SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS INSTALLATION INSTRUCTIONS

Size: px
Start display at page:

Download "SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS INSTALLATION INSTRUCTIONS"

Transcription

1 SEL-ONTAINED PAKAE AI ONDITIONES AND HEAT PUMP UNITS INSTALLATION INSTUTIONS ATTENTION INSTALLATION PESONNEL Prior to installation, thoroughly familiarize yourself with this instruction manual. Observe all safety warnings. During installation or repair, caution is to be observed. It is your responsibility to install the product safely and to educate the customer on its safe use. Placeholder for arode Keep this literature in a safe place for future reference. These installation instructions cover the outdoor installation of self-contained package air conditioner and heating units. See the Specification Sheets applicable to your model for information regarding accessories. NOTE: Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual. hirlpool old Models PHM, PM PIO-95 Tradewinds Distributing ompany, LL reakers Drive Jacksonville, lorida 58

2 SAET INSTUTIONS... TO THE INSTALLE... IMPOTANT NOTE TO THE ONE EADIN PODUT AANT... SHIPPIN INSPETION... EPLAEMENT PATS... ODES AND EULATIONS... EPA egulations... National odes... MAJO OMPONENTS... PEINSTALLATION HEKS... learances and Accessibility... Unit Location... round Level Preinstallation Details... ooftop Preinstallation Details... oof urb Installations Only...5 igging Details...5 IULATIN AI AND ILTES...5 Airflow onversion...5 Ductwork... ilters... PIPIN... onnect ondensate Drain... IIN...7 High Voltage iring...7 Low Voltage iring...7 Internal iring...7 STAT-UP, ADJUSTMENTS AND HEKS...8 Start-up Procedure and hecklist ooling ycle...8 Start-up Procedure Heat Pump...8 inal System hecks...8 TALE O ONTENTS SAET INSTUTIONS OMPONENTS...9 ontactor...9 rankcase Heater...9 ondenser Motor...9 ompressor...9 ontactor elay...9 Defrost ontrol...9 Outdoor Thermostat...9 eversing Valve oil...9 Indoor lower Motor...9 lower Interlock elay Single-Phase PS Models Only...9 HEAT PUMP OPEATION...9 ooling ycle...9 Heating ycle...9 Defrost ontrol... SUESTED IELD TESTIN/TOULESHOOTIN... AILO MEASUEMENT AND ADJUSTMENT... Speed Tap Adjustments for Indoor lower Motor... LOE PEOMANE DATA... efrigerant harge hecks... ELETIAL ADJUSTMENTS... SSTEM MAINTENANE... Service... TOULESHOOTIN HAT...5 APPENDIX... iring Diagram PAM... iring Diagram P(8-)AM...7 iring Diagram PH( - )AM...8 iring Diagram PH(8, )AM...9 Product Dimensions... ASSISTANE O SEVIE... The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner s and installer s responsibility to read and comply with all safety information and instructions accompanying these symbols. ailure to heed safety information increases the risk of personal injury, property damage and/or product damage. ecognize this symbol as a safety precaution. ANIN Hazards or unsafe oodman practices could result in property damage, product damage, severe personal injury or death. AUTION Hazards or unsafe practices may result in property damage, product damage, personal injury or death. ANIN Do not connect to or use any device that is not designcertified for use with this oodman unit. Serious property damage, personal injury, reduced unit performance and/or hazardous conditions may result from the use of such non-approved devices. ANIN HIH VOLTAE! Disconnect ALL power before servicing. oodman Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. ANIN onnecting unit ductwork oodman to unauthorized 98 heat producing devices such as a fireplace insert, stove, etc., may result in property damage, fire, carbon monoxide poisoning, explosion, personal injury or death.

3 ANIN This product contains oodman or produces a 5 chemical or chemicals which may cause serious illness or death and which are known to the State of alifornia to cause cancer, birth defects or other reproductive harm. ANIN To avoid property damage, personal injury or death, do not use this furnace if any part of the furnace has been under water. Immediately call a qualified service technician to inspect the furnace and to replace any part of the control system and any gas control having been under oodman 8 water. ANIN This unit must not be used as a construction heater during the finishing phases of construction on a new oodman 79 structure. This type of use may result in premature failure of the unit due to extremely low return air temperatures and exposure to corrosive or very dirty atmospheres. ANIN To prevent the risk of property damage, personal injury, or death, do not store combustible materials or use gasoline or other flammable liquids or vapors in the vicinity of this unit. ANIN Installation and repair of this unit should be performed ONL by individuals meeting the requirements of an Entry Level Technician, at a minimum, as specified by the Air-onditioning, Heating and efrigeration Institute (AHI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death. TO THE INSTALLE arefully read all instructions for the installation prior to installing unit. Make sure each step or procedure is understood and any special considerations are taken into account before starting installation. Assemble all tools, hardware and supplies needed to complete the installation. Some items may need to be purchased locally. After deciding where to install unit, closely look over the location both the inside and outside of the home. Note any potential obstacles or problems that might be encountered as noted in this manual. hoose a more suitable location if necessary. IMPOTANT NOTE: If a crankcase heater is used, the unit should be energized hours prior to compressor start-up to ensure the crankcase heater has sufficiently warmed the compressor. ompressor damage may occur if this step is not followed. IMPOTANT NOTE TO THE ONE EADIN PODUT AANT our warranty certificate is supplied as a separate document with the unit installed by your contractor. ead the limited warranty certificate carefully to determine what is and is not covered. Keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate, please contact your installing contractor, or contact customer service at to obtain a copy. To receive the -ear Parts Limited arranty, online registration must be completed within days of installation. Online registration is not required in alifornia or Quebec. ull warranty details and instructions are available at To register your unit, go to lick on the manufacturer s omfort ommitment TM arranty link located at the bottom center of the home page. Next, click on the lick Here to egister our Product link located at the top center of the page, and complete the forms in the manner indicated. SHIPPIN INSPETION Upon receiving the unit, inspect it for damage from shipment. laims for damage, either shipping or concealed, should be filed immediately with the shipping company. heck the unit model number, specifications, electrical characteristics and accessories to determine if they are correct. In the event an incorrect unit is shipped, it must be returned to the supplier and must not be installed. The manufacturer assumes no responsibility for installation of incorrectly shipped units. EPLAEMENT PATS hen reporting shortages or damages, or ordering repair parts, give the complete product model and serial numbers as stamped on the product. eplacement parts for this product are available through your contractor or local distributor. or the location of your nearest distributor, consult the white business pages, the yellow page section of the local telephone book or contact: Tradewinds Distributing ompany, LL reakers Drive Jacksonville, lorida If you are replacing an air handler, the system must be manufacturer-approved and Air-onditioning, Heating, and efrigeration Institute (AHI) matched. NOTE: Installation of unmatched systems is strongly discouraged. ODES AND EULATIONS The P/PH M-series air conditioners and heat pumps are designed for outdoor use only. PH M-Series is available in cooling capacities of, ¹ ₂,, ¹ ₂, and 5 nominal tons of cooling. P M-Series is available in cooling capacities of, and 5 nominal tons of cooling. Optional field-installed heat kits are available in 5, 8,, 5 and k. The units can be easily installed in manufactured or modular homes with existing highstatic ductwork. The units can also be easily converted to accommodate a plenum for normal or low-static applications.

4 The P/PH M-series are self-contained packaged units so the only connections needed for installation are the supply and return ducts, the line and low voltage wiring and drain connection. The units are ETL listed and AHI certified. The information on the rating plate is in compliance with the T and DOE rating for single-phase units. The efficiency ratings of these units are a product of thermal efficiency determined under continuous operating conditions independent of any installed system. EPA egulations IMPOTANT: The United States environmental protection agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants in this unit. ailure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. ecause regulations may vary due to passage of new laws, we suggest a certified technician perform any work done on this unit. Should you have any questions, please contact the local office of the EPA. National odes This product is designed and manufactured to permit installation in accordance with National odes. It is the installer s responsibility to install the product in accordance with National odes and/or prevailing local codes and regulations. MAJO OMPONENTS The unit includes a hermetically sealed refrigerating system (consisting of a compressor, condenser coil, evaporator coil with flowrator), an indoor blower, a condenser fan and all necessary internal electrical wiring. The heat pump also includes a reversing valve, solenoid, defrost thermostat and control and loss of charge protection. The system is factory-evacuated, charged and performance tested. efrigerant amount and type are indicated on rating plate. PEINSTALLATION HEKS efore attempting any installation, the following points should be considered: Structural strength of supporting members learances and provision for servicing Power supply and wiring Air duct connections Drain facilities and connections Location may be on any sides of a home, manufactured or modular, to minimize noise. learances and Accessibility The unit is designed to be located outside the building with unobstructed condenser air inlet and discharge. Additionally, the unit must be situated to permit access for service and installation. ondenser air enters from sides. Air discharges upward from the top of the unit. efrigerant gauge connections are made on the right side of the unit as you face the compressor compartment. Electrical connections can be made either on the right, bottom or duct panel side of the unit. The best and most common application is for the unit to be located " (5. cm) from the wall (" [. cm]) minimum) with the connection side facing the wall. lose to the wall application minimizes exposed wiring. lose to the wall application assures free, unobstructed air to the other sides. In more confined application spaces, such as corners, provide a minimum " (.5 cm) clearance on all air inlet sides. Allow " (9. cm) minimum for service access to the compressor compartment and controls. The top of the unit should be completely unobstructed. If units are to be located under an overhang, there should be a minimum of 8" (.9 cm) clearance and provisions made to deflect the warm discharge air out from the overhang. Unit Location onsider the affect of outdoor fan noise on conditioned space and any adjacent occupied space. It is recommended that the unit be placed so that the condenser air discharge does not blow toward windows less than 5 ft (7. m) away. onsideration should also be given to shade and unit appearance. Heat pumps require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have holes under the outdoor coil to permit drainage of defrost water accumulation. The unit must be situated to permit free unobstructed drainage of the defrost water and ice. A minimum " (5 cm) clearance under the outdoor coil is required in the milder climates. round Level Preinstallation Details The unit should be set on a solid, level foundation preferably a concrete slab at least " (. cm) thick. The slab should be above ground level and surrounded by a graveled area for good drainage. Any slab used as a unit s foundation should not adjoin the building as it is possible that sound and vibration may be transmitted to the structure. round Level Installation A A. 8" (.9 m) minimum. " (.5 cm) minimum. " (9. cm) minimum service clearance D. " (. cm) minimum ooftop Preinstallation Details Ensure that the roof is weather tight and allows proper drainage of condensation. Use steel or treated wood beams as unit support for load distribution. NOTE: To ensure proper condensate drainage, unit must be installed in a level position. D

5 To avoid possible property damage or personal injury, the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. onsult a structural engineer to determine the weight capabilities of the roof. The unit may be installed directly on wood floors or on lass A, lass or lass roof covering material. To avoid possible personal injury, a safe, flat surface for service personnel should be provided. ooftop Installation igging Details ANIN To prevent property damage, the unit should remain in an upright position during all rigging and moving operations. To facilitate lifting and moving when a crane is used, place the unit in an adequate cable sling. ANIN To prevent property damage, personal injury or death, ensure the roof has sufficient structural strength to carry the weight of the unit(s), roof curb, snow loads and water loads as required by local codes. onsult a structural engineer to determine the weight capabilities of the roof. AUTION To avoid possible personal injury, a safe, flat surface for service personnel should be provided. oof urb Installations Only NOTE: Sufficient structural support must be determined prior to locating and mounting the curb and package unit. urb insulation, cant strips, flashing and general roofing material are furnished by the contractor. urbing must be installed in compliance with the National oofing ontractors Association Manual. onstruct ductwork using current industry guidelines. The ductwork must be placed into the roof curb before mounting the package unit. IMPOTANT: If you are using bottom discharge with roof curb, ductwork should be attached to the curb prior to installing the unit. Lower unit carefully onto roof mounting curb. hile rigging unit, center of gravity will cause condenser end to be lower than supply air end. igging oof urb Installation IULATIN AI AND ILTES Airflow onversion Units can easily be converted from horizontal to down-discharge airflow delivery. In down-discharge or high-static installations, the installer should measure the total external static and review the blower performance charts before performing the installation. In some installations, it will be necessary to change the blower speed to provide proper airflow. 5

6 Duct over Installations Down-Discharge emove the panels for down-discharge duct applications. A. Supply air panel. eturn air panel Down-Discharge Applications ut insulation around bottom openings and remove panels from the bottom of the unit, saving the screws holding the panels in place. NOTE: Down-discharge models require installation of horizontal duct kit Number 5PDK (medium chassis) and Number 5PDK (large chassis). Ductwork Duct systems and register sizes must be properly designed for the..m. and external static pressure rating of the unit. Ductwork should be designed in accordance with the recommended methods of Air onditioning ontractors of America Manual D (esidential) or Manual Q (ommercial). All ductwork exposed to the outdoors must include a weatherproof barrier and adequate insulation. A duct system should be installed in accordance with Standards of the National oard of ire Underwriters for the Installation of Air onditioning, arm Air Heating and Ventilating Systems. Pamphlets Number 9A and 9. The supply duct from the unit through a wall may be installed without clearance. However, minimum unit clearances must be maintained. The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger. A cover should be tightly attached to prevent air leaks. or duct flange dimensions on the unit, refer to the Unit Dimension illustration in the appendix. or down-discharge applications, the ductwork should be attached to the roof curb prior to installing the unit. Ductwork dimensions are shown in the roof curb installation manual. If desired, supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmission. ilters A An optional factory-approved internal filter rack may also be used. A field-installed filter grille is recommended for easy and convenient access to the filters for periodic inspection and cleaning. hen installing filters, ensure the airflow arrows on the filter are pointing toward the circulator blower. efer to the following unit filter size chart for filter size information. Minimum ilter Size Nominal Size in. (cm) Nominal Area sq ft (cm ) x (5. x 5.8). (,) x (5. x 5.8).9 (,75) x 5 (5. x.5). (,) 5 x (8. x 5.8). (,95) x (. x 5.8). (,) x 5 (. x.5).8 (,) x (5.8 x 5.8).8 (,) x 5 (5.8 x.5).5 (,5) 5 x 5 (.5 x.5). (,995) NOTE: ilters must have adequate face area for the rated quantity of the unit. See the Air Delivery Table for the recommended filter size. Size the filters in accordance with their manufacturer recommendations. Throwaway filters must be sized for a maximum face velocity of ft per minute. Air Delivery Table Nominal ilter Area sq ft (cm ) 7 (,5) (5,57) 5 (,5) (,7) (,787) (,858) 5,,5,,5,,5 Airflow - SM PIPIN onnect ondensate Drain The condensate drain connection of the evaporator is a half coupling of ³ ₄" N.P.T. A trap must be provided to have proper condensate drainage. ondensate Drain onnection A Disposable ilter Permanent ilter AUTION To prevent property damage due to fire and loss of equipment efficiency or equipment damage due to dust and lint build up on internal parts, never operate unit without an air filter installed in the return air system. ilters are not provided with unit and must be supplied and externally installed in the return duct system by the installer. E D A. Drain connection. " (5. cm) minimum. " (7. cm) minimum D. Positive liquid seal (required) E. lexible tubing, hose or pipe. Unit

7 Install the condensate drain trap as shown. Use a ³ ₄" (.9 cm) NPT drain connection size or larger. Do not operate without a trap. Unit must be level or slightly inclined toward drain. IIN NOTE: All wiring should be made in accordance with the National Electrical ode (N.E.). onsult your local power company to determine the availability of sufficient power to operate the unit. heck the voltage, frequency and phase at the power supply to ensure it corresponds to the unit s rated voltage requirement. In accordance with the N.E.. or local codes, install a branch circuit fused disconnect near the unit. Determine wire sizes and overcurrent protection from the unit nameplate ampacity and in accordance with ranch ircuit Ampacity chart or the N.E.. The wiring should never be sized smaller than is recommended by either of these sources. uses smaller than that recommended on the rating plate could result in unnecessary fuse failure or service calls. The use of protective devices of larger size than indicated could result in extensive damage to the equipment. The manufacturer bears no responsibility for damage caused to equipment as result of the use of larger than is recommended size protective devices. All units have undergone a run test prior to packaging for shipment. This equipment has been started at minimum rated voltage and checked for satisfactory operation. IMPOTANT: Do not attempt to operate this unit if the voltage is not within the minimum and maximum voltages shown on nameplate. All exterior wiring must be within approved weatherproof conduit. The unit must be permanently grounded in accordance with local codes, or in absence of local codes, with N.E.. ANSI/ NPA Number 7-98 or latest edition by using ground lug in the control box. uses or HA type circuit breakers may be used where codes permit. T T T or Internal iring, See iring Label Attached To Unit ontactor L L L High Voltage Disconnect Switch High Voltage Power iring -Volt ontrol iring Low Voltage onnectors NOTE: Low voltage connectors do not apply to heat pumps with electric heat. Low voltage connectors apply only to P units with electric heat. IMPOTANT: Some single-phase units are equipped with a single-pole contactor. Exercise caution when servicing as only one leg of the power supply is broken with the contactor. ool an ommon Heat *See Note. Thermostat Subbase To wire the unit, make the following high- and low-voltage connections. High Voltage iring Single Phase leads should be connected to terminals L and L in the electrical control section, using wire sizes specified in the wiring diagram. -Phase leads should be connected to terminals L, L and L in the electrical control section, using wire sizes specified in the wiring diagram. Lead Low Voltage iring Air onditioners onnect V wires from the thermostat to the corresponding wires in the control box using Number 8 A as follows: ed reen ellow hite rown ANIN To avoid the risk of fire or equipment damage, use copper conductors. ANIN HIH VOLTAE! oodman Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. Thermostat (V) (an) (ool) (Heat)* (Heat)* *Optional field installed heat connections Heat pumps onnect V wires from the thermostat to the corresponding wires in the control box using Number 8 A as follows: Lead Thermostat ed (V) reen (an) Orange O (ev. Valve) hite (Heat, nd )* rown (Heat, rd )* ellow (ool) lue (V ommon) *Optional field installed heat connections Internal iring A diagram detailing the internal wiring of this unit is located on the electrical box cover. If any of the original wire supplied with the appliance must be replaced, the wire gauge and insulation must be the same as the original wiring. 7

8 Transformer is wired for volts on the 8/ models. See the wiring diagram for 8-volt wiring. or branch circuit wiring (main power supply to unit disconnect), the minimum wire size for the length of run can be determined using the circuit ampacity found on the unit rating plate and the following ranch ircuit Ampacity chart. rom the unit disconnect to unit, the smallest wire size allowable may be used for the ampacity, as the Disconnect must be in sight of the unit. oute the field supply wires through the line voltage conduit opening to the electrical connection area, providing sufficient length to connect to the pigtail leads. ranch ircuit Ampacity Supply ire Length ft (m) () 5 (5.7) 8 (.5) (5.) 8 8 ire size based on rated wire insulation and ambient temperature (8 [º]). or more than conductors in a raceway or cable, see the N.E.. for derating the ampacity of each conductor. STAT-UP, ADJUSTMENTS AND HEKS Start-up Procedure and hecklist ooling ycle ANIN oodman HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death.. Disconnect power at all disconnects.. Turn the thermostat system switch to OOL and the fan switch to AUTO.. Turn the temperature setting to the highest setting.. Inspect all of the registers and set them to the normal open position. 5. Turn on the electrical supply at the disconnect.. Turn the fan switch to the ON position. The blower should operate after a 7-second delay. 7. Turn the fan switch to the AUTO position. The blower should stop after a 5-second delay. 8. Slowly lower the cooling temperature until the unit starts. The compressor, blower and fan should now be operating. 9. Allow the unit to run for minutes. Make sure that cool air is being supplied by the unit.. Turn the temperature setting to the highest position, stopping the unit. The indoor blower will continue to run for 5 seconds.. Turn the thermostat system switch to O and disconnect all power when servicing the unit. Start-up Procedure Heat Pump. heck that the cooling mode for the heat pump is working properly according to the procedure listed in the Start-up Procedure and hecklist ooling ycle section. The reversing valve is energized when the thermostat is placed in the cooling position. A clicking sound should be noticeable from the reversing valve. y lowering the temperature setting to call for cooling, the contactor is energized. The compressor, blower and fan should then be running.. After the cooling mode is checked out, turn the thermostat system switch to O.. Turn the thermostat switch to HEAT and the fan switch to AUTO.. Slowly raise the heating temperature setting. hen the heating st stage makes contact, stop raising the temperature setting. The compressor, blower and fan should now be running with the reversing valve in the de-energized (heating) position. 5. After giving the unit time to settle out, make sure that the unit is supplying heated air.. If the outdoor ambient is above 8 (.7º), the unit may trip on its high pressure cutout when on heating. The compressor should stop. IMPOTANT: The heating cycle must be thoroughly checked, so postpone the test to another day when conditions are more suitable. Do not fail to test the unit. 7. If the outdoor ambient is low and the unit operates properly on the heating cycle, you may check the pressure cutout operation by blocking off the indoor return air until the unit trips. 8. If the unit operates properly in the heating cycle, raise the temperature setting until the heating nd stage makes contact. Supplemental resistance heat, if installed, should now turn on. Make sure that the supplemental resistant heat operates properly. NOTE: If outdoor thermostats are installed, the outdoor ambient temperature must be below the set point of these thermostats for the heaters to operate. It may be necessary to jumper these thermostats to check heater operation if outdoor ambient temperature is mild. 9. or thermostats with an emergency heat switch, return to Step 8. NOTE: The emergency heat switch is located at the bottom of the thermostat. Move the switch to emergency heat. The heat pump will stop, the blower will continue to run, all heaters will come on and the thermostat emergency heat light will turn on. All -phase models are single-stage heat only.. If checking the unit in the wintertime when the outdoor coil is cold enough to activate the defrost control, observe at least one defrost cycle to make sure the unit defrosts completely. inal System hecks. heck to see if all supply and return air grilles are adjusted and the air distribution system is balanced for the best compromise between heating and cooling.. heck for air leaks in the ductwork. See Airflow Measurement and Adjustment and hecking harge.. Make sure that the unit is free of rattles, and the tubing in the unit is free from excessive vibration.. Make sure that the tubes and lines are not rubbing against each other or against the sheet metal surfaces or edges. If contact is found, correct the trouble. 8

9 5. Set the thermostat at the appropriate setting for cooling and heating or automatic changeover for normal use.. heck that the owner is instructed on the unit operation, filter, servicing, correct thermostat operation, etc. 7. The previous sections are recommended to serve as an indication that the unit will operate normally. OMPONENTS ontactor This control is activated (closed) by the room thermostat for both heating and cooling. The contactor has a V coil and supplies power to the compressor and outdoor fan motor. rankcase Heater This item is ON whenever power is supplied to the unit and the crankcase heater thermostat is closed. The crankcase heater thermostat closes at 7º (9º) and opens at 85º (9º). It warms the compressor crankcase thereby preventing liquid migration and subsequent compressor damage. The insert type heater is self-regulating. It is connected electrically to the contactor L and L terminals. ondenser Motor This item is activated by the contactor during heating and cooling, except during defrost and emergency heat operation. ompressor This item is activated by the contactor for heating and cooling, except during emergency heat. It is protected by an internal overload. ontactor elay This control is activated by the thermostat (V coil) and supplies power to the contactor. Defrost ontrol The Defrost control provides time/temperature initiation and termination of the defrost cycle. hen a defrost cycle is initiated, the defrost control shifts the reversing valve to ooling mode, stops the outdoor fan and brings on supplemental heat. Normally, a defrost cycle will take only to minutes unless the system is low on refrigerant charge or outdoor conditions are severe (windy and cold). The defrost control also provides for a -minute off-cycle compressor delay. Outdoor Thermostat These optional controls are used to prevent full electric heater operation at varying outdoor ambient ( to 5 [-8º to 7º]). They are normally open above their set points and closed below to permit staging of the indoor supplement heater operation. If the outdoor ambient temperature is below (-8 ) with 5% or higher relative humidity (H), an outdoor thermostat (OT) must be installed and set at ( ) on the dial. ailure to comply with this requirement may result in damage to the product which may not be covered by the manufacturer s warranty. eversing Valve oil This coil is activated by the thermostat, in the cooling mode and during defrost. It positions the reversing valve pilot valve for cooling operation. Indoor lower Motor This is activated by setting the room thermostat to OOLIN or AN ON position. The motor is energized through the ETD for PS motors and directly by the room thermostat for X- motors ( or 5 Ton units). X- motors are constant torque motors with very low power consumption. This motor is energized by a V signal from the thermostat. See Airflow Measurement and Adjustment for speed adjustment instructions. lower Interlock elay Single-Phase PS Models Only This relay is used to energize the blower during the electric heat operation. Some room thermostats do not energize the motor during electric heat. This relay ensures blower operation when the room thermostat energizes heat. This relay has a -volt coil and an 8-amp contact relay. This relay is energized by the electric heat kit sequencer. HEAT PUMP OPEATION ooling ycle hen the heat pump is in the cooling cycle, it operates exactly as a summer air conditioner unit. In this mode, all the charts and data for service that apply to summer air conditioning apply to the heat pump. Most apply on the heating cycle except that the condenser becomes the evaporator, the evaporator becomes the condenser and cooling becomes heating. Heating ycle The heat pump operates in the heating cycle by redirecting refrigerant flow through the refrigerant circuit external to the compressor. This is accomplished through the reversing valve. Hot discharge vapor from the compressor is directed to the indoor coil (evaporator on the cooling cycle) where the heat is removed, and the vapor condenses to liquid. It then goes through the expansion device to the outdoor coil (condenser on the cooling cycle) where the liquid is evaporated, and the vapor goes to the compressor. hen the solenoid valve coil is operated either from heating to cooling or vice versa, the piston in the reversing valve to the low pressure (high pressure) reverse positions in the reversing valve. The following illustrations show a schematic of a heat pump on the cooling cycle and the heating cycle. In addition to a reversing valve, a heat pump is equipped with an expansion device and check valve for the indoor coil, and similar equipment for the outdoor coil. It is also provided with a defrost control system. 9

10 ooling ycle D At the same time, the outdoor fan stops to hasten the temperature rise of the outdoor coil and lessen the time required for defrosting. The indoor blower continues to run and the supplementary heaters are energized. A H A. Indoor coil. Service valves. Service ports Heating ycle I D. eversing valve E. Outdoor coil. Accumulator I H E. ompressor H. Distributors I. heck valve orifices. Defrost ontrol During operation, the power to the circuit board is controlled by a temperature sensor, which is clamped to a feeder tube entering the outdoor coil. Defrost timing periods of, and 9 minutes may be selected by setting the circuit board jumper to, and 9 respectively. Accumulation of time for the timing period selected starts when the sensor closes (approximately [5º]), and when the wall thermostat calls for heat. At the end of the timing period, the unit s defrost cycle will be initiated provided the sensor remains closed. hen the sensor opens (approximately [º]), the defrost cycle is terminated and the timing period is reset. If the defrost cycle is not terminated due to the sensor temperature, a -minute override interrupts the unit s defrost period. ircuit oard D H H A I I E A. Indoor coil. Service valves. Service ports D. eversing valve E. Outdoor coil. Accumulator. ompressor H. Distributors I. heck valve orifices. The expansion devices are flowrator distributors and perform the same function on the heating cycle as on the cooling cycle. The flowrator distributors also act as check valves to allow for the reverse of refrigerant flow. hen the heat pump is on the heating cycle, the outdoor coil is functioning as an evaporator. The temperature of the refrigerant in the outdoor coil must be below the temperature of the outdoor air in order to extract heat from the air. Thus, the greater the difference in the outdoor temperature and the outdoor coil temperature, the greater the heating capacity of the heat pump. This phenomenon is a characteristic of a heat pump. It is a good practice to provide supplementary heat for all heat pump installations in areas where the temperature drops below 5 (7º). It is also a good practice to provide sufficient supplementary heat to handle the entire heating requirement should there be a component failure of the heat pump, such as a compressor, or refrigerant leak, etc. Since the temperature of the refrigerant in the outdoor coil on the heating cycle is generally below the freezing point, frost forms on the surfaces of the outdoor coil under certain weather conditions related to temperature and relative humidity. Therefore, it is necessary to reverse the flow of the refrigerant to provide hot gas in the outdoor coil to melt the frost accumulation. This is accomplished by reversing the heat pump to the cooling cycle. SUESTED IELD TESTIN/ TOULESHOOTIN. un the unit in the heating mode (room thermostat calling for heat).. heck the unit for proper charge. NOTE: ands of frost on the condenser coil indicate low refrigerant charge.. Turn off power to the unit.. Disconnect the outdoor fan by removing the purple lead from D on the defrost control. 5. estart the unit and allow frost to accumulate.

11 . After a few minutes of operation, the defrost thermostat should close. To verify this, check for volts between DT and on the control board. If the temperature at the thermostat is less than 8 (-º) and the thermostat is open, replace the defrost thermostat, since it is defective. 7. hen the unit s defrost thermostat has closed, short the test pins on the circuit board until the reversing valve shifts, indicating defrost. This should take up to seconds depending on what timing period the control is set. NOTE: After defrost initiation, the short must instantly be removed, or the unit s defrost period will last only. seconds. 8. After the unit s defrost thermostat has terminated, check the defrost thermostat for volts between DT and. The reading should indicate volts (open sensor). 9. Turn off power to the unit.. eplace the outdoor fan motor lead to terminal D on the circuit board and turn on power. AILO MEASUEMENT AND ADJUSTMENT After reviewing the Ductwork section in irculating Air and ilters, proceed with the airflow measurements and adjustments. The unit blower curves (see Specification Sheets) are based on the external static pressure (ESP per in./..). The duct openings on the unit are considered internal static pressure. As long as ESP is maintained, the unit will deliver the proper air up to the maximum static pressure listed for the M required by the application (for example, home, building, etc.). In general, M per ton of cooling capacity is a rule of thumb. Some applications depending on the sensible and latent capacity requirements may need only 5 M or up to 5 M per ton. heck condition space load requirements (from load calculations) and equipment expanded ratings data to match M and capacity. After the unit is set and the ductwork completed, verify the ESP with a " (.5 cm) inclined manometer with pitot tubes or a Magnahelic gauge and confirm M to blower curves in the Specification Sheets. All units have -speed blower motors. If the low speed is not utilized, the speed tap can be changed to medium or high speed. NOTE: Never run M below 5 M per ton. Evaporator freezing or poor unit performance is possible. Speed Tap Adjustments for Indoor lower Motor PS Motor Adjust the M by changing the speed tap of the indoor blower motor at the ETD OM connection with one of the speed taps on M or M. (lack High Speed, lue Medium Speed, ed Low Speed.) X- Motor LOE PEOMANE DATA Adjust the M by changing the V low-voltage lead at the speed terminal block on the motor (T Low Speed, T and T Medium Speed, T and T5 High Speed). E.S.P. (In. of H O) Model Speed Volts PAM Low M,,78, atts Med M,87,,,9,9, atts High M,5,5,88,,,,55 99 atts P8AM T () M,,95,,,5,5,9, atts T/T M,795,75,75,95,5,,5,75 atts T/T5 M,8,8,785,75,7,5,55,95 atts PAM T () M,755,7,85,5,5,57,5,5 atts T/T M,85,8,775,75,75,75,,95 atts T/T5 M,8,5,5,975,875,8,55,5 atts

12 E.S.P. (In. of H O) Model Speed Volts PHAM T () M atts T/T M atts T/T5 M,,8,, atts PHAM T () M,97,59, atts T/T M,5,,8,97, atts T/T5 M,8,8,,58,9,,8 8 atts PHAM Low M,,78, atts Med M,87,,,9,9, atts High M,5,5,88,,,,55 99 atts HIH M,55,5,5,,,5,5 885 atts PHAM Low M,,78, atts Med M,87,,,9,9, atts High M,5,5,88,,,,55 99 atts PH8AM T() M,,95,,,5,5,9, atts T/T () M,795,75,75,95,5,,5,75 atts T/T5 () M,8,8,785,75,7,5,55,95 atts PHAM T () M,755,7,85,5,5,57,5,5 atts T/T () M,85,8,775,75,75,75,,95 atts T/T5 () M,8,5,5,975,875,8,55,5 atts NOTES: Data shown is dry coil. et coil pressure drop is approximately." H for -row indoor coil,." H for -row indoor coil; and." H for -row indoor coil. Data shown does not include filter pressure drop, approximately.8" H O. All models should run no less than 5 M/Ton. educe airflow by % for 8-volt operation.

13 efrigerant harge hecks After completing airflow measurements and adjustments, the unit s refrigerant charge must be checked. The unit is factory charged based on M per ton at minimum ESP per AHI test conditions (generally between.5 and.5 ESP). hen air quantity or ESP differs from this, charge must be readjusted to the proper amount. All package units are charged to the superheat method at the compressor suction line (these are fixed orifice devices). or charging in the warmer months, 8º +/-º superheat at the compressor is required at conditions: 95º (5º) outdoor ambient (dry bulb temperature), 8º (7º) dry bulb / 7º (9º) wet bulb indoor ambient, approximately 5% humidity. This superheat varies when conditions vary from the conditions described. A superheat charge chart is available for other operating conditions. Use it to provide the correct superheat at the conditions the unit is being charged at. After superheat is adjusted it is recommended to check unit subcooling at the condenser coil liquid line out. In most operating conditions º to 5º of subcooling is adequate. Determine Superheat. ead suction pressure.. Determine Saturated Suction Temperature from tables or pressure gauge saturated temperature scale (-A).. ead suction line temperature.. Use the following formula to determine Superheat. Superheat = Suction Line Temperature - Saturated Suction Temperature Saturated Suction Pressure Temperature hart Suction Pressure Saturated Suction Temperature º PSI -A Saturated Suction Pressure Temperature hart Suction Pressure Saturated Suction Temperature º PSI -A Subcooling = Saturated Line Temperature - Liquid Line Temperature Saturated Liquid Pressure Temperature hart Liquid Pressure Saturated Liquid Temperature º PSI -A

14 Saturated Liquid Pressure Temperature hart Liquid Pressure Saturated Liquid Temperature º PSI -A ELETIAL ADJUSTMENTS This series of electric cooling and heat pump package equipment is designed to accept a field-installed electric heat kit. The unit is equipped to easily install the HK Series Electric Heat Kit. ull installation instructions are included in this kit. Please use this document for guidance in field equipping the package unit with electric heat. hoose the heat kit that fits the application for the specific installation. Permanently mark the unit s nameplate with the model being installed. High and low voltage connections are detailed in the heat kit instructions. Indoor blower motor speed tap selection may need to be modified to accommodate normal continuous operation to prevent a nuisance trip. See the following charts. Electric Heat K Unit Model Number PHAM M () M () M () H NA PHAM M () M () M () H NA P/PHAM H () H () NA PHAM H () H () NA P/PH8AM () () () () () P/PHAM () () () () () () actory setting Speed Taps Description: H/, 5 High; M/, Medium; L/ Low -Speed (H)igh/(M)edium/(L)ow: PS motor -speed (H)igh/(ML) Medium Low/(MH) Medium High/(L)ow: PS motor ////5: X- motor SSTEM MAINTENANE ANIN HIH VOLTAE! Disconnect ALL power before servicing. oodman Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. These few steps will help to keep the product up time to a maximum. The System Troubleshooting chart should help in identifying problems if the unit does not operate properly. Service NOTE: The following information is for use by qualified service agency only. Others should not attempt to service this equipment. ommon auses of Unsatisfactory Operation of Heat Pump on the Heating ycle. Inadequate Air Volume Through Indoor oil hen a heat pump is in the heating cycle, the indoor coil is functioning as a condenser. The return air filter must always be clean, and sufficient air volume must pass through the indoor coil to prevent excessive discharge pressure, and high pressure cutout. Outside Air Into eturn Duct Do not introduce cold outside air into the return duct of a heat pump installation. Do not allow air entering the indoor coil to drop below 5 (8º). Air below this temperature will cause low discharge pressure, thus low suction pressure, and excessive defrost cycling resulting in low heating output. It may also cause false defrosting. Undercharge An undercharged heat pump on the heating cycle will cause low discharge pressure resulting in low suction pressure and frost accumulation on the outdoor coil. Poor Terminating Sensor ontact The defrost terminating sensor must make good thermal contact with the outdoor coil tubing. Poor contact may not terminate the defrost cycle quickly enough to prevent the unit from cutting out on high discharge pressure. Malfunctioning eversing Valve This may be due to:. Solenoid not energized In order to determine if the solenoid is energized, touch the nut that holds the solenoid cover in place with a screwdriver. If the nut magnetically holds the screwdriver, the solenoid is energized and the unit is in the cooling cycle.. No voltage at the solenoid heck unit voltage. If no voltage, check wiring circuit.. Valve will not shift If the unit is undercharged, check for leaks. If valve body damaged, replace valve. If unit is properly charged, and it is on the heating cycle, raise the discharge pressure by restricting airflow through the indoor coil. If the valve does not shift, tap it lightly on both ends with a screwdriver handle. NOTE: Do not tap the valve body. If the unit is on the cooling cycle, raise the discharge pressure by restricting airflow through the outdoor coil. If the valve does not shift after the above attempts, turn off the unit and wait until the discharge and suction pressure equalize, and repeat above steps. If the valve does not shift, replace it. The self-contained package air conditioner or heat pump should operate for many years without excessive service calls if the unit is installed properly. However, it is recommended that the homeowner inspect the unit before a seasonal start-up. The coils should be free of debris, so adequate airflow is achieved. The return and supply registers should be free of any obstructions. The filters should be cleaned or replaced.

15 TOULESHOOTIN HAT ANIN HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. Symptom Possible ause emedy High head estriction in liquid line or flowrator emove or replace with proper size flowrator. low suction High head Dirty condenser coil lean coil. high or normal Overcharged orrect system charge. suction ondenser fan not running epair or replace condenser fan. Low head Incorrect flowrator eplace with correct flowrator. high suction Defective compressor valves eplace compressor. lowrator not seating properly heck for debris under flowrator or deformed flowrator. emove debris or replace flowrator. Unit will not Power off or loose electrical connection heck for unit voltage at contactor in unit. run. Thermostat out of calibration; set too eset thermostat. high heck for volts at contactor coil. eplace if contacts are open. Defective contactor eplace fuse or reset circuit breaker. heck wiring. eplace lown fuses or tripped circuit breaker transformer. Transformer defective eset high pressure control or check unit charge. High or low pressure control (optional) open High pressure control opens at psig, and low pressure control opens at psig. ompressor overload contacts open eplace compressor. NOTE: ait at least hours for overload to reset. ondenser fan Loose connection heck for unit voltage at compressor. runs; ompressor stuck heck and tighten all connections. compressor rounded or open winding ait at least hours for overload to reset. If still open, replace the does not run. Open internal overload compressor. Low voltage connection At compressor terminals, voltage must be within % of nameplate volts when unit is operating. apacitor weak, open or shorted heck capacitor. eplace if defective. Low suction Low indoor airflow Increase speed of blower or reduce restriction. cool compressor, eplace air filters. iced evaporator coil ompressor Defective overload protector eplace overload protector. heck for correct voltage. short cycles Unit cycling on low pressure control heck refrigerant charge and/or airflow. egisters Low airflow Increase speed of blower or reduce restriction. sweat eplace air filters. High suction Excessive load echeck load calculation pressure Defective compressor eplace compressor. eversing valve not seating properly. eplace reversing valve. Insufficient Improperly sized unit ecalculate load. cooling Improper airflow heck airflow should be approximately M per ton. Incorrect refrigerant charge. harge per procedure attached to unit service panel. Incorrect voltage At compressor terminals, voltage must be within % of nameplate volts when unit is operating. Evaporator Low airflow heck airflow should be approximately M per ton. coil freezing or frosting Low refrigerant charge Properly charge unit. Operating unit in cooling mode below 5º (8º) outdoor temperature Install or check low ambient control should be open below 5º (8º) outdoor temperature. 5

16 APPENDIX iring Diagram PAM oodman Long ANIN HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. NOTE: iring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. Placeholder for iring Diagram Supply Voltage 8-// N M S L L ETD XM- XM- Speed Up K K M 8 NO OM P V NOTE # P T T P L See NOTE # L ND 8 - / / H P PL P + + T h e r m o s t a t EM Speed (TANS V ) P (M) (OM) High Low EM Speed Optional M S ETD OM P NOTE# NO EM OM NOTE # 8 - T V T OMP S.A. H NOTE # M L P H T L H M NOTE #5 ETD 5 SA (If Used) See NOTE 5 LVJ See NOTE # Thermostat L P P N M P P P P HPS ontrol ox P HPS actory iring Line Voltage Low Voltage Optional High Voltage ield iring High Voltage Low Voltage Symbol olor : lack : lue : rown : reen O: Orange P: Purple : ed : hite : ellow omponent Legend ontactor M ondenser Motor OMP ompressor D Defrost ontrol DT Defrost Thermostat ND Equipment round HPS High Pressure Switch HVD High Voltage Defrost elay LPS Low Pressure Switch LVD Low Voltage Defrost elay LVJ Low Voltage Junction ox PL emale Plug onnector V eversing Valve oil un apacitor for ompressor and an SA Start Assist T Transformer VSM Variable Speed Motor VST Variable Speed Terminal lock ETD NOTES:. eplacement wire must be the same size and the same type insulation as original (at least 5º). Use copper conductor only.. To change the evaporator motor speed, move the white and yellow leads from the EM and to EM and 5. If both leads are energized, the higher speed setting is used.. rankcase heat not supplied on all units.. or 8-volt transformer operation, move the purple wires from Terminal to Terminal on the transformer. 5. Start assist factor equipped, when required.. Use copper conductors only. ++ Use N.E.. lass wire.

17 iring Diagram P(8-)AM oodman Long ANIN HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. NOTE: iring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. P 8 T V NOTE P T T P L L See NOTE 5 ND 8 - / / P LVJ H PL SA (If Used) See NOTE P ++ T he r m os t a t L N 5 EM P Placeholder for iring Diagram M S OMP /PK /PK HPS ontrol ox See NOTE L Supply Voltage 8-// NOTE If Used NOTE EM 8- T V actory iring Line Voltage Low Voltage Optional High Voltage ield iring High Voltage Low Voltage Symbol olor : lack : lue : rown : reen O: Orange P: Purple : ed : hite : ellow omponent Legend M OMP D DT ND HPS HVD LPS LVD LVJ PL V SA T VSM VST ontactor ondenser Motor ompressor Defrost ontrol Defrost Thermostat Equipment round High Pressure Switch High Voltage Defrost elay Low Pressure Switch Low Voltage Defrost elay Low Voltage Junction ox emale Plug onnector eversing Valve oil un apacitor for ompressor and an Start Assist Transformer Variable Speed Motor Variable Speed Terminal lock L T OMP S H S.A. T NOTE M L PL 5 EM See NOTE N Thermostat HPS NOTES:. eplacement wire must be the same size and the same type insulation as original (at least 5º). Use copper conductor only.. To change evaporator motor speed, move white and yellow leads from EM and to EM and 5. If both leads are energized, the higher speed setting is used.. or 8-volt transformer operation, move the purple wires from Terminal to Terminal on the transformer.. Start assist factor equipped, when required. 5. Use copper conductors only. ++ Use N.E.. lass wire. 7

18 iring Diagram PH( - )AM oodman Long ANIN HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. NOTE: iring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. /PK /PK LPS P P P P P 8 T ETD K NO V XM- XM- K OM SPEED NOTE P N UP M M -PS D PS LVD HVD D D P -V NT O O-V -DT DT O H SA P See NOTE 5 PL See NOTE 5 O P P P T T L L P P O See NOTE P P See NOTE 8 See NOTE 7 ND /PK LVJ /PK -8 / / HPS T h e r m O o s t a ++ t ontrol ox Symbol O P /PK olor lack lue rown reen Orange Purple ed hite ellow lue/pink actory iring Line Voltage Low Voltage Optional High Voltage ield iring High Voltage Low Voltage 8-/ / - A P EM Speed DT V (TANSV) P (M) LO (OM) HIH EM Speed Optional P M OMP Placeholder for iring Diagram S See NOTE HS See NOTE H NOTES:. eplacement wire must be the same size and the same type insulation as original (at least 5º). Use copper conductor only.. To change the evaporator motor speed, replace the lead on ETD OM with lead on ETD M or M.. rankcase heater and crankcase heater switch factoryequipped, when required.. or 8-volt transformer operation, move the purple wires from Terminal to Terminal on the transformer. 8 L Supply Voltage 8-// L See NOTE H HS T T OMP HVD H S M S.A. -Pole Only See NOTE 7 See NOTE 5 P L N ETD NO See NOTE M M ETD OM EM 8- See NOTE T V ETD DT V -DT DT O-V -V D NT -PS PS O LPS HPS P L 5 O Thermostat omponent Legend ontactor M ondenser Motor OMP ompressor D Defrost ontrol DT Defrost Thermostat ND Equipment round HPS High Pressure Switch HVD High Voltage Defrost elay LPS Low Pressure Switch LVD Low Voltage Defrost elay LVJ Low Voltage Junction ox PL emale Plug onnector V eversing Valve oil un apacitor for ompressor and an SA Start Assist T Transformer VSM Variable Speed Motor VST Variable Speed Terminal lock 5. Start Assist factor-equipped, when required.. Use copper conductors only. ++ Use N.E.. lass wire 7. Double-pole contactor shown. Single-pole contactor could be factory-equipped as an alternate configuration. 8. ommon side of contactor cannot be grounded or connected to any other common (V). 9. See unit rating plate for type and size of overcurrent protection.

19 iring Diagram PH(8, )AM oodman Long ANIN HIH VOLTAE! Disconnect ALL power before servicing. Multiple power sources may be present. ailure to do so may cause property damage, personal injury or death. NOTE: iring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. P L L Supply Voltage 8-// L N 5 See NOTE T T OMP LPS /PK /PK EM HVD H S M S.A. L -V -PS PS HVD D D D D D LVD P P Pole Only See NOTE 7 See NOTE NT O O-V -DT DT DT V See NOTE HS P H See NOTE L O EM N D H ontrol ox See NOTE 8- P 8 V T Placeholder for iring Diagram T See NOTE PL 5 SA See NOTE HPS DT V P /PK /PK V -DT DT O-V -V D NT -PS PS O P P P LPS M HPS P See NOTE EM P 5 O S PL T T P OMP P L L P P O Thermostat P O See NOTE 8 See NOTE 7 See NOTE 5 ND LVJ HS O / / T he r m os t a t See NOTE See NOTE Symbol O P /PK actory iring Line Voltage Low Voltage Optional High Voltage ield iring High Voltage Low Voltage 8-/ / - A H omponent Legend ontactor M ondenser Motor OMP ompressor D Defrost ontrol DT Defrost Thermostat ND Equipment round HPS High Pressure Switch HVD High Voltage Defrost elay LPS Low Pressure Switch LVD Low Voltage Defrost elay LVJ Low Voltage Junction ox PL emale Plug onnector V eversing Valve oil un apacitor for ompressor and an SA Start Assist T Transformer VSM Variable Speed Motor VST Variable Speed Terminal lock olor lack lue rown reen Orange Purple ed hite ellow lue/pink NOTES:. eplacement wire must be the same size and the same type insulation as original (at least 5º). Use copper conductor only.. To change evaporator motor speed, move white and yellow leads from EM and to EM and 5. If both leads are energized, the higher speed setting is used.. or 8-volt transformer operation, move the purple wires from Terminal to Terminal on the transformer.. Start Assist factor-equipped, when required. 5. Use copper conductors only. ++ Use N.E.. lass wire. rankcase heater and crankcase heater switch factoryequipped, when required. 7. Double-pole contactor shown. Single-pole contactor could be factory-equipped as an alternate configuration. 8. ommon side of contactor cannot be grounded or connected to any other common (V). 9

20 Unit Dimensions ear Product Dimensions Unit Dimensions Inside A A T S Q H J I? K P O D N E K? D M? L E D E A. lower access panel. " (55.9 cm). Air return D. Air supply E. " (7.9 cm). 5³₄" (. cm) A. 7" (9. cm). 5" (9.5 cm). Medium: " (8. cm); Large: " (. cm) D. " (. cm) E. 5¹ ₂" ( cm). ³ ₈" (.5 cm). ¹ ₈" (.5 cm) H. ¹ ₈" (5. cm) I. ¹ ₂" (.5 cm) J. 8" (. cm) K. Medium: " (. cm); Large: 8" (5.7 cm) L. ³ ₄" (7 cm) M. Air supply N. Air return O. " (7. cm) P. ontrol wire entrance Q. 8⁷ ₈" (7.9 cm). ondensate drain connection ³ ₄" (.9 cm) NPT female S. Power wire entrance T. Suction/liquid pressure ports If you need further assistance, you can write to the below address with any questions or concerns: Tradewinds Distributing ompany, LL reakers Drive Jacksonville, L 58 ASSISTANE O SEVIE Please include a daytime phone number in your correspondence. Or call toll free: PIO-95. All rights reserved. egistered Trademark/TM Trademark of hirlpool, U.S.A., Manufactured under license by Tradewinds Distributing ompany, LL, Jacksonville, lorida. arranty provided by manufacturer. All other trademarks are owned by their respective companies. OMOT OMMITMENT is a trademark of Tradewinds Distributing ompany, LL. 8/ Printed in U.S.A.

INSTALLATION INSTRUCTIONS FOR PACKAGE HEAT PUMP OR PACKAGE COOLING UNIT

INSTALLATION INSTRUCTIONS FOR PACKAGE HEAT PUMP OR PACKAGE COOLING UNIT INSTALLATION INSTUTIONS FO PAKAE HEAT PUMP O PAKAE OOLIN UNIT ATTENTION INSTALLATION PESONNEL Prior to installation, thoroughly familiarize yourself with this installation manual. Observe all safety warnings.

More information

INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS

INSTALLATION INSTRUCTIONS FOR SELF-CONTAINED PACKAGE AIR CONDITIONERS AND HEAT PUMP UNITS INSTALLATION INSTUTIONS O SEL-ONTAINED PAKAE AI ONDITIONES AND HEAT PUMP UNITS ATTENTION INSTALLATION PESONNEL Prior to installation, thoroughly familiarize yourself with this installation manual. Observe

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

543-0032-00, 943-0032-00. User s Manual

543-0032-00, 943-0032-00. User s Manual 543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:

HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS TABLE OF CONTENTS 1. Warnings...2 2. Accessibility Of Appliance...3 3. Unit Dimensions And Specifications...3 4. Unit Specifications

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Installation Instructions

Installation Instructions Installation Instructions Model TSTATG2111 Use with most systems: 2-Heat, 1-ool 1- Day Prog ram m ab l e Digital Thermostat u p t o 2 - H e a t & 1 - o o l ontrol up to 2 Heat & 1 ool Stages Backlit Display

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

User s Information/Installation Instructions

User s Information/Installation Instructions Outdoor Heat Pump User s Information/Installation Instructions 13 SEER R-410A High Efficiency Split System These units have been designed and tested for capacity and effi ciency in accordance with A.R.I.

More information

LOBOY 16 AIR CONDITIONERS

LOBOY 16 AIR CONDITIONERS INSTRUCTION MANUAL FOR: LOBOY 16 AIR CONDITIONERS McLean Midwest Corp. dba: McLean Cooling Technology 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleancoolingtech.com

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Central Air Conditioner

Central Air Conditioner Central Air Conditioner USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL AIR CONDITIONER NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

Installation Instructions

Installation Instructions H5HK Series Installation Instructions 3 Phase Electric Heater Kits 7.5 and 0 TON Package A/C Systems Description Installation of 08/40V and 480V H5HK 3 Phase Heater Kits in 7.5 and 0 TON Packaged Air Conditioners.

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP

Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT YEAR-ROUND

More information

E2 Series Electric Furnaces

E2 Series Electric Furnaces E2 Series Electric Furnaces Service Manual Table of Contents Electrical Requirements... 10 Codes, Specifications Requirements... 10 Connection Supply Service Wires... 10 Furnace Sequence of Operation...

More information

CEILING CASSETTE FAN COIL UNIT

CEILING CASSETTE FAN COIL UNIT CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

Install Guide 3M-50. Caution. Caution

Install Guide 3M-50. Caution. Caution PG 1 Install Guide 3M-50 aution Your thermostat is a precise instrument, handle it with care. Turn off electricity to the HVA system before installing or servicing thermostat or any part of the system.

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS Ducted System RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased: This manual must be read and

More information

Installation Instructions for Alarm Module Kit A043F059

Installation Instructions for Alarm Module Kit A043F059 Instruction Sheet 07-2013 Installation Instructions for Alarm Module Kit A043F059 1 Introduction The information contained within is based on information available at the time of going to print. In line

More information

How To Install An Evaporator Coil

How To Install An Evaporator Coil EVAPORATOR COIL INSTALLATION INSTRUCTIONS EVAPORATOR COIL SAFETY... INSTALLATION REQUIREMENTS... Tools and Parts... System Requirements... Location Requirements... Drain Requirements... INSTALLATION INSTRUCTIONS...

More information

Dehumidifier Users manual. For Models: DH45S DH65S

Dehumidifier Users manual. For Models: DH45S DH65S Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW52AL AW64AL AW52AL 387030095 AW64AL 0.8180.463.0 07/05 TECHNICAL DATA & SERVICE MANUAL INDOOR UNIT: AW52AL AW64AL SPLIT SYSTEM AIR CONDITIONER Model No. Product Code No. AW52AL 387030095 AW64AL 387030096 0.8180.463.0 07/05 IMPORTANT! Please read before installation

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167 PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION

More information

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST

INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST INSTALLATION INSTRUCTIONS COMMERCIAL ROOM VENTILATORS WITH EXHAUST MODEL CHCRV-5 For Use with Bard CH Series 3, 4 & 5 Ton 2-Stage Wall Mount Heat Pumps AND W38H, W43H, W49H and W61H Single Stage Wall Mount

More information

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents

INSTALLER'S GUIDE. Supplementary Electric Heaters 18-GJ08D1-1. Table of Contents INSTALLER'S GUIDE ALL phases of this installation must comply with NATIONAL, STATE AND LOCAL CODES Models: BAYEAAC051A BAYEAAC05LG1A BAYEAAC081A BAYEAAC08LG1A BAYEAAC101A BAYEAAC10LG1A BAYEABC151A BAYEABC201A

More information

SPLIT SYSTEM OUTDOOR UNIT

SPLIT SYSTEM OUTDOOR UNIT SPLIT SYSTEM OUTDOOR UNIT CKL, CKF, CPKF SERIES INSTALLATION & OPERATING INSTRUCTIONS 2-2 Goodman Manufacturing Company, L.P. San Felipe, Suite, Houston, TX 776 www.goodmanmfg.com -or- www.amana-hac.com

More information

CENTRAL AIR CONDITIONER A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL AIR CONDITIONING UNIT.

CENTRAL AIR CONDITIONER A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL AIR CONDITIONING UNIT. CENTRAL AIR CONDITIONER A GUIDE TO OPERATING AND MAINTAINING YOUR RESIDENTIAL AIR CONDITIONING UNIT. NOTE TO INSTALLER: THIS MANUAL SHOULD BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT HOME COOLING

More information

TECHNICAL MANUAL GDS8 & GHS8

TECHNICAL MANUAL GDS8 & GHS8 TECHNICAL MANUAL AL GDS8 & GHS8 33-3/8" 80% Gas Furnace Units Refer to Service Manual RS6610004 for installation, operation, and troubleshooting information. All safety information must be followed as

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10100E / AC-10100H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS ELECTRICAL SAFETY This appliance is for indoor use only. Always turn off the unit and unplug

More information

Miami Heat Pump HP Series Installation Guide

Miami Heat Pump HP Series Installation Guide CAUTION- THIS UNIT IS FOR INDOOR USE ONLY!! WARNING BEFORE ANY INSTALLATION OR MAINTANCE IS STARTED PLEASE READ COMPLETE INSTLLATION GUIDE. INSTALLATION START-UP AND SERVICE INSTRUCTION- The HP Water Source

More information

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS

INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL: WA121 Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual : 2100-234 E Supersedes: 2100-234

More information

Air Conditioning System

Air Conditioning System Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR

TECHNICAL SUPPORT MANUAL 3 Phase Air Conditioner Component R2A3**GHR 3 Phase Air Conditioner Component R2A3**GHR DANGER, WARNING, CAUTION, and NOTE The signal words DANGER, WARNING, CAU- TION, and NOTE are used to identify levels of hazard seriousness. The signal word DANGER

More information

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility

More information

Test Code: 8297 / Version 1

Test Code: 8297 / Version 1 Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment

More information

Packaged Terminal Air Conditioner Wall Sleeve Installation

Packaged Terminal Air Conditioner Wall Sleeve Installation Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation

More information

Troubleshooting Your Refrigerator

Troubleshooting Your Refrigerator Troubleshooting Your Refrigerator With conscientious care, a refrigerator will perform for years with little or no repairs. Refrigerators are categorized according to the way frost is removed from them.

More information

Electric Water Heater

Electric Water Heater Electric Water Heater Operation and Installation Manual (LIMITED WARRANTY AND TANK REPLACEMENT POLICY) The following information should be noted at time of installation and retained for future reference.

More information

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION:

WARNING: FAILURE TO FOLLOW THESE RULES MAY RESULT IN SERIOUS PERSONAL INJURY CAUTION: INSTALLATION LOCATION: Revision Level: 01 Revision Date: 07/07/2011 Please read all instructions carefully to help ensure a correct and SAFE installation of your Second Wind Ultraviolet Germicidal Air Purifier. Failure to do

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008 Installation Manual Rental Services Air Handling Units July 2008 CHS-SVN01A-EN Copyright 2008 Trane All rights reserved This document and the information in it are the property of Trane and may not be

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.

More information

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7

Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7 Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator

More information

How To Understand Evaporator

How To Understand Evaporator SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.

More information

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS

ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...

More information

CENTRAL AIR CONDITIONER with PURON REFRIGERANT

CENTRAL AIR CONDITIONER with PURON REFRIGERANT USER S INFORMATION MANUAL CENTRAL AIR CONDITIONER with PURON REFRIGERANT NOTE TO INSTALLER: This manual must be left with the equipment user. WELCOME TO EFFICIENT HOME COOLING COMFORT Congratulations on

More information

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA

USER S MANUAL FH052EAV1 FH070EAV1. System Air Conditioner (Cooling and Heating) ENGLISH ESPAÑOL FRANÇAIS ITALIANO PORTUGUÊS DEUTSCH E HNIKA USER S MANUAL FH052EAV1 FH070EAV1 E HNIKA PORTUGUÊS ENGLISH ESPAÑOL ITALIANO DEUTSCH FRANÇAIS System Air Conditioner (Cooling and Heating) E S F I P D G DB98-29263A(1) Safety Precautions Register your

More information

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY

SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY SERVICE MANUAL 12VDC WALL THERMOSTAT AIR CONDITIONING SYSTEMS ROOFTOP UNITS ONLY! WARNING - SHOCK HAZARD! TO PREVENT THE POSSIBILITY OF SEVERE PERSONAL INJURY, DEATH, OR EQUIPMENT DAMAGE DUE TO ELECTRICAL

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P) Low Water Cut-Off/Pump Controllers For Steam Boilers and Other Level Control Applications McDonnell & Miller Installation & Maintenance Instructions

More information

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Name of Equipment Silver King Model SKMCD1P/C1 This equipment chapter is to be inserted in the appropriate section of the Equipment Manual. Manufactured exclusively for McDonald s By Silver King Refrigeration,

More information

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013

ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in

More information

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps

A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps A.Y. McDonald Mfg. Co. Troubleshooting Submersible and Jet Pumps Troubleshooting Submersible Pumps Fuse overload or circuit breaker trips when motor is started 1. Incorrect line voltage. Check the line

More information

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units.

Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL. for SPLIT SYSTEM. Bus Air Conditioning Units. R Transport Air Conditioning TRANSPORT AIR CONDITIONING OPERATOR S MANUAL for SPLIT SYSTEM Bus Air Conditioning Units T--326 Rev -- OPERATOR S MANUAL BUS AIR CONDITIONING UNITS GEN IV & GEN V CONTENTS

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost

More information

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2

SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with

More information

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200

T15 AIR CONDITIONER INSTRUCTION MANUAL FOR: McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 INSTRUCTION MANUAL FOR: T15 AIR CONDITIONER McLean Thermal 11611 Business Park Blvd. N Champlin, MN 55316 Tel: 763-323-8200 Fax: 763-576-3200 www.mcleanthermal.com INSTRUCTION MANUAL TABLE OF CONTENTS

More information

Ceiling Mount Air Handler Manual

Ceiling Mount Air Handler Manual www.surna.com 303.993.5271 Ceiling Mount Air Handler Manual Models: CMAH12, CMAH18, CMAH24, CMAH30, CMAH36, CMAH48, CMAH60 Revised: September 2014 Table of Contents Warranty Information 4 Limited Warranty

More information

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor

More information

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6

INSTALLATION INSTRUCTIONS R 410A Split System Air Conditioner N4A3, C4A3, H4A3, T4A3, NXA6, CXA6, HXA6, TXA6 N4A3, 4A3, H4A3, T4A3, NXA6, XA6, HXA6, TXA6 These instructions must be read and understood completely before attempting installation. DANGER, WARNING, AUTION, and NOTE The signal words DANGER, WARNING,

More information

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10)

Use & Care Manual. Electric Tankless Water Heaters. With Installation Instructions for the Installer AP15447 (10/10) Use & Care Manual With Installation Instructions for the Installer Electric Tankless Water Heaters The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations

More information

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation

TABLE OF CONTENTS. SECTION 1 General Information: Pg 2 Description of Operation GTRDD SERIES HEATLESS DRYER INSTALLATION, OPERATION & MAINTENANCE MANUAL TABLE OF CONTENTS SECTION 1 General Information: Pg 2 Description of Operation SECTION 2 Safety Instructions: Pg 3 Installation

More information

Model 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information

Model 800 Residential Steam Humidifier Owner s Manual. Includes Safety & Operating Instructions and Warranty Information Steam Humidifier Model 800 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions and Warranty Information READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety Cautions...

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

Chilled Water HVAC Systems

Chilled Water HVAC Systems Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS

NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS NewAir AC-10000E, AC-10000H Portable Air Conditioner Owner s Manual PLEASE READ AND SAVE THESE INSTRUCTIONS BEFORE USE GENERAL SAFETY INSTRUCTIONS: ALWAYS OPERATE THE UNIT IN AN UPRIGHT POSITION AND PLACE

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3A30NA MXZ-4A36NA ATTENTION. English. Français. Español Split-type Air-Conditioner MXZ-3A30NA MXZ-4A36NA INSTALLATION MANUAL Refer to the installation manual of each indoor unit for indoor unit installation. English Français Español ATTENTION This manual mentions

More information

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13

CONTROL PANEL INSTALLATION INSTRUCTIONS. Single Phase Simplex Page 2-7. 3-Phase Simplex Page 8-13 CONTROL PANEL INSTALLATION INSTRUCTIONS Single Phase Simplex Page 2-7 3-Phase Simplex Page 8-13 Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3 Manufactured by SJE-Rhombus Installation Instructions

More information

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com

ICE AIR. Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE MANUAL. Wo r l d C l a s s C o m f o r t. www.ice-air.com 80 Hartford Avenue Mount Vernon New York 10553 Tel: 914-668-4700 EXT. 203 Fax: 914-668-5643 www.ice-air.com Wo r l d C l a s s C o m f o r t Console Water Source Heat Pump (WSHP) OPERATING & MAINTENANCE

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

Failure code manual. content

Failure code manual. content Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一

More information

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor INSTALLATION, OPERATION AND MAINTENANCE MANUAL For SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor Yeomans Chicago Corporation 3905 Enterprise Court P.O. Box 6620 Aurora, IL 60598-0620 Phone:

More information

Single Zone LCD Thermostat Operating Instructions

Single Zone LCD Thermostat Operating Instructions Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip

More information