Fire precautions in dwellings. Private sector housing Providing homes building communities
|
|
|
- Dinah Newman
- 10 years ago
- Views:
Transcription
1 Fire precautions in dwellings Private sector housing Providing homes building communities Version 3 Published by Norwich City Council August 2011
2 Contents Page Introduction 1 2 Types of dwellings (A) Shared houses Two storeys (or less) 3 4 Three or more storeys 5 6 (B) Bedsits Two storeys (or less) 7 8 Three or more storeys 9 10 (C) Converted flats (D) Single family dwellings 13 Appendix Fire precautions what needs to be in place Appendix Fire standards further information Appendix Fire risk assessment form Appendix 4 43 Fire risk assessment form notes
3 Introduction The reason for insisting on fire precautions in houses in dwellings is to save lives and prevent injury by: providing early warning in the event of fire stopping smoke and fire spreading before residents have a chance of escape ensuring residents have a protected means of escape. Residents in a HMO (house in multiple occupation) are potentially at greater risk. In general terms, an HMO means accommodation where two or more households share amenities where a household includes families, single people and couples. Fire guidance This guidance sets out the fire precautions which the council would expect in different types of HMO properties and also for single family dwellings. Each property is unique. It is therefore not possible to have prescribed standards. However this guide is aimed at providing an understanding of the minimum standards required. In drawing up this guidance, reference has been made to the national fire guide Housing fire safety published by Local Authorities Coordinators of Regulatory Services (Lacors). The layout plans in this guide makes reference to the Lacors document. The guidance has been drawn up with Norfolk Fire Service under the terms of the: joint service level agreement between Norfolk Fire and Rescue Service and Norwich City Council. Risk assessments The fire precautions which are appropriate in a property will vary. They will depend on the circumstances at the property. The circumstances taken into account include, for example: number of residents number of floors arrangements for cooking layout and ease of escape in the event of fire the presence of fire escape windows construction of the building and flammability of building elements safety of appliances and services such as gas and electricity whether part of the building is used commercially The decisions concerning the standards which will be necessary are based on risk assessments carried out under: the Housing Health and Safety Rating Scheme under Part 1 Housing Act 2004 the Regulatory Reform Order (Fire Safety) Order
4 Housing Health and Safety Rating Scheme (HHSRS) The HHSRS is a new tool for assessing the living conditions of a property. The system is based on 29 possible hazards to the most vulnerable occupiers. The Housing Act 2004 requires local authorities to use the HHSRS to assess conditions in dwellings. The HHSRS is therefore used to assess risk from fire in HMOs and single family dwellings. Regulatory Reform Order (Fire Safety) Order 2005 (RRO) Persons who are responsible persons under the terms of the RRO have a legal obligation to carry out risk assessments. Responsible persons include: owners and persons having control of the dwelling which can mean agents. Failure to carry out a fire risk assessment is an offence enforced by the fire service who can ask to see a copy of your risk assessment at anytime. You can either undertake a fire risk assessment yourself or pay a consultancy to carry it out. The aims of the assessment are: to identify potential fire hazards to detail options for reducing the risk from those hazards to as low a risk as possible to decide what physical precautions and management arrangements are necessary to ensure the safety of people in your premises if the fire starts. The assessment should also record any significant findings namely specific problems which need urgent attention. General This guide outlines the fire precautions which we would expect to find in an HMO. In appendix 1 there is a flow chart with layout plans and schedules of the standards expected in different types of HMOs. In appendix 2 there are summary notes on the fire precautions highlighted in appendix 1. More detailed information can be found in Lacors national fire guidance Housing fire safety. In appendix 3 there is a specimen risk assessment form to guide landlords in their risk assessments, and guidance notes in appendix 4. Please contact: Private sector housing City Hall Norwich NR2 1NH t: e: [email protected] 2
5 Types of dwellings (A) Shared houses, two storeys These include houses where the residents live together as friends (such as a group of students or work mates). The fire precautions required for this type of property depend upon the risks involved. Risks can depend on factors such as: the number of people sharing the stability of the group (do residents keep moving out and being replaced?) the vulnerability of the occupants (for example children or elderly persons, physically or mentally disabled persons) whether there are cooking facilities in the rooms whether the first floor windows are suitable for emergency escape the construction and the layout of the property whether all rooms have close fitting doors whether there is an adverse risk of arson (for instance is the property used for persons retreating from domestic violence). A typical house would include one shared kitchen and there may also be a shared living room or dining room. There would be six or less occupants and no vulnerable persons. Means of escape Means of escape refers to the provision of a safe route of escape in the event of fire. Escape routes includes: the stairways, hallways, landing areas and corridors leading from each risk room to the final exit and place of safety. The escape must usually be protected to a minimum level of 30 minutes fire protection. This will include fire doors opening out into escape routes. However, in a typical low risk shared house a protected means of escape (fire doors etc) will not be required. Fire detection A Grade D LD3 system is required. This means: Grade D Mains powered interlinked detectors each with an integral standby supply (battery back up). LD3 The detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings) and in rooms or areas that present a high fire risk* to occupants. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as any electrical item other than fixed lighting). 3
6 Extinguishers and blankets A 2kg multi purpose dry powder extinguisher to BS EN 3:1996 is required in each room with cooking facilities. All extinguishers are to be wall mounted on wall brackets in accordance with BS 5428: 1987, with carrying handle approximately 1m above ground level, maintained in good order and readily available for use at all times. A wall mounted fire blanket situated approximately 1.5m above floor level to comply with BS EN 1869:1997 is required in all rooms containing cooking facilities. Fire fighting equipment must be maintained in accordance with BS 5306:Part 3:1988. Emergency lighting Emergency lighting may be required if the protected escape route is not provided with adequate background light either natural or borrowed from street lighting to ensure the safe movement to the final exit door. Where emergency lighting is provided it must comply with BS 5266 Part 1:1988. Please note: The exit from the building should not involve going through a risk room, such as a bedroom, living room or kitchen. The route out of a building has to be kept clear, free from ignition sources, free from furniture and stored goods. A bedroom or a living room would not be able to provide this protection. In situations where this does occur a satisfactory alternative route must be provided. Please refer to the floor plans in Appendix 1 for an example of how this can be carried out. 4
7 Shared houses, three or more storeys This includes houses built with three storeys or houses with converted basements or attics. The type of resident will typically be the same as a two storey shared house (although there may be six or more persons). Means of escape A house with three or more storeys is considered higher risk. This means that the escape route needs protecting. A route of escape typically includes the main staircases and all corridors/landings that a person would have to travel through to reach the front door. A protected route of escape means: that all walls between the escape route and risk rooms must be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that all ceilings between the route of escape and risk rooms* must be capable of giving 30 minutes fire and smoke protection. Gaps for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that cupboards leading onto the means of escape should be emptied of flammable goods and kept locked that understairs soffitts must be underlined to provide 30 minutes fire protection understairs cupboards must be emptied of flammable goods and kept locked that all cupboards containing risk of ignition (such as electrical fuse boards or water heaters) must be 30 minutes fire protected that all doors leading from risk rooms* onto the means of escape must be 30 minutes fire and smoke protected that there is no storage on the means of escape the final exit door should be capable of being opened from inside without the use of a key walls and ceilings dividing risk rooms* must be fire protected and capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2). Sprinkler systems A domestic sprinkler system may be considered. In some cases where a domestic sprinkler system and an alarm system is installed it may not be necessary to provide certain structural features such as fire doors, fire extinguishers, or to upgrade walls and staircases. Any installation must be installed in accordance with BS 9251:2005. If such a system is being considered this must be carried out in consultation with the council s private sector housing team. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as any electrical item except fixed lighting). 5
8 Fire detection In most cases a Grade D LD2 system is required (see appendix 2). This means: Grade D LD2 Mains powered interlinked detectors each with an integral standby supply (battery back up). The detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings) and in rooms or areas that present a high fire risk* to occupants. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source. * Any electrical item Extinguishers and blankets A 2kg multi purpose dry powder extinguisher to BS EN 3:1996 is required in each room with cooking facilities. All extinguishers are to be wall mounted on wall brackets in accordance with BS 5428: 1987, with carrying handle approximately 1m above ground level, maintained in good order and readily available for use at all times. A wall mounted fire blanket situated approximately 1.5m above floor level to comply with BS EN 1869:1997 is required in all rooms containing cooking facilities. Fire fighting equipment must be maintained in accordance with BS 5306:Part 3:1988. Emergency lighting Emergency lighting may be required if the protected escape route is not provided with adequate background light either natural or borrowed from street lighting to ensure the safe movement to the final exit door. Where emergency lighting is provided it must comply with BS 5266 Part 1:
9 (B) Bedsit type accommodation, two storeys These are typically houses where the tenants have their own room/rooms but the units are not fully self contained (there is some sharing of either a kitchen or a bathroom). Means of escape The escape route needs protecting. A route of escape typically includes the main staircases and all corridors/landings that a person would have to travel through to reach the front door. A protected route of escape means: that all walls between the escape route and risk rooms must be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that all ceilings between the route of escape and risk rooms* must be capable of giving 30 minutes fire and smoke protection. Gaps for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that cupboards leading onto the means of escape should be emptied of flammable goods and kept locked that understairs soffitts must be underlined to provide 30 minutes fire protection understairs cupboards must be emptied of flammable goods and kept locked that all cupboards containing risk of ignition (such as electrical fuse boards or water heaters) must be 30 minutes fire protected that all doors leading from risk rooms* onto the means of escape must be 30 minutes fire and smoke protected that there is no storage on the means of escape the final exit door should be capable of being opened from inside without the use of a key walls and ceilings dividing risk rooms* must be fire protected and be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2). Sprinkler systems A domestic sprinkler system may be considered. In some cases where a domestic sprinkler system and an alarm system is installed it may not be necessary to provide certain structural features such as fire doors, fire extinguishers, or to upgrade walls and staircases. Any installation must be installed in accordance with BS 9251:2005. If such a system is being considered this must be carried out in consultation with the council s private sector housing team. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as any electrical item except fixed lighting). 7
10 Fire detection In most cases a Grade D LD2 system is required (see appendix 2). This means: Grade D Mains powered interlinked detectors each with an integral standby supply (battery back up). LD2 The detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings) and in rooms or areas that present a high fire risk* to occupants. Extinguishers and blankets A 2kg multi purpose dry powder extinguisher to BS EN 3:1996 is required in each room with cooking facilities. All extinguishers are to be wall mounted on wall brackets in accordance with BS 5428: 1987, with carrying handle approximately 1m above ground level, maintained in good order and readily available for use at all times. A wall mounted fire blanket situated approximately 1.5m above floor level to comply with BS EN 1869:1997 is required in all rooms containing cooking facilities. Fire fighting equipment must be maintained in accordance with BS 5306:Part 3:1988. Emergency lighting Emergency lighting may be required if the protected escape route is not provided with adequate background light either natural or borrowed from street lighting to ensure the safe movement to the final exit door. Where emergency lighting is provided it must comply with BS 5266 Part 1:1988. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as a water heater). 8
11 Bedsit type accommodation, three or more storeys Means of escape A house with three or more storeys is considered higher risk. The route of escape needs protecting. A route of escape typically includes the main staircases and all corridors/landings that a person would have to travel through to reach the front door. A protected route of escape means: that all walls between the escape route and risk rooms must be capable of giving half hour fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that all ceilings between the route of escape and risk rooms* must be capable of giving 30 minutes fire and smoke protection. Gaps for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that cupboards leading onto the means of escape should be emptied of flammable goods and kept locked that understairs soffitts must be underlined to provide 30 minutes fire protection understairs cupboards must be emptied of flammable goods and kept locked that all cupboards containing risk of ignition (such as electrical fuse boards or water heaters) must be 30 minutes fire protected that all doors leading from risk rooms* onto the means of escape must be 30 minutes fire and smoke protected that there is no storage on the means of escape the final exit door should be capable of being opened from inside without the use of a key walls and ceilings dividing risk rooms* must be fire protected and be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2). Sprinkler systems A domestic sprinkler system may be considered. In some cases where a domestic sprinkler system and an alarm system is installed it may not be necessary to provide certain structural features such as fire doors, fire extinguishers, or to upgrade walls and staircases. Any installation must be installed in accordance with BS 9251:2005. If such a system is being considered this must be carried out in consultation with the council s private sector housing. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as any electrical item except fixed lighting). 9
12 Fire detection In most cases a Grade D LD2 system is required (see appendix 2). This means: Grade D LD2 Mains powered interlinked detectors each with an integral standby supply (battery back up), with central control equipment. The detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings) and in rooms or areas that present a high fire risk* to occupants. When identified large, high risk HMOs will require a Grade D LD2 system in the individual dwelling units and a Grade A LD2 system in the communal areas. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source. * Any electrical item Extinguishers and blankets A 2kg multi purpose dry powder extinguisher to BS EN 3:1996 is required in each room with cooking facilities. All extinguishers are to be wall mounted on wall brackets in accordance with BS 5428: 1987, with carrying handle approximately 1m above ground level, maintained in good order and readily available for use at all times. A wall mounted fire blanket situated approximately 1.5m above floor level to comply with BS EN 1869:1997 is required in all rooms containing cooking facilities. Fire fighting equipment must be maintained in accordance with BS 5306:Part 3:1988. Emergency lighting Emergency lighting may be required if the protected escape route is not provided with adequate background light either natural or borrowed from street lighting to ensure the safe movement to the final exit door. Where emergency lighting is provided it must comply with BS 5266 Part 1:
13 (C) Converted flats This category includes buildings converted into flats where the conversion was carried out before 1 June 1992, or if it has been converted since 1992 but does not meet standards set in the Building Regulations Means of escape The escape route needs protecting. A route of escape typically includes the main staircases and all common corridors/landings that a person would have to travel through to reach the front door. A protected route of escape means: that all walls between the escape route and risk rooms must be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that all ceilings between the route of escape and risk rooms* must be capable of giving 30 minutes fire and smoke protection. Gaps for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2) that cupboards leading onto the means of escape should be emptied of flammable goods and kept locked that understairs soffitts must be underlined to provide 30 minutes fire protection understairs cupboards must be emptied of flammable goods and kept locked that all cupboards containing risk of ignition (such as electrical fuse boards or water heaters) must be 30 minutes fire protected that all doors leading from risk rooms* onto the means of escape must be 30 minutes fire and smoke protected that there is no storage on the means of escape the final exit door should be capable of being opened from inside without the use of a key walls and ceilings dividing risk rooms* must be fire protected and be capable of giving 30 minutes fire and smoke protection. Gaps in walls for pipes and cables must be filled to provide protection. Unkeyed plaster (particularly lath and plaster) will need to be upgraded (see appendix 2). Sprinkler systems A domestic sprinkler system may be considered. In some cases where a domestic sprinkler system and an alarm system is installed it may not be necessary to provide certain structural features such as fire doors, fire extinguishers, or to upgrade walls and staircases. Any installation must be installed in accordance with BS 9251:2005. If such a system is being considered this must be carried out in consultation with the council s private sector housing team. * Risk rooms: This includes all rooms used for living and/or sleeping accommodation and kitchens. It does not include bathrooms unless there is an ignition source (such as any electrical item except fixed lighting). 11
14 Fire detection In buildings where some or all of the flats are rented, a Grade D LD2 system is required (see appendix 2). This means: Grade D LD 2 Mains powered interlinked detectors each with an integral standby supply (battery back up). The detectors should be sited: in all circulation spaces in the common areas (for example in all landings and in the entrance hall) in each flat, situated in the room/lobby that leads onto the means of escape (ie near to the front door to the flat). Extinguishers and blankets A 2kg multi purpose dry powder extinguisher to BS EN 3:1996 is required in each room with cooking facilities. All extinguishers are to be wall mounted on wall brackets in accordance with BS 5428: 1987, with carrying handle approximately 1m above ground level, maintained in good order and readily available for use at all times. A wall mounted fire blanket situated approximately 1.5m above floor level to comply with BS EN 1869:1997 is required in all rooms containing cooking facilities. Fire fighting equipment must be maintained in accordance with BS 5306:Part 3:1988. Emergency lighting Emergency lighting may be required if the protected escape route is not provided with adequate background light either natural or borrowed from street lighting to ensure the safe movement to the final exit door. Where emergency lighting is provided it must comply with BS 5266 Part 1:
15 (D) Single family dwellings Fire precautions in dwellings This category is typically a dwelling that is not an HMO. This would include a self contained flat or house occupied by either a family, a couple, a single person, two people living together. In a house of less than three storeys a Grade F system is required. This means one or more battery-powered smoke alarms (usually in the entrance hall and first floor landing). In a house of three or more storeys it is advisable to fit a Grade D LD3 system. This will ensure that any person who has the furthest distance to get to an exit, has an early warning of fire. This means: Grade D Mains powered interlinked detectors each with an integral standby supply (battery back up). LD3 Fire blanket The detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings). A wall mounted fire blanket, situated approximately 1.5m above floor level, to comply with BS EN 1869:1997 is required in all rooms with cooking facilities. 13
16 Appendix 1: Fire precautions what needs to be in place As each property is unique we can not plan for every scenario but we have provided a flow chart and different layouts that should help you provide the relevant fire precaution. For further information and guidance there are page references to the national guidance Housing fire safety published by the Local Authorities Coordinators of Regulatory Services (Lacors). When using the flow chart you need to consider how it relates specifically to your property in relation to the following. Number of residents. Number of floors. Arrangements for cooking. Layout and ease of escape in the event of fire. The presence of fire escape windows. Construction of the building and flammability of building elements. Safety of appliances and services such as gas and electricity. Whether part of the building is used commercially. Furnishings. Likely behaviour and activities of tenants. This flowchart has been designed to support you in making the right decisions concerning fire precautions and also help you in writing your risk assessments. The Regulatory Reform (Fire Safety) Order 2005 requires landlords to write and keep current a fire risk assessment so we hope you find it helpful. However, if you have any queries or concerns, please contact us. Private sector housing City Hall Norwich NR2 1NH t: e: [email protected] 14
17 Flow chart to assist in selecting fire precautions which need to be taken depending on the layout of the accommodation. Use the flow chart below to find out which layout best matches your property. A brief description is given of possible layouts and this guides you to the layout and the appropriate fire precautions. Please note that not all the options have layout plans. However a description of the appropriate fire precautions is provided. Layout of property Escape windows Layout or description reference Shared house Corridor to outside from bottom of stairs Are the first floor windows emergency escape windows YES NO Layout A1 Layout A2 Shared house Access to outside via dining room and kitchen to rear and living room to the front Are the first floor windows emergency escape windows YES NO Layout B1 Layout B2 Shared house Access to outside via dining room and kitchen to rear and bedroom to the front Are the first floor windows emergency escape windows YES NO Layout C1 Layout C2 Shared house. Two bedrooms on first floor Staircase descends direct into the living room Escape windows to both bedrooms Escape window to front bedroom only. Layout D1 Layout D2 15
18 Layout of property Escape windows Layout or description reference Shared house. Three bedrooms on first floor Staircase descends direct into the living room Escape windows to all first floor bedrooms No escape windows to first floor bedrooms Layout E1 Layout E1 or Layout E2 Bedsit accommodation One to three storeys Cooking in bedsit rooms Layout F Shared accommodation One to three storeys Shared cooking and washing facilities Layout G Shared or bedsit accommodation Four or more storeys Description H Single family let One or two storeys Description I Self contained flats Two or more storeys Description J 16
19 Index key: Layout A1 House type: Shared house Layout: Two storey LAYOUT A1 Escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Hallway Landing Living room Heat detectors: Kitchen 2) Doors Close fitting doors of sound construction. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Corridor linking the stairs to the front door. First floor: Fire escape windows in first floor rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 17
20 Index key: Layout A2 House type: Shared house Layout: Two storey LAYOUT A2 No escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Hallway Landing Living room Heat detectors: Kitchen 2) Doors Fire doors to all risk rooms grade FD30. Fire door (FD30S) to the kitchen. (Include smoke seal, intumescent strip and self closure). 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Corridor linking the stairs to the front door. First floor: No escape windows in first floor rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 18
21 Index key: Layout B1 House type: Shared house Layout: Two storey LAYOUT B1 Escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Close fitting doors of sound construction to all rooms. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Escape through either living room or rear kitchen. First floor: Fire escape windows in all rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 19
22 Index key: Layout B2 House type: Shared house Layout: Two storey LAYOUT B2 No escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Fire doors (FD30) to all risk rooms Fire door (FD30S) to the kitchen. (Include smoke seal, intumescent strip and self closure.) 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Escape through either living room or rear kitchen. First floor: No fire escape windows in all rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 20
23 Index key: Layout C1 House type: Shared house Layout: Two storey LAYOUT C1 Escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room First floor landing Ground floor bedroom Heat detectors: Kitchen 2) Doors Close fitting doors of sound construction to all rooms. Fire door (FD30S) to the kitchen. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Escape through either: ground floor front bedroom or rear kitchen. First floor: Fire escape windows in all rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 21
24 Index key: Layout C2 House type: Shared house Layout: Two storey LAYOUT C2 No escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Fire doors (FD30) to first floor bedrooms, middle and front. Fire doors (FD30) to ground floor bedroom and dining room. Fire door (FD30s) to the kitchen. 3) Escape window/door Provide escape window or door to ground floor living room. Provide escape to first floor window front window. 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 5) Emergency lighting Emergency light on first floor landing. 6) Escape access to first floor bedroom No lock on bedroom door. Adequate fire exit signs. Fire escape instructions for tenants. Management control to ensure access to bedroom at all times. Ground floor: Escape through either: ground floor front bedroom room or rear kitchen First floor: No fire escape windows in all rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 22
25 Index key: Layout D1 House type: Shared house Layout: Two storey. Two bedrooms on the first floor. LAYOUT D1 Escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Close fitting doors of sound construction to all rooms. Fire door (FD30S) to the kitchen. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Stairs comes down direct into the dining room. First floor: Fire escape windows in all rooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 23
26 Index key: Layout D2 House type: Shared house Layout: Two storey. Two bedrooms on the first floor LAYOUT D2 No escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Fire door (FD30s) to the kitchen. 3) Fire escape windows Escape window or door to the dining room. Escape window to first floor front bedroom 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 5) Emergency lighting Emergency light on first floor landing. 6) Escape access to first floor bedroom No lock on bedroom door. Adequate fire exit signs. Fire escape instructions for tenants. Management control to ensure access to bedroom at all times. Ground floor: Stairs comes down direct into the dining room. First floor: If no escape windows there must be at least a fire escape window to first floor front bedroom window. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 24
27 Index key: Layout E1 House type: Shared house Layout: Two storey. Three bedrooms on the first floor LAYOUT E1 Escape windows Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Fire doors (FD30) to: First floor bedroom, first floor middle bedroom and ground floor bedroom. Fire door (FD30S) to the kitchen. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 4) Emergency lighting Emergency light on first floor landing. Ground floor: Stairs comes down direct into the dining room. First floor: Fire escape windows in all rooms. Note: If you do not have escape windows you will need to adopt this plan or layout E2. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 25
28 Index key: Layout E2 House type: Shared house Layout: Two storey. Three bedrooms on the first floor LAYOUT E2 No escape window. Fire precautions 1) Fire alarm system Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Dining room Landing Living room Heat detectors: Kitchen 2) Doors Fire doors (FD30) to: First floor bedroom, first floor middle bedroom and ground floor bedroom. Fire door (FD30S) to the kitchen. 3) Protected means of escape Provide corridor from the bottom of stairs to the external. The partition wall with the dining room should provide 30 minute fire resistance. The door from the new corridor into the dining room will have to be to standard FD30S with self closure. 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. 5) Emergency lighting Emergency light on first floor landing. Ground floor: Stairs comes down direct into the dining room. First floor: No fire escape windows in bedrooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 26
29 Index key: Layout F House type: Bedsit accommodation Layout: Two or three storey Fire precautions 1) Fire alarm system a) Whole house Grade D LD3+ system Grade D system: A system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detection in the following areas: Smoke detectors: Hallway and corridor Each landing Living room Heat detectors: In each bedsit with cooking facilities b) Each bedsit Grade D LD3 system Each bedsit should have own smoke detector. Ideally mains powered but tamper proof detectors with 10year life lithium batteries can be considered. 2) Doors Fire doors (FD30S): including smoke seals, intumescent strips and self closures to all doors opening onto common area forming the means of escape. 3) Emergency lighting Emergency lighting on each landing and hallway. 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. LAYOUT F Escape from the rooms into protected means of escape providing 30 minutes fire and smoke protection Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 27
30 Index key: Layout G House type: Shared house Layout: Three floors and shared cooking and bathing facilities LAYOUT G Escape from the rooms into protected means of escape providing 30 minutes fire and smoke protection Fire precautions 1) Fire alarm system a) Older converted buildings with poor fire separation. Grade D LD2 system Grade D: System of mains powered interlinked smoke and heat detectors with integral battery back-up. LD2 detection: detectors in the following areas: Smoke detectors: Hallway and corridor Each Landing Risk rooms including bedrooms, lounge and dining areas Heat detectors: In rooms with cooking facilities. b) New developments Grade D LD3+ system Grade D system of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3+ detection. Detectors in the following areas: Smoke detectors: Hallway and corridor Each Landing Living room and dining area Heat detectors: In rooms with cooking facilities 2) Doors Grade D LD2 system Fire doors (FD30S) include smoke seals, intumescent strips and self closures to all doors opening onto a common area forming the means of escape. Grade D LD3 system Fire doors (FD30): these do not need smoke seals, but otherwise the same as FD30S above. 3) Emergency lighting Emergency lighting on each landing and hallway. 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 28
31 Index key: Description H House type: Shared house or bedsit accommodation Layout: Four or more storeys DESCRIPTION H no layout plan Escape from the rooms into protected means of escape providing 30 minute fire and smoke protection Fire precautions 1) Fire alarm system Grade A LD2 system Grade A system: A system of electrically operated smoke and heat detectors linked to a control panel. (The panel should be secure and tamper protected and can be only reset by nominated key holder. The contact details of the key holder should be displayed in the prominent position near to the panel. A monthly record of testing should be also displayed close to the panel). LD2 detection. Detection in the following areas: Smoke detectors: Hallways, corridors and landings In all risk rooms including bedrooms and communal rooms. Heat detectors: Any room with cooking facilities. 2) Doors Fire doors (FD30S): including smoke seals, intumescent strips and self closures to all doors opening onto common area forming the means of escape. 3) Emergency lighting Emergency lighting on each landing and hallway. 4) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 29
32 Index key: Description I House type: Individual family let Layout: Single family property Fire precautions 1) Fire alarm system Grade D or F LD3 system Grade D system: System of mains powered interlinked smoke and heat detectors with integral battery back-up. Grade F system: A system of battery operated detectors. These must be tamper proof with 10year life lithium batteries. LD3 detection. Detection in the following areas: Smoke detectors: Hallway and landings. Lounge and/or dining room area. depending on the layout. Heat detectors: Kitchen depending on layout. 2) Doors Doors should be of sound construction and there should always be a door into the kitchen. 3) Equipment Fire blanket in the kitchen. DESCRIPTION I no layout plan Ground floor: Stairs comes down direct into the dining room. First floor: No fire escape windows in bedrooms. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 30
33 Index key: Description J House type: Self contained flats Layout: Block development Description J no layout plan Flats share common staircase and entrances out of the building. Fire precautions 1) Alarm systems a) Common areas Grade D or Grade A LD2 system. Grade D system: System of mains powered interlinked smoke and heat detectors with integral battery back-up. Grade A system: A system of electrically operated smoke and heat detectors linked to a control panel. LD2 detection. Detection in the following areas: Smoke detectors: Common hallways, entrances and landings. Lounge and/or dining room area depending on the layout. Heat detectors: Front entrance lobby of each flat. b) Each flat Grade D or Grade F systems. Grade D LD3 system. Grade D system: System of mains powered interlinked smoke and heat detectors with integral battery back-up. LD3: Smoke detectors near kitchens and risk room Grade F system: A system of battery operated detectors. These must be tamper proof with 10year life lithium batteries. 2) Doors FD30S standard for doors which open out onto the common areas providing the route of escape. 3) Emergency lighting Provided on route of escape including landings and hallways. 3) Equipment Fire blanket and 2kg dry powder extinguisher in the kitchen. Notes: National fire guidance is provided by Lacors in its guide: Housing fire safety. This guide can be seen at: Read the following pages in guide for further information. 1. Fire alarm system: Pages Fire doors: Pages Escape window: Page Emergency lighting: Pages Fire fight equipment: Page 28 31
34 Appendix 2: Fire standards further information Notes Standards The standards detailed in the chart are those which would normally be expected. Variations from the standard can occur depending on circumstances and the result of risk assessments. General Fire alarm systems systems to be installed according to BS :2004. Smoke detectors ensure optical type detectors are installed to rooms and ionising type to: landings hallways and corridors. Fire doors to FD30S (30 minutes fire and smoke protection) incorporating intumescent strips, smoke seals and self closures. Kitchens all cases provision of fire blanket and 2kg dry powder fire extinguisher. Construction generally there must be a 30 minute fire resisting structure to walls and ceilings separating habitable rooms and other habitable rooms kitchens and the common escape routes. 60 minute fire resistance may be needed such as for basements and properties above and adjoining commercial premises. Fire escape windows to comply with current building regulations. Place of safety enclosed courtyards and absence of rear exits which prevent escape from building area are considered not providing place of safety. Place of safety (alley gates) in properties where exit from the rear to the front is via a locked alley gate, arrangements need to be considered for ensuring that the gate can be easily opened particularly where a mortice lock is used. Keys need to be readily available in an emergency. Providing a key pad lock could be considered. Emergency lighting to be installed according to BS 5266 where deemed necessary following risk assessment. However it would probably be judged as necessary in most instances. Risk assessments The standards set out in the flow chart are guide standards and can be subject to variation depending on risk assessments undertaken under the Housing Health and Safety Rating Scheme by the council and fire risk assessments carried out by the landlord under the provisions of the Regulatory Reform Order (Fire Safety) Variations from the guide standard can arise because of particular circumstances and layout existing at the premises. Variations can follow from discussions between councils, fire service and landlords. Fire fighting equipment For each room with cooking facilities provide a 2kg multi pupose dry powder extinguisher to BS EN 3:1996. All extinguishers are to be wall mounted in accordance with BS 5428:1987 and a wall mounted fire blanket approximately 1.5m above floor level in accordance with BS EN 1869:
35 Sprinkler systems Owners may benefit from a range of accepted and established fire precautions design freedoms where they install a residential sprinkler system. These design freedoms can be applied on a risk-assessed basis and may actually allow HMOs to be used in a more user friendly and flexible manner appropriate to the home environment. A residential sprinkler system installed and maintained in accordance with BS 9251:2005 can: actively save more lives and prevent more injuries in the event of a fire (especially in HMOs where the risk to occupants from fire is widely acknowledged to be disproportionately high); reduce property damage in the event of a fire; assist with business continuity by allowing speedy reoccupation of areas affected by a fire; and minimise the amount of water used to extinguish any fire that occurs by restricting the growth of that fire. There are potential safety, economic and management reasons for installing a sprinkler system. Installation should be carried out by an experienced contractor suitably qualified and registered with the FIRAS / Fire Sprinkler Association third party certification scheme. Alternatively, installers may be certificated under the LPS 1048 Scheme Requirements for certified sprinkler installers, supervising bodies and supervised installers. Fire alarm systems Grade A system Fire alarm system to comply with current British Standard (BS) 5839 Part 6 Grade A. This comprises a system of electrically operated smoke and/or heat detectors which are linked to a control panel to give information on the location of any fire or any fault which may develop. The control panel must conform to current British Standard 5839 Part 4. Grade D system Fire alarm system to comply with current British Standard 5839 Part 6: Grade D This comprises a system of one or more interlinked mains powered and/or heat detectors each with a standby battery and built in alarm. LD 2: means Detectors are to be in all circulation spaces that form part of the escape route (typically in corridors and landings) and in rooms or areas that present a high risk to occupants. (High risk rooms include rooms used for living and/or sleeping and kitchens. LD 3: means The detectors are to be in all circulation spaces that form part of the escape route. Installation of fire alarm system is to be in accordance with BS :2004 and BS :2002 and should ensure that the alarm signal gives a sound level of 75dB(A) in all rooms particularly in bedrooms. 33
36 Installation of detectors Type There are two types of detectors optical and ionization. It is better to install optical in most situations as these are less likely to cause false alarms. Mounting position Smoke and heat detectors should preferably be mounted on ceilings on a horizontal surface. Detectors should not be positioned at an angle. The detectors should be placed at least 500mm horizontally from any wall/beam or light fitting. Obstructions The detector should be positioned either side of a ceiling obstruction such as beams or down-stands which are greater than 150mm depth. Power supply The detectors can be supplied from the lighting circuits. However if the tenant is on a payment meter the supply must be taken from the landlord s supply ie. the power supply will need to come from a dedicated circuit from the main consumer unit. A competent installer should install the system in accordance with BS 7671.The installer should certify that the installation conforms to the recommendation of BS 5839 for the type Grade D LD2. Upon completion of the installation obtain and submit to private sector housing a completion certificate in a form which satisfies the requirements of BS Fire doors Fire doors to provide a minimum of 30 minutes fire and smoke protection (FD30s) complying with BS 476: Part and Section 31.1:1983. The doors must be installed to satisfy the requirements of BS 8214:1990 as set out in the notes below: Unless otherwise stated each fire door to meet the standards below: a To be fitted with plain steel butt hinges of not less 100mm x 75mm. b To be fitted with heat activated intumescent seals 4mm x 10 mm rebated in the head and sides of the doors or into the frame coincident with the closed position of the door sides and head. (The strip must not be rebated into the door stops or a coincident position with the stops on the door.) c To be fitted with a self closing device (preferably of the overhead hydraulic type) manufactured to satisfy the requirements of BS EN 1154:1997. d The self closing device to be capable of: closing the door positively onto the latch or where the latch is not required, of holding the door for not less than 30 mins. e The gap between the door and door lining (or frame) to be not more than 3mm. f All hinges and latch parts necessary for holding the door in place during a fire to have a melting point in excess of 8000 C and to comply with BS 8214:1990 and BS 5872:1980. g Where there are gaps between the door lining and the surrounding construction fill all voids with fire stopping material such as an intumescent foam or filler. h Where glazing is incorporated into the fire doors install 6mm Georgian wired glass or fire resistant glazing. The glazing to be fixed to BS 476 parts requirements. 34
37 Emergency lighting Emergency lighting systems must comply with the provisions of BS :1999. Upon completion of the installation obtain and submit to private sector housing a completion certificate in a form which satisfies the requirements of BS 5266 Part Wall and ceiling finishes Wall and ceiling finishes should provide 30 minute fire resistance. For new stud partitions this can be achieved by: Constructing a frame of 75mm X 50mm timbers with head and sole plate and studs at 600mm centres. Providing 12.5mm plasterboard for each face, taping the joints and finishing with a top coat of 3mm multi finish plaster. For existing wall and ceiling surfaces the appropriate construction standard to bring them up to the 30 minute standard will have to be agreed following the site inspection. This may include the upgrading of unkeyed plaster (particularly lath and plaster) by fitting 9.5mm plasterboard on both faces. The scriming of joints and also junctions with ceilings with 75mm wide scrim tape and applying setting coat of multi finish plaster, finished flush with existing surfaces. Wall and ceilings adjoining commercial premises should provide 60 minutes fire resistance. Fire escape windows Where windows are proposed to be used as a means of escape they must comply with the following: The window must have an unobstructed openable window area of at least 0.33m 2 with the width and height dimension being a minimum of 450mm. Side hung opening lights are recommended. The bottom of the openable area (window sill level) must be not more than 1100mm and not less than 800mm above floor level. Windows are suitable for means of escape where the drop from the window to the ground level is one storey only (not exceeding 4.5m from first floor level to outside ground level). Note: The ground below the windows must be flat and free from hazards (low walls and railings etc). 35
38 36
39 Appendix 3 Norwich City Council Fire safety in houses in multi occupation (HMOs) Fire risk assessment form Address of premises: Owner of premises: Size of premises: Age of premises: 2 storey 3 storey 4+ storeys Name of person carrying out fire risk assessment: Position/responsibility: Fire risk assessment key steps reviewed Date of review: Key steps Assessment made? Fire hazards Yes No Signed: People at risk Yes No Risk review Yes No Record keeping Yes No Dated: Review and plan of action Yes No Fire safety in houses in multi occupation. Regulatory Reform (Fire Safety) Order 2005 risk assessment form Fire risk assessment for: Postcode Address: To ensure the adequacy of existing fire precautions within a house in multi occupation (HMO), a risk assessment should be carried out: by or on the behalf of; the owner, the licensee/ prospective licensee to establish both the risk of a fire occurring and the risk to people in the event of fire. Under the Regulatory Reform (Fire Safety) Order 2005 you must: carry out a fire-risk assessment identifying any possible dangers and risks. consider who may be especially at risk. remove or reduce the risk of fire and provide general fire precautions to deal with any remaining risk. create a plan to deal with any emergency and keep a record of your findings. review your findings when necessary. The risk assessment form below guides you in the steps you need to take in undertaking a risk assessment. It provides you with a series of questions, which you will need to consider in undertaking an assessment. The checklist or something similar must be submitted to Norwich City Council. The answer to all the questions should be yes, no or not applicable (N/A). For those who are responsible for smaller HMOs you may think some of the questions are do not apply to you. However you should indicate this by marking the not applicable column. It is important for the council to see that you have considered all the questions. In the details/justification column you should provide further information on: the deficiencies identified the arrangements in place which satisfy the question the justification for answering the question not applicable. 37
40 Fire risk assessment Key steps Yes No N/A Details/justification Action taken Step one - Hazards 1 Have the premises been recently modified as a result of: a building control requirements and/or b a schedule issued by the council. 2 Have flammable and combustible materials (eg paints, cleaning agents, aerosols, stored furnishings etc) been identified and minimised where possible? 3 Are all flammable substances and combustible materials stored safely? 4 Are heating appliances fixed in a position at a safe distance from any combustible materials and suitably guarded? (eg are curtains, drapes furniture too near heating appliances?) 5 Have you a gas safety certificate issued in the past year by a Gas Safe registered engineer? 6 Is the furniture upholstery made of fire resistant materials meeting the Furniture and Furnishings (Fire) (Safety) Regulations 1988? 7 Has there been an electrical safety certificate issued for the premises in the past five years? 8 Are all items of electrical equipment fitted with fuses of the correct rating? 9 Are all lengths of flexible cable and multipoint adaptors kept to a minimum? 10 Are cables run only where damage is unlikely and not under any floor coverings or through doorways? 11 Have you had portable appliances tests on electrical equipment? 12 Are the premises free from accumulations of rubbish, waste-paper or other materials which could cause a fire if set alight? 13 Have measures been taken to reduce the risk of either accidental or deliberate fire? 14 Are there suitable management procedures in place to ensure fire safety standards are maintained? 15 Have you in place management arrangements for dealing with tenants whose behaviour might lead to a risk to other tenants? Step two people at risk Have you made an assessment of risk to residents and visitors arising out of special needs such as; disability, mental health problems, behavioural problems, language difficulties? Regarding the above have you considered the following 1 are all your residents able to understand the fire safety measures you have put in place? 38
41 Key steps Yes No N/A Details/justification Action taken Step two people at risk continued 2 Have residents been given clear instruction on fire safety? 3 Are all the residents in the property reasonably mobile? 4 Are there suitable procedures in place for the evacuation of residents? 5 Have you assessed whether any resident may present a particular fire risk? Step three reducing the risk A means of escape 1 Is the fire detection system adequate for the size of property and the number of people accommodated? 2 Is the property of sound construction with suitable fire resistance to walls, floors, landings, stairwells and ceilings? 3 Are there sufficient exits for the number of people present? 4 Do all residents have access to a protected means of escape in the event of a fire? 5 Do all exits lead to a place of safety? (Enclosed rear gardens are not considered as a place of safety.) 6 Do residents have to go through a risk room as the means of escape? (Risk rooms include bedrooms, living rooms, dining rooms and kitchens.) 7 Are all corridors and escape routes free from obstruction? 8 Are the floor surfaces on escape routes free from tripping and slipping hazards? 9 Are all internal fire doors clearly labelled? 10 Are all doors used as means of escape in good repair and can these doors be easily and immediately opened without the use of a key? 11 Can all fire safety signs and exit notices be clearly seen? (Notices and signs should comply with BS 5499: Part ) 12 Are self closing devices on fire doors in working order? 13 Are all vents and service ducts, etc suitably protected where appropriate to prevent the spread of fire, heat or smoke? B Lighting 1 Has the need for emergency lighting being considered? 2 Are routes to a place of safety adequately lit? 3 Is the emergency lighting in working order and maintained regularly? 39
42 Key steps Yes No N/A Details/justification Action taken C Fire alarm 1 Is there an automatic fire alarm system ie a system with mains power supply? 2 Is the automatic fire alarm system in working order? 3 Is the fire alarm system tested and maintained regularly? 4 Has a test certificate for the alarm system been issued in the past year? D Fire fighting 1 Is there sufficient fire fighting equipment of the correct type? (Each kitchen are should have a fire extinguisher and fire blanket) 2 Are portable fire extinguishers, fire blankets etc, suitably located and available for use? 3 Have portable fire extinguishers been serviced in the past year? 4 Is the fire fighting equipment in working order? E Fire instructions/ emergency plan 1 Are fire instructions clearly displayed throughout the premises? 2 Have steps been taken to plan what actions everyone should take if a fire starts? 3 Have these steps been brought to the attention of all the residents? Step four record keeping 1 Have you recorded the findings of your risk assessment? 2 Has a procedure been established to review the fire risk periodically? 3 Do you keep records of the routine testing of the fire alarms? 4 Do you keep maintenance check records to monitor any defects or damage, which may arise, leading to a fire risk? 5 Do you have records of the annual checks for the fire alarm system and fire fighting equipment? Note: Once completed, this checklist should help you to meet your responsibilities under the Regulatory Reform (Fire Safety) Order 2005 in that you have identified fire hazards in your HMO. What you must also do is reduce the risk of those hazards and decide what physical fire precautions and management requirements are required to ensure fire safety is achieved. Depending on your answers in the above checklist you should identify the risks on the sheet below and also detail the actions you will be taking to reduce the risk and set a date by which time the works are to be completed. 40
43 Note: You should list below those areas for attention identified both from the checklist above and any other investigations. You should list these in priority order under the headings urgent attention etc. Record of significant findings Actions to be taken Completion date Step five review and plan of action Signature: Date: Print name: 41
44 Appendix 4: Risk assessment form notes Step one question 5 You have duties under the Gas Safety (Installation and Use) Regulations 1998 to arrange maintenance by a Gas Safe-registered installer for all pipe work, appliances and flues, which you own and have provided for your tenants use. You must also arrange for an annual gas safety check to be carried out every 12 months by a Gas Safe-registered installer. You must keep a record of the safety check for two years and issue a copy to each existing tenant within 28 days of the check being completed and issue a copy to any new tenants before they move in. Step one question 6 Furniture and Furnishing Regulations (Fire) (Safety) Regulations Landlords and agents must ensure any furniture or furnishings they provided in the property meet appropriate safety standards. Under these regulations landlords must ensure their furniture and furnishings meet the following standard tests: Upholstered articles must have fire resistant material. Upholstered articles must pass the match resistance test. Combinations of cover material and filling material have passed the cigarette resistance test. Step one question 7 Landlords should have electrical safety certificates issued on the premises every five years. The certificate should be issued by a competent electrician namely one who is a member of the following: NECEIC Electrical Contractors Association CITB defined competency scheme NAPIT certification scheme (You will need building regulation approval for electrical work unless it is carried out by a competent electrician). Step one question 11 Since 1997 it has been mandatory under the Electrical Equipment (Safety) Regulations for all electrical appliances supplied with rented accommodation to be safe. This applies to both new and second hand equipment. The best way to be sure that appliances are safe is to have a portable appliance test undertaken by a competent person. Step three all questions Please refer to the guidance contained within this document. 42
45 Notes 43
46 Notes 44
47 Notes 45
48 If you require this booklet in another language or format, eg large print, audio cassette or Braille, please contact Norwich City Council on or Published by Norwich City Council August 2011 Norwich City Council, City Hall, Norwich, NR2 1NH
SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS
Document F SPECIFIC GUIDANCE FOR A HOUSE IN MULTIPLE OCCUPATION (HMO) CONVERTED ENTIRELY INTO SELF CONTAINED FLATS This document is intended as a specific guide for persons who own, manage or control Houses
For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
London Borough of Barnet. Fire Safety in Houses in Multiple Occupation. A Guide to Landlords
London Borough of Barnet Fire Safety in Houses in Multiple Occupation A Guide to Landlords March 2016 Contents Introduction p.3 Summary of main requirements p.3 Fire Safety Precautions p.4 Protecting the
FIRE DETECTION AND ALARM SYSTEMS
HMO Information Sheet No 1 FIRE DETECTION AND ALARM SYSTEMS 1. Introduction When a property is in multiple occupation, the risk of fire breaking out is greater than in an ordinary single family home. Some
For use by landlords of small premises Premises Address
fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties
A Guide to Fire and Security Protection in Multi-Occupied Residential Properties Advice for Property Owners, Managers and Contractors Revision 2015 Foreword HOMESTAMP is a partnership consortium with an
Building Control. Householder Guidance Leaflet No. 29. Fire detection in dwellings
Building Control Householder Guidance Leaflet No. 29 Fire detection in dwellings This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum GUIDANCE NOTE FOR HOME OWNERS
Northern Ireland Housing Executive: HMO Fire Safety Guide
Northern Ireland Housing Executive: HMO Fire Safety Guide Contents Equality Statement 5 Houses in Multiple Occupation (HMOs) means of escape in case of fire and other fire precautions 6 1.0 Introduction
How To Write A Fire Risk Assessment
Fire Safety Risk Assessment This form is to aid you in carrying out a fire safety risk assessment of a property. The form is separated in to two parts: Part 1 initial assessment form and guidance notes
Guide to Houses in Multiple Occupation Self Contained Flats
Guide to Houses in Multiple Occupation Self Contained Flats Kitchens Bathrooms Fire Safety Room Sizes Toilets HMO self contained flat std0 Version 4 201106 INTRODUCTION GENERAL INFORMATION The Housing
To promote and protect the private residential landlord. Fire Safety Logbook. Information. Advice. Support. Services START DATE:
To promote and protect the private residential landlord Fire Safety Logbook Information Advice Support Services START DATE: PROPERTY DETAILS Property Address: Post Code: Licence Holder/Manager: CONTACT
BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010
Building Control Charnwood Borough Council Southfield Road Loughborough LE11 2TN BUILDING CONTROL GUIDANCE SHEET SMOKE ALARMS IN STANDARD DWELLINGS Last updated 16/12/2010 Page 1 of 7 PURPOSE: This Guidance
Property Accreditation Standards 2014/2015
Property Accreditation Standards 2014/2015 Promoting responsible renting of student housing in the city of Southampton Letting period 1st July 2014 to 30th June 2015 Version 1, 10/12/2013 All properties
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION
LONDON BOROUGH OF BROMLEY STANDARDS FOR HOUSES IN MULTIPLE OCCUPATION (HMO) INTRODUCTION 1. Minimum Standards: This document sets out the minimum standards required in HMOs located within the London Borough
Building Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
Fire Standards & Regulations Are you confused?
Fire Standards & Regulations Are you confused? Regulatory Reform (Fire Safety) Order Local Licensing Requirements BS 5839-6: 2013 Building Regulations Document B LACORS Fire Safety Guidance Fire Alarm
Guidance on loft conversions in two-storey houses
Guidance on loft conversions in two-storey houses Technical guidance for building control surveyors, designers and installers 01 Guidance on loft conversions in two-storey houses Technical guidance for
Application Guide HMOs
Application Guide HMOs 2 Aims of this guide 3 What is AlarmSense? 3 What is an HMO 3 Fire Protection for an HMO 3 Approved Document B 4 Mandatory Licensing 4 BS 5839 4 Categories of System 6 Application
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK. Website www.iomfire.com
ISLE OF MAN FIRE & RESCUE SERVICE FIRE PRECAUTIONS LOGBOOK Website www.iomfire.com ADDRESS OF PREMISES FIRE CERTIFICATE No. (where applicable).. LOCATION OF LOG BOOK. CONTENTS OF LOG BOOK Useful telephone
Fire. The Fire Installers Mate. A guide to fire alarm systems design
Fire The Fire Installers Mate A guide to fire alarm systems design BS 5839 Part 1:2002 A guide to BS 5839 Part 1:2002 Disclaimer This booklet is not intended to be a comprehensive guide to all aspects
Guide For Owners, Agents and Managers of HMOs
Guide to Fire Safety in Houses in Multiple Occupation This guide outlines the fire safety provisions recommended for HMOs in Hertfordshire and is based upon the national guidance produced by LACORS. Guide
AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Fire Alarm Systems Design. a guide to BS5839
AVAILABLE TO DOWNLOAD ON THE APOLLO APP a guide to Fire Alarm Systems Design BS5839 Part1:2013 The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply! What
Fire Safety Requirements for Child Care Centre
Fire Safety Requirements for Child Care Centre A. Restrictions on Location Child care centre shall not be located : - (a) (b) in any premises designed for residential use; in any industrial building, warehouses,
LONDON BOROUGH OF BARKING AND DAGENHAM PRIVATE SECTOR HOUSING HMO LICENSING APPLICATION FORM GUIDANCE NOTES
LONDON BOROUGH OF BARKING AND DAGENHAM PRIVATE SECTOR HOUSING HMO LICENSING APPLICATION FORM GUIDANCE NOTES NOTES TO PART 1 If you are the person filling in this application form, then you are the applicant.
FIRE SAFETY RISK ASSESSMENT
FIRE SAFETY RISK ASSESSMENT For small single occupancy premises Premises Hertco Ltd ACME House, Old London Road, Hertford SG17 7LD Fire Safety Risk Assessment for Small Premises Introduction Regulatory
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
What you need to know about. Smoke alarms for residential buildings
What you need to know about Smoke alarms for residential buildings Are s compulsory? Smoke alarms are compulsory and must be installed in residential buildings on or near the ceiling of every storey. What
Fire safety for landlords
Fire safety for landlords Acting Acting to to Protect & Save Are you a landlord and confused about your responsibilities towards fire safety? The law and regulations can often seem complicated and grey.
ADVISORY NOTES FOR LICENSED HOUSES IN MULTIPLE OCCUPATION (CATEGORY C HOSTELS)
ADVISORY NOTES FOR LICENSED HOUSES IN MULTIPLE OCCUPATION (CATEGORY C HOSTELS) THESE NOTES SHOULD BE READ IN CONJUNCTION WITH YOUR HMO LICENCE ISSUED BY LEEDS CITY COUNCIL HOUSING REGULATION TEAM HEALTH
I.S. 3218 :2013 Fire Detection & Alarm Systems
I.S. 3218 :2013 Fire Detection & Alarm Systems Overview of significant changes 26 th March 2014 FPS Ltd Today s Programme Commencement Transition Competence & Qualifications System Certification System
RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS
RHP SERVICES: INFORMATION FOR LANDLORDS AND PROPERTY OWNERS Types of Property We are looking for licensed houses in multiple occupation (HMOs), studio, one, two, three four and five bedroom homes. RHP
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems
Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Appendix A Proposed amended Acceptable Solution for Warning Systems s in the grey boxes form part of the proposed
Practice Note 2006-27
Practice Note Self-Contained smoke alarms to existing buildings This updates the previous Practice Note 2005-27 issued May 2005. Reference to the BCA in this Practice Note means Volume One and Volume Two
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III. HOUSES IN MULTIPLE OCCUPATION Space Standards
ENVIRONMENTAL HEALTH PROFESSIONAL PRACTICE VOL II CHAPTER III HOUSES IN MULTIPLE OCCUPATION Space Standards ADOPTED HOUSING STANDARDS:CATEGORY F HOUSES Houses within this category would be of a low priority
Contents. 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4
Contents 1. Introduction 1.1 Reason for this Guide 3 1.2 Interpretation 1.3 Principles of Fire Safety 1.4 Legal Provisions 4 2. Scope and Application 2.1 Scope of the Guide 5 2.2 Premises to which the
HOUSES IN MULTIPLE OCCUPATION STANDARDS. Housing Executive
HOUSES IN MULTIPLE OCCUPATION STANDARDS Housing Executive Contents 1.0 Introduction 3 2.0 Standards 4 3.0 Method of Measurement 6 4.0 Overcrowding 7 5.0 Over Occupation 8 6.0 Facilities for Storage, Preparation
NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS
NUstudenthomes PROPERTY MANAGEMENT SERVICE A GUIDE FOR LANDLORDS NUstudenthomes Student Services Newcastle University King s Gate Newcastle upon Tyne NE1 7RU Tel 0191 208 3333 WHAT IS THE NUstudenthomes
1.0 APPOINTMENTS 2.0 FIRE RISK ASSESSMENTS
Fire Risk assessment 1.0 APPOINTMENTS 1.1 Responsible Person. In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO) the School s Head, Mrs J M Miles is appointed as the Responsible Person
The terms hazard and risk are often used, which we define as the following:
Fire Safety Last updated in October 2010 This information sheet aims to give safety reps a basic understanding of fire safety and fire risk assessments under the current law. More detailed information
FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS
Fire Safety Technical Guide FURNITURE & FURNISHINGS - FIRE SAFETY STANDARDS 1.0. Introduction 1.1. Furniture and furnishings may significantly increase fire spread in rooms and those circulation spaces,
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
Introduction. CE marked construction products
Introduction This Technical Booklet has been prepared by the Department of Finance and Personnel and provides for certain methods and standards of building which, if followed, will satisfy the requirements
Fire Safety Risk Assessment Checklist for Residential Care Premises
Checklist for Residential Care Premises Name of Premises: Address of Premises: Name of Responsible Person: What area / location does the assessment cover? Does the assessment cover the whole site YES or
Smoke Alarms. New smoke alarm requirements for existing buildings from 1 May 2006. Introduction. Advisory note March 2006
New smoke alarm requirements for existing buildings from 1 May 2006 Advisory note March 2006 Introduction To enhance safety and minimise loss-of-life in building fires, the NSW Parliament, in July last
Fire Alarm system Installation Guide
Fire Alarm system Installation Guide Fire Alarm System Categories Systems designed for Protection of Property only, fall into two classifications P1 or P2. but a manual system is also needed, then this
Houses in Multiple Occupation
Houses in Multiple Occupation Houses in Multiple Occupation Foreword This document has been created to both encourage and advise landlords, property owners and agencies to understand the Houses in Multiple
GENERAL FIRE SAFETY TERMS & DEFINITIONS
UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:
EAST LONDON GUIDANCE ON HMO STANDARDS (3)
EAST LONDON GUIDANCE ON HMO STANDARDS (3) This guidance is intended for Houses in Multiple Occupation (HMOs) in the London Boroughs of Barking & Dagenham, Hackney, Havering, Newham, Redbridge, Tower Hamlets
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective
SMOKE DETECTOR INSTALLATION PROGRAM The Burlington Ordinance Perspective The National Fire Alarm Code, NFPA 72, sets the minimum requirements of performance, selection, use and location of automatic detection
FIRE SAFETY REGISTER. Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie
FIRE SAFETY REGISTER Premises Name: Premises Address: Fire Safety Manager: Contact No. Kerry County Fire Service www.kerrycoco.ie 1 CONTENTS Section Title Page 1.0 Introduction 3 2.0 Guidance for the completion
Grasshoppers Rugby Football Sports and Social Club. The Fire Risk Assessment
Grasshoppers Rugby Football Sports and Social Club The Fire Risk Assessment Revision 1 Dated: 15th February 2013 CONTENTS 1. PREMISES DETAILS 2. PREMISES PLAN 3. HAZARDS 4. HISTORY 5. MITIGATING THE EFFECTS
Fire Safety Log Book
Fire Safety Log Book Company... Address........ Responsible Person. Competent Person. Date Started For Additional Information: Safety Management (UK) Ltd Holme Suite, Clawthorpe Hall Business Centre, Burton
DOMESTIC SMOKE ALARMS
DIgest DG 525 DOMESTIC SMOKE ALARMS Emma Warren Smoke alarms in homes can save lives, are easy to use and are inexpensive. If correctly specified, installed and maintained, they will give an early warning
Guidance Sheet : Legislative Requirements for Rented Properties
Guidance Sheet : Legislative Requirements for Rented Properties Introduction: Letting your property and becoming a landlord may seem like the simple solution to filling an empty property and it can be
BS5839 Part 1:2002 Overview
BS5839 Part 1:2002 Overview 1 Contents Introduction So why is the current standard being revised? The brief for the new standard Changes to structure of current Standard Enhanced certification of Fire
Fire safety advice for landlords
YOU CAN PREVENT IT Fire safety advice for landlords Introduction Each year there are over 50,000 fires in dwellings in the UK. These result in around 300 hundred fatalities and several thousand serious
Call reduction guidance for false alarm/ unwanted fire signals
Call reduction guidance for false alarm/ unwanted fire signals Acting to Protect & Save Introduction Devon & Somerset Fire & Rescue Service attend in excess of 20,000 incidents each year, approximately
EAST LONDON HMO GUIDANCE (4)
EAST LONDON HMO GUIDANCE (4) This guidance is intended for Houses in Multiple Occupation (HMOs) in the London Boroughs of Barking & Dagenham, Hackney, Havering, Newham, Redbridge, Tower Hamlets Waltham
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK MARIE CURIE SCEAUX GARDENS ESTATE LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
720r Addendum: Siting the 720r
720r Addendum: Siting the 720r UK 1 Cooper Security Limited 2013 Every effort has been made to ensure that the contents of this leaflet are correct. However, neither the authors nor Cooper Security Limited
Greater Manchester Fire and Rescue Service
Greater Manchester Fire and Rescue Service Record of Fire Safety Equipment Testing CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS 4. EMERGENCY
FIRE RISK ASSESSMENT SW13 0HA
FIRE RISK ASSESSMENT at Carmichael Court Grove Road London SW13 0HA ON BEHALF OF Farrar Property Management Date of assessment: 14/01/2013 Recommended review date: January 2015 CONTENTS 1.0 INTRODUCTION
UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS
Fire Safety Technical Guide UCL FIRE RISK ASSESSMENT POLICY& ARRANGEMENTS 1.0. BACKGROUND 1.1. The Regulatory Reform (Fire Safety) Order (known Fire Safety Order) applies to England and Wales (Northern
Fire Risk Assessment For Simple Premises
Fire Risk Assessment For Simple Premises Responsible Person (Employer or other person having control of the relevant premises) Company / Premises Name Address of Premises Postcode Primary Use of Premises
St. John s University
St. John s University Fire Safety Plan Founder s Village Townhouses Page 1 St. John s University Fire Safety Plan Part 1-Building Information Section Founder s Village Townhouses 8000 Utopia Parkway Jamaica
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 24.00: FIRE WARNING SYSTEMS INSTALLED IN BUILDINGS WITHIN THE COMMONWEALTH OF MASSACHUSETTS Section 24.01: Purpose 24.02: Scope 24.03: Definitions 24.04: Approval of Design 24.05: Power Supply
Fire Safety Risk Assessment
1 Sources of ignition The main sources of ignition in Cass building are: PAF arrange for the fixed electrical installation to be tested in accordance with the British Standards. Test certificates are kept
RESIDENTS FIRE SAFETY INFORMATION PACK
RESIDENTS FIRE SAFETY INFORMATION PACK CASTLEMEAD CAMBERWELL ROAD LONDON SE5 THE CONTENTS OF YOUR PACK Section Page No. 1. 3. Introduction Here we will explain the purpose of the Fire Safety Information
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY
CITY OF LONDON SCHOOL FOR GIRLS FIRE SAFETY, PROCEDURE AND RISK ASSESSMENT POLICY This policy was written in July 2014 and will be agreed by the Board of Governors in October 2014. To be reviewed by June
527 CMR: BOARD OF FIRE PREVENTION REGULATIONS
527 CMR 31.00: CARBON MONOXIDE ALARMS Section 31.01: Purpose and Scope 31.02: Definitions 31.03: General Installation Provisions 31.04: Specific Installation Provisions 31.05: Carbon Monoxide Protection:
Action required (Please tick) If you answered YES, record Action Points at STEP 4
RECORD OF FIRE SAFETY RISK ASSESSMENT Building Name & Use: Address: Postcode: Name of person(s) with fire safety duties: Name and contact details of assessor: Date of Assessment: 6 th February 2011 Laurel
Fire Safety Management Strategy 2015-2018
Fire Safety Management Strategy 2015-2018 Introduction This strategy is a plan and method of approach to how Medway Council Housing Services (the council) will both continue to meet our statutory obligations
FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT This template has been provided to assist the Responsible Person with the preparation of a Fire Risk Assessment and is not intended for commercial
UPP Residential Services Fire Risk Assessment
UPP Residential Services Fire Risk Assessment TS11151-R02-DRAFT1 15 August 2011 for: Keynes College University Road Canterbury Kent Recommended latest review date 14 August 2011 Executive summary This
FIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS
1 FIRE ALARMS IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per annum, according to BS 5839-6: 2004.
DOMESTIC SMOKE ALARMS
SOUTH AUSTRALIAN METROPOLITAN FIRE SERVICE HOME FIRE SAFETY INFORMATION For further advice contact the Community Safety Department South Australian Metropolitan Fire Service on 8204 3611 DOMESTIC SMOKE
ELECTRONIC FIRE & SECURITY SYSTEMS. Smoke Alarms, Fire Detection and Alarm Systems in Dwellings
ELECTRONIC FIRE & The FS Short Guide Series Smoke larms, Fire Detection and larm Systems in Dwellings n Introduction to BS 5839-6:2004 and the associated legislative framework SECURITY SYSTEMS Supporting
SMOKE ALARMS CLASS 1A BUILDINGS
SMOKE ALARMS CLASS 1A BUILDINGS A smoke alarm is a device that combines both smoke detection and alarm facilities into a single unit. Smoke alarms are required to be installed in all new residential Class
Fire Evacuation Procedures Network Building, 97 Tottenham Court Road, London, W1
Network Building Fire Safety Management Plan & Fire Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting
Minimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS 5839-1. Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety.
Management Checklist 1. Fire Safety Policy and Responsibilities. Consult the Employer s Fire Safety Policy and establish responsibilities of staff for fire safety. 2. Fire Hazard and Risk Assessment. Use
Landlord/Agent Code of Conduct
Landlord/Agent Code of Conduct Commitment to this is a requirement of the Home Stamp accreditation scheme The Home Stamp Code of Conduct aims to provide guidance and advice regarding the management of
HOUSING FIRE SAFETY. Guidance on fire safety provisions for certain types of existing housing
HOUSING FIRE SAFETY Guidance on fire safety provisions for certain types of existing housing Foreword by Communities and Local Government ministers Fire safety within the home is an extremely important
Lee Baron FIRE RISK ASSESSMENT
FIRE RISK ASSESSMENT, 13/21 Cantelupe Road, East Grinstead Prepared for: Lee Baron 7 Swallow Place Oxford Circus London W1B 2AG Prepared by: Violet McIntyre CMIOSH William Martin Compliance Solutions Limited
Proposed Residential Complex At Holding No. - 98, B.T. Road, Kolkata - 700090 Developer Premier Mica Mining And Manufacturing Company
RISK MANAGEMENT PLAN is an integral part of a modernized and sophisticated residential complex. No efforts will be spared in identifying the all possible risks and disasters, evaluating them, installing
CERTIFICATE OF COMPLIANCE
CERTIFICATE OF COMPLIANCE (Smoke Detector Inspection) Smoke detectors and carbon monoxide detectors must be in the proper locations and operational. Your house must also be properly numbered in order to
FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005
FIRE SAFETY GUIDANCE NOTE Regulatory Reform (Fire Safety) Order 2005 Number: GN66 This Guidance Note provides advice on the requirements of the Regulatory Reform (Fire Safety) Order 2005 and how to complete
section one guide to design, installation,commissioning and maintenance of fire systems in non domestic premises Consultant s Guide
section one Consultant s Guide section one section one contents About this manual Purpose Readership Electronic Format Acknowledgments 1 3 4 4 Section One: Guide to Design of Fire Systems 1. 1.1 1.1.1
Frequently Asked Questions Mains Powered Smoke, Heat and RF Alarms
Mains Powered Smoke, Heat and RF Alarms Aico Ltd, Mile End Business Park, Maesbury Road, Oswestry, Shropshire SY10 8NN Tel: 0870 758 4000 Fax: 0870 758 4010 e-mail: [email protected] www.aico.co.uk
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition
Compliance Document for New Zealand Building Code Clause F7 Warning Systems Fourth Edition Prepared by the Department of Building and Housing This Compliance Document is prepared by the Department of Building