Guidelines to Assess Hail Damage to Shingle Roofs
|
|
|
- Alexandra York
- 10 years ago
- Views:
Transcription
1 Guidelines to Assess Hail Damage to Shingle Roofs B. East, M.S., P.E., M.ASCE 1 T. Lozos, CPE 2 S. Verhulst, M.S., P.E., M. ASCE 3 M. DeLeon M.E., P.E., M.ASCE 4 D. Ahuja M.S., P.E., M.ASCE 5 1 Project Director, Nelson Architectural Engineers, Inc., 9701 Brodie Lane, Suite 201, Austin, Texas 78748; PH (512) ; Fax (512) [email protected] 2 Technical Director, Nelson Architectural Engineers, Inc., 2740 Dallas Parkway, Suite 220, Plano, Texas 75093; PH (469) ; Fax (469) [email protected] 3 Austin Branch Director, Nelson Architectural Engineers, Inc., 9701 Brodie Lane, Suite 201, Austin, Texas 78748; PH (512) ; Fax (512) [email protected] 4 Vice President of Research and Development, Nelson Architectural Engineers, Inc., 2740 Dallas Parkway, Suite 220, Plano, Texas 75093; PH (469) ; Fax (469) [email protected] 5 Executive Vice-president, Nelson Architectural Engineers, Inc., 2740 Dallas Parkway, Suite 220, Plano, Texas 75093; PH (469) ; Fax (469) [email protected] ABSTRACT The severity of hail damage to residential and commercial roofs depends on several parameters including the age and type of roofing material, the roofing assembly, hail size, and roof slope, among others. Asphalt shingled roofs comprise a large percentage of insurance claims submitted for roof-related hail damage. For asphalt shingled roofs, hail damage typically consists of radial/circular areas of granule loss, which constitute latent damage and may affect the future performance and lifespan of the shingles. The severity and extent of hail damage to asphalt shingled roofs is not as visually apparent as compared with some other common high-slope roofing materials, such as metal panels, wood shakes, and clay/concrete tiles. Assessing the extent of hail damage to shingled roofs and developing a scope of repairs can be difficult. Furthermore, guidelines for such assessment are not well established. Based on the authors' experience, we propose guidelines and procedures to assess the extent of hail damage to asphalt shingled roofs from which a scope of repairs can be developed. A cost analysis for the consideration of repair versus replacement is also presented.
2 WEATHER RESEARCH AND DETERMINATION OF HAIL SIZE During an investigation of hail damage to roofing materials, it is important to determine the approximate size of the impacting hail. Hail size will vary not only between different storm events, but also within a particular storm event. Because of the exponential increase in kinetic energy with the increase in hail size (due to increased mass and increased velocity), the size of the largest hailstones from the storm event are of primary interest (Noon 2001). Weather research can be conducted using information freely available from the National Oceanic and Atmospheric Administration (NOAA) or by obtaining a more detailed site specific meteorological report by private companies. Because hail size can vary between locations during a hail event, the distance between the site and the location of reported hail should be considered. Even if an investigator has reported weather information, the conditions at the site are typically the best indicator of hail size and severity. Indentations in metal surfaces and burnish markings on metal or other smooth surfaces can provide valuable information regarding hail size and even the directionality of falling hail during a storm event. Burnish marks occur where impact from hailstones removes the surfacing of an exposed material, such as dirt, fungal discoloration on wood surfaces, or slight oxidation on metal surfaces. This burnishing changes the appearance of the surface, leaving distinct markings which can be useful in determining the approximate size and distribution of hailstones. Burnish marks on vertical surfaces and the splash patterns of burnish marks on horizontal surfaces can also aid in determination of the directionality of hail impacts. Considering typical light gauge metal surfaces (such as 24 or 26 gauge metal panels or parapet wall cap flashing), an indentation from hail impact will usually measure approximately half the diameter of the impacting hailstone (Koontz and Crenshaw 2002). Indentations in softer metal surfaces, such as aluminum coil fins at roof top HVAC units and soft metal covering for pipe insulation, can also give an indication of hail size (Noon 2001). While it is important to evaluate the shingle roofing for evidence of impact damage, the information gained from the weather data and the conditions at other building materials can assist in the overall evaluation of hail occurrence. HAIL DAMAGE TO SHINGLE ROOFING When evaluating shingles for hail damage, two types of damage are considered: latent damage and severe damage. Latent damage may affect the function of the roof materials at a later time. Latent damage to shingles exists when the hailstone impact removes the protective mineral surface granules and exposes the asphaltic matrix to
3 ultraviolet light. This can accelerate the deterioration of a shingle. Severe damage exists when a shingle is punctured/fractured or torn by a hailstone impact. Shingles overlaying a previous shingle roof are more susceptible to impact damage from hail than if the same shingles had been installed directly over a roof deck. Underlying shingles are much more forgiving (or less resistant) than wood decking, which allows impacting hailstones to better penetrate a roof system comprised of two or more layers of shingles. Additionally, inadequate ventilation and/or material deficiencies can cause shingles to curl at the edges. These curled edges are unsupported and typically brittle, and are therefore susceptible to impact damage from hail. Furthermore, as shingles age, they can become more brittle as the asphalt hardens within, decreasing their hail impact resistance. ASSESSMENT OF HAIL DAMAGE TO SHINGLES When assessing hail damage to shingle roofs, the roof should be walked thoroughly and a roof plan should be drawn. In addition to evaluating roof shingles for hail damage, roof appurtenances (i.e., vents, any rooftop units/equipment, etc.) should be evaluated. Figure 1 below shows typical indents due to hail on a roof vent cover. Additionally, the exterior of the structure, including auxiliary structures (i.e., carports), should also be visually evaluated for signs of hail distress. Observed hail distress at both the roof and exterior of the structure should be properly documented. Roof Plan. Prior to evaluating both the roof and exterior for hail distress, a roof plan should be drawn. For larger and more complex structures an aerial image, such as those freely available through Google Earth or Bing Maps, can aid in the development of the roof plan. At the site, dimensions can be measured and recorded on the aerial image and the various features (i.e., roof pitch, roof edge, valleys, hips, ridges, vents, etc.) can be outlined. For smaller and simpler structures, a scaled roof sketch can be prepared on-site. With a roof plan, the roof size can be computed, field notes can be recorded, and observed distress can be accurately located. General On-Site Observations. In addition to evaluating the roof, the exterior of the structure should also be evaluated for hail distress. This includes evaluating the exterior finishes of the structure, window assemblies, door assemblies, and auxiliary structures. Any evidence of hail distress, such as burnish marks or indentations in metal materials, should be documented. Additionally, exposed condenser coil fins at air conditioning units are susceptible to impact damage and should be evaluated. Figures 2 shows typical hail indents in condenser coil fins.
4 Figure 1. Hail indents on a roof vent cover. Figure 2. Hail indents in condenser coil fins. When evaluating the roof shingles for hail damage, all accessible roof areas should be evaluated. At the accessible roof areas, impact damage to the shingles should be documented. Care should be taken to ensure that the impact damage is consistent with hail. Granule loss on roof coverings can occur from hail impacts; however, granule loss in and of itself does not prove hail damage. Granule loss can also be the result of material and/or installation defects, natural weathering, foot traffic from maintenance, and miscellaneous impact abuse. In the authors' experience, circular areas of granule loss are generally consistent with hail impact damage. For older hail damage, the circular impact marks are typically more clearly defined. Over time, the underlying asphalt at the area of impact shrinks/contracts due to ultraviolet exposure, which creates a distinct circular mark, such as that shown below in Figure 3. For newer (or more recent) hail damage, the area of impact will appear bruised similar to that shown below in Figure 4. Figure 3. Hail impact mark on a roof shingle. Figure 4. Hail impact mark on a roof shingle. When documenting hail distress at both the exterior and roof of a structure, the evaluator should pay close attention to the directionality of the hail distress. At the exterior, the evaluator should determine which side(s) exhibits the greatest frequency of hail distress. Similarly, at the roof, the evaluator should determine which roof slope direction has been impacted most by hail. Evaluating impact marks within a sample area (as discussed in further detail in the following paragraph) will assist in
5 determining the frequency of impact distress at the roof. In addition to documenting the directionality of hail distress, the size of the hail impact mark should also be documented. This includes measuring the diameters of burnish marks, indentations in metal surfaces, and/or impact marks on the shingles. The directionality of the hail distress and the impact size can be correlated with the researched weather data. Sample Areas. In order to obtain a representative sampling of hail distress at the roof, sample areas are used. For typical residential roofs, one sample area per roof slope direction will suffice. For larger residential structures or multi-family dwellings, such as apartment buildings, it may be beneficial to evaluate more than one sample area per roof slope direction for each building. Typical sample areas should measure approximately 10' by 10'. However, based on the roof size and/or for safety purposes, the evaluator may have to limit the size of the sample areas to 10' by 5' or even 5' by 5'. For statistical purposes, it may be preferable that the sample areas include only full shingles. Since each course of shingles are offset from the adjacent courses, this will require the sample areas to be irregularly shaped. Each sample area should be carefully evaluated, and within each sample area, impact marks consistent with hail distress should be documented. Analysis. When analyzing the sample areas, it is the authors' recommendation that a table/spreadsheet be created. The table should include (at a minimum) the roof slope cardinal direction where the sample areas were taken, the number of impact marks consistent with hail distress within the sample areas, and the percentage of damaged shingles within the sample areas (for both architectural and 3-tab shingles). For 3-tab shingles, the percentage of damaged shingles should be calculated based on full shingles (as opposed to the number of tabs), because proper replacement of a damaged tab requires replacement of the full shingle. When calculating the percentage of damaged shingles within the sample areas, the evaluator may assume that not more than one impact affected a shingle (conservative assumption for high density storms where more than one hail impact may affect a given shingle). Recommendations for repair versus replacement of the shingles will be based on the percentage of damaged shingles within the sample areas. COST ANALYSIS The purpose of the cost analysis in this paper is to determine an estimated percentage threshold of hail damage which will generally signify that roof replacement should be considered as more economically feasible than individual shingle repair. Labor and material costs may vary significantly by geographic area, time of year, contractor experience and availability, and other factors. Exact pricing may be unknown at the time of the roofing evaluation. However, based on sampled costs and standard industry repair methods, it is the authors' opinion that it is generally possible to formulate a repair/replace decision within a reasonable certainty based on the percentage of hail-damaged shingles observed.
6 Repair Method. Replacement of hail-damaged shingles should be done according to industry standard repair methods. The repair method for replacement of individual shingles outlined in CertainTeed's "Shingle Applicators' Manual" was used for the purposes of this paper. Most major roofing manufacturers publish similar methods for individual shingle replacement. The general process to replace individual damaged shingles includes unsealing the adhesive strip on the damaged shingle and the shingle(s) on the first and second course immediately above the damaged shingle. The nails in the damaged shingle and in the shingle(s) on the course immediately above that also penetrate the damaged shingle are removed. After installation, the replacement shingle and all loosened tabs are hand-sealed with an acceptable asphalt adhesive (CertainTeed Corporation 2011). Depending on its location on the roof, this process requires manipulation of two to four other shingles in addition to the damaged shingle. Figure 5 below represents a typical 10' by 10' sample area and illustrates this repair process. The darker shaded shingle denotes a hail damaged shingle requiring replacement. The lighter shaded shingles denote shingles requiring manipulation to replace the hail damaged shingle. Figure 5. 10' by 10' sample area. In Figure 6 below, the eight hail-damaged shingles represent approximately 10% of the total number of shingles within the sample area, yet the total number of shingles which must be manipulated (including the hail damaged shingles) is 31, or approximately 39% of the total number of shingles in the sample area.
7 Depending on the location and density of damaged shingles relative to one another, some overlapping of the repair process generally occurs. The replacement of adjacent, undamaged shingles which overlap the repair process is frequently more cost effective as the savings on labor more than accounts for the limited additional material cost. As illustrated in Figure 6, since the damaged shingle on course 15 overlaps the repair process for the damaged shingle on course 13, there is little incentive to attempt to salvage the undamaged shingle in between the two as replacement is more efficient. Similar overlapping occurs between course 21 and course 23, which would most likely lead to the roofer replacing the adjacent undamaged course 22 shingles. Figure 6. 10' by 10' sample area. PRICING RESEARCH Cost data was assembled using Xactimate estimating software (version 27.3) and XactAnalysis Industry Trend Reports by Xactware Solutions, Inc. (Xactware) with published national, state, and local pricing for roofing labor, materials, and equipment as of April Xactimate is one of the most commonly used property claims estimating software suites and pricing data service in the property insurance and restoration industry.
8 Model Roof Baseline. For estimating purposes, a model roof baseline for replacement was selected using the XactAnalysis Roof 25 yr Shingle - Labor & Materials industry trend report. This model roof baseline is based on a SQ (4,633 square feet) typical residential 25-year 3-tab shingle roof replacement, including appurtenances such as drip edge, valley metal, ridge, and flashing. (Xactware Solutions, Inc. 2012). Based on published pricing data, the national average cost for total replacement of the model roof baseline was $13,600 with a cost ratio of approximately 60% labor and 40% materials ($8,193 in labor and $5,407 in materials). By comparison, the national average cost for individual shingle replacement was estimated to be $13.72 per shingle with a cost ratio of approximately 89% labor and 11% materials ($12.19 in labor and $1.53 in materials). ESTIMATION METHODOLOGY Estimating parameters and assumptions used for the purposes of estimating the costs to repair individual shingles versus costs to replace the model roof baseline are as follows: General Conditions. Site conditions affecting the repair were assumed to be minimal, that is, the roof was assumed to be of standard slope (4/12), one story, and accessible with no unusual site conditions which would significantly alter a contractor's proposed costs. Shingle Exposure. The number of shingles within 1 square (100 square feet) of roofing was assumed to be 80. Repair Process. For the purposes of this paper, the authors' assumed that, on average, three shingles require manipulation. Repairs to ridge shingles were calculated based on the lineal footage of ridge per square in the model roof baseline. Shingle Breakage. Replacement of individual shingles may cause damage to adjacent, undamaged shingles during the course of repair dependent upon factors such as the age and condition of the existing shingles, weather conditions during the repairs, and training and experience of the roofer. For the purposes of this paper, the authors' assumed a breakage factor of 10%. Other Factors. This paper does not consider replacement of shingles for colormatching or other aesthetic purposes. Replacement shingles are assumed to be commercially available at market prices. The remaining service life of the undamaged shingles was also not included in the calculations. Other Costs: Sales tax has not been added to the estimated costs in this paper. Other expenses such as permits or fees have also been excluded.
9 REPAIR/REPLACE ANALYSIS Based on the industry standard repair methods, pricing research, other parameters, and assumptions previously detailed, Table 1 below lists the estimated costs to individually repair shingles by assessed percentage of hail damage compared to the total replacement costs for the model roof baseline. Unit costs are based on the previously discussed national averages of labor and materials. Table 1. Per Shingle Repairs v. Total Roof Replacement Percent of Hail-Damage Total Number of Shingles Replaced (Hail + Breakage) Total Number of Shingles Replaced or Manipulated Number of Shingles Replaced or Manipulated (as % of the Total Roof Shingles) Estimated Cost for Shingle Repairs Estimated Cost for Shingle Repairs (as % of Total Roof Replacement Cost) 1% % $ % 2% % $1, % 3% % $1, % 4% % $2, % 5% % $3, % 6% % $3, % 7% % $4, % 8% % $5, % 9% % $5, % 10% % $6, % 11% % $7, % 12% % $7, % 13% % $8, % 14% % $9, % 15% % $9, % 16% % $10, % 17% % $11, % 18% % $11, % 19% % $12, % 20% % $13, % 21% % $13, % REPAIR/ REPLACE DETERMINATION The percentage threshold of hail damage for repair/replace determination is based on multiple factors, such as reasonable economic feasibility. For example, at 21% hail damage in Table 1 above, the cost for individual shingle repair is approximately equal to the replacement cost for the entire roof, drip edge, valley metal, ridge, and flashing. Recommending individual shingle repair to this extent is obviously not reasonable or practical.
10 Below 10% hail damage, complete replacement solely because of hail damage is generally not required as individual shingle repairs are economically practical. Unusual factors or general conditions unrelated to the hail damage may apply that would make individual shingle repairs impractical in rare cases. At 10% hail damage, the number of shingles requiring replacement/manipulation exceeds 40% of the total roof shingles. At 12% hail damage, greater than 50% of the total roof shingles require replacement/manipulation. In the authors' opinion, complete replacement should be considered within this range as substantial efforts in terms of shingle manipulation and cost are required. Individual shingle repairs may preferable in certain cases, and complete roof replacement preferable in others. Above 12% hail damage, complete replacement solely because of hail damage is generally always required as individual shingle repairs are not economically practical. Unusual factors or general conditions unrelated to the hail damage may apply that would make individual shingle repairs practical in rare cases. It is the authors' recommendation that the final determination of individual shingle repair versus roof replacement due to hail impact damage take into consideration additional factors such as the age and general condition of the shingles, number of affected slopes, and the willingness of roofing contractors to accept a repair project without exposure to disproportionate risk based on the extent of repairs. REFERENCES CertainTeed Corporation. (2011). "Shingle Applicator s Manual 10th Edition." Valley Forge, PA. Crenshaw, Vickie and Koontz, Jim D. (2002). "Hail: Sizing it Up!." Western Roofing Magazine, May/June. Noon, Randal K. (2001). "Forensic Engineering Investigation." Boca Raton, FL: CRC Press. Xactware Solutions, Inc. "XactAnalysis Industry Trend Reports." (Accessed April 2012). Xactware Solutions, Inc. "Pricing Research Methodology." (Accessed April 2012). Xactware Solutions, Inc. "About Xactware." (Accessed April 2012).
What are the effects of hail on residential roofing products?
What are the effects of hail on residential roofing products? This article examines the sometimes-devastating effects that hail can have on asphalt shingles, wood shingles and shakes, and concrete tile
Final inspections are completed by site visit only. Access to fenced yards shall be planned.
ROOFING RESIDENTIAL BUILDING INSPECTIONS DEPARTMENT www.ci.blaine.mn.us This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Blaine City ordinances,
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Evaluating Composition Shingles
Evaluating Composition Shingles Is my roof damaged by hail? The information in this brochure covers some of the more common types of damage to composition roofs. It shows what hail damage typically looks
ROOF INVESTIGATION SURVEY
ROOF INVESTIGATION SURVEY Prepared For: Susan Sametz Property Manager AAS Community Management P.O. Box 4382 St. Louis, MO 63123 Location: Rush Creek Homeowners Association Building #8 (8 units) 2025-2039
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
Science and Law of Hail Damage
Science and Law of Hail Damage WIND Regional Symposium SCIENCE AND LAW OF HAIL DAMAGE SCIENCE HAIL And It s s Effects on Roofing Systems Presented By: HAIL FORMATION Hail is most commonly formed in frontal
Ball Peen Hammer Test
Ball Peen Hammer Test A HAAG Engineering Co. Publication COMPANY PROFILE Haag Engineering Co. is one of the oldest firms in this country specializing in the engineering analysis of failure and damage.
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
Detached accessory structures that contain no conditioned floor area are exempt.
RESIDENTIAL ROOFING PERMITS: A roofing permit is required for roofing of residential dwellings and garages in accordance with Section R105 of the International Residential Code. Updated 11/2013 City of
How To Improve Roof Drainage
The Roof Drainage Epidemic Stewart M. Verhulst, M.S., P.E., M.ASCE 1 Marco A. Deleon, M.E., P.E., M.ASCE 2 Bradley L. East, M.S., M.ASCE 3 1 Nelson Architectural Engineers, Inc., 9701 Brodie Lane, Suite
Wright House, Wrong Peril A Case Study in Hail Damage to a Frank Lloyd Wright Residence. Erik L. Nelson, Ph.D., P.E., M. ASCE 1
Wright House, Wrong Peril A Case Study in Hail Damage to a Frank Lloyd Wright Residence Erik L. Nelson, Ph.D., P.E., M. ASCE 1 1 President & CEO, Nelson Architectural Engineers, Inc., 2740 Dallas Parkway
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
REPLACE YOUR ROOF TO VISUALLY INSPECT YOUR ROOF REGULARLY SO YOU CAN DISCOVER PROBLEMS WHILE THEY ARE STILL MINOR AND CAN BE REPAIRED.
???????????????????? REPLACE YOUR ROOF ???????????????????? REPLACE YOUR ROOF YOUR ROOF PROTECTS YOUR HOME FROM THE SUN, WIND AND RAIN. AGE, WEATHER AND THE SUBTROPICAL FLORIDA CLIMATE CAN TAKE THEIR TOLL
OnTheRock Engineering, LLC
OnTheRock Engineering, LLC File No. L14-Sample www.ontherockeng.com 502-225-6203 FAX 502-225-6204 RESIDENTIAL ROOF EVALUATION Hail Damage Claim - Sample Short Report Claim Number: XYZ Insured: Joe Homeowner
Insured: John Smith Home: (555) 123-4567 Property: 1234 Avenue D Wapakoneta, OH 45895
1 Insured: John Smith Home: (555) 123-4567 Property: 1234 Avenue D Wapakoneta, OH 45895 Claim Rep.: CSI Representative John Smith Estimator: CSI Representative John Smith Reference: Business: (456) 555-1234
PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
SITE INSPECTION CHECKLIST
SITE INSPECTION CHECKLIST Numerous steps are required in determining that a site is suitable for the installation of a solar system. The inspection procedures and their proper chronology are outlined below.
BRADEN ROOFING NEWS. Hail often damages ridge shingles.
BRADEN ROOFING NEWS Vol. 2 Welcome to Braden Roofing News Volume II. We hope this article will help you better understand exactly what hail damage is and how it affects your home (and pocketbook). We appreciate
ROOFS - Guidance for Repair, Maintenance and Replacement
ROOFS - Guidance for Repair, Maintenance and Replacement Guilford Association Architectural Committee ROOFING Slate and tile roofs are a critical design feature of Guilford homes. The homes were designed
TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"
2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE
How To Replace A Roofing System In Florida
Florida Consumer Considerations in Replacing their Roofing System The Florida Roofing, Sheet Metal and Air Conditioning Contractors Association provides the following general information to help Florida
CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION
IF SUBSIDIARY, PROVIDE MASTER PERMIT NUMBER HERE: CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION Location of Improvements
ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof
ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find
Obvious statement of the day: the storm was strong enough to damage the storm and hailstones can often be gathered
Obvious statement of the day: the storm was strong enough to damage the storm and hailstones can often be gathered Hail can damage low-slope roof, in today s age of information, chances from these eyewitness
Rooftop Matters. 2 0 1 2 Benchmark Report. Executive Summary
The 2012 Benchmark Report is our initial survey covering results from roof inspections and service calls over a six-month period. Our intention is to update these results annually in order to provide meaningful
COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE
www.epdmroofs.org COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE By Ric Vitiello President Forensic Roof Consulting and Hail Damage Assessment Training www.benchmark-services.com
How To Compare Roofing Material
Roofing Material Comparisons Housing Fact Sheets One of the great strengths of our market economy is the number of product choices we are provided with. So when it comes time to replace the roof on your
FUNCTIONAL vs. NON-FUNCTIONAL HAIL DAMAGE TO CEDAR ROOFING PRODUCTS
FUNCTIONAL vs. NON-FUNCTIONAL HAIL DAMAGE TO CEDAR ROOFING PRODUCTS E. Brian Webb, P.E., C.M.I. 1.0 INTRODUCTION The purpose of this document is to describe the difference between the various types of
CHAPTER 5 ASPHALT-SHINGLE ROOFING
CHAPTER 5 ASPHALT-SHINGLE ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 5.1.1 References double-coverage shingles provide two layers over Specifications for shingles and allied materials are most
Commercial Roof Inspection Form
Inspection Date: Inspector: Building Information Building ID: No.: Used For: Year Roof Applied: Building Description: Permanent Temporary Building Type: Retail Industrial Residential Building Name: Building
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10
Guideline for Fire Safety Elements of Solar Photovoltaic Systems July 17, 2008 Rev: 1/1/10 This document was developed by the Orange County Fire Chiefs Association, Orange County Fire Marshal Committee.
IBHS Roofing Research
IBHS Roofing Research ARMA Steep Slope Committee Meeting August 14, 2013 Tanya M. Brown, PhD South Carolina Wind and Hail Underwriting Association Research Engineer IBHS Research Center Specimen Construction
HERITAGE WOODGATE LAMINATED ASPHALT SHINGLES Dallas, TX
Application Instructions for THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR OTHER ROOFING
Residential Roofing Handbook
Minneapolis: (612) 343-3301. St. Paul Area: (651) 772-5456 Maple Grove Area:. Eden Prairie Area: (952) 854-5251 Residential Roofing Handbook Table of Contents Residential Roofing 101 Asphalt-Fiberglass
National Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067
Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com
DURATION STORM. TruDefinition. TruDefinition Duration STORM Shingles are a component of the Owens Corning Total Protection Roofing System.
TruDefinition DURATION STORM Impact-Resistant Shingles with WeatherGuard and SureNail Technologies Onyx Black TruDefinition Duration STORM Shingles are a component of the Owens Corning Total Protection
TARRANT COUNTY DETAIL STANDARDS
TARRANT COUNTY DETAIL STANDARDS 1. Standard Coping 2. Coping at End Wall 3. Standard Sheet Metal Engagement Details 4. Gravel Guard 5. Gravel Guard Wall Termination 6. Gravel Guard, Gutter, and Downspout
The Wo rd. Shingle Warranties - Getting Real
The Wo rd A look at terms used in home inspection reports Photo I ONCE AGAIN THE WORD INVITES YOU TO TRAVEL into the dark realm of subjects that are sometimes misunderstood by home inspectors. The Word
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
Roof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1
City of Cotati Building Division 201 W. Sierra Ave. Cotati, CA 94931 707 665-3637 Fax 792-4604 INSTALLATION GUIDELINES for SOLAR PHOTOVOLTAIC SYSTEMS 1 Any PV system on a new structures should be included
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
TruDefinition. Duration Storm. Impact-Resistant Shingles with WeatherGuard Technology. Onyx Black
TruDefinition Duration Storm Impact-Resistant Shingles with WeatherGuard Technology Onyx Black Teak Beauty that s designed to weather the storm. TruDefinition Duration STORM Impact- Resistant Shingles
Shingle Roofing: What s below the surface is important
What s below the surface is important The roof is leaking, the shingles look old, and the downspouts are dripping. It must be time to replace the roof or is it? Shingle roofs may seem simple, but a roof
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma
The Impact of Market Demands on Residential Post-Tensioned Foundation Design: An Ethical Dilemma Bart B. Barrett, B.S., P.E.1 Kerry S. Lee, M.B.A., P.E., M. ASCE2 Erik L. Nelson, Ph.D., P.E., M. ASCE3
C. Remove all existing asphalt shingles, underlayment and any loose debris into contractor provided dumpsters.
SCOPE OF WORK Project Title: Replace Deteriorated Roof Singles at Cape Lookout National Seashore Maintenance Shop PMIS # 159350 Prepared By: Mike Baker Cape Lookout National Seashore 131Charles St Harkers
If you are a web registered user of ArlingontPermits.com you may also request an inspection at:
TECHNICAL BULLETIN Community Development & Planning, Building Inspections TOPIC: Permits & Inspections for Roofing Replacement Effective November 1, 2011 Revised This Technical Bulletin will provide contractors
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
How To Choose A Roofing Shingle
CertainTeed Homeowner s Guide to Reroofing So You Need to Reroof Your Home? Maybe you re not quite sure where to start? Or maybe you have reroofed your home before, but you need to brush up on some of
Structural Assessment Report
Report Dallas Township Elementary School Dallas, Pennsylvania (JBCI Project No. 144911) 1655 Suburban Station Building 1617 John F. Kennedy Boulevard Philadelphia PA 19103 215 665 0497 5 Sandwood Drive
Roofing 101 - Signs that Your Roof Needs Repair/Replacement
By: Cherie Martel Roofing 101 - Signs that Your Roof Needs Repair/Replacement 1. Tell us a little bit about your company and its foundation. In 1963, Samuel T. Martel began a small family run roofing company,
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09
TITLE: MASONRY PARAPET WALLS AND FLAT ROOF REQUIREMENTS 11/1/09 PMT GUIDE # 10 Book of Order Section G-10.0102o: "The session is responsible for the mission and government of the particular church. It
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Inspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com [email protected]
COMMON FOR ARCHITECTS AND ENGINEERS Excerpts from HB 2284, 82 nd R
Legislation passed by the 82 nd legislature has modified the Texas Engineering Practice Act and the Texas Architect Practice Act. In order to give the public a clearer understanding of these changes, the
16 2 10.3 Materials and Colors
16 2 10.3 Materials and Colors To create a harmonious and coherent image for each development, building designs shall pay close attention to choice of materials and colors. Building construction shall
Chapter 6 ROOF-CEILING SYSTEMS
Chapter 6 ROOF-CEILING SYSTEMS Woodframe roof-ceiling systems are the focus of this chapter. Cold-formed steel framing for a roof-ceiling system also is permitted by the IRC but will not be discussed;
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
ROOF CONSTRUCTION Roof Styles Gable Roof Hip Roof Gambrel Roof
ROOF CONSTRUCTION The overall appearance of a building is greatly affected by the roof lines and the roofing materials. The designer has many standard designs to choose from and should be able to find
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2
Warranty Information TABLE OF CONTENTS PROCEDURES FOR WARRANTY 2 PROTECTING YOUR DURO-LAST ROOFING 3 Safety Measures 3 Inspection 3 Maintenance Program 4 Sealants 4 Drainage 4 Parapets Walls 4 Building
CHAPTER VII. TITLE: STANDARDS FOR NEW ROOFING July 2015 CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS
TITLE: STANDARDS FOR NEW ROOFING CONSTRUCTION, RE-ROOFING CONSTRUCTION AND ROOFING SYSTEM GUARANTEE REQUIREMENTS Responsible Organization: Office of Facilities Planning Instructions: This Manual supersedes
CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -
CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
NRCA s steep-slope manual is thoroughly revised for 2013
Photo courtesy of Boone Brothers Roofing, Omaha, Neb. NRCA s steep-slope manual is thoroughly revised for 2013 by Maciek Rupar 38 www.professionalroofing.net MARCH 2013 P ublished in January, The NRCA
Hail-related fallacies float through neighborhoods, from one property owner to the next, just as fast as the storms that barrel through.
HAIL DAMAGE MYTHS THE MOST COMMON HOMEOWNER MISCONCEPTIONS Author: Doug Brown, PE, RRC - Project Manager, American Structurepoint Hail-related fallacies float through neighborhoods, from one property owner
CHAPTER 6 ASPHALT ROLL ROOFING
CHAPTER 6 ASPHALT ROLL ROOFING Section I. DESCRIPTION AND GENERAL DISCUSSION 6.1.1 General 6.1.3 Mineral-Surfaced Asphalt roll roofing is roofing in sheet form Mineral-surfaced roll roofing is composed
Exterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
What to Do About Your Roof and How to Hire a Roofing Contractor
ROOFI NG What to Do About Your Roof and How to Hire a Roofing Contractor On those rare occasions when it rains in Arizona and you have a leak, you may wonder if you need a brand new roof, especially if
CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs
CertainTeed Self-Adhering Roof Systems for Low Slope Residential Roofs Goes down fast. Stays on strong. Flintlastic SA performs in all the right ways. What s more important to you? Speed of installation,
Estimated Cost of Repair
1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
Pre-Drywall Inspection Report
SM MEDALLION INSPECTIONS helping people make informed decisions Pre-Drywall Inspection Report 5657 Garden Valley Place Milton, Georgia 30024 Prepared for Betsy and Paul Dougherty January12, 2015 Medallion
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Shingle Installation Guide
Shingle Installation Guide Getting Started Dedicated to improving the environment, NewTech manufactures roofing tiles that are composed of up to 90% recycled post-industrial plastic. The manufacture of
BUSI 441 Project 1: Reserve Fund Study
BUSI 441 Project 1: Reserve Fund Study Estimating Roofing Replacement Cost In Project 1, Part One, section (b) you are instructed to identify the roofing type and area for your subject building. The section
ROOF ASSEMBLIES CHAPTER 9
CHAPTER 9 ROOF ASSEMBLIES SECTION R901 GENERAL R901.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies. SECTION R902 ROOF CLASSIFICATION
Dollars & Sense of Compliance!
CRCA s 29 th Annual Trade Show Oakbrook k Terrace, IL January 19 20, 2012 Dollars & Sense of Compliance! Mark S. Graham Associate ExecutiveDirector Director, Technical Services National Roofing Contractors
Colorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
October 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.
117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This
ROOF INSPECTION REPORT
ROOF INSPECTION REPORT Date: October 9, 2012 Requesting Firm: FIRST CHOICE INSPECTIONS Santiago Salazar Address: 447 Chilberg Court, San Jose, CA 95133 Phone #: 408-771-7563 Roof Inspected At: 1465 Gerlach
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010
Larry Haight's Residential Roofing Co, Inc 15203 NE 95th Street Redmond, Washington Phone: (425) 881-9771 Fax: (425) 869-1010 Custom bid generated for: Job site address: Lake Villas Condominium Attention:
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Lighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: [email protected] Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011
GYPSUM AREA SEPARATION FIREWALLS GA-620-2011 GA-620-2011 Copyright 2011 Gypsum Association All rights reserved. Printed in U.S.A. Characteristics, properties, or performance of materials or systems herein
Page & Turnbull imagining change in historic environments through design, research, and technology
DCI+SDE STRUCTURAL EVALUATIONS OFFICE BUILDING, TOOL SHED & WATER TANK, AND BLACKSMITH & MACHINE SHOP BUILDINGS SAN FRANCISCO, CALIFORNIA [14290] PRIMARY PROJECT CONTACT: H. Ruth Todd, FAIA, AICP, LEED
Assessment Report for Windmill Rehabilitation Project. Anne Curren, Town Clerk Town of North Castle 15 Bedford Road Armonk, New York 10504
Assessment Report for Windmill Rehabilitation Project Anne Curren, Town Clerk Town of North Castle 15 Bedford Road Armonk, New York 10504 Investigation and Documentation MAP employees measured all three
BURNISHED SLATE COVER PHOTO: SLATE GREY
BURNISHED SLATE COVER PHOTO: SLATE GREY Never. Yet millions of homeowners annually purchase asphalt shingle roofs that will only last 20 years at best. Fortunately, this is changing. Homeowners are discovering
CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name:
STATE OF CALIFORNIA RESIDENTIAL ALTERATIONS - RE-ROOF CERTIFICATE OF COMPLIANCE Prescriptive Residential Re-roof Project Name: CALIFORNIA ENERGY COMMISSION CF-1R-ALT-01-E (Page 1 of 2) Date Prepared: A.
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
ROOF ASSEMBLIES AND ROOFTOP STRUCTURES
CHAPTER 15 ROOF ASSEMBLIES AND ROOFTOP STRUCTURES SECTION 1501 GENERAL 1501.1 Scope. The provisions of this chapter shall govern the design, materials, construction and quality of roof assemblies, and