MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES



Similar documents
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL

SPECIAL RESIDENCE (ASSISTED SELF-PRESERVATION) OCCUPANCIES (Adopted by the State of Oregon)

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

General Safety & Health Standards Published by the Division of Building Safety In Cooperation with the Idaho Industrial Commission

CHILD CARE CENTER INFORMATION SHEET

SCHOOL FIRE AND LIFE SAFETY INSPECTION CHECKLIST

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

Educational. Educational-Existing 1/28/2014. OCCUPANT LOADS [no change] Application. Application

MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY

FIRE SAFETY REQUIREMENTS

New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings

Health Care Facilities

527 CMR: BOARD OF FIRE PREVENTION REGULATIONS

BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS

Building Codes Update: The 2009 International Fire Code and the Apartment Industry

RULES OF DEPARTMENT OF MENTAL HEALTH AND DEVELOPMENTAL DISABILITIES OFFICE OF LICENSURE CHAPTER LIFE SAFETY LICENSURE RULES TABLE OF CONTENTS

Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.

Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013

MINIMUM STANDARDS FOR HIGH-RISE BUILDINGS

c. As mandated by law, facilities must obtain and maintain valid zoning permits as well as permits for intended use.

Fire Alarm Systems Requirements by Occupancy Type

Area of Rescue Assistance Communication System ADA Code Applicable excerpts:

St. John s University

MINNESOTA DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division STATEMENT OF POLICY. State Fire Marshal


Overview of Hotel Fire Safety Requirements

Smoke & Carbon Monoxide

Instructions for Obtaining a Certificate of Smoke Detector, Carbon Monoxide Alarm, and Kitchen Fire Extinguisher Compliance

CHAPTER 9 FIRE PROTECTION SYSTEMS

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

ICC CODE CORNER 2012 IFC Code & Commentary

M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003

FIRE SAFETY INSPECTION REPORT

General Fire Code Requirements Within Commercial Tenant Spaces

INSPECTION AND TESTING OF FIRE ALARM SYSTEMS

Life Safety Code Enabling References

Ch. 58 DIVISION D-O 34 CHAPTER 58. DIVISION D-O ORDINARY COMMERCIAL, INDUSTRIAL, OFFICE OCCUPANCY GROUP CONSTRUCTION TYPE MAXIMUM STORY HEIGHT

Winnipeg Fire Department Fire Prevention Branch

ALBERTA FIRE CODE SAFETY EQUIPMENT MAINTENANCE REQUIREMENTS

We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.

2007 ICC FINAL ACTION AGENDA

How To Install A Carbon Monoxide Detector

How To Build A Basement House

CERTIFICATE OF COMPLIANCE

Hotel Fire Safety for staff

Dennis Fire Department Fire Prevention Mark Dellner Fire Chief

Smoke & Carbon Monoxide

Guide to Massachusetts Smoke & Carbon Monoxide Requirements

City of Riverside Building & Safety Division Phone: (951)

Indiana Building Rehabilitation Standard

FACILITY FIRE PREVENTION AND EMERGENCY PREPAREDNESS INSPECTION CHECKLIST

FIRE AND LIFE SAFETY REQUIREMENTS FOR CONVENTIONS, TRADE SHOWS AND EXHIBITS

NFPA SELECT SIGNIFICANT CHANGES

FIRE PREVENTION & INVESTIGATION DIVISION 125 Idylwyld Drive South Saskatoon, SK S7M 1L4 Phone: (306) Fax: (306)

Mobile Fire Rescue Department Bureau of Fire Prevention

Errata has been identified as follows:

The New Life Safety Chapter What It Applies to and How Organizations Can Comply with It

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection. OSHA Office of Training and Education 1

* Any required illumination shall be arranged so that the failure of any single lighting unit shall not leave any area in darkness.

Building Code Clarifications - 7. Fire Resistance

The terms hazard and risk are often used, which we define as the following:

SECTION 903 AUTOMATIC SPRINKLER SYSTEMS

EMERGENCY ACTION, EVACUATION AND FIRE PREVENTION SAFETY PROGRAM

CONSTRUCTION FIRE SAFETY PLANNING GUIDELINES

Table of Contents. Residential Care Facilities Presentation Handout 1

The Commonwealth of Massachusetts Executive Office of Public Safety Department of Fire Services

NC Rehab Code Case Study Cheerwine Building January 17, 2002; rev 4/12/02

New York City Department of Buildings

New Ambulatory Health Care Occupancies

FIRE SAFETY SURVEY REPORT 2000 CODE - HEALTH CARE Medicare Medicaid

Berkeley Castle. Occupant Fire Safety

OCFRD TENT STANDARD This Standard operates under the authority of Orange County, Florida Ordinance and State Statutes.

Required Certification Documentation. Contractor's installation certification for range hood fire suppression systems.

Code Requirements for Existing Buildings

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS. 1. All Floors (inspect from top floor to basement): Yes No

Underwriting Guidelines for Condominium Pac and Condominium Pac Plus

ESTABLISHMENT OF A NEW BUSINESS

How To Evacuate The University Of California Building

Harris County Fire Code Electronic Lock Procedures

GENERAL FIRE SAFETY TERMS & DEFINITIONS

FIRE SAFETY SELF-INSPECTION FORM FOR CULTURAL INSTITUTIONS

Rhode Island State Fire Marshal Fire Protection Systems Narrative Reports. What is a Narrative Report?

RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS

FIRE SAFETY INSPECTION REPORT

BUILDING PERMIT SPECIFICATIONS

Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:

Ontario Fire Code SECTION 5.13 DIP TANKS. Illustrated Commentary. Office of the Ontario Fire Marshal

The replacement or modification of existing windows shall comply with the following requirements:

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

OFM-TG Office of the Fire Marshal F M FIRE DRILLS GUIDELINE

City of Bettendorf Fire Alarm System Requirements

FIRE ALARM PLAN REVIEW. Office of the State Fire Marshal Massachusetts Department of Fire Services December 2009

VILLAGE OF HUDSON FALLS 220 MAIN STREET HUDSON FALLS, NY (518) /

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

Environment of Care Fire Safety Management Plan 2014

Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata Developer Premier Mica Mining And Manufacturing Company

COMPRESSED GASES. 1.2 The contents of each cylinder and container must be clearly identified (by tag or stamp) on the cylinder.

Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1

Transcription:

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms Break?? Questions?? Please set cell phones/pagers to stun

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES - HELPING YOU PROTECT THE PEOPLE IN YOUR CARE -

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES The purpose of this seminar is to provide a brief overview of some of the major requirements of the 2007 MN Statet Fire Code that apply to facilities registered as Housing with Services/Assisted i Livingi in order to help ensure that the residents of such facilities are housed in a fire-safef environment

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES Abbreviations Used in Seminar HWS/AL MSFC MSBC NFPA SFMD Housing with Services/Assisted Living Minnesota State Fire Code Minnesota State Building Code National Fire Protection Association State Fire Marshal Division

FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES SPECIAL CONSIDERATIONS Combustible construction Lack of smoke compartmentation Limited staffing to assist with evacuation Vulnerable population

FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES In a fire emergency, rescue should be the Number 1 priority This can be very labor-intensive i and time-consuming

HWS/AL The occupants HWS/AL facilities serve a very vulnerable population Residents with vision, hearing and/or mobility impairments Residents with respiratory problems Medications may affect how residents react in a fire situation Residents with dementia

FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES State and national fire safety codes and standards d are based on the assumption that a fire WILL occur in your facility at some point in time An unsafe act by one resident can endanger the lives of all the other building occupants

FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES Types of fires that can occur in residential occupancies include: Cooking equipment Heating equipment Laundry Electrical Smoking materials Intentionally set

MN STATE FIRE CODE The current Minnesota State Fire Code (MSFC) was adopted on July 10, 2007 The 2007 Minnesota State Building Code (MSBC) was adopted on the same date

MSFC Code application MSFC applies statewide It is a minimum code With some limitations, local jurisdictions allowed to adopt more restrictive requirements It applies to both new and existing buildings

MN STATE FIRE CODE: New vs. Existing Buildings constructed or for which plans were reviewed or a permit issued prior to July 10, 2007 are considered EXISTING Buildings constructed or for which plans were reviewed or a permit issued on or after July 10, 2007 are considered NEW (this would include additions to and/or major renovations of existing buildings)

MSFC Code enforcement The Minnesota SFMD has no mandate to inspect HWS/AL program facilities Local Fire Marshals/Inspectors may inspect these types of facilities depending on their personnel resources Whether or not any particular building is inspected by a fire marshal, the requirements of the MSFC still apply

Federal Medicare/Medicaid certification When an assisted living program building is attached to a licensed/certified health care facility, the two occupancies must be separated by a fire barrier having not less than a 2-hour fire resistance rating This separation will be reviewed at the time of the health care facility s annual fire inspection NFPA 101(00), Sec. 18/19.1.2

MSFC Occupancy Classification Many of the major requirements of the MSFC are based on occupancy classification Factors affecting occupancy classification include: Number of residents Resident self-preservation capabilities Facilities registered as HWS/AL can fall under any of 5 occupancy classifications MSFC(07), Sec. 202

MSFC Occupancy Classification Group R-2 Occupancies: Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature (e.g. apartment houses, boarding houses and dormitories)

MSFC Occupancy Classification Group R-3 Occupancies: Facilities housing five (5) or less persons on a 24-hour basis

MSFC Occupancy Classification Group R-4 Occupancies: Facilities housing at least six (6) but not more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services Occupants must be capable of responding to an emergency situation without physical assistance from staff

MSFC Occupancy Classification Group I-1 Occupancies: Facilities housing more than 16 persons, on a 24-hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services Occupants must be capable of responding to an emergency situation without physical assistance from staff

MSFC Occupancy Classification Group I-2 Occupancies: Buildings used for medical, psychiatric, nursing or custodial care on a 24-hour basis for more than five (5) persons who are not capable of self-preservation

MSFC Occupancy Classification For purposes of this seminar, it will be assumed that facilities registered as HWS/AL fall into one of the three following occupancy groups: Group R-3 Group R-4 Group I-1

MSFC Evacuation philosophies Health care occupancies: Residents need assistance with evacuation Defend in place Residential style occupancies: Occupants expected to be capable of exiting on their own Full evacuation

EGRESS DOOR SECURITY What does the code say? Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Sec. 1008.1.8.3, 1 8 however, authorizes the use of certain types of locks and latches to prevent the operation of exit doors, including the use of: Delayed egress locks Special egress-control devices (e.g. mag locks) MSFC(07), Sec. 1008.1.8

EGRESS DOOR SECURITY Things to consider before locking any doors in the means of egress Which doors need to be secured in some fashion? What level of security is absolutely necessary? Which of those doors are part of the required means of egress?

EGRESS DOOR SECURITY Delayed egress locks are allowed but must comply with ithmsfc(07) MSFC(07), Sec. 1008186 1008.1.8.6: Locks must be listed Building must be protected throughout by either a supervised automatic: Smoke detection system or Fire sprinkler system

DELAYED EGRESS LOCKS Specific signage required on door: Delay of up to 30 seconds allowed with prior approval from AHJ Not more than one delayed egress locking device allowed in any egress path

EGRESS DOOR SECURITY Special egress control devices These door-locking arrangements are allowed only where the clinical needs of the patients require specialized security measures for their safety Not allowed in Group R-2 occupancies MSFC(07), Sec. 1008.1.11

EGRESS DOOR SECURITY One way to meet clinical needs standard of MSFC(07), Sec. 1008.1.11 is with use of transponder-activated locking systems Activation of building fire alarm system or fire sprinkler system must override and release locks

EGRESS DOOR SECURITY Other locking arrangements that prevent egress (e.g. electric strikes or latches, magnetic locks, etc.) must comply with MSFC(07), Sec. 1008.1.111 11 Newly installed locking arrangements must also comply with MSBC(07), Sec. 1008.1.3.6 Smoke compartmentation required Restrictions based on construction type

MSBC/MSFC LOCKING REQUIREMENTS Building, or affected fire area, must be protected by an automatic fire sprinkler system and an automatic corridor smoke detection system In at least one egress path, not more than one such locking arrangement is located No public assembly space allowed within secured area MSFC(07), Sec. 1008.1.11

MSBC/MSFC LOCKING REQUIREMENTS 24-hour supervision must be provided within the secured area Keys or devices that function like keys must be carried by staff at all times This requirement can be met with the use of fkeypad or card swipe release Locks must be capable of being released from an approved location within the locked area MSFC(07), Sec. 1008.1.11

MSBC/MSFC LOCKING REQUIREMENTS Locks must also release upon: Activation of fire sprinkler system Activation of corridor smoke detection system Activation of automatic fire alarm system Loss of electrical l power Relocking must be by manual means from within the secured area MSFC(07), Sec. 1008.1.11 1 11

EGRESS DOOR SECURITY An additional note HWS/AL facilities that secure, segregate or provide a special program or special unit for residents with diagnosisi of probable bl Alzheimer s disease or a related disorder are considered a special care unit Special care units must provide written disclosure that includes description of security features MN Statute 325F.72

ESCAPE WINDOWS Emergency escape windows are required in all Group R and I-1 occupancy sleeping rooms below the 4 th story, including basements Minimum net clear opening of 5.7 ft 2 required, but there are exceptions based on date of installation and location above grade MSFC(07), Sections 1001.11 & 1026

ESCAPE WINDOWS See State Fire Marshal web site for more info: www.fire.state.mn.us MSFC Inspection Policies INS-04 Emergency escape windows are not required in buildings protected throughout by an approved, automatic fire sprinkler system MSFC(07), Sec. 1026.1, Exception 3

Automatic Fire Sprinklers Required in all NEW Group R-3 located in a building housing another dwelling unit (e.g. duplexes) AND either >9,250 ft 2 in area or located more than 3 stories above grade Group R-4 >9,250 ft 2 in area or located more than 3 stories above grade Group I-1 MSFC(07), Sections 903.2.5 & 903.2.7

Automatic Fire Sprinklers Required in EXISTING Group I-1 basements exceeding 2,500 ft 2 in size unless approved fire department access is provided Recommended for EXISTING Group R-3, Group R-4 and Group I-1 MSFC(07), Sec. 903.6.2

Automatic Fire Sprinklers Required in all NEW and EXISTING Groups R-3, R-4 and I-1 where : Delayed egress locks are used on exit doors, UNLESS building is protected by a fullcoverage automatic smoke detection system Special egress control devices (e.g. mag locks) used on exit doors MSFC(07), Sections 1008.1.8.6 & 1008.1.11

Fire Alarm System Manual and automatic ti fire alarm system required in all NEW and EXISTING Group I-1 Approved automatic fire detectors required in hazardous areas Exception: Sprinklered buildings where fire sprinklers activate fire alarm system MSFC(07), Sections 907.2.6, 907.3.3, 903.4.2 & 907.14

Fire Alarm System Fire alarm systems in NEW and EXISTING Group I-1 must include: Automatic smoke detectors in waiting areas open to corridors Automatic fire department notification MSFC(07), Sections 907.2.6 & 907.3.3

Fire Alarm System Fire alarm systems in NEW and EXISTING Group R and Group I-1 must include: Corridor smoke detection where special egress control devices (e.g. mag locks) used on exit doors MSFC(07), Sec. 1008.1.11

Fire Alarm System Smoke Alarms An automatic fire alarm system is required in NEW Group R-3 and R-4 consisting of smoke alarms located: Outside each sleeping area Inside each room used for sleeping purposes On each story MSFC(07), Sec. 907.2.10

Smoke Alarms Smoke alarms in NEW Group R-3 and R-4 must be: Hard-wired and equipped with battery back-up Interconnected in such a manner that the activation of one alarm will activate all the alarms in the unit MSFC(07), Sec. 907.2.10

Smoke Alarms Smoke alarms required in EXISTING Group R-3 and R-4 as specified in code in effect at time of construction ti Otherwise smoke alarms must be provided d as specified in MSFC(07), Sec. 907.2.10 MSFC(07), Sec. 907.3.6

Smoke Alarms Sleeping room smoke alarms required in NEW and EXISTING Group I-1 System-connected smoke detectors are RECOMMENDED in sleeping rooms of non-sprinklered facilities MSFC(07), Sections 907.2.10 & 907.3.6

Carbon Monoxide (CO) Alarms CO alarms required within 10 ft of each room used for sleeping purposes As an alternate, CO alarms may be Installed within 15 to 25 ft of COproducing equipment, and Arranged to activate a signal at a constantly attended staff location or central station service MN Statute 299F.51

Carbon Monoxide (CO) Alarms Facilities thatt contain minimal or no sources of CO may request an exemption from the Commissioner of Public Safety MN Statute 299F.51, subd. 5(b)

Corridor Walls NEW Must be fire-resistance rated in NEW: Group R-4 where occupant load served by corridor greater than 10 persons Group I-1 Only foyers, lobbies or reception rooms allowed to be open to corridor when corridor required to be fire-resistance rated MSFC(07), Sec. 1017

Corridor Walls EXISTING Corridor walls must be fireresistance rated in EXISTING Group R-4 and Group I-1 where occupant load served by corridor greater than 10 persons No fire resistance rating required in fully sprinklered existing buildings MSFC(07), Sec. 1027.17

Corridor Width Minimum corridor width required: 36 inches in NEW and EXISTING Group R-3 and Group R-4 36 inches in EXISTING Group I-1 MSFC(07), Sections 1017.2 and 1027.17.3

Corridor Width Minimum corridor width required: 36 inches in NEW Group I-1, where occupant load served by corridor <49 persons 44 inches in NEW Group I-1, where occupant load served by corridor >50 persons MSFC(07), Sections 1017.2 and 1027.17.317

Corridor Doors In NEW and EXISTING Group I-1 and Group R-4, where corridors required to be fire-resistance rated, corridor doors must: Carry minimum 20-minute fire-resistance rating, AND Be self-closing or automatic-closing with smoke detection MSFC(07), Sections 1017, 701.11 & 1027.17.2.117 2 1

Corridor Doors In EXISTING Group I-1 and Group R-4, corridor doors of solid wood or insulated steel construction are allowed No fire resistance rating required in fully sprinklered EXISTING buildings When door closers required, reduced opening force and/or delayed d action closers recommended

Emergency Lighting Must be provided in NEW and EXISTING facilities whenever two or more means of egress required Needs to cover corridors, stairways, exits, and exterior landings at exit discharge doors MSFC(07), Sec. 1006.3 and 1027.5.3

Number of Exits General Rule of Thumb Minimum of 2 exits required in Group I-1 and Group R-4: Basements Where occupant load exceeds 10 persons on 1st Floor All levels above 1st Floor MSFC(07), Sec. 1019 and 1027.2323

Open Stairways No vertical opening protection required for NEW or EXISTING Group R-3 No vertical opening protection required for openings connecting two stories in NEW or EXISTING Group R-4 MSFC(07), Sections 701 and 704.1

Enclosed Stairways Minimum 1-hr enclosure of vertical openings required in NEW and EXISTING Group I-1 MSFC(07), Sections 701 and 704.1

Storage, Handling & Use of Oxygen Oxygen is not flammable and will not explode BUT it does support combustion Oxygen makes things burn faster and ignite easier

Storage, Handling & Use of Oxygen Storage, handling and use of medical gases (e.g. O 2 ) required to comply with requirements of NFPA 99 Ensure that each supplier provides users with information about safe storage, handling and use of oxygen MSFC(07), Sections 3006.1 & 3006.4

Storage, Handling & Use of Oxygen General safe practices: Store cylinders in upright position with protective caps in place Properly secure cylinders to prevent them from being knocked over Store cylinders away from combustibles and heat or ignition sources (e.g. smoking) Do not store cylinders in a confined space such as a closet Place proper signage on doors to resident units in which O 2 is stored or used to alert first responders of the potential dangers within

Inspection, Testing & Maintenance Check fire extinguishers monthly and have them serviced annually Test and maintain batteryoperated smoke alarms per manufacturer s instructions

Inspection, Testing & Maintenance Test battery-operated emergency lights monthly Kitchen hood extinguishing systems must be serviced at least every 6 months

Inspection, Testing & Maintenance Fire alarm and fire sprinkler systems must be inspected and tested at least annually in accordance with NFPA Standards 72 and 25 MSFC(07), Sec. 901.6.1

Inspection, Testing & Maintenance I PROTECT YOURSELF DOCUMENT all inspection, testing and maintenance performed If it isn t documented, it didn t happen

Fire emergency plans Approved fire safety and evacuation plan required in Group R-4 and Group I-1 Must be reviewed or updated annually or as necessitated by changes in staff assignments, occupancy or physical environment Must be amended upon admission of any resident with unusual needs MSFC(07), Sections 404 & 408

Staff training Group R-4/GroupI-1 Employees must receive training in their duties, as assigned in the fire safety plan, as part of new employee orientation ti and at least annually thereafter Such instruction must be reviewed by staff at least every 2 months MSFC(07), Sections 406 & 408

Resident training Group R-4/Group I-1 Residents capable of assisting in their own evacuation must be trained in proper actions to take in event of fire and trained to assist each other to extent their physical and mental abilities permit without additional personal risk Training in fire prevention and actions to take in event of fire must be part of any rehabilitation or habilitation training MSFC(07), Sections 408.5.3 & 408.10.3

Emergency evacuation drills 6 emergency evacuation drills required each year in Group R-4 and Group I-1 Two times per year on each shift 12 drills required in first year of operation Drills must involve actual evacuation of residents to a selected assembly point MSFC(07), Sections 408.5 & 408.10

MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES Are there any questions??? THANK YOU!!