EMS PROBE 7 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm

0395 917 EMS PROBE 7 HIGH HUM THOLD 1 PERCENT Probe 7 High Humidity Threshold 0396 918 EMS PROBE 7 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0397 919 EMS PROBE 7 MAXIMUM TEMP THOLD 1 DEGREES Probe 7 Maximum Temperature Threshold 0398 920 EMS PROBE 7 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0399 921 EMS PROBE 7 MINIMUM TEMP THOLD 1 DEGREES Probe 7 Minimum Temperature Threshold 039A 922 EMS PROBE 7 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039B 923 EMS PROBE 7 MAXIMUM HUM THOLD 1 PERCENT Probe 7 Maximum Humidity Threshold 039C 924 EMS PROBE 7 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 039D 925 EMS PROBE 7 MINIMUM HUM THOLD 1 DEGREES Probe 7 Minimum Humidity Threshold 039E 926 EMS PROBE 7 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Short-term Increasing Variance 039F 927 EMS PROBE 7 SHORT-TERM INCREASING TIME 1 SECONDS Probe 7 Short-term Increasing Time 03A0 928 EMS PROBE 7 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A1 929 EMS PROBE 7 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Short-term Decreasing Variance 03A2 930 EMS PROBE 7 SHORT-TERM DECREASING TIME 1 SECONDS Probe 7 Short-term Decreasing Time 03A3 931 EMS PROBE 7 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A4 932 EMS PROBE 7 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A5 933 EMS PROBE 7 LONG-TERM INCREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A6 934 EMS PROBE 7 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03A7 935 EMS PROBE 7 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 7 Long-term Increasing Variance 03A8 936 EMS PROBE 7 LONG-TERM DECREASING TIME 1 HOURS Probe 7 Long-term Increasing Time 03A9 937 EMS PROBE 7 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03AA 938 EMS PROBE 7 RESERVED REGISTERS 22 NA Reserved // Probe 8 03C0 960 EMS PROBE 8 NAME 11 ASCII Probe 8 Name 03CB 971 EMS PROBE 8 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 03CC 972 EMS PROBE 8 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03CD 973 EMS PROBE 8 LOW TEMP THOLD 1 DEGREES Probe 8 Low Temperature Threshold 03CE 974 EMS PROBE 8 TEMP 1 DEPENDENCY Probe 8 Temperature 03CF 975 EMS PROBE 8 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D0 976 EMS PROBE 8 HIGH TEMP THOLD 1 DEGREES Probe 8 High Temperature Threshold 03D1 977 EMS PROBE 8 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D2 978 EMS PROBE 8 LOW HUM THOLD 1 PERCENT Probe 8 Low Humidity Threshold 03D3 979 EMS PROBE 8 HUM 1 PERCENT Probe 8 Humidity 03D4 980 EMS PROBE 8 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D5 981 EMS PROBE 8 HIGH HUM THOLD 1 PERCENT Probe 8 High Humidity Threshold 03D6 982 EMS PROBE 8 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D7 983 EMS PROBE 8 MAXIMUM TEMP THOLD 1 DEGREES Probe 8 Maximum Temperature Threshold 03D8 984 EMS PROBE 8 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03D9 985 EMS PROBE 8 MINIMUM TEMP THOLD 1 DEGREES Probe 8 Minimum Temperature Threshold 03DA 986 EMS PROBE 8 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DB 987 EMS PROBE 8 MAXIMUM HUM THOLD 1 PERCENT Probe 8 Maximum Humidity Threshold 03DC 988 EMS PROBE 8 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03DD 989 EMS PROBE 8 MINIMUM HUM THOLD 1 DEGREES Probe 8 Minimum Humidity Threshold 03DE 990 EMS PROBE 8 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Short-term Increasing Variance 03DF 991 EMS PROBE 8 SHORT-TERM INCREASING TIME 1 SECONDS Probe 8 Short-term Increasing Time 03E0 992 EMS PROBE 8 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E1 993 EMS PROBE 8 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Short-term Decreasing Variance 03E2 994 EMS PROBE 8 SHORT-TERM DECREASING TIME 1 SECONDS Probe 8 Short-term Decreasing Time 03E3 995 EMS PROBE 8 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E4 996 EMS PROBE 8 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E5 997 EMS PROBE 8 LONG-TERM INCREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E6 998 EMS PROBE 8 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03E7 999 EMS PROBE 8 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 8 Long-term Increasing Variance 03E8 1000 EMS PROBE 8 LONG-TERM DECREASING TIME 1 HOURS Probe 8 Long-term Increasing Time 03E9 1001 EMS PROBE 8 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 03EA 1002 EMS PROBE 8 RESERVED REGISTERS 22 NA Reserved // Probe 9 0400 1024 EMS PROBE 9 NAME 11 ASCII Probe 9 Name 040B 1035 EMS PROBE 9 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 040C 1036 EMS PROBE 9 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 040D 1037 EMS PROBE 9 LOW TEMP THOLD 1 DEGREES Probe 9 Low Temperature Threshold 040E 1038 EMS PROBE 9 TEMP 1 DEPENDENCY Probe 9 Temperature 040F 1039 EMS PROBE 9 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0410 1040 EMS PROBE 9 HIGH TEMP THOLD 1 DEGREES Probe 9 High Temperature Threshold 0411 1041 EMS PROBE 9 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0412 1042 EMS PROBE 9 LOW HUM THOLD 1 PERCENT Probe 9 Low Humidity Threshold 0413 1043 EMS PROBE 9 HUM 1 PERCENT Probe 9 Humidity 0414 1044 EMS PROBE 9 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0415 1045 EMS PROBE 9 HIGH HUM THOLD 1 PERCENT Probe 9 High Humidity Threshold 0416 1046 EMS PROBE 9 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0417 1047 EMS PROBE 9 MAXIMUM TEMP THOLD 1 DEGREES Probe 9 Maximum Temperature Threshold 0418 1048 EMS PROBE 9 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0419 1049 EMS PROBE 9 MINIMUM TEMP THOLD 1 DEGREES Probe 9 Minimum Temperature Threshold 041A 1050 EMS PROBE 9 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041B 1051 EMS PROBE 9 MAXIMUM HUM THOLD 1 PERCENT Probe 9 Maximum Humidity Threshold 041C 1052 EMS PROBE 9 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 041D 1053 EMS PROBE 9 MINIMUM HUM THOLD 1 DEGREES Probe 9 Minimum Humidity Threshold 041E 1054 EMS PROBE 9 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Short-term Increasing Variance 041F 1055 EMS PROBE 9 SHORT-TERM INCREASING TIME 1 SECONDS Probe 9 Short-term Increasing Time 0420 1056 EMS PROBE 9 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0421 1057 EMS PROBE 9 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Short-term Decreasing Variance 0422 1058 EMS PROBE 9 SHORT-TERM DECREASING TIME 1 SECONDS Probe 9 Short-term Decreasing Time 0423 1059 EMS PROBE 9 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0424 1060 EMS PROBE 9 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance 0425 1061 EMS PROBE 9 LONG-TERM INCREASING TIME 1 HOURS Probe 9 Long-term Increasing Time

0426 1062 EMS PROBE 9 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0427 1063 EMS PROBE 9 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 9 Long-term Increasing Variance 0428 1064 EMS PROBE 9 LONG-TERM DECREASING TIME 1 HOURS Probe 9 Long-term Increasing Time 0429 1065 EMS-EMU2 PROBE 1 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 042A 1066 EMS PROBE 9 RESERVED REGISTERS 22 NA Reserved // Probe 10 0440 1088 EMS PROBE 10 NAME 11 ASCII Probe 10 Name 044B 1099 EMS PROBE 10 STATE 1 ENUM 01 = Not Installed 02 = Normal 03 = Alarm 04 = Lost Comms 044C 1100 EMS PROBE 10 LOW TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 044D 1101 EMS PROBE 10 LOW TEMP THOLD 1 DEGREES Probe 10 Low Temperature Threshold 044E 1102 EMS PROBE 10 TEMP 1 DEPENDENCY Probe 10 Temperature 044F 1103 EMS PROBE 10 HIGH TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0450 1104 EMS PROBE 10 HIGH TEMP THOLD 1 DEGREES Probe 10 High Temperature Threshold 0451 1105 EMS PROBE 10 LOW HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0452 1106 EMS PROBE 10 LOW HUM THOLD 1 PERCENT Probe 10 Low Humidity Threshold 0453 1107 EMS PROBE 10 HUM 1 PERCENT Probe 10 Humidity 0454 1108 EMS PROBE 10 HIGH HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0455 1109 EMS PROBE 10 HIGH HUM THOLD 1 PERCENT Probe 10 High Humidity Threshold 0456 1110 EMS PROBE 10 MAXIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0457 1111 EMS PROBE 10 MAXIMUM TEMP THOLD 1 DEGREES Probe 10 Maximum Temperature Threshold 0458 1112 EMS PROBE 10 MINIMUM TEMP MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0459 1113 EMS PROBE 10 MINIMUM TEMP THOLD 1 DEGREES Probe 10 Minimum Temperature Threshold 045A 1114 EMS PROBE 10 MAXIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045B 1115 EMS PROBE 10 MAXIMUM HUM THOLD 1 PERCENT Probe 10 Maximum Humidity Threshold 045C 1116 EMS PROBE 10 MINIMUM HUM MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 045D 1117 EMS PROBE 10 MINIMUM HUM THOLD 1 DEGREES Probe 10 Minimum Humidity Threshold 045E 1118 EMS PROBE 10 SHORT-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Short-term Increasing Variance 045F 1119 EMS PROBE 10 SHORT-TERM INCREASING TIME 1 SECONDS Probe 10 Short-term Increasing Time 0460 1120 EMS PROBE 10 SHORT-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0461 1121 EMS PROBE 10 SHORT-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Short-term Decreasing Variance 0462 1122 EMS PROBE 10 SHORT-TERM DECREASING TIME 1 SECONDS Probe 10 Short-term Decreasing Time 0463 1123 EMS PROBE 10 SHORT-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0464 1124 EMS PROBE 10 LONG-TERM INCREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance 0465 1125 EMS PROBE 10 LONG-TERM INCREASING TIME 1 HOURS Probe 10 Long-term Increasing Time 0466 1126 EMS PROBE 10 LONG-TERM INCREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0467 1127 EMS PROBE 10 LONG-TERM DECREASING VARIANCE 1 DEGREES Probe 10 Long-term Increasing Variance 0468 1128 EMS PROBE 10 LONG-TERM DECREASING TIME 1 HOURS Probe 10 Long-term Increasing Time 0469 1129 EMS PROBE 10 LONG-TERM DECREASING MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 046A 1130 EMS PROBE 10 RESERVED REGISTERS 22 NA Reserved // Sensor 1 0480 1152 EMS SENSOR 1 DESCRIPTION NAME 3 ASCII Sensor 1 Descriptive Name 0483 1155 EMS SENSOR 1 NAME 11 ASCII Sensor 1 Custom Name 048E 1166 EMS SENSOR 1 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 048F 1167 EMS SENSOR 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0490 1168 EMS SENSOR 1 NORMAL 1 ENUM 01 = Closed 02 = Open 0491 1169 EMS SENSOR 1 DELAY 1 SECONDS Sensor 1 Delay 0492 1170 EMS SENSOR 1 RESERVED REGISTERS 46 NA Reserved // Sensor 2 04C0 1216 EMS SENSOR 2 DESCRIPTION NAME 3 ASCII Sensor 2 Descriptive Name 04C3 1219 EMS SENSOR 2 NAME 11 ASCII Sensor 2 Custom Name 04CE 1230 EMS SENSOR 2 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 04CF 1231 EMS SENSOR 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 04D0 1232 EMS SENSOR 2 NORMAL 1 ENUM 01 = Closed 02 = Open 04D1 1233 EMS SENSOR 2 DELAY 1 SECONDS Sensor 2 Delay 04D2 1234 EMS SENSOR 2 RESERVED REGISTERS 46 NA Reserved // Sensor 3 0500 1280 EMS SENSOR 3 DESCRIPTION NAME 5 ASCII Sensor 3 Descriptive Name 0505 1285 EMS SENSOR 3 NAME 11 ASCII Sensor 3 Custom Name 0510 1296 EMS SENSOR 3 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 0511 1297 EMS SENSOR 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0512 1298 EMS SENSOR 3 NORMAL 1 ENUM 01 = Closed 02 = Open 0513 1299 EMS SENSOR 3 DELAY 1 SECONDS Sensor 3 Delay 0514 1300 EMS SENSOR 3 RESERVED REGISTERS 44 NA Reserved // Sensor 4 0540 1344 EMS SENSOR 4 DESCRIPTION NAME 3 ASCII Sensor 4 Descriptive Name 0543 1347 EMS SENSOR 4 NAME 11 ASCII Sensor 4 Custom Name 054E 1358 EMS SENSOR 4 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 054F 1359 EMS SENSOR 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0550 1360 EMS SENSOR 4 NORMAL 1 ENUM 01 = Closed 02 = Open 0551 1361 EMS SENSOR 4 DELAY 1 SECONDS Sensor 4 Delay 0552 1362 EMS SENSOR 4 RESERVED REGISTERS 46 NA Reserved // Sensor 5 0580 1408 EMS SENSOR 5 DESCRIPTION NAME 3 ASCII Sensor 5 Descriptive Name 0583 1411 EMS SENSOR 5 NAME 11 ASCII Sensor 5 Custom Name 058E 1422 EMS SENSOR 5 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 058F 1423 EMS SENSOR 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0590 1424 EMS SENSOR 5 NORMAL 1 ENUM 01 = Closed 02 = Open 0591 1425 EMS SENSOR 5 DELAY 1 SECONDS Sensor 5 Delay 0592 1426 EMS SENSOR 5 RESERVED REGISTERS 46 NA Reserved // Sensor 6 05C0 1472 EMS SENSOR 6 DESCRIPTION NAME 2 ASCII Sensor 6 Descriptive Name 05C2 1474 EMS SENSOR 6 NAME 11 ASCII Sensor 6 Custom Name 05CD 1485 EMS SENSOR 6 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 05CE 1486 EMS SENSOR 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 05CF 1487 EMS SENSOR 6 NORMAL 1 ENUM 01 = Closed 02 = Open 05D0 1488 EMS SENSOR 6 DELAY 1 SECONDS Sensor 6 Delay

05D1 1489 EMS SENSOR 6 RESERVED REGISTERS 47 NA Reserved // Sensor 7 0600 1536 EMS SENSOR 7 DESCRIPTION NAME 2 ASCII Sensor 7 Descriptive Name 0602 1538 EMS SENSOR 7 NAME 11 ASCII Sensor 7 Custom Name 060D 1549 EMS SENSOR 7 STATE 1 ENUM 01 = Alarm 02 = Normal 03 = Not Installed 060E 1550 EMS SENSOR 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 060F 1551 EMS SENSOR 7 NORMAL 1 ENUM 01 = Closed 02 = Open 0610 1552 EMS SENSOR 7 DELAY 1 SECONDS Sensor 7 Delay 0611 1553 EMS SENSOR 7 RESERVED REGISTERS 47 NA Reserved // Contact 1 0640 1600 EMS-EMU2 CONTACT 1 NAME 11 ASCII Contact 1 Name 064B 1611 EMS-EMU2 CONTACT 1 STATE 1 ENUM 01 = Closed 02 = Open 064C 1612 EMS-EMU2 CONTACT 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 064D 1613 EMS-EMU2 CONTACT 1 NORMAL 1 ENUM 01 = Closed 02 = Open 064E 1614 EMS-EMU2 CONTACT 1 RESERVED REGISTERS 50 NA Reserved // Contact 2 0680 1664 EMS-EMU2 CONTACT 2 NAME 11 ASCII Contact 2 Name 068B 1675 EMS-EMU2 CONTACT 2 STATE 1 ENUM 01 = Closed 02 = Open 068C 1676 EMS-EMU2 CONTACT 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 068D 1677 EMS-EMU2 CONTACT 2 NORMAL 1 ENUM 01 = Closed 02 = Open 068E 1678 EMS-EMU2 CONTACT 2 RESERVED REGISTERS 50 NA Reserved // Contact 3 06C0 1728 EMS-EMU2 CONTACT 3 NAME 11 ASCII Contact 3 Name 06CB 1739 EMS-EMU2 CONTACT 3 STATE 1 ENUM 01 = Closed 02 = Open 06CC 1740 EMS-EMU2 CONTACT 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 06CD 1741 EMS-EMU2 CONTACT 3 NORMAL 1 ENUM 01 = Closed 02 = Open 06CE 1742 EMS-EMU2 CONTACT 3 RESERVED REGISTERS 50 NA Reserved // Contact 4 0700 1792 EMS-EMU2 CONTACT 4 NAME 11 ASCII Contact 4 Name 070B 1803 EMS-EMU2 CONTACT 4 STATE 1 ENUM 01 = Closed 02 = Open 070C 1804 EMS-EMU2 CONTACT 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 070D 1805 EMS-EMU2 CONTACT 4 NORMAL 1 ENUM 01 = Closed 02 = Open 070E 1806 EMS-EMU2 CONTACT 4 RESERVED REGISTERS 50 NA Reserved // Contact 5 0740 1856 EMS CONTACT 5 NAME 11 ASCII Contact 5 Name 074B 1867 EMS CONTACT 5 STATE 1 ENUM 01 = Closed 02 = Open 074C 1868 EMS CONTACT 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 074D 1869 EMS CONTACT 5 NORMAL 1 ENUM 01 = Closed 02 = Open 074E 1870 EMS CONTACT 5 RESERVED REGISTERS 50 NA Reserved // Contact 6 0780 1920 EMS CONTACT 6 NAME 11 ASCII Contact 6 Name 078B 1931 EMS CONTACT 6 STATE 1 ENUM 01 = Closed 02 = Open 078C 1932 EMS CONTACT 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 078D 1933 EMS CONTACT 6 NORMAL 1 ENUM 01 = Closed 02 = Open 078E 1934 EMS CONTACT 6 RESERVED REGISTERS 50 NA Reserved // Contact 7 07C0 1984 EMS CONTACT 7 NAME 11 ASCII Contact 7 Name 07CB 1995 EMS CONTACT 7 STATE 1 ENUM 01 = Closed 02 = Open 07CC 1996 EMS CONTACT 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 07CD 1997 EMS CONTACT 7 NORMAL 1 ENUM 01 = Closed 02 = Open 07CE 1998 EMS CONTACT 7 RESERVED REGISTERS 50 NA Reserved // Contact 8 0800 2048 EMS CONTACT 8 NAME 11 ASCII Contact 8 Name 080B 2059 EMS CONTACT 8 STATE 1 ENUM 01 = Closed 02 = Open 080C 2060 EMS CONTACT 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 080D 2061 EMS CONTACT 8 NORMAL 1 ENUM 01 = Closed 02 = Open 080E 2062 EMS CONTACT 8 RESERVED REGISTERS 50 NA Reserved // Relay 1 0840 2112 EMS-EMU2 RELAY 1 NAME 11 ASCII Relay 1 Name 084B 2123 EMS-EMU2 RELAY 1 STATE 1 ENUM 01 = Closed 02 = Open 084C 2124 EMS-EMU2 RELAY 1 NORMAL 1 ENUM 01 = Closed 02 = Open 084D 2125 EMS-EMU2 RELAY 1 RESERVED REGISTERS 51 NA Reserved // Relay 2 0880 2176 EMS RELAY 2 NAME 11 ASCII Relay 2 Name 088B 2187 EMS RELAY 2 STATE 1 ENUM 01 = Closed 02 = Open 088C 2188 EMS RELAY 2 NORMAL 1 ENUM 01 = Closed 02 = Open 088D 2189 EMS RELAY 2 RESERVED REGISTERS 51 NA Reserved // Outlet 1 08C0 2240 EMS OUTLET 1 NAME 11 ASCII Outlet 1 Name 08CB 2251 EMS OUTLET 1 STATE 1 ENUM 01 = On 02 = Off 08CC 2252 EMS OUTLET 1 NORMAL 1 ENUM 01 = On 02 = Off 08CD 2253 EMS OUTLET 1 RESERVED REGISTERS 51 NA Reserved // Outlet 2 0900 2304 EMS OUTLET 2 NAME 11 ASCII Outlet 2 Name 090B 2315 EMS OUTLET 2 STATE 1 ENUM 01 = On 02 = Off 090C 2316 EMS OUTLET 2 NORMAL 1 ENUM 01 = On 02 = Off 090D 2317 EMS OUTLET 2 RESERVED REGISTERS 51 NA Reserved // Beacon (or Fan), see Note 6 0940 2368 EMS-EMU2 BEACON STATE 1 ENUM 01 = On 02 = Off 03 = Not Installed 0941 2369 EMS-EMU2 BEACON RESERVED REGISTERS 15 NA Reserved // ARU 1 0950 2384 EMS-EMU2 ARU 1 NAME 11 ASCII ARU 1 Name 095B 2395 EMS-EMU2 ARU 1 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 095C 2396 EMS-EMU2 ARU 1 TEMP1 1 DEGREES ARU 1 - Fan 1 Temperature 095D 2397 EMS-EMU2 ARU 1 TEMP2 1 DEGREES ARU 1 - Fan 2 Temperature 095E 2398 EMS-EMU2 ARU 1 TEMP3 1 DEGREES ARU 1 - Fan 3 Temperature

095F 2399 EMS-EMU2 ARU 1 RESERVED 1 NA Reserved 0960 2400 EMS-EMU2 ARU 1 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0961 2401 EMS-EMU2 ARU 1 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0962 2402 EMS-EMU2 ARU 1 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0963 2403 EMS-EMU2 ARU 1 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0964 2404 EMS-EMU2 ARU 1 DIP SWITCH 1 BINARY See Note 4. 0965 2405 EMS-EMU2 ARU 1 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0966 2406 EMS-EMU2 ARU 1 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0967 2407 EMS-EMU2 ARU 1 RESERVED REGISTERS 41 NA Reserved // ARU 2 0990 2448 EMS-EMU2 ARU 2 NAME 11 ASCII ARU 2 Name 099B 2459 EMS-EMU2 ARU 2 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 099C 2460 EMS-EMU2 ARU 2 TEMP1 1 DEGREES ARU 2 - Fan 1 Temperature 099D 2461 EMS-EMU2 ARU 2 TEMP2 1 DEGREES ARU 2 - Fan 2 Temperature 099E 2462 EMS-EMU2 ARU 2 TEMP3 1 DEGREES ARU 2 - Fan 3 Temperature 099F 2463 EMS-EMU2 ARU 2 RESERVED 1 NA Reserved 09A0 2464 EMS-EMU2 ARU 2 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09A1 2465 EMS-EMU2 ARU 2 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09A2 2466 EMS-EMU2 ARU 2 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09A3 2467 EMS-EMU2 ARU 2 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09A4 2468 EMS-EMU2 ARU 2 DIP SWITCH 1 BINARY See Note 4. 09A5 2469 EMS-EMU2 ARU 2 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09A6 2470 EMS-EMU2 ARU 2 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09A7 2471 EMS-EMU2 ARU 2 RESERVED REGISTERS 41 NA Reserved // ARU 3 09D0 2512 EMS-EMU2 ARU 3 NAME 11 ASCII ARU 3 Name 09DB 2523 EMS-EMU2 ARU 3 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 09DC 2524 EMS-EMU2 ARU 3 TEMP1 1 DEGREES ARU 3 - Fan 1 Temperature 09DD 2525 EMS-EMU2 ARU 3 TEMP2 1 DEGREES ARU 3 - Fan 2 Temperature 09DE 2526 EMS-EMU2 ARU 3 TEMP3 1 DEGREES ARU 3 - Fan 3 Temperature 09DF 2527 EMS-EMU2 ARU 3 RESERVED 1 NA Reserved 09E0 2528 EMS-EMU2 ARU 3 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 09E1 2529 EMS-EMU2 ARU 3 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 09E2 2530 EMS-EMU2 ARU 3 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 09E3 2531 EMS-EMU2 ARU 3 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 09E4 2532 EMS-EMU2 ARU 3 DIP SWITCH 1 BINARY See Note 4. 09E5 2533 EMS-EMU2 ARU 3 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 09E6 2534 EMS-EMU2 ARU 3 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 09E7 2535 EMS-EMU2 ARU 3 RESERVED REGISTERS 41 NA Reserved // ARU 4 0A10 2576 EMS-EMU2 ARU 4 NAME 11 ASCII ARU 4 Name 0A1B 2587 EMS-EMU2 ARU 4 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A1C 2588 EMS-EMU2 ARU 4 TEMP1 1 DEGREES ARU 4 - Fan 1 Temperature 0A1D 2589 EMS-EMU2 ARU 4 TEMP2 1 DEGREES ARU 4 - Fan 2 Temperature 0A1E 2590 EMS-EMU2 ARU 4 TEMP3 1 DEGREES ARU 4 - Fan 3 Temperature 0A1F 2591 EMS-EMU2 ARU 4 RESERVED 1 NA Reserved 0A20 2592 EMS-EMU2 ARU 4 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A21 2593 EMS-EMU2 ARU 4 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A22 2594 EMS-EMU2 ARU 4 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A23 2595 EMS-EMU2 ARU 4 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A24 2596 EMS-EMU2 ARU 4 DIP SWITCH 1 BINARY See Note 4. 0A25 2597 EMS-EMU2 ARU 4 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A26 2598 EMS-EMU2 ARU 4 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A27 2599 EMS-EMU2 ARU 4 RESERVED REGISTERS 41 NA Reserved // ARU 5 0A50 2640 EMS-EMU2 ARU 5 NAME 11 ASCII ARU 5 Name 0A5B 2651 EMS-EMU2 ARU 5 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A5C 2652 EMS-EMU2 ARU 5 TEMP1 1 DEGREES ARU 5 - Fan 1 Temperature 0A5D 2653 EMS-EMU2 ARU 5 TEMP2 1 DEGREES ARU 5 - Fan 2 Temperature 0A5E 2654 EMS-EMU2 ARU 5 TEMP3 1 DEGREES ARU 5 - Fan 3 Temperature 0A5F 2655 EMS-EMU2 ARU 5 RESERVED 1 NA Reserved 0A60 2656 EMS-EMU2 ARU 5 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0A61 2657 EMS-EMU2 ARU 5 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0A62 2658 EMS-EMU2 ARU 5 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0A63 2659 EMS-EMU2 ARU 5 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0A64 2660 EMS-EMU2 ARU 5 DIP SWITCH 1 BINARY See Note 4. 0A65 2661 EMS-EMU2 ARU 5 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0A66 2662 EMS-EMU2 ARU 5 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0A67 2663 EMS-EMU2 ARU 5 RESERVED REGISTERS 41 NA Reserved // ARU 6 0A90 2704 EMS-EMU2 ARU 6 NAME 11 ASCII ARU 6 Name 0A9B 2715 EMS-EMU2 ARU 6 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0A9C 2716 EMS-EMU2 ARU 6 TEMP1 1 DEGREES ARU 6 - Fan 1 Temperature 0A9D 2717 EMS-EMU2 ARU 6 TEMP2 1 DEGREES ARU 6 - Fan 2 Temperature 0A9E 2718 EMS-EMU2 ARU 6 TEMP3 1 DEGREES ARU 6 - Fan 3 Temperature 0A9F 2719 EMS-EMU2 ARU 6 RESERVED 1 NA Reserved 0AA0 2720 EMS-EMU2 ARU 6 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AA1 2721 EMS-EMU2 ARU 6 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AA2 2722 EMS-EMU2 ARU 6 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AA3 2723 EMS-EMU2 ARU 6 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AA4 2724 EMS-EMU2 ARU 6 DIP SWITCH 1 BINARY See Note 4. 0AA5 2725 EMS-EMU2 ARU 6 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AA6 2726 EMS-EMU2 ARU 6 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AA7 2727 EMS-EMU2 ARU 6 RESERVED REGISTERS 41 NA Reserved // ARU 7 0AD0 2768 EMS-EMU2 ARU 7 NAME 11 ASCII ARU 7 Name

0ADB 2779 EMS-EMU2 ARU 7 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0ADC 2780 EMS-EMU2 ARU 7 TEMP1 1 DEGREES ARU 7 - Fan 1 Temperature 0ADD 2781 EMS-EMU2 ARU 7 TEMP2 1 DEGREES ARU 7 - Fan 2 Temperature 0ADE 2782 EMS-EMU2 ARU 7 TEMP3 1 DEGREES ARU 7 - Fan 3 Temperature 0ADF 2783 EMS-EMU2 ARU 7 RESERVED 1 NA Reserved 0AE0 2784 EMS-EMU2 ARU 7 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0AE1 2785 EMS-EMU2 ARU 7 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0AE2 2786 EMS-EMU2 ARU 7 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0AE3 2787 EMS-EMU2 ARU 7 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0AE4 2788 EMS-EMU2 ARU 7 DIP SWITCH 1 BINARY See Note 4. 0AE5 2789 EMS-EMU2 ARU 7 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0AE6 2790 EMS-EMU2 ARU 7 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0AE7 2791 EMS-EMU2 ARU 7 RESERVED REGISTERS 41 NA Reserved // ARU 8 0B10 2832 EMS-EMU2 ARU 8 NAME 11 ASCII ARU 8 Name 0B1B 2843 EMS-EMU2 ARU 8 MAP 1 ENUM 01 = No Alarms 02 = Major Alarm 04 = Minor Alarm 08 = Outlet 1 Alarm 16 = Outlet 2 Alarm 32 = Beacon (or Fan) Alarm 64 = Relay 1 Alarm 128 = Relay 2 Alarm 0B1C 2844 EMS-EMU2 ARU 8 TEMP1 1 DEGREES ARU 8 - Fan 1 Temperature 0B1D 2845 EMS-EMU2 ARU 8 TEMP2 1 DEGREES ARU 8 - Fan 2 Temperature 0B1E 2846 EMS-EMU2 ARU 8 TEMP3 1 DEGREES ARU 8 - Fan 3 Temperature 0B1F 2847 EMS-EMU2 ARU 8 RESERVED 1 NA Reserved 0B20 2848 EMS-EMU2 ARU 8 MAN SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 0B21 2849 EMS-EMU2 ARU 8 REM SET POINT 1 DEGREES OR KILOWATTS 01 = ARU Off 02 = 85F or 29C 03 = 90F or 32C 04 = 95F or 35C 05 = 100F or 38C 06 = 7KW 07 = 5KW 08 = 3KW 09 = 2kW 10 = REM 0B22 2850 EMS-EMU2 ARU 8 REM TEMP OVRD ENABLE/DISABLE 1 ENUM 01 = Disable 02 = Enable 0B23 2851 EMS-EMU2 ARU 8 REM OVRD SETPOINT 1 DEGREES Remote Over Temperature Setpoint 0B24 2852 EMS-EMU2 ARU 8 DIP SWITCH 1 BINARY See Note 4. 0B25 2853 EMS-EMU2 ARU 8 ALARMS 1 ENUM 01 = No Alarms 02 = Fan 1 Fail 04 = Fan 2 Fail 08 = Fan 3 Fail 16 = Smoke Alarm 32 = Out of Thermal Control 64 = Over Temperature 0B26 2854 EMS-EMU2 ARU 8 STATE 1 ENUM 01 = Not Installed 02 = NormaI 03 = Lost Comms 0B27 2855 EMS-EMU2 ARU 8 RESERVED REGISTERS 41 NA Reserved // Logging Registers FFEE 65518 APC RX CRC ERRORS 2 LONG RX CRC ERRORS FFF0 65520 APC RX PACKET COUNTER 2 LONG RX PACKET COUNTER FFF2 65522 APC TX PACKET COUNTER 2 LONG TX PACKET COUNTER FFF4 65524 APC SER FRAME ERRORS 2 LONG SER FRAME ERRORS FFF6 65526 APC SER OVERRUN ERRORS 2 LONG SER OVERRUN ERRORS FFF8 65528 APC SER PARITY ERRORS 2 LONG SER PARITY ERRORS FFFA 65530 APC SER RX15 ERRORS 2 LONG SER RX15 ERRORS FFFC 65532 APC SER RX35 ERRORS 2 LONG SER RX35 ERRORS FFFE 65534 APC SER BAUD RATE 1 INTEGER SER BAUD RATE // END OF DATA Note 1: The temperature value returned will be either in Celsius or Fahrenheit depending on the value read from Modbus Register EMS TEMP DISPLAY TYPE. Note 2: The "Alarm Map" represents a bit map of the alarm state(s) Only Beacon (or Fan) and Relay1 are available for EMU2. 01 = No Alarms (bit 0) 02 = Major Alarm (bit 1) 04 = Minor Alarm (bit 2) 08 = Outlet 1 Alarm (bit 3) 16 = Outlet 2 Alarm (bit 4) 32 = Beacon (or Fan) Alarm (bit 5) 64 = Relay 1 Alarm (bit 6) 128 = Relay 2 Alarm (bit 7) Note 3. This value may be in units of DEGREES or Kilowatts. Note 4. The 4 least significant bits of this register define the following: 0000 wxyz - w is the temperature override bit. If w is set, the temperature override condition exists. - x is the least significant bit of the 3 bit ARU CAN bus address - y is the middle bit of the 3 bit ARU CAN bus address - z is the most significant bit of the 3 bit ARU CAN bus address Note 5. The Hardware State is defined as follows: 00 = No Fault. 01 = Alink Fault. (Current Overload condition on the Alink ports.) 02 = Sensor Connection Fault.( Motion or Smoke Alarm port does not have the correct sensor.) 03 = Both Alink and Sensor Connection Fault. Note 6. On some model SKUs, Beacon functionality is replaced by a Fan.