Protecting Your Server Room from Environmental Threats

Size: px
Start display at page:

Download "Protecting Your Server Room from Environmental Threats"

Transcription

1 Protecting Your Server Room from Environmental Threats

2 TABLE OF CONTENTS Eecutive Summary... 3 Environmental Threats and Their Costs... 4 Temperature...4 Humidity...5 Water Leaks...5 Human Error...6 Intrusion...6 Vibration...6 Power Outage...6 Weaknesses of Current Monitoring Practices... 7 ENVIROMUX Server Environment Monitoring Solutions... 8 ENVIROMUX-SEMS ENVIROMUX-MINI...10 Trademark Copyright ILLUSTRATIONS Figure 1-Eample of Alarm Notifications for the ENVIROMUX-SEMS Figure 2-Eample Configuration of ENVIROMUX-SEMS Figure 3-Eample Configuration of ENVIROMUX-MINI...10 TABLES Table 1- Sensor Comparison

3 Eecutive Summary While focused on protecting networks from security attacks and connectivity failures, administrators often inadvertently miss the subtle, ever-present danger of environmental threats. These threats include temperature, humidity, water leaks, intrusion, human error, vibration, and power outages. According to the Uptime Institute, 25% of all information downtime results from the interaction of computer hardware with its physical environment. The environment can damage equipment, slow performance, and force hardware to shutdown. The costs of environmental threats are Replacement of damaged items Lower worker productivity due to downtime Lost revenues from unavailable server-based applications, such as e-commerce sites or customer service centers Additional administrative time and money to investigate and fi problems The most common environment monitoring practice today is to have administrators, security officers, and facilities personnel observe areas and report any problems. This practice has several weaknesses, such as: Not recognizing all threats Constantly changing environmental conditions Gaps in monitoring and responsibility Inability to track environmental changes Focusing on catastrophes, not daily threats that will eventually damage equipment A server environment monitoring system helps prevent the damages caused by environmental threats by monitoring critical conditions (such as temperature, humidity, and water leakage) that could destroy network components in a server room. It uses sensors to track environmental conditions around servers, workstations or data centers. When the system detects an abnormality, such as a temperature increase over the recommended limit, it sends an alert. Alerts can be flashing lights, buzzers, and messages via SNMP traps, , and the system's Web-based administrative interface. After IT administrators receive the alert, they can investigate and resolve the issue. Many systems log environmental data, which administrators can use to investigate problems. The remainder of this paper discusses the following topics: Common server room environmental threats and the damage they cause Weaknesses of the current practice of using personnel to monitor the environment The benefits and features of two systems from Network Technologies Inc (NTI), ENVIROMUX-SEMS-16 and ENVIROMUX-MINI 3

4 Environmental Threats and Their Costs The most common environmental threats to server rooms are temperature, humidity, water leaks, human error, intrusion, vibration, and power outage. Many of these threats, such as temperature and humidity, are related, which complicates environment monitoring and heightens the need for an automated, sophisticated system. Temperature Temperature is the main environmental threat to computer hardware. The generally accepted, ideal temperature is between 68 and 74 degrees Fahrenheit (20 to 24 degrees Celsius). Ecessive heat degrades network performance and causes downtime. As the temperature increases, a heat sinks fan works harder to cool the central processing unit (CPU). Continuous overworking causes the fan to fail, leading to a machine overheating. A machine shuts down when it reaches an unsafe temperature in order to prevent permanent damage. An administrator must then be located, day or night, go to the machine, and reboot it after it has cooled. Consequently, services hosted by a down machine are unavailable until it is restarted, which can take minutes or hours. If the server hosts critical services (e.g., e-commerce, user validation, ) that are not distributed to backup servers, revenues can be lost, users cannot login, and communications are interrupted. If the shut down is not done properly, data can be lost. Ecessive heat and rapid temperature changes also damage equipment. Rapid temperature increases can increase humidity, while rapid drops can cause water in humid air to condense on equipment. Together, heat and moisture accelerate the break down of materials used in microchips, motherboards, and hard drives, which is called premature aging. In worst cases, a machine won't shut down when the temperature eceeds safe levels, and circuits are damaged. Ultimately, heat-damaged equipment must be replaced, increasing the cost of network maintenance. Controlling temperature is becoming more important and more difficult because of changes in equipment design and greater use of network services. New equipment runs hotter because it runs faster and does more work. Also, more circuits are placed closer and closer together, trapping heat in a smaller space. Smaller equipment also means that more equipment can be placed in the same space, usually packed tighter together. The increase in density of equipment causes a rise in the amount of heat dissipating in a rack cabinet. Increased network usage also increases heat, so as usage levels change during the day, so does the temperature and the need for cooling. For networks that operate near capacity 24 hours a day, every day of the year, there is little, if any, time for machines to cool down. 4

5 Humidity When the temperature is between 68 and 74 degrees Fahrenheit (20 to 24 degrees Celsius), the relative humidity (i.e., the amount of water in the air) should be between 40% and 50%. A high humidity level can produce the following problems in the server room: Condensation -- Condensation occurs when humidity levels are too high or when there is a rapid temperature drop. Water that condensates inside equipment causes rust, short circuits, or deposits of dirt and minerals that corrode equipment. Moisture absorbing circuit boards epand and contract with changes in relative humidity levels. Epansion and contraction of these boards can break microelectronic circuits and edge connectors. Finally, condensation increases heat levels. Deposits of dirt and minerals act like insulation that traps heat in equipment and prevents it from diffusing into the air. Fungus -- Persistent humidity levels above 60% and elevated temperatures promote the growth of fungi. These contaminate the air with dirt and spores, which clog a machine's airflow and promote heat retention and condensation. They also retain moisture and promote corrosion, which damage circuits and motherboards. Some fungi "eat" tetile plastics (e.g., polyester) and PVCs, a phenomenon in which fungi breakdown the material used in these items. Most electronic equipment has some PVC materials, such as the PVC insulation used in cabling. A persistent low humidity level can produce the following problems: ESD -- Electrostatic discharge (ESD) occurs in dry environments because there is not enough water to neutralize the charge buildup. ESD intermittently interferes with hardware and can cause system damage or temporary malfunctions. Plastic Breakdown -- Some plastics breakdown in low humidity environments, which is another form of premature aging. Water Leaks Proper planning moves equipment away from water pipes that might burst, basements that might flood, or roofs that might leak. However, there are other water leaks that are more difficult to recognize and detect. Blocked ventilation systems can cause condensation if warm, moist air is not removed quickly. If vents are located above or behind machines, condensation can form small puddles that no one sees. Standalone air conditioners are especially vulnerable to water leaks if condensation is not properly removed. Even small amounts of water near air intakes raise humidity levels and fill servers with moisture. In addition, water from small pipe leaks can travel for long distances behind walls and continue for a long time before anyone notices it. Server rooms with raised floors are particularly vulnerable. All of the cables and wires for an entire network are concealed beneath floor panels. While this approach keeps cords safe from being accidentally unplugged, it makes monitoring their physical status difficult. Cables may be soaking in water for a long period before anyone notices. This situation breaks down insulation, and the loss of insulation causes signal leakage and performance degradation. 5

6 Human Error Administrators/personnel can unknowingly create environment problems in server rooms by: Adjusting the heat or air conditioning while working in the server room and forgetting to reset it when they leave Placing boes in front of vents "temporarily" and forgetting to move them, which blocks airflow Moving equipment, which changes the room's airflow and causes hotspots Bumping equipment, which changes the direction of vent baffles and causes the ehaust of one machine to blow at the intake of another machine Installing new equipment, unaware that it creates more heat than the old equipment Failing to put blank panels behind empty rack shelves, which inhibits air from flowing up. Similarly, cleaning crews sometimes close doors that should be left open for ventilation, thus increasing the temperature and reducing airflow. Intrusion Intruders, such as disgruntled employees and industrial spies, often strike at the most critical yet vulnerable points: the physical devices that store and control access to data. The small and delicate nature of modern computing equipment makes it easy to damage or steal; hard drives are compact enough to carry out in a briefcase, backpack, coat pocket, or purse. Less sinister, but just as potentially harmful, are animal intrusions. Rodents, insects, birds and even larger animals have found their way into highly sensitive areas to wreak havoc upon equipment. Tiny contaminants, such as fur, dust, and dander, can cause component failure. Mice and rats chew through cable. Vibration Too much movement loosens connections within the server housing unseating boards and chips. Vibration can also damage the hard drive disk, which rotates at etremely high speeds. Being bumped or moved can cause the platter, where the information is stored, and the head, which reads the information, to physically connect, causing scratches that permanently harm the disk drive. Generally, vibration comes from mundane sources: being too close to halls or walkways, or being moved or bumped. Good space planning can keep shocks to a minimum, but IT staff should still monitor the situation. Some vibrations, such as those generated by a failing air conditioner, actually serve as warnings. Most machines vibrate more as performance worsens, so tracking fluctuations in equipment vibration becomes an important means to predicting failures. Power Outage Power outages, brown outs, and voltage dips and spikes represent big problems for computing equipment. A simple hiccup in power levels, let alone a lightning strike, can cause servers to fail. In best-case scenarios, this costs precious time before rebooting. In worst-case scenarios, circuitry is irreparably damaged and must be replaced. 6

7 Weaknesses of Current Monitoring Practices In a typical business, three groups monitor the environment: network administrators, security personnel, and facility maintenance employees. Network administrators often rely on a single thermometer and subjective notions about "comfort" to control the temperature of server rooms and data centers. In addition, security personnel and facility maintenance departments monitor areas outside of the server rooms. These three groups usually attempt to coordinate their efforts, but they maintain separate systems and practices. Ultimately, network administrators are primarily responsible for protecting hardware. This approach has the following weaknesses: Not recognizing all threats - Damage caused by the environment can be subtle, unseen, or attributed to other causes. Accelerated equipment aging due to heat or condensation occurs over years and is often written off as a natural process (i.e., "equipment just wears out"). Condensation, rust, and heat damage is usually hidden inside machines, out of administrators' sight. Inconsistency - Administrators check room thermometers only when the environment feels hot or cold to them. Unfortunately, the sense of a "comfortable" temperature and humidity level varies from person to person, so problems are not always recognized. Gaps in monitoring - Environment threats occur 24 hours a day, seven days a week. But administrators are not always in the equipment room, especially on nights and weekends. Depending on staffing levels and schedules, server room environments can be unmonitored up to seventy percent of the time during an average week. Responsibility gaps - Another gap occurs because of shared responsibility. Water leaks and intrusion are monitored by maintenance personnel, security officers, and network administration. Frequently, one group will not monitor an area because it thinks another group already controls that area. Or one group will detect an incident but fail to inform all of the other groups. Consequently, vulnerabilities develop and potential problems are never investigated until it is too late. Inability to track environmental changes - Temperature and humidity levels constantly increase and decrease. Without a log of conditions, administrators cannot identify problems caused by these changes. Often, these problems continue for days or months, while time and money is wasted investigating false causes and solutions. Focus on catastrophes, not daily problems - Current practices avoid catastrophes, such as broken water pipes or power outages that shut down air conditioning systems. But they do little to protect from threats that slowly damage hardware or promote preventative maintenance, such as detecting gradual temperature increases that indicate a need to clean fans or air filters. An effective server environment monitoring system addresses the weaknesses in the current practice of having personnel monitor the environment. 7

8 ENVIROMUX Server Environment Monitoring Solutions NTI offers two server environment monitoring solutions, the ENVIROMUX-SEMS-16 and ENVIROMUX-MINI. Both units monitor critical environmental conditions (such as temperature, humidity, and water leakage) that could destroy network components in a server room. When a sensor eceeds a configurable threshold, the system will notify the selected administrators/staff via , SNMP traps, Web-page alerts and a visual indicator (LED). The systems connect to your IP network, so they can be configured and monitored from any workstation with a Web browser. Figure 1-Eample of Alarm Notifications for the ENVIROMUX-SEMS-16 Both systems provide the following benefits: Control costs - In a stable environment, equipment lasts longer, and less equipment is damaged and needs replaced. Typically, the savings from not having to replace equipment can pay for the cost of the monitoring system. Increase lead-time to fi a problem - The earlier the warning alarm sounds, the sooner personnel can solve the problem before it becomes a disaster. For eample, a leak, if caught early, will not turn into a flood. Reduce downtime - Hardware housed at the recommended environmental conditions operates more efficiently, while also shutting down less frequently. Consequently, employees stay productive, and e-commerce sites continue to generate revenue. Log environmental data for greater insight - In order to maintain stable conditions in the server room, administrators must have accurate records of what has happened. Logging is also critical for investigating problems. 8

9 ENVIROMUX-SEMS-16 The ENVIROMUX-SEMS-16 supports the following sensors/devices: 3 internal sensors: temperature, humidity and power 16 eternal configurable sensors (such as temperature, humidity, temperature/humidity, liquid detection, smoke detection, glass break, vibration and motion sensors) via RJ45 connectors. 8 dry contact input devices, such as door contact sensors, via terminal pair connectors 4 dry contact output devices, such as fans or door locks, via terminal pair connectors The ENVIROMUX-SEMS-16 supports the following alerts: Network messages via SNMP via SMTP Messages to the Web interface A flashing LED SMS messages via eternal GSM modem Figure 2-Eample Configuration of ENVIROMUX-SEMS-16 9

10 ENVIROMUX-MINI The ENVIROMUX-MINI accommodates the following sensors/devices: 2 temperature, humidity or combination sensors via RJ45 connectors. The sensors use fleible super-flat CAT5e cable, which conserves space and makes them easy to position between servers and in other tight areas. 1 liquid detection sensor via a terminal pair connector. 4 dry contact input devices, such as door contact sensors, via terminal pair connectors. The ENVIROMUX-MINI supports the following alerts: Network messages via SNMP via SMTP Messages to the Web interface A red LED indicator Figure 3-Eample Configuration of ENVIROMUX-MINI 10

11 Table 1- Sensor Comparison Sensor Type ENVIROMUX-SEMS-16 ENVIROMUX-MINI Temperature Humidity Temperature / Humidity Combination Liquid Detection Door Contact Emergency/Panic Button Tamper Switch Infrared Motion Detector Vibration/Shock Sensor Glass Break Detection Smoke Detection Access Control Key Station Access Control Digital Keypad Electric Strike (Fail-safe and Fail-secure) Alarm Beacon Siren 11

12 Trademark ENVIROMUX is a registered trademark of Network Technologies Inc. All rights reserved. Copyright Copyright 2006, Network Technologies Incorporated. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise without the prior written consent of Network Technologies Inc, 1275 Danner Drive, Aurora, Ohio For more information, please contact Network Technologies Inc at (800) or (330) RGB.TECH ( ) Toll Free: US & Canada International calls Worldwide fa [email protected] , NTI. All rights reserved.

White Paper: Server Room Environmental Monitoring

White Paper: Server Room Environmental Monitoring White Paper: Server Room Environmental Monitoring Monitoring temperature, humidity and other environmental parameters to ensure maximum reliability while lowering cooling costs and achieving greener IT

More information

Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.

Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co. Sensor Monitoring and Remote Technologies 9 Voyager St, Linbro Park, Johannesburg Tel: +27 11 608 4270 ; www.batessecuredata.co.za 1 Environment Monitoring in computer rooms, data centres and other facilities

More information

Access Control and Operating Conditions Monitoring System for Telecommunication and Server Racks

Access Control and Operating Conditions Monitoring System for Telecommunication and Server Racks Access Control and Operating Conditions Monitoring System for Telecommunication and Server Racks Why is Supracontrol so superior? It adjusts to the existing access identification system It adjusts to the

More information

DCIM Data Center Infrastructure Monitoring

DCIM Data Center Infrastructure Monitoring DCIM Data Center Infrastructure Monitoring ServersCheck offers a flexible, modular and affordable DCIM solution. It is based on our range of IP & SNMP hardware environmental sensors and management software.

More information

Choosing Close-Coupled IT Cooling Solutions

Choosing Close-Coupled IT Cooling Solutions W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of

More information

BNA FEDERAL CREDIT UNION DISASTER RECOVERY PLAN

BNA FEDERAL CREDIT UNION DISASTER RECOVERY PLAN BNA FEDERAL CREDIT UNION DISASTER RECOVERY PLAN INTRODUCTION The need for a contingency plan for business interruptions is vital to the operations of the BNA Federal Credit Union. Without such a plan,

More information

User Manual. RK-2d / RK-2t. dedicated KVM switch and rackmount screen technology. Designed and manufactured by Austin Hughes

User Manual. RK-2d / RK-2t. dedicated KVM switch and rackmount screen technology. Designed and manufactured by Austin Hughes dedicated KVM switch and rackmount screen technology User Manual RK-2d / RK-2t 1U Short Depth Keyboard Drawer Designed and manufactured by Austin Hughes 751 Legal Information First English printing, October

More information

The Buhl Electric Secure Home. Brought to you by Buhl Electric. Security Packages and Options

The Buhl Electric Secure Home. Brought to you by Buhl Electric. Security Packages and Options The Buhl Electric Secure Home Brought to you by Buhl Electric Security Packages and Options Contents Why do I Need a Security System... 4 What Are the Advantages of a Hard-Wired Security System... 4 Security

More information

StorTrends 3400 Hardware Guide for Onsite Support

StorTrends 3400 Hardware Guide for Onsite Support StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200

More information

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems

ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems ABB Stotz-Kontakt GmbH ABB safe&smart Project planning of security systems Content Introduction Preventing unauthorized access by perimeter surveillance Monitoring unauthorized access by indoor surveillance

More information

www.aten.com Application Guide Guardian Over the NET Server Room Solution

www.aten.com Application Guide Guardian Over the NET Server Room Solution www.aten.com Guardian Over the NET Server Room Solution Develop a Secure, Stable Server Room For security reasons, more and more companies house all their servers in a secure environment a server room

More information

MCR1900 Media Converter 19-Slot Chassis

MCR1900 Media Converter 19-Slot Chassis MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MN12CES / MN10CESWW Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MN12CES / MN10CESWW Voltage rating: 120V~60Hz Power rating : 1100W (MN12CES) Power rating : 900W (MN10CESWW) Customer

More information

Advanced Fencing and Security Technologies Ltd

Advanced Fencing and Security Technologies Ltd G.M. Advanced Fencing and Security Technologies Ltd P.O. Box 2327 Kfar Sava Industrial Area 44425, Israel Tel +972-9-7662965 Fax + 972-9-7662964 E-mail: [email protected] Website: www.gmsecurity.com

More information

Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc.

Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc. Monitoring the Computer Room s Physical Environment A white paper from Sensaphone, Inc. Introduction Nearly all small- and medium-sized businesses rely on a computer network to maintain operations, communicate

More information

Zertico Rack Monitoring Unit

Zertico Rack Monitoring Unit Zertico Rack Monitoring Unit Typical applications of Zertico Monitoring devices: - Monitoring of IT infrastructure (e.g. data center) - Monitoring of technical rooms in branch offices - Remote monitoring

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CCS. Voltage rating: 115V~60Hz Power rating : 1400W Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CCS Customer Support : 1-800-474-2147 Voltage rating: 115V~60Hz Power rating : 1400W For product inquiries or support

More information

Ultrasonic support removal tank

Ultrasonic support removal tank Ultrasonic support removal tank User guide and safety manual See inside for use and safety information. The Ultrasonic support removal tank automatically removes PLA support material from a printed ABS

More information

ALARM SYSTEM INSTALLATION GUIDE

ALARM SYSTEM INSTALLATION GUIDE ALARM SYSTEM INSTALLATION GUIDE Congratulations on the purchase of your Egardia alarm system. Egardia's website www.egardia.com Customer services Please visit www.egardia.com if you would like further

More information

Major Risks and Recommended Solutions

Major Risks and Recommended Solutions Major Risks and Recommended Solutions www.icdsecurity.com OVERVIEW Are you familiar with the main security risks that threaten data centers? This paper provides an overview of the most common and major

More information

User s Guide. Security Systems D220

User s Guide. Security Systems D220 User s Guide Security Systems D220 Table of Contents About This User s Guide... 3 Introduction... 3 Security System Basics... 4 Controlled Points... 5 24-Hour Points... 6 Keypad Keys... 6 Keypad Lights...

More information

Air Conditioner Water Heater - A Product of HotSpot Energy LLC

Air Conditioner Water Heater - A Product of HotSpot Energy LLC Air Conditioner Water Heater - A Product of HotSpot Energy LLC PLEASE READ THIS BEFORE YOU INSTALL THE UNIT 1. This air conditioner must be installed and/or repaired by a qualified technician. If you perform

More information

Keys to understanding your alarm system

Keys to understanding your alarm system Keys to understanding your alarm system This section is designed to allow you to familiarize yourself with most of the security system devices that may be installed or proposed to be installed in your

More information

Application Briefs: Remote Office Environment

Application Briefs: Remote Office Environment Overview Remote offices are a definite sign of growth, but it can constitute an immense challenge from an IT infrastructure standpoint. Remote offices may include a wide variety of wiring closets and small

More information

Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller

Vertical Display and Storage B1350-2. SKOPE Gen2: Three Door Chiller Vertical Display and Storage User Manual MAN1227 Rev. 3.0 March 2008 edition CONTACT ADDRESSES Designed and Manufactured by New Zealand SKOPE INDUSTRIES LIMITED PO Box 1091, Christchurch New Zealand Freephone:

More information

ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL

ISO IEC 27002 2005 (17799 2005) INFORMATION SECURITY AUDIT TOOL 9.1 USE SECURITY AREAS TO PROTECT FACILITIES 1 GOAL Do you use physical methods to prevent unauthorized access to your organization s information and premises? 2 GOAL Do you use physical methods to prevent

More information

SWIMMING POOL HEAT PUMP

SWIMMING POOL HEAT PUMP SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical

More information

securıty HOME home protection 101

securıty HOME home protection 101 securıty HOME home protection 101 Do I really need a security system? Yes, you do! There is always the sonal electronic sentry, able to see and risk of fire, theft, or home intrusion. hear trouble. It

More information

SMART SENSOR COLLECTION

SMART SENSOR COLLECTION TEMPERATURE SENSOR This sensor measures temperature in degrees Celsius or Fahrenheit. It works with all SensorHawk base units (SensorHawk-2, SensorHawk-8 and SensorHawk8/20) as well as the SecurityHawk-8

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications December 28, 2015 Revision 5 920 N Trade Winds Pkwy Columbia, MO 65201 Ammonia detection system codes and design specifications Following is a discussion

More information

Introducing Tripp Lite s PowerAlert Network Management Software

Introducing Tripp Lite s PowerAlert Network Management Software Introducing Tripp Lite s PowerAlert Network Management Software What Can It Do For You? Improve the accuracy and efficiency of the network operations staff in the context of power and environmental management

More information

CenterMind G+ Smart and Proactive Environment Monitoring

CenterMind G+ Smart and Proactive Environment Monitoring CenterMind G+ Smart and Proactive Environment Monitoring Smart and Proactive Environment Monitoring real-time visibility into the state of your computer room or data center environment, 24/7 RiT CenterMind

More information

Portable Air Conditioner

Portable Air Conditioner Portable Air Conditioner Owner's Manual Model:3 in 1 12,000 Btu/h Series 3 Please read this owner s manual carefully before operation and retain it for future reference. CONTENTS 1. SUMMARY...1 2. PORTABLE

More information

Rogers Smart Home Monitoring QUICK START GUIDE ROG_6093_QST_GDE_EN.indd 1 9/22/12 8:29 AM

Rogers Smart Home Monitoring QUICK START GUIDE ROG_6093_QST_GDE_EN.indd 1 9/22/12 8:29 AM Rogers Smart Home Monitoring QUICK START GUIDE STAY CONNECTED TO YOUR HOME AND YOUR FAMILY. This Quick Start Guide is designed to help you get the most out of your new system right away and help ensure

More information

Wireless Alarm System. Window/Door Sensor. User s Manual. Choice ALERT. Control all Sensors & accessories from one location

Wireless Alarm System. Window/Door Sensor. User s Manual. Choice ALERT. Control all Sensors & accessories from one location 45131 Wireless Alarm System Window/Door Sensor User s Manual Choice ALERT Control all Sensors & accessories from one location Table of Contents Important Safeguards 4 Introduction 5 Installation 6 Assigning

More information

Water Management & Damage Prevention:

Water Management & Damage Prevention: Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and

More information

Introduction, Overview & Justification

Introduction, Overview & Justification To: IT Data Center, Computer Room & Facilities Managers From: The Team At AVTECH Introduction, Overview & Justification AVTECH s Room Alert products for Physical IT & Facilities Environment Monitoring

More information

APC APPLICATION NOTE #112

APC APPLICATION NOTE #112 #112 Best Practices for Deploying the InfraStruXure InRow SC By David Roden Abstract The InfraStruXure InRow SC (ACSC100 and ACSC101) is a self-contained air conditioner for server rooms and wiring closets.

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MF08CESWW. Voltage rating: 115V~60Hz Power rating : 800W MODE ALARM Portable Air Conditioner OWNER S MANUAL Read these instructions before use 8 Model: MF08CESWW Voltage rating: 115V~60Hz Power rating : 800W Customer Support : 1-800-474-2147 For product inquiries

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live!

U.S. Department of Housing and Urban Development Office of Public and Indian Housing. A Good Place to Live! U.S. Department of Housing and Urban Development Office of Public and Indian Housing A Good Place to Live! Introduction Having a good place to live is important. Through your Public Housing Agency (or

More information

Best Practices for Wire-free Environmental Monitoring in the Data Center

Best Practices for Wire-free Environmental Monitoring in the Data Center White Paper 11800 Ridge Parkway Broomfiled, CO 80021 1-800-638-2638 http://www.42u.com [email protected] Best Practices for Wire-free Environmental Monitoring in the Data Center Introduction Monitoring for

More information

dedicated KVM switch and rackmount screen technology User Manual IP-S101 Combo KVM Extender Designed and manufactured by Austin Hughes

dedicated KVM switch and rackmount screen technology User Manual IP-S101 Combo KVM Extender Designed and manufactured by Austin Hughes dedicated KVM switch and rackmount screen technology User Manual IP-S101 Combo KVM Extender Designed and manufactured by Austin Hughes 751 Legal Information First English printing, October 2002 Information

More information

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation

RVH/BCH Data Centres Proposals for Surge Protection and Ventilation REPORT Proposals for Surge Protection and Ventilation BELFAST HEALTH AND SOCIAL CARE TRUST ROYAL GROUP OF HOSPITALS GROSVENOR ROAD BELFAST BT12 6BA Rev. 01 6th September 2013 Table of Contents 1.0 Ventilation

More information

2» 10» 18» 26» PD3 34 00 42»

2» 10» 18» 26» PD3 34 00 42» » STARDOM Safe Capsule Series User Manual... 2» STARDOM Safe Capsule Serie Bedienungsanleitung... 10» Série STARDOM Safe Capsule Manuel de l utilisateur... 18 26 PD3500 34» Manual de usuario de STARDOM

More information

www.dataspan.com 800.660.3586 Data Center and Computer Room Services Specialty Services Data Center and Computer Room Products Sub-Floor Cleaning

www.dataspan.com 800.660.3586 Data Center and Computer Room Services Specialty Services Data Center and Computer Room Products Sub-Floor Cleaning Data Center Cleaning Services The best way to eliminate downtime? Stop problems before they start. Our specialized anti-static cleaning services will protect your storage media and other important infrastructure

More information

How To Run A Data Center Efficiently

How To Run A Data Center Efficiently A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly

More information

Dehumidifier Users manual. For Models: DH45S DH65S

Dehumidifier Users manual. For Models: DH45S DH65S Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but

More information

FLOOD SENSOR. perfection in every detail. Home intelligence. Patent Pending

FLOOD SENSOR. perfection in every detail. Home intelligence. Patent Pending FLOOD SENSOR perfection in every detail The most beautiful and functional flood sensor ever made Fibaro Flood Sensor futuristic design, compact size, and a wide variety of additional functions. Fibaro

More information

SoftRAID 5 QUICK START GUIDE. for OWC ThunderBay

SoftRAID 5 QUICK START GUIDE. for OWC ThunderBay SoftRAID 5 QUICK START GUIDE for OWC ThunderBay TABLE OF CONTENTS INTRODUCTION...1 1.1 MINIMUM SYSTEM REQUIREMENTS 1.2 FEATURES 1.3 ABOUT THIS MANUAL SYSTEM SETUP...2 2.1 GETTING STARTED 2.2 INITIALIZING,

More information

Understanding Alarm Systems

Understanding Alarm Systems Understanding Alarm Systems A false alarm occurs when an alarm signal designed to elicit an immediate emergency Law Enforcement, Fire, or Medical response is activated, when in fact no emergency exists.

More information

Important Safeguards

Important Safeguards Table of Contents Important Safeguards...2 Product Layout...3 Preparing for Use...4 Air-conditioning without installation...4 Air-conditioning with installation...5 Control Panel...6 Operating from the

More information

How To Use A Sata Dsa Hard Disk Storage System

How To Use A Sata Dsa Hard Disk Storage System EXTERNAL RAID STORAGE OF HDDS INSTRUCTION MANUAL CAUTION RISK OF ELECTRIC SHOCK CAUTION TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT OPEN COVER. NO USER SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED

More information

ReadyNAS OS 6 Desktop Storage Systems

ReadyNAS OS 6 Desktop Storage Systems ReadyNAS OS 6 Desktop Storage Systems Hardware Manual Models: ReadyNAS 102 ReadyNAS 104 ReadyNAS 312 ReadyNAS 314 ReadyNAS 316 ReadyNAS 516 ReadyNAS 716X EDA 500 October 2013 202-11206-04 350 East Plumeria

More information

LET S GO. Get your Ultra Broadband ready Business gateway up and running

LET S GO. Get your Ultra Broadband ready Business gateway up and running LET S GO Get your Ultra Broadband ready Business gateway up and running CONTENTS BUSINESS GATEWAY ULTRA BROADBAND READY 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Equipment Check 2 Getting Started 3 Setting Up

More information

GNOME PELLET E.I. Pellet Heater Owner's Manual Installation and Operating Instructions. Please read this entire manual before installation.

GNOME PELLET E.I. Pellet Heater Owner's Manual Installation and Operating Instructions. Please read this entire manual before installation. Pellet Heater Owner's Manual Installation and Operating Instructions Please read this entire manual before installation. Save these instructions. SAFETY NOTICE HEATER MUST BE PROPERLY INSTALLED AND MAINTAINED

More information

Server Room, Data Centre Management and Monitoring Solutions

Server Room, Data Centre Management and Monitoring Solutions Server Room, Data Centre Management and Monitoring Solutions Published in October 2007 Management & Monitoring Solutions The ability to alert a business to disasters or potential performance issues at

More information

LYNX Touch Small Business Solutions DYNAMIC, FULL COLOR SELF-CONTAINED BUSINESS CONTROL SYSTEM. Your Connected Business

LYNX Touch Small Business Solutions DYNAMIC, FULL COLOR SELF-CONTAINED BUSINESS CONTROL SYSTEM. Your Connected Business LYNX Touch Small Business Solutions DYNAMIC, FULL COLOR SELF-CONTAINED BUSINESS CONTROL SYSTEM Your Connected Business LYNX Touch Protected and Connected Honeywell s LYNX Touch self-contained business

More information

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability

Considerations for a Highly Available Intelligent Rack Power Distribution Unit. A White Paper on Availability Considerations for a Highly Available Intelligent Rack Power Distribution Unit A White Paper on Availability Introduction Data centers are currently undergoing a period of great change. Data center managers

More information

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167

PROAIR Water-Cooled Air Conditioner. CR43WC Model INSTRUCTION MANUAL. Rev. E 2013 Pentair Technical Products P/N 10-1008-167 PROAIR Water-Cooled Air Conditioner CR43WC Model INSTRUCTION MANUAL Rev. E 2013 Pentair Technical Products P/N 10-1008-167 87976466 TABLE OF CONTENTS HANDLING & TESTING THE AIR CONDITIONER...3 INSTALLATION

More information

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS

Portable Air Conditioner. OWNER S MANUAL Read these instructions before use. Model: MM14CHCSCS Portable Air Conditioner OWNER S MANUAL Read these instructions before use Model: MM14CHCSCS Voltage rating: 120V~60Hz Power rating : 1400W(Cooling) Power rating : 1350W(Heating) Customer Support : 1-800-474-21477

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

14. Troubleshooting Guide

14. Troubleshooting Guide 14. Guide 14.1 Refrigeration Cycle System In order to diagnose malfunctions, ensure the air conditioner is free from electrical problems before inspecting the refrigeration cycle. Such problems include

More information

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual

Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2. Instruction Manual Firmware version: 1.10 Issue: 7 AUTODIALER GD30.2 Instruction Manual Firmware version: 2.0.1 Issue: 0.6 Version of the GPRS transmitters configurator: 1.3.6.3 Date of issue: 07.03.2012 TABLE OF CONTENTS

More information

Why is my air conditioner dripping on my customers?

Why is my air conditioner dripping on my customers? De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These

More information

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF

Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator

More information

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit

SERVICE INSTRUCTION R410A. WALL MOUNTEDtype INVERTER SPLIT TYPE ROOM AIR CONDITIONER. Models Indoor unit Outdoor unit SERVICE INSTRUCTION SPLIT TYPE ROOM AIR CONDITIONER WALL MOUNTEDtype INVERTER Models Indoor unit Outdoor unit ASYG07LECA ASYG09LECA ASYG12LECA ASYG14LECA AOYG07LEC AOYG09LEC AOYG12LEC AOYG14LEC R410A CONTENTS

More information

securıty HOME home protection 101

securıty HOME home protection 101 securıty HOME home protection 101 Do I really need a security system? Yes, you do! There is always the risk of fire, theft, or home intrusion. Whether at home during the day, asleep at night, or away,

More information

PTAC Preventive Maintenance Guide. Step-by-step instructions and information to keep your units operating in peak condition

PTAC Preventive Maintenance Guide. Step-by-step instructions and information to keep your units operating in peak condition PTAC Preventive Maintenance Guide Step-by-step instructions and information to keep your units operating in peak condition The Importance of Proper PTAC Maintenance Welcome to the PTAC Preventive Maintenance

More information

Tk20 Network Infrastructure

Tk20 Network Infrastructure Tk20 Network Infrastructure Tk20 Network Infrastructure Table of Contents Overview... 4 Physical Layout... 4 Air Conditioning:... 4 Backup Power:... 4 Personnel Security:... 4 Fire Prevention and Suppression:...

More information

5 Reasons. Environment Sensors are used in all Modern Data Centers

5 Reasons. Environment Sensors are used in all Modern Data Centers 5 Reasons Environment Sensors are used in all Modern Data Centers TABLE OF CONTENTS 5 Reasons Environmental Sensors are used in all Modern Data Centers Save on Cooling by Confidently Raising Data Center

More information

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU

Section 7. Evaporator thermistor. Under-and-over pressure safety switches. Connections to the ECU Automatic Temperature Control Diagnosis and Repair Diagnosis of Automatic A/C Systems The most common automatic A/C system malfunctions tend to be the result of basic air conditioning problems. These problems

More information

How to Save a Wet Cell Phone www.wikihow.com

How to Save a Wet Cell Phone www.wikihow.com How to Save a Wet Cell Phone www.wikihow.com Have you ever accidentally dropped your cell phone in the sink, or even worse... the toilet? Did you leave it in your pocket and run it through the washing

More information

Thank you for your support and welcome to Maxis! Yours sincerely, Maxis

Thank you for your support and welcome to Maxis! Yours sincerely, Maxis Welcome Congratulations, you are now on your way to a world of faster internet! With your newly-installed Maxis Fibre Internet, you will enjoy faster downloads, enhanced online shopping, smoother video

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR

USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR USER INSTRUCTIONS FOR GET PORTABLE 12k BTU AIR CONDITIONER MODEL No. GPACU12HR CONTENTS Introduction Safety Notes Identification of parts Installation instructions Operation instructions Maintenance Troubleshooting

More information

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments

Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch

More information

How to Prevent Liquid Damage Property Losses

How to Prevent Liquid Damage Property Losses 1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines

More information

SC100 Series Seismic Vibration Sensors. The Best Way to Protect High-Risk Commercial Assets

SC100 Series Seismic Vibration Sensors. The Best Way to Protect High-Risk Commercial Assets SC100 Series Seismic Vibration Sensors Protect BANK VAULTS, Safes, ATMS AND MORE The Best Way to Protect High-Risk Commercial Assets SC100 Series Seismic Vibration Sensors BeArmed for Any Attack SC100

More information

Using Portable Spot Air Conditioners in Industrial Applications

Using Portable Spot Air Conditioners in Industrial Applications Using Portable Spot Air Conditioners in Industrial Applications Cooling People, Processes and Equipment In today s highly competitive manufacturing sector, companies are constantly looking for new ways

More information

False Alarm/Unwanted Fire Signals Reduction Guidance

False Alarm/Unwanted Fire Signals Reduction Guidance False Alarm/Unwanted Fire Signals Reduction Guidance Compiled By: South Wales Fire and Rescue Service Contents Introduction Why reduce false alarms Typical Causes Actions that can be taken Introduction

More information

Split Type Room Air Conditioner. KSWM units

Split Type Room Air Conditioner. KSWM units OWNER S MANUAL Split Type Room Air Conditioner KSWM units Please read the operating instructions and safety precautions carefully and thoroughly before installing and operating your room air conditioner.

More information

Enterprise Remote Monitoring

Enterprise Remote Monitoring Enterprise Remote Monitoring Alarm Management, Predictive Maintenance, Advanced Network Security Services For Business-Critical Continuity Can You Really Afford Not To Know? Loss of productivity and the

More information

Service & Maintenance:

Service & Maintenance: Service & Maintenance: Condensation About Condensation Tips for Controlling Humidity and Condensation Frequently Asked Questions Sources 1 condensation: What is it? Introduction Moisture on windows and

More information

Energy Saving Tips. They can have a dramatic impact on your bill. The cheapest energy is the energy you don t use.

Energy Saving Tips. They can have a dramatic impact on your bill. The cheapest energy is the energy you don t use. Energy Saving Tips They can have a dramatic impact on your bill. The cheapest energy is the energy you don t use. Drive by your building at night. Driving by your building at night makes it easy to check

More information

FT-100 Fire Training Fog Machine User Manual English

FT-100 Fire Training Fog Machine User Manual English FT-100 Fire Training Fog Machine User Manual English 2015 Antari Lighting and Effects Ltd. User Manual - English Safety Information Please read the following safety information carefully before operating

More information

Home inspectors are not mold inspectors, however they do inspect for defects that

Home inspectors are not mold inspectors, however they do inspect for defects that CONDENSATION IN THE WALLS Home inspectors are not mold inspectors, however they do inspect for defects that can result in mold. Mold grows in wet or damp environments. Defects that result in a wet or damp

More information

Mobile Data Power Model: MDP-25

Mobile Data Power Model: MDP-25 Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss

More information

PowerPanel Business Edition USER MANUAL

PowerPanel Business Edition USER MANUAL USER MANUAL Rev. 0.9 2007/10/26 Copyright 2006-2007 Cyber Power Systems, Inc. All rights reserved. PowerPanel Business Edition USER S MANUAL PowerPanel Business Edition provides power management Services.

More information

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation

Heat Trace Fundamentals. Monte Vander Velde, P.E. President, Interstates Instrumentation Heat Trace Fundamentals Monte Vander Velde, P.E. President, Interstates Instrumentation Contents Introduction... 3 Purpose of Heat Trace... 3 Types of Heat Trace... 4 Steam Trace vs. Electric Trace...

More information

SOLAR PV SYSTEM MAINTENANCE GUIDE

SOLAR PV SYSTEM MAINTENANCE GUIDE SOLAR PV SYSTEM MAINTENANCE GUIDE GUYANA HINTERLANDS STAND-ALONE SOLAR PV INSTALLATIONS IMPROVING HEALTH FACILITY INFRASTRUCTURE (IHFI) GUYANA CONTRACT NO. EPP-I-00-03-00008-00, TASK ORDER 07 APRIL 2013

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

How To Use A Power Supply Unit (Upu)

How To Use A Power Supply Unit (Upu) BRAVER UPS (Uninterruptible Power System) User s Manual Safety CAUTION! This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The unit contains no user replaceable parts.

More information

Microwave Oven. Warning: a) This oven is not for commercial use. b) Don't open the cover of the machine except professional person.

Microwave Oven. Warning: a) This oven is not for commercial use. b) Don't open the cover of the machine except professional person. HOME ELECTRONICS HE900E/CONV-SS Instruction manual for electronic control microwave oven CONTENTS 1. Specifications 2. Check after unpacking 3. General Safety instructions 4. Special safety instruction

More information

GET THE ALARM.COM ADVANTAGE.

GET THE ALARM.COM ADVANTAGE. BETTER SECURITY REMOTE WEB CONTROL MOBILE APPS GET THE ALARM.COM ADVANTAGE. STAY SECURE. STAY CONNECTED. WIRELESS TECHNOLOGY VIDEO MONITORING INTERACTIVE SERVICES HOME AUTOMATION ENERGY MANAGEMENT Alarm.com

More information